Professional Documents
Culture Documents
HVAC Systems
HVAC Systems
HVAC Systems
Advanced Vapour
Compression Cycles
CONTENTS
Advanced Vapour Compression 1-2A to 1-10A
Part-1 :
Cycles: Review of Vapour
Compression Cycle
1-1A (ME-Sem-7)
1-2A (ME-Sem-7) Advanced Vapour Compression Cycles
PART-1
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
This mechanism consists of following essential parts as shown in
Fig. 1.2.1.
i. Compressor :
1. The low pressure and temperature vapour refrigerant from evaporator
is drawn into the compressor through the inlet or suction valve A,
where it is compressed to a high pressure and temperature.
2 This high pressure and temperature vapour refrigerant is discharged
into the condenser through the delivery or discharge valve B.
Insulated cold
chamber
Low pressure
liquid vapour
mixture
Evaporator
Low pressure vapour Expansion valve
Pressure gauge
Pressure or refrigerant
control valve
gauge High pressure
Low pressure side
vapour
High pressure
liquid
A B Condenser
Compressor
Receiver
Que 1.3.
Describe a simple vapour compression refrigeration
system with the help of p-h and T-s diagram.
Answer
The working of a single stage simple vapour
compression cycle is
explained with the help of following five cases:
When the Vapour is Dry and Saturated at the End of
Compression : The four process of the cycle are shown on T-s and
p-h diagrams in Fig. 1.3.1(a) and (b).
|T,=T,
Temperature. Cond. 2
P2P3 Cond.
2
Comp. Pressure
Comp.
Exp. PiP4/ Exp.
4, Evap.
1
4 Evap
S= S
Entropy h
(a) T-s diagram Enthalpy
(b) p-h diagram
Fig. 1.3.1.
i.
Compression Process (1-2):
1. The
vapour refrigerant at low pressure p, and
temperature T, is
compressed isentropically to dry saturated vapour.
2. Work done
during isentropic compression per kg is given by,
W=h,-h,
Where, h, = Enthalpy of vapour
T, (i.e., at suction ofrefrigerant
at temperature
the compressor), and
HVAC Systems 15A (ME-Sem-7)
COP =
Refrigerating effect
Work done
Exp.
Exp.
P1=P4 T41Evap.
4 Evap.
Entropy Enthalpy
(a) T-s diagram (6) p-h diagram
Fig. 1.3.2.
C When the Vapour is Superheated after Compression :
1. Avapour compression cycle with superheated vapour after compression
is shown on T-s and p-h diagrams in Fig. 1.3.3a) and (b) respectively.
Exp.
Exp. P,=P.
A
T,=T,
Evap. /
4
Evap.
Entropy hy=h, h, h,
(a) T-s diagram Enthalpy
(b) p-h diagram
Fig. 1.3.3.
2. In this cycle, the enthalpy at point 2is found out with the help of degree
of superheat.
3. The degree of superheat may be found out by equating the entropies at
points 1 and 2.
d. When the Vapour is Superheated before Compression:
1. Avapour compression cycle with superheated vapour before compression
is shown on T-s and p-h diagram in Fig. 1.3.4(a) and (b) respectively.
2. In this cycle, the evaporation starts at point 4 and continues upto point
1', when it is dry saturated. The vapour is now superheated before
entering the compressor upto the point 1.
3. The coefficient of performance may be found out as usual from the
relation,
COP = Refrigerating effect h, - h,
Work done h, -h,
HVAC Systems 1-7A (ME-Sem-7)
-Temperature Cond. 2
3 2"
Pressure 2
Comp.
1 1
Sat. vapour
Sat. liquid line
line Cond.
Temperature 2
Pressure 3/ Cond.
3' 2'
3 2
2
Under
cooling Comp. Under
IComp.
cooling
Exp 1
4 4' Evap. 4
Evap.
-Entropy Enthalpy
(a) T-s diagram. (6) p-h diagram.
Fig. 1.3.5.
2 The ultimate effect of the undercooling is to increase the value of
coefficient of performance under the same set of conditions.
3 In this case, the refrigerating effect or heat absorbed or
extracted,
R, = h, -h, =h, - hg (:: h, =h)
and work done, W= h,-h,
COP = Refrigerating effect
Work done
1-8A (ME-Sem-7) Advanced Vapour Compression Cycles
36.022 187.397
Answer
Given : hy =h, = 84.868 kJ/ kg, h, =187.397 kJ/kg, Q=7 tonne
h, = 210 kJ/kg, T, = 50°C
To Find: iRefrigerant flow rate.
i Power required to run the compressor.
ü COP of the system.
1. The cycle is shown on T-s diagram in Fig. 1.4.1.
3
Condensation
50 °C
Evaporation
1 0 °C
R,
Entropy
Fig. 14.1.
2 The refrigerant flow rate,
m = 210Q
(h, - h) x60
210 x7
(187.397-84.868) x60
HVACSystems 1-9A (ME-Sem-7)
= 0.238 kg/s
3. The power required to run the compressor
= m(h,-h,)
= 0.238 (210- 187.397)
= 5.38 kW
2
2
333 2
(K)
Temperature
318 Pressure
4
263/
4
h,
hy
h,
Entropy Enthalpy
(a) T-s diagram (6) p-h diagram
Fig. 1.5.1.
