BS-6Y Pressure Transmitter User Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

BS-6Y User Manual

Version: VR1.0
Xiamen Kechuan Technology Co., Ltd.

1 Overview
 Two-wire passive working mode, 5-digit LCD display.
 Supports 15 unit switching and 5 display modes such as pressure, temperature,
liquid level, current, percentage, etc.
 Supports main variable clearing, display resolution adjustment, factory data
restoration and other functions, suitable for customers' special needs.
 Full digital calibration, 2~5 points non-linear correction function, higher accuracy.
 It has over-current, over-voltage, short-circuit and reverse-connection protection.
Even if the load is short-circuited, direct 24V power supply will not cause damage.
 Enhanced anti-interference design, suitable for various harsh industrial
environments.
2 Main parameters and indicators
 Working mode: 4~20mA passive mode.
 Working voltage drop: <3.5V at 4mA; <3.8V at 20mA;
 Display range: -19999~99999
 Current resolution: 1uA
 Machine accuracy: 0.1%
 Temperature drift coefficient: <35ppm
 Working environment: temperature -20~70℃, humidity <85%, dry and corrosion-free
environment.
 Overall dimensions: 65×45×45mm (height×width×thickness)

3 Appearance and wiring


3.1 Outline drawing
3.2 Wiring diagram
4 function settings
4.1 Key function description
4.1.1 Up key “▲”
 Short press in measurement mode to switch display mode.
 Press and hold for 5 seconds in measurement mode to enter the main variable
clearing.
 Short press in setting mode to move the flashing bit.
4.1.2 Down key “▼”
 Short press in measurement mode to switch display mode.
 In the setting mode, it is a function to add one to the setting parameters. When long
pressing, the continuous shift increases by one.
4.1.3 Setting keys “▲” + “▼”
 Press “▲” and “▼” at the same time to set the key function.
 Press "▲" and "▼" simultaneously in measurement mode to enter the setting state.
 In setting mode, press "▲" and "▼" simultaneously to set or confirm parameter
modification.
4.1.4 Overview of key functions

The instrument realizes all parameter input and calibration data setting and collection
through two buttons on the panel. This instrument Various optimization measures have
been taken to improve the customer's operating efficiency:
 The shift key and increase key of the instrument have variable rate function.
 In user setting mode, if there is no user operation within 60 seconds, it will
automatically exit to the measurement state.
 The meter will save all set parameters only when exiting the menu normally.

SET UP BLOCK DIAGRAM


Indicates that two keys are pressed at the same time

4.3 Menu description


The menu of this instrument is divided into three levels: "Production and Debugging
Menu"; "Advanced User Menu"; "Common User Menu".
It is distinguished by the entry password for each level of menu.
 “Production debugging menu”
The entry password is "00066", which is used by the transmitter manufacturer to set
the basic parameters of the meter. It determines the accuracy, calibration value and
other parameters of the meter. Therefore, the production debugging menu cannot be
opened to general users.
No calibration data is destroyed.
 “Advanced User Menu”
The entry password is "00016", which is used when making some special settings for
on-site use requirements.
 “Normal User Menu”
The entry password is "00001" to set the display unit and display mode.
Note: During advanced user and user menu settings, if there is no key operation within
60 seconds, the setting will be automatically exited and
Return to measurement mode.

4.3.1 Password setting menu


Lock: Password input menu, the range can be set (19999~99999), the menu prompt is
"PIN", and the setting menu enters
Enter the password. If the password is entered incorrectly or there is no key operation
within 30 seconds, it will automatically return to the measurement mode.

4.3.2 Normal user menu


Unit: User unit setting, the range can be set (0~18), the menu prompt is the set unit
There are 15 types of unit settings, namely "MPa", "kPa", "Pa", "bar", "psi",
"Kgf", "mHg", "mH2", "m", "cm", "mm", "℃", "℉",
"%" ,"mA"
SHO: Display mode setting, configurable range (0~5)
"0"--Display the main variable
"1"--display current
"2"--display percentage
"3"--The main variable and current are displayed alternately, prompt "P-A"
"4"--The main variable and percentage are displayed alternately, and the prompt is "P-
b"
"5"--current and percentage are displayed alternately, prompt "A-b"

4.3.3 Advanced User Menu


-dot-: Display accuracy setting, the range can be set (0~4), the menu prompt is the
current pressure unit
The display resolution is the number of decimal places displayed in the measurement
mode. The user can set it according to the requirements of on-site use.
The more decimal places displayed, the better. Priority should be given to ensuring the
stability of the displayed value. At the same time, this menu value will be affected by
Limitation of the maximum display value of the transmitter during calibration. If the set
number of decimal point display digits is higher than the maximum display value of the
transmitter,
When the displayed value exceeds the 5-digit display range, the set number of
decimal places will be limited to ensure that the maximum display value can be within
the normal display range.
For example: the calibration range of the transmitter is 0.0000~20.000MPa; then the
setting range of the display accuracy is (0~3),
If the display accuracy setting value is 4, the maximum display value will exceed the
maximum 5-digit display range.

diSAL: Over-range alarm switch, settable range (0~1)


This setting means that when the pressure value exceeds 125% of the upper limit of
the calibrated range or is lower than 25% of the lower limit of the calibrated range, it
will flash.
Flashing prompt.
“0”—turn off the alarm function, prompt “NO”
“1”—turn on the alarm function, prompt “YES”

oFFSt: Displays the offset value, the range can be set (-19999~99999), the menu
prompt displays the current pressure unit
By setting the value of this menu, the displayed value can be offset. The factory
default value of this menu is 0. Generally In this case, there is no need to set this
menu value.

