1 Overview
Two-wire passive working mode, 5-digit LCD display.
Supports 15 unit switching and 5 display modes such as pressure, temperature,
liquid level, current, percentage, etc.
Supports main variable clearing, display resolution adjustment, factory data
restoration and other functions, suitable for customers' special needs.
Full digital calibration, 2~5 points non-linear correction function, higher accuracy.
It has over-current, over-voltage, short-circuit and reverse-connection protection.
Even if the load is short-circuited, direct 24V power supply will not cause damage.
Enhanced anti-interference design, suitable for various harsh industrial
environments.
2 Main parameters and indicators
Working mode: 4~20mA passive mode.
Working voltage drop: <3.5V at 4mA; <3.8V at 20mA;
Display range: -19999~99999
Current resolution: 1uA
Machine accuracy: 0.1%
Temperature drift coefficient: <35ppm
Working environment: temperature -20~70℃, humidity <85%, dry and corrosion-free
environment.
Overall dimensions: 65×45×45mm (height×width×thickness)
The instrument realizes all parameter input and calibration data setting and collection
through two buttons on the panel. This instrument Various optimization measures have
been taken to improve the customer's operating efficiency:
The shift key and increase key of the instrument have variable rate function.
In user setting mode, if there is no user operation within 60 seconds, it will
automatically exit to the measurement state.
The meter will save all set parameters only when exiting the menu normally.
oFFSt: Displays the offset value, the range can be set (-19999~99999), the menu
prompt displays the current pressure unit
By setting the value of this menu, the displayed value can be offset. The factory
default value of this menu is 0. Generally In this case, there is no need to set this
menu value.
-dot-: Factory display accuracy setting, the range can be set (0~4), the menu prompt is
the current pressure unit
Display accuracy refers to the number of decimal places displayed in measurement
mode. More decimal places is not always better. It should be ensured first.
Display value is stable.
diS-L: Calibration range lower limit setting, the range can be set (-19999~99999), the
menu prompt displays the current pressure unit
diS-H: Setting the upper limit of the calibration range, the range can be set (-
19999~99999), the menu prompt displays the current pressure unit
LinE: Calibration point setting, settable range (2,3,5), menu prompt “Pot”
After selecting the calibration points, the software will automatically bisect the
calibration range. If the bisection value is not within the input range, you can
Modify in the corresponding calibration point settings. At the same time, it should be
noted that the given value must be monotonic during the calibration process.
That is: (AdC-L)<(AdC-1)<(AdC-2)<(AdC-3)<(AdC-H) or
(AdC-L)>(AdC-1)>(AdC-2)>(AdC-3)>(AdC-H),
The default acquisition value of the instrument is 2-point calibration, which can meet
most application requirements. If a higher line
The accuracy can be set to 5-point calibration.
AdC-H: Full calibration point, the acquisition method is the same as zero point
calibration
PCt-L: Zero value of the progress bar, the range can be set (-19999~99999),
corresponding to the starting point of the progress bar, set "diS-L"
After the value, the "Pct-L" value will be equal to it. When you need to modify the zero
value of the progress bar, you can modify it in this menu.
PCt-H: The full value of the progress bar, the range can be set (-19999~99999),
corresponding to the end point of the progress bar, set "diS-H"
After the value, the "Pct-H" value will be equal to it. When you need to modify the full
value of the progress bar, you can modify it in this menu.
ZErO: Zero-to-full shielding coefficient, settable range (0.00~2.00), menu prompt "%"
The setting value in this menu indicates the zero-to-full shielding range. When the
setting value is "0.00", the zero-to-full shielding function is turned off.
Example: When set to 0.10, it means that when the transmitter output is close to zero
or full point, add or subtract 0.10% of the transmitting range.
, the transmitter output will automatically stabilize at the zero point or full point, and
there will be no output jump due to interference.
SCALE: Minimum display resolution, settable range (1~9). The menu prompt is the
unit for calibration. Set this parameter.
After that, the last digit of the value displayed on the main screen will change
incrementally according to this set value.