1. The various values as head from p-h chart of R-40 are as follows :
hy = 45.4 kJ/kg, h, = 133 kJ/kg, h, =460.7 k.J/kg, h, =483.6 kJ/kg,
Sn = 0.183 kJ/kg-K, Sg =0.485 kJ/kg-K, s, =S, = 1.637 kJ/kg-K,
S, = 1.587 kJ/kg-K
1-10A (ME-Sem-7) Advanced Vapour Compression Cycles
2 We know that entropy at point 2,
$,= Sy +2.3 C, log
333
1.637 = 1.587 + 2.3 C,,log
318
= 1.587+ 2.3 C, x 0.02 = 1.587+ 0.046 C,
C = 1.09
3. Enthalpy at point 2,
h, = hy + C, x Degree of superheat
= hy +CT,-T;)
= 483.6+ 1.09(333 -318)
= 483.6 + 16.35
= 500 kJ/kg
4. COP of the refrigerator,
460.7-133
COP =
500 -460.7
= 8.34
PART-2
Questions-Answers
P2 33'
P1t 2 2
h (Enthalpy)
Fig. 1.6.1. Effect of superheating.
B. Effect of Sub Cooling of Condensate:
1 From p-h diagram, Fig. 1.6.2, it is clear that refrigerating effect, R,
increases from (h, -h,) to (h,-h,) without any change in compressor
work, We
2. We know that, COP = Rg
We
p (Pressure)
4' 4
P2 3
P1
1' 1
h (Enthalpy)
Fig. 1.6.2. Effect of sub cooling of liquid.
3 The sub cooling results in increase of COP provided that no further
energy has to be spent to obtain the extra cold coolant required.
4 Sub cooling of condensate is generally used to improve the COP of the
cycle.
Que 1.7. Discuss the effect of variation of condenser and
evaporator pressure on COP.
Answer
A. Effect of Change in Suction Pressure (Evaporator Pressure) :
1 In actual practice, the suction pressure (or evaporator pressure)
decreases due to the frictional resistance of flow of the refrigerant.
1-12A (ME-Sem-7) Advanced Vapour Compression Cyeles
2 Let us consider a theoretical vapour compression cycle 1l-2-3-4' when
the suction pressure decreases fromp, to p, as shown on p-h diagram in
Fig. 1.7.1.
2 2'
Pa
Pressure
p. 4
hg=hy =h hhË hy hy
Enthalpy
Fig. 1.7.1. Effect of suction pressure.
3. It may be noted that the decrease in suction pressure:
Decreases the refrigerating efect from (h, -h) to (h,, -h,), and
Increases the work required for compression from (h, - h,) to
(h, -h,).
4 Since the COP of the system is the ratio of refrigerating effect to the
work done, therefore with the decrease in suction pressure, the net
effect is to decrease the COP of the refrigerating system for the same
amount of refrigerant flow.
B. Effect of Change of DeliveryPressure (Condenser Pressure):
1. In actual practice, the discharge pressure (or condenser pressure)
increases due to frictional resistance of flow of the refrigerant.
2 Let us consider a theoretical vapour compression cycle 1-2-3-4' when
the discharge pressure increases fromp,to p, as shown onp-h diagram
in Fig. 1.7.2.
3
Pi 2
4Pa 2
Pressure
hg=h, h =hË hË h, hy
-Enthalpy
Fig. 1.7.2. Efect of discharge pressure.
1-13 A (ME-Sem-7)
HVAC Systems
PART-3
Questions-Answers
Answer
1. Atranscritical cycle is a closed thermodynamic cycle where the working
fluid goes through both subcritical and supercritical states
2 In transcritical systems, CO, is cooled but does not condense at the gas
cooler outlet, being above critical temperature.
3 Transcritical CO, booster systems are the most promising solutions for
using natural refrigerants in retail contexts, above all in climates that
are not too hot.
4 Advantages of transcritical cycle are :
It completely uses natural refrigerants (CO,), and
Higher efficiency.
5 Disadvantages of transcritical cycle are:
High pressures involved, and
Systems are normally more complex than traditional ones.
Que 1.9. Discuss in brief ejector refrigeration system with help
of diagram.
Answer
1. An ejector refrigeration system can be considered as a modification of a
conventional vapour compression cycle (VCC).
1-14A (ME-Sem-7) Advanced Vapour Compression Cycles
2. An ejector takes the place of a compressor to pressurize the
refrigerant
vapour flowing from an evaporator and discharge it toa condenser.
3. The conventional
ejector refrigeration cycle is shown in Fig. 1.9.1.
4. Working fluid is heated at a high pressure and
temperature in the
generator. High-pressure refrigerant vapour enters the nozzle. Working
fluid is then accelerated to a high velocity and entrains motive steam
from the evaporator, resulting in a cooling effect.
5. After that, mixed vapour steams are discharged from the nozzle to the
condenser where they are cooled down and condensed to liquid fluids.
6. A part of the liquid refrigerant returns to the evaporator
through an
expansion valve whereas the other part is pumped to the generator.
7. Ejector cooling technology can be used for air conditioning in trains and
large buildings.
Heat source
4
Gnrator
Eragorgtor
4
Cooling effect
Fig. 1.9.1.
4 The region on the chart to the left of the saturated liquid line is called
the sub-cooled region.
5. The area to the right of the saturated vapour line is superheated region
in the form of a superheated vapour.
6. The section of the chart between the saturated liquid and saturated
vapour lines is the two phase region and represents the change in phase
of the refrigerant between liquid and vapour phases.