CoEFF: Sensor sensitivity correction coefficient, settable range (0.0001~1.9999),


menu prompt "GAN"
During the use of the transmitter, if the sensitivity of the sensor changes, you can
correct it through this menu.
Before performing sensitivity correction, the zero point error of the meter should be
corrected through the main variable zeroing function.
To ensure that the linearity of the transmission after sensitivity correction is normal, the
default value of this menu is "1.0000".

FiLtE: Filter setting, configurable range (0~2)


"0" - low filtering, prompt "LO"
"1"--during filtering, prompt "MId"
"2"--High filtering, prompt "HIg"
The larger the filter constant value is set, the stronger the ability to suppress
interference, but the sensitivity will decrease. During production calibration
The default value of this menu is "1" with medium filtering effect, which is suitable for
most applications.

rESEt: Restore factory data, configurable range (0~1)


This menu function is to restore the transmitter data to the factory state. This function
is only available after exiting the settings and saving the data.
Valid at the time of writing.
"0"--turn off the factory restore function, prompt "NO"
"1"--Open the factory restore function, prompt "YES"
4.3.4 Production debugging menu

dAtE: Production number, settable range (00000~99999), menu prompt "ID"


This menu is used by the manufacturer to set the numbering information of the header.
Unit: Factory unit setting, the range can be set (0~18), the menu prompt is the setting
unit, the same as the user menu description.

-dot-: Factory display accuracy setting, the range can be set (0~4), the menu prompt is
the current pressure unit
Display accuracy refers to the number of decimal places displayed in measurement
mode. More decimal places is not always better. It should be ensured first.
Display value is stable.

diS-L: Calibration range lower limit setting, the range can be set (-19999~99999), the
menu prompt displays the current pressure unit

diS-H: Setting the upper limit of the calibration range, the range can be set (-
19999~99999), the menu prompt displays the current pressure unit

LinE: Calibration point setting, settable range (2,3,5), menu prompt “Pot”
After selecting the calibration points, the software will automatically bisect the
calibration range. If the bisection value is not within the input range, you can
Modify in the corresponding calibration point settings. At the same time, it should be
noted that the given value must be monotonic during the calibration process.
That is: (AdC-L)<(AdC-1)<(AdC-2)<(AdC-3)<(AdC-H) or
(AdC-L)>(AdC-1)>(AdC-2)>(AdC-3)>(AdC-H),
The default acquisition value of the instrument is 2-point calibration, which can meet
most application requirements. If a higher line
The accuracy can be set to 5-point calibration.

AdC-L: Zero calibration point


When the "▲" and "▼" keys are pressed at the same time, the zero point calibration
point acquisition is started, and the menu prompt
"A/D" starts to flash, indicating that acquisition is in progress. After the acquisition
value is stable, press "▲" at the same time.
Confirm this collection with the "▼" key.
AdC-1~ AdC-3: Intermediate calibration point, the acquisition method is the same as
zero point calibration
diS-1~ diS-3: The middle point displays the value, which is automatically divided
equally by the software based on the number of calibration points. If the equal value is
not entered,range, it can be modified in this menu.

AdC-H: Full calibration point, the acquisition method is the same as zero point
calibration

PCt-L: Zero value of the progress bar, the range can be set (-19999~99999),
corresponding to the starting point of the progress bar, set "diS-L"
After the value, the "Pct-L" value will be equal to it. When you need to modify the zero
value of the progress bar, you can modify it in this menu.

PCt-H: The full value of the progress bar, the range can be set (-19999~99999),
corresponding to the end point of the progress bar, set "diS-H"
After the value, the "Pct-H" value will be equal to it. When you need to modify the full
value of the progress bar, you can modify it in this menu.

ZErO: Zero-to-full shielding coefficient, settable range (0.00~2.00), menu prompt "%"
The setting value in this menu indicates the zero-to-full shielding range. When the
setting value is "0.00", the zero-to-full shielding function is turned off.
Example: When set to 0.10, it means that when the transmitter output is close to zero
or full point, add or subtract 0.10% of the transmitting range.
, the transmitter output will automatically stabilize at the zero point or full point, and
there will be no output jump due to interference.

SCALE: Minimum display resolution, settable range (1~9). The menu prompt is the
unit for calibration. Set this parameter.
After that, the last digit of the value displayed on the main screen will change
incrementally according to this set value.

diSAL: Over-range alarm switch, settable range (0~1)


This setting means that when the pressure value exceeds 125% of the upper limit of
the calibrated range or is lower than 25% of the lower limit of the calibrated range, it
will flash.
Flashing prompt.
“0”—turn off the alarm function, prompt “NO”
“1”—turn on the alarm function, prompt “YES”
4.3.5 Exit setting menu
End: Exit the setting menu, settable range (0~1)
“0”—Do not save the setting value and exit the setting state, the prompt is “NO”
"1" - Save the setting value and exit the setting state, the prompt is "YES"