Professional Documents
Culture Documents
Atx 410 A
Atx 410 A
GENERAL DESCRIPTION
• Applicable for R410A
• Application: General refrigeration and air conditioning
system.
• Suitable for refrigeration systems with hot gas defrosting.
SPECIFICATIONS
• Max. working pressure: 3.3 MPa {33kgf/cm2}
• Adjustable range of static superheat: 1 to 7°C
• Increase about 0.007MPa / rotation
TYPE ATX–D
C 10 to −20
− TS TB
CL −10 to −40
VALVE NOMENCLATURE
Catalog No. is decided according to the specifications.
Example: ATX – 34006 B V C
Ⅰ Ⅱ Ⅲ Ⅳ Ⅴ
Ⅰ: Type ... ATX–Thermostatic expansion valve for general use.
Ⅱ: Model ... The first and the second digits indicate inlet and outlet pipe size respectively.
The last three digits indicate nominal capacity.
Ⅲ: Connection ... B–Flare Nut Connection D–Solder Connection
Ⅳ: Refrigerant ... V = R410A
Ⅴ: Charge type ... C = C–charge, CL = CL–charge
65
DIMENSIONS Type H h A B
Type ATX–B
φ68 ATX–34006D
φ3×2000 107 30 31 38
to 34045D
ATX–57060D
132 52 34
to 71160D
51
ATX–12220D
107
138 56 36
to 12500D
31
100
φ16
30
38 ACCESSORY
Sensing Bulb Mounting Band
●
φ68
14
φ3×2000 φ6 12.6 11×φ6
16
116.6 10×12.6
(=126)
(5.4)
267
t=0.4
H
100
φ16
h
14
B φ6 12.6 12×φ6
7
OD
16
ID
174 11×12.6
(=138.6)
(5.4)
337
t=0.4
SYSTEM EXAMPLE
Heat Pump Chiller System
• In case of using ATX in heat pump circuits, sensing bulb and external equalizer shall be mounted at a position
between 4way reversing valve and accumulator.
COMPRESSOR
HEATING CYCLE
ACCUMULATOR
Outlet
Inlet
66