7. p-h chart gives directly the changes in enthalpy and pressure during a
process for thermodynamic analysis.
Critical point
TT
Critical pressure i
Superheated
vapour region
Sub-cooled Wet vapour
Pressure
liquid region region
iSuperheated
vapour line
V
Saturated
liquid line
Enthalpy
Constant volume
Constant temperature
Constant entropy
Fig. 1.10.1. Pressure enthalpy (p-h) chart.
Apa 8
10 9
11
Pe
2
"Ps
TAps
PART-4
Questions-Answers
system.
Que 1.12. Classify the refrigerants used in refrigeration
Answer
Refrigerant
Secondary refrigerant
Primary refrigerant
Halocarbon compounds
Water
Azeotropes Sodium chloride brine
Hydrocarbons Calcium chloride brine
Inorganiccompounds
Unsaturated organic compounds Ethylene glycol
refrigerant and its types.
Que 1.13. Discuss in brief about primary
Answer
refrigerantswhich directly take part in
A Primary Refrigerants:Thosecool the substance by the absorption of
the refrigeration system and
latent heat are called primary refrigerants.
chloride,
Example: Ammonia, Caron dioxide, Sulphurdioxide, Methyl
Freon group etc.
B. Types of Primary Refrigerants :
i. Halocarbon Compounds : They are obtained after replacing one or
with halogens
more hydrogen atoms in a hydrocarbon ethane or methane
(chlorine, bromine or fluorine).
Example : R-11 (Trichloro-nonofluoromethane), R-12 (Dichlorodi
fluoromethane)
ii. Azeotropes: The refrigerants belonging to this group consist of mixtures
of different substances. These substances cannot be separated inte
1-18 A (ME-Sem-7) Advanced Vapour Compression Cycles
components by distillation. They possess fixed thermodynamic properties
and do not undergo any separation with changes in temperature and
pressure. An azeotrope behaves like a simple substance.
Example:R-500, R-502, etc.
iii. Hydrocarbons : Most of the refrigerants of this group are organic
compounds. Several hydrocarbons are used successfully in commercial
and industrial installations. Most of them possess satisfactory
thermodynamic properties but are highly inflammable.
Example :Methane, Ethane Butane, etc.
iv. Inorganic Refrigerants:The inorganic refrigerants were exclusively
used before the introduction of halo-carbon refrigerants. These
refrigerants are still in use due to their inherent thermodynamic and
physical properties.
Example :R-717 (Ammonia), R-729 (Air), etc.
V.
Unsaturated Organic Compounds : The refrigerants belonging to
this group possess ethylene or propylene as their constituents.
Example :R-1120 (Trichloroethylene), R-1130 (Dichloroethylene), etc.
Que 1.14. Write short note on following:
i. CFC, ii. HFC,
iii. HOFC, and iv. Zeotropic.
Answer
i. CFC:
1 CFC refers to the chemical composition of the refrigerant.
Chlorofluorocarbon indicates that the refrigerant is comprised of
Chlorine, Fluorine, and Carbon.
2. Common CFC refrigerants are: R-11, R-12, R-13, R-113, R-114, and R
115.
ii. HFC:
1 HFC refrigerant (hydrofluorocarbons) is the third generation of
fluorinated refrigerants.
2 Recognized as Ozone Depleting Potential (ODP) and Global
Potential (GWP), they represent a greener alternative to Warming
CFC and
HCF.
iii. HCFC:
1
Hydrochlorofluorocarbons
used in the
(HCFCs) are chemical compounds commonly
foam, refrigeration, and air conditioning
the protective ozone layer and contribute to climatesectors that destroy
change.
2 It is essential to reduce and phase out the use of
practices. HCFCs in industry
HVACSystems 1-19 A (ME-Sem-7)
iv. Zeotropic:
1. Zeotropic refrigerant contains two or more components whose
equilibrium vapour phase and liquid phase compositions differ.
2. The temperature of a zeotropic refrigerant change as it evaporates or
condenses at constant pressure.
Answer
1 An anti-freeze is an additive which lowers the freezing point of water
based liquid and increases its boiling point. The most common anti
freeze used in refrigerator is ethylene glycol.
2 Anti-freeze solution is atype of aditive which is responsible for lowering
the freezing point of any type of fluid which is water-based.
3 Such solutions can be used in the engine coolant systems of different
types of vehicles or in the solar panel water heating systems too.
4 One major substance which is very commonly used as an anti-freeze
substance is the compound of ethylene glycol.
5. Itis specifically used in the coolant systems ofengines. It is also used for
several other systems like the compression of gas, air conditioning, and
ventilating systems.
1-20 A (ME-Sem-7)
Advanced Vapour Compression Cycles
Que 1.17. Explain in brief about phase
changing materials.
Answer
1. Phase changing materials (PCMs) are ideal products for thermal
management solutions. This is because they store and release thermal
energy during the process of melting and freezing (changing from one
phase to another).
2 When such a material freezes, it releases large amounts of
the form of latent heat of fusion, or energy of energy in
when the material is melted, an equal amount crystallization. Conversely,
of
from the immediate environment as it changes fromenergy is absorbed
solid to liquid.
3 This property of PCMs can be used inanumber of ways,such as
energy storage whereby heat or coolness can be stored from one thermal
or period in time, and used at a later date or process
different location.
4 PCMs are also very useful in providing thermal barriers or
for example in temperature controlled transport. insulation,
5 The simplest, cheapest, and most
effective phase change material is
water/ice. Unfortunately, the freezing temperature of water is fixed at
0°C(32°F), which makes it unsuitable for the majority of
applications.
energy storage
6 Therefore a number of different materials have been identified and
developed to offer products that freeze and melt like waterice, but at
temperatures from the cryogenic range to several hundred degrees
centigrade.
PART-5
Desired Properties of Refrigerants, Requirements for Refrigerant,
Classification based on Safety, Refrigerant Oils and Applications,
Properties and uses of Commonly used Refrigerant,
Greenhouse Effect, Global Warming, Future
Refrigerants Like Hydrofluoro-Olefines.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
1-21A (ME-Sem-7)
HVACSystems
Que 1.18. What are the desirable properties of an ideal
refrigerant ?
Answer
The desirable properties of an ideal refrigerant are as follows :
1. Low boiling point,
2. Low specific heat of liquid,
3. Low specific volume of vapour,
4. Low cost,
5. High eritical temperature,
6. High latent heat of vapourisation,
7. Non-corrosive to metal,
8 Non-toxi,
9. High thermal conductivity,
10. Non-flammable, and
11. Easily available.
Answer
A On Basis of Safety Refrigerant :
1. Higher flammable,
2. Lower flammable, and
3. No flame propagation.
B. On Basis of RefrigerantsOils:
1 Immiscible,
2. Miscible, and
3 Partially miscible.
commnonly
Que 1.21. Write down the propertiesand uses of some
used refrigerants.
Answer
i. Air (R-729) :
a. Properties:
1 No cost involved, easily available.
2. Completely non-toxic.
3 Completely safe.
b. Uses : It is used in aireraft refrigeration.
ii. Ammonia (R-717):
a. Properties:
1. It is highly toxic, flammable, irritating and food destroying.
2 It has excellent thermal properties.
3. It has the highest refrigerating effect per kg of refrigerant.
HVAC Systems 1-23 A (ME-Sem-7)
b. Uses:
1 It is widely used in large industrial and commercial reciprocating
compression systems where high toxicity is secondary.
2 It is widely used as the refrigerant in absorption systems.
ii. R-12 Dichlorodifluoromethane)or Freon-12 (CCI,,) :
a, Properties:
1 It is non-toxic, non-flammable, non-explosive and non-corrosive
therefore, it is most suitable refrigerant.
2 It is fully oil miscible therefore it simplifies the problem ofoil return.
3 It does not break even under the extreme operating conditions.
b. Uses:
1 It is suitable for high, medium and low temperature applications.
2 It is used for domestic applications.
iv. R-113 (Trichlorotrifluoroethane) or Freon-13 (CCI,FCCIF, or
C,Cl,F,) :
a. Properties:
1 It has a boiling point of 47.6 °C at atmospheric pressure.
2 It remains liquid at room temperatures and pressures and as such
it can be carried in sealed tins rather than cylinders.
b. Uses: It is used in commercial and industrial air-conditioning with
centrifugal compressor systems.
Answer
1. Ethane in very low temperature refrigeration and in non-mechanical
heat transfer.
2. Isobutane in retail food refrigeration (stand-alone commercial
refrigerators and freezers) and in vending machines.
3. Propane in household refrigerators, freezers, or combination
refrigerators and freezers, in vending machines and in room air
conditioning units.
4. The hydrocarbon blends R-441A in retail food refrigeration, in vending
machines and in room air conditioning units.
5. HFC-32 (difluoromethane) in room air conditioning units. HFC-32 has
one-third the global warming potential (GWP) of conventional
refrigerants currently used in room air conditioning units.
1-24 A (ME-Sem-7) Advanced Vapour Compression Cycles
Answer
Hydrofluoro-ole fins (HFOs) are unsaturated organic compounds
composed of hydrogen, fluorine and carbon.
2 These organofluorine compounds are of interest as refrigerants. Unlike
traditional hydrofluorocarbons (HFCs)and chlorofluorocarbons (CFCs),
which are saturated, HFOs are olefins, otherwise known as alkenes.
CONTENTS
Part-1 : Review of Psychrometry : .2-2A to 2-7A
Psychrometric Properties
Part-2 : Psychrometric Chart and 2-7A to 2-14A
Psychrometric Processes
PART-1
Review of Psychrometry :Psychrometric Properties.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
P, Pb
Ps 1-Po
Pb
iii. Relative Humidity :
1 It is the ratio of actual mass of water vapour (m,)in a given volume of
moist air to the mass of water vapour (m,) in the same volume of
saturated air at the same temperature and pressure. It is denoted by .
Relative humidity (4) =
m,
2. Let p,, V, I, m, and R, = Pressure, volume, absolute temperature,
mass and gas constant respectively for water vapour in actual conditions,
and
1-Ps 1-P
P P
1 P
1-¢x P Ps
Pb Pb
=
1-(1-)P
Pb
iv. Pressure of Water Vapour : According to Carrier's equation, the
partial pressure of water vapour,
P,= Pw (p, -PT-T,)
1544-1.44T,
Where, P, = Saturation pressure corresponding to wet bulb
temperature (from steam tables),
P;= Barometric pressure,
T, = Dry bulb temperature, and
= Wet bulb temperature.
v. Vapour Density or Absolute Humidity :
1 The vapour density or absolute humidity is the mass of water vapour
present in 1m² of dry air.
2 Let, V, =Volume of water vapour in mkg of dry air at its partial
pressure,
U, = Volume of dry air in m³kg of dry air at its partial pressure,
P, = Density of water vapour in kg/m corresponding to its
partial pressure and dry bulb temperature T, and
P, = Density of dry air in kg/m of dry air.
3. We know that mass of water vapour is,
..(2.2.6)
4 Mass of dry air,
m, = U, Pa ...(2.2.7)
5. Dividing eq. (2.2.6) by eq. (2.2.7), we get
2-6A (ME-Sem-7) Review of Psychrometry
V,Pa
W= P
Pa
Or
P, = Wp, ..(2.2.8)
6. We know that, P,U,= ma ...(2.2.9)
Since Va = Vp, and m, = 1 kg, therefore substituting these values in
eq. (2.2.9), we get
1
P, X T,
Pa
Or
Pa
Pa =
R,T,
7. Substituting the value of p, in eq. (2.2.8), we get
P, = Wp,W(P,-P,) (" P, =P, +P,)
R,T,
Where, P.= Pressure of air in kN/m²,
R, = Gas constant for air = 0.287 kJ/kg-K, and
T, = Dry bulb temperature in K.
Que 2.3. 10 grams of moisture per kg of dry air is removed from
atmospheric air when it is passed through an air conditioning
system and its temperature becomes 20 °C. The atmospheric
conditions are 40 °C DBT and 60 % RH.
Find the following for the conditioned air :
i. Relative humidity,
ii. Wet bulb temperature,
ii. Dew point temperature,
iv. Enthalpy change for the air, and
Assume standard atmospheric pressure.
AKTU 2015-16, Marks 10
Answer
= P
0.60 = P,
0.0737
P, = 0.044 bar
3. Specific humidity,
W= 0.622p,
P.-P,
0.622x0.044 (: p,= 1.0132 bar)
W=
1.0132-0.044
W= 0.0282 Kg Kg of dry air
4. Specific humidity after remaining 0.010 kg of water vapour,
W, =0.0282 0.010 = 0.0182 Kg Kg of dry air
and partial pressure of water vapour, p, , at this condition,
W, = 0.622p,
P.-P,
0.0182 = 0.622p,
1.0132-p,
0.01844-0.0182 p, = 0.622p,
,0.01844 = 0.6402 p,
P, = 0.0288 bar
4. Corresponding to 20 °C from steam table, P, =0.0234 bar
0.0288
5 Relative humidity, =P =1.23 or 123 %
Pus 0.0234
6 Corresponding to 0.0288 bar, from steam table
Dew point temperature, T,, = 24 °C
7. From psychrometric chart,
Wet bulb temperatuie, Twp = 17 °C
8. Enthalpy of air, h, = 1.005 T, + W(2500 + 1.88 T)
= 1.005 x 24 + 0.0182 (2500 + 1.88 x 24)
= 70.44 kJ/kg
and enthalpy of air corresponding to 40 °C DBT and 60 %RH,
h, = 112.5 kJ/kg
9. So, enthalpy change =h, -h, = 112.5 70.44 = 42 kJ/kg
PART-2
Questions-Answers
Sp.
humidity
'2
W=W2
Ta2 Tas
Dry bulb temperature
Fig. 2.4.1. Sensible heating.
HVAC Systems 2-9A (ME-Sem-7)
ii. Sensible Cooling :
1. The cooling of air without any change in its specific humidity is known
as sensible cooling.
2 Thus the sensible cooling can be achieved by passing the air over
cooling coil like evaporating coil of the refrigeration cycle or secondary
brine coil.
3. The heat rejected by air during sensible cooling is obtained from the
psychrometric chart by the enthalpy difference (h, - h,).
Enthalpy
h Sp.
humidity
W, =W2
Sp.
humidity Sp.
humidity
W2 W
1
W 2 W
Sp.
humidity
W.
T=7u1
humidity
Sp.
Tw13
3 2 2" W3
W
W
Enth
humnidity
W
ADP Sp.
4
Ta2 Ta1
Dry bulb temperature
Fig. 2.4.6. Cooling and dehumidification.
5. Let, T = Dry bulb temperature of air entering the coil,
Tdol = Dew point temperature of the entering air, and
=Ta3
T = Efective surface temperature or ADP of the coil.
6. Under ideal conditions, the dry bulb temperature of the air leaving the
cooling coil (ie., T,) should be equal to the surface temperature of the
cooling coil (ie., AP), which is never possible due to inefficiency of the
cooling coil.
7. Thus, the resulting condition of air coming out of the coil is shown by a
point 2 on the line 1-4.
8. The total heat removed from the air during the cooling and
dehumidification process is,
Q= h,-h, =(h,-h) +(h, -hy)
= LH+ SH
Where, LH=h,-h, = Latent heat removed, and
SH= h,-h, =Sensible heat removed.
9. We know that sensible heat factor,
Sensible heat SH
SHF =
Total heat LH +SH h-h
vii. Heating and Dehumidification :
1 In this process, the air is passed over chemicals which have an affinity
for moisture.
2 As the air comes in contact with these chemicals, the moisture gets
condensed out of the air and gives up its latent heat.
3. Due to the condensation, the specific humidity decreases and the heat
of condensation supplies sensible heat for heating the air and thus
increasing its dry bulb temperature.
4 The effectiveness or efficiency of the dehumidifier is given as,
HVAC Systems 2-13A (ME-Sem-7)
Actual increase in DBT T:a -T1
Ideal increase in DBT
T2-Ta
Actual
absorption Sp.
humidity
dehumidification
W,
3 W3
Adiabatic
dehumidification I2 -W
h
My h, W1 humidity
W,
W, Sp.
i
3> mhg, Ws
W2
Dry bulb temperature
Fig. 2.4.8. Adiabatic mixing of two air streams.
Let m, = Mass of air entering at 1,
h, = Enthalpy of air entering at 1,
W, = Specific humidity of air entering at 1,
m,, h, and W,= Corresponding values of air entering at 2, and
m, hg and W, = Corresponding values of the mixture leaving at 3.
4 Assuming no loss of enthalpy and specific humidity during the air mixing
process, we have
2-14A (ME-Sem-7) Review of Psychrometry
i For the mass balance,
m, + m= m,
i. For the energy balance,
m,h, t m,hy= m,h,
ili. For the mass balance of water vapour,
m,W, +m,W,= m,W,
PART-3
Questions-Answers
Answer
1. By-pass factor is defined as the ratio of the difference between the
mean surface temperature of the coil and leaving air temperature to the
difference between the mean surface temperature and the entering air
temperature.
Let 1 kg of air at temperature T, is passed over the coil having its
temperature T, as shown in Fig. 2.5.1.
Insulated apparatus
T43
Ta2
Tai
Fig. 2.5.1. By-pass factor.
3. When the air passes over a coil, some of it (say x kg) just by-passes
unaffected while the remaining (1 -x) kg comes in direct contact with
the coil. This by-pass process of air is measured in terms of a by-pass
factor.
4. The by-pass factor depends upon the following factors :
The pitch of the cooling coil fins.
The number of rows in a coil in the direction offlow.
iüi. The velocity of flow of air.
5. On balancing the enthalpies, we get
x Com Ta +(1-*) Cpm Tds = 1x Cpm Ta2
Where, pm = Specific humid heat.
Or
x(Td8-1)=13-Td2
-Ta2
Tas-Ta1
Where x is called by-pass factor of the coil and is generally written as
BPF.
7. By-pass factor for heating coil is given by
BPF = Tas -Ta2
Tas-Ta1
8. Similarly, by-pass factor for cooling coil is given by
BPF = Ta2-Ta3
T-Tas
Que 2.6. Write short note on
Cooling,
iü.. Dehumidifying coils,
iüi. Apparatus dew point,
; iv. Heating coils.
-16 A (ME-Sem-7) Review of Psychrometry
Answer
Cooling :It is a general phenomenon where a medium exchanges its
heat with another colder medium either when both are separated by a
barrier or when both mixes, resulting in lower temperature.
ii. Dehumidifying Coil :
1 Any air conditioning coil carrying either chilled water or refrigerant or
chilled brine can result in a surface temperature lower than the dew
point of surrounding air.
2 When surrounding air passes over this surface, it loses its moisture
content. Also, the air gets cooled to a favorable temperature which could
be used for air conditioning.
iüi. Apparatus Dew Point (ADP):It is the effective surface temperature
of thecooling coi. It is also the temperature at afixed flow rate at which
both sensible and latent heat gains are removed at the required rates. It
is alsooften called as the 'Coil Temperature'.
iv. Heating Coils : It may be used with hot water or steam as the heat
transfer media whilst frost pre-heaters usually have electric heating
elements.
PART-4
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Que 2.7. With the help of a neat sketch explain about an air
washer.
Answer
In air washer system, the outsideor entering air is cooled below its dew
point temperature so that it loses moisture by condensation.
2. The moisture removal is also accomplished when the spray water is
chilled water and its temperature is lower than the dew point temperature
of the entering air.
HVAC Systems 2-17A (ME-Sem-7)
3. Since the air leaving the air washer has
its dry bulb temperature much
below the desired temperature in the room, therefore a heating coil is
placed after the air washer.
4 The air washer humidification may be
three ways : accomplished in the following
i By usingre-circulated spray water without prior heating of air.
iü. By pre-heating the air and then washing it with
re-circulated water.
i. By using heated spray water.
Make up
water
Pud T
E S
Pve
T>
Adsorption
dehumidification
Constant 2
WBT line
Answer
i. Water Injection :
1. Let liquid water at temperature t, be injected and sprayed into a flowing
air stream with the help of nozzles.
2 The condition of the air will change dpending on the amount of water
that evaporates.
3. The enthalpy of vaporization will come from the enthalpy of the air.
4. Let us consider that the amount of water that has been evaporated, m,
is exactly equal to the amount injected.
5. The process line is as shown in Fig. 2.10.1. The air flow rate is m,.
6. The mass and enthalpy balances give,
...(2.10.1)
m,
h, = h +
Curent WBT 20
2a
T1 T
h, = h + ...(2.10.4)
Ta
4. The process is shown in Fig. 2.10.2. The dry bulb temperature of air
changes very little during the process.
hg
2
Steam
injection
(0
T, T,
Fig. 2.10.2. Process with steam injection.
HVACSystems 2-21 A (ME-Sem-7)
PART-5
Summer Air Conditioning,
Winter Air Conditioning.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Questions-Answers
Answer
i Sensible Heat Factor (SHF):
1. It is defined as the ratio of the sensible heat to the total heat.
2. Mathematically, it is given as,
SH SH
SHF =
TH SH+ LH
Where, SH = Sensible heat,
LH= Latent heat,and
TH= Total heat.
ii. Grand Sensible Heat Factor (GSHF) :
1. Itis defined as the ratio of the total sensible heat to the grand total heat
which the cooling coil or the conditioning apparatus is required to handle.
HVAC Systems 2-23 A (ME-Sem-7)
PART-7
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Reservoir Blowers
Hot air
Fig. 2.14.1.
Answer
S. No. Comfort Air Conditioning Industrial Air Conditioning
1 In this, the dry bulb| In this, the dry bulb temperature
temperature of air and relative and relative humidity is kept
humidity is brought to the constant for proper functioning
required condition for human of machines and electronic
health, efficiency and comfort. items.
suitable sketch.
Que 2.18. Discuss in brief about comfort chart with
conditioning ?
What is the use of comfort chart for comfort air
Answer
A. Comfort Chart :
temperature is shown
1 The practical application of the concept ofeffective
by the comfort chart.
of people
2. This chart is the result of research made on different kinds
subjected to wide range of environmental temperature, relative humidity
and air movement by the American Society of Heating, Refrigeration
and Air-conditioning Engineers (ASHRAE).
velocity) to situations
3 It is applicable to reasonably still air (5 to 8 m/min air
where the occupants are seated at rest or doing light work and to spaces
the air
whose enclosing surfaces are at a mean temperature equal to
dry bulb temperature.
HVACSystems 2-27A (ME-Sem-7)
4. In the comfort chart, the dry bulb temperature is taken as abscissa and
the wet bulb temperature as ordinates.
5. The relative humidity lines are replotted from the psychrometric chart.
6. The statistically prepared graphs corresponding to summer and winter
season are also superimposed.
B. Use of Comfort Chart for Comfort Air Conditioning:The comfort
chart gives the following information :
1 0% 0
32 9 %
0
S u m m
s e
e a
rs o n
30
28 28
26 R H
i n
. e s
°C
24
temperature,
22
peol omfor a0
0
20
%
20
bulb
Wet 18 1 0
%
16
16
Comfort fe ling -26
peoplecomtortat
ZOne
14 14
F24.
12 10
12 20
A30
10
A0
50 of
60
o
A90
Ui00
6
Winte
ser ason
14
12
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
Answer
Factors affecting human comfort are as follows:
1, Effective Temperature: The numerical value ofeffective temperature
is made equal to the temperature of still saturated air, which produces
the same sensation of warmth or coolness as produced under the given
conditions.
2 Heat Production and Regulation in Human Body :The human
body acts like a heat engine which gets its energy from the combustion
of food within the body. The process of combustion produces heat and
energy due to oxidation. The rate at which the body produces heat is
termed as metabolic rate.
3. Heat and Moisture Loss from the Human Body:The heat is given
off from the human body as either sensible or latent heat or both. In
order to design any air conditioning system for spaces which human
bodies are tooccupy, it is necessary to know the rates at which these
two forms of heat are given off under different conditions of air
temperature and body activity.
4. Moisture Content of Air : The moisture content of outside air during
winter is generally low and it is above the average during summer
because the capacity of the air to carry moisture is dependent upon its
dry bulb temperature.
5. Quality of Air : The air in an occupied space at all times should be free
from toxic, unhealthful or disagreeable fumes such as CO,. It should
always be free from dust and odour.
6 Air Motion : The air motion which includes the distribution of air is
very important to maintain uniform temperature in the conditioned
space. No air conditioning system is satisfactory unless the air handled
isproperly circulated and distributed.
HVAC Systems 2-29 A (ME-Sem-7)
Constant effective
temperature line
0 10 20 30
Fig. 2.20,.1. Effective temperature chart.
Que 2.21. What are the outside design conditions for air
conditioning ?
2-30 A (ME-Sem-7) Review of Psychrometry
Answer
1. For the outside design conditions in summer, it is recommended to use
the mean monthly maximum dry bulbtemperature and its corresponding
wet bulb temperature.
2. The wet bulb temperatures fall usually at the time of maximum dry bulb
temperature.
3. However, it is essential to take the value of the wet bulb temperature in
this manner, and not the value of the maximum wet bulb temperature
as that would lead to an erroneously high cooling load. This is because
the relative humidity is the lowest when the dry bulb temperature is the
highest, and vice versa
4. As for winter, the concept of degree-days is used. It is found that the fuel
consumption in winter for the heating of buildings varies almost directly
as the difference between the outside temperature and a reasonably
comfortable inside temperature of 18.5°C (65°F).
5. Thus the fuel consumption would be practically nil if the outside
temperature is 18.5°C.
6. On the other hand, the fuel consumption, would double if the outside
temperature dropped from 13.5 to 8.5°C. A degree-day is obtained for
every degree when the mean outside temperature is below 18.5°C during
the 24- hour period.
7. Accordingly, if in a given locality the outside temperature average of 30
days is 10°C, the degree days for the period would be (18.5- 10(30) =
255.
3
UNIT
Heat Pump and
Ventilation
CONTENTS
Part-1 : Heat Pump : Introduction, .3-2A to 3-8A
Package Heat Pump with
Reversible Cycle, Decentralized
Heat Pump, Heat Pump with
a Double Bundle Condenser,
Industrial Heat Pump
3-1 A (ME-Sem-7)
3-2A (ME-Sem-7) Heat Pump and Ventilation
PART-1
Heat Pump : Introduction, Package Heat Pump with Reversible
Cycle, Decentralized Heat Pump, Heat Pump with a Double Bundle
Condenser, Industrial Heat Pump.
Questions-Answers
Que 3.1. What is heat reservoir ?Also discuss about heat pump.
Answer
A. Heat Reservoir:
1. Aheat reservoir is a body with a very large heat capacity to which, and
from which, heat can be transferred without any change in its
temperature.
2 Such a body at high temperature is referred to as a high temperature
reservoir.
If heat is transferred from it, then it is considered as a heat source.
3.
4
Abody at low temperature is referred to as a low temperature reservoir.
5.
If heat is transferred to it,then it is considered as a heat sink.
6 By definition, a heat reservoir is a closed system with no
work
interaction.
7. The environment constitutes the largest heat reservoir operating without
and
any change in temperature usually employed as a heat sink,
sometimes as a heat source.
8. The mediums in the environment which are used as such are generally
the following:
Atmosphere air,
Ocean, river or well water, and
ii. Ground.
is its
9. The characteristic which remains constant for a heat reservoir
temperature. Hence, a heat reservoir is characterised by its temperature.
B. Heat Pump:
1. A heat pump is a reversed heat engine. It receives heat from a low
temperature reservoir (source) and rejects it to a high temperature
reservoir (sink).
HVAC Systems 3-3A (ME-Sem-7)
2 This transfer of heat from a low temperature body to a high
one is essentially a non-spontaneous process. And that callstemperature
for the help
of an external work which is supplied to the heat
pump (Fig. 3.1.1).
High temperature sink
(T) T,>T,
W +Heat pump
COPHp =M
W ...(3.1.2)
- , =W
Hence, eg. (3.1.2) becomes
COP,HP = ...(3.1.3)
Answer
A. Carnot Cycle Operations (Processes) :
1 The system inside the cylinder has an initial volume and initial pressure
as indicated by the state point 'l' onp-V diagram.
2. Let Q, be the heat supplied to the system at T, (source temperature).
Since the heat supply (addition) takes place at constant temperature,
the system volume increases at constant temperature thus performing
an isothermal expansion.
a. Process 1-2 :(Isothermal Heat Addition Process):
1 During this process, the working substance (air) expands
isothermally from state '1' to state 2.
2 At point 2' heat supply is cut off and cylinder head is brought in
contact with an insulator or adiabatic cover.
b. Process 2-3 : (Reversible Adiabatic Expansion):
1 Adiabaticcover is brought in contact with the cylinder head and during
this process; the working substance is allowed to expand adiabatically so
that its temperature becomes T,.
C. Process 3-4 : (Reversible Isothermal Heat Rejection):
1. Adiabatic cover is removed and heat sink is brought in contact with the
cylinder head.
2 The working substance is compressed isothermally thus transferring
heat Q, to the heat sink at T,.
d. Process 4-1: (Reversible AdiabaticCompression) :
1 The adiabatic cover is again brought in contact with the cylinder
head and the system is compressed adiabatically.
Heat source T; Q, Cylinder with insulated walls
Piston
Insulator or |iair!
adiabatic cover
Heat sink T,
4
4
14
P-----}1 I3' I2
Volume Entropy
(a) p-v diagram. (6) T-s diagram.
Fig. 3.2.3. Reversed Carnot cycle.
2 At point 1, letp,, V,,T, be the pressure, volume and temperature of air
respectively.
3. The four processes of the cycle are as follows :
IsentropicCompression Process :
1. The air is compressed isentropically as shown by the curve 1-2 on
and T-s iagrams. p-u
2. During this process, the pressure of air increases fromp, top, specific
volume decreases from v, to v, and temperature increases from T,to
3. We know that during isentropic compression, no heat is
rejected by the air. absorbed or
b. Isothermal Heat Rejection Process :
1 The air is now compressed isothermally (i.e., at
T, = T)as shown by the curve 2-3 on p-v and T-s constant temperature,
diagrams.
During this process, the pressure of air increases from p, top, and
specific volume decreases fromu, to Ug.
3 We know that the heat rejected by the air during
per kg of air, isothermal compression
4R=42-3= Area233-2'
= T,8,- 8j)=Ts,-8)
C
Isentropic Expansion Process :
1 The air is now expanded
3-4 on p-V and T-s diagrams. isentropically as shown by the curve
3-6A (ME-Sem-7) Heat Pump and Ventilation
T,(s, - 8,) T
(T, - TXS, - S,) T, -T,
6. Though the reversed Carnot cycle is the most efficient between the
fixed temperature limits, yet no refrigerator has been made using this
cycle.
This is due to the reason that the isentropic processes of the cycle
require high speed while the isothermal processes require an extremely
low speed.
8 This variation in speed of air is not practicable.
Answer
PART-2
Ventilation : Introduction, Purposeof Ventilation.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
A Ventilation : Ventilation is the replacement of indoor air with fresh
outdoor air in order to dilute and displace the air pollutants (substances
that are harmful to humans) inside a building.
B. Purpose of Ventilation :
i. To Provide Oxygen : The oxygen concentration is 21% by volume in
atmospheric air. It should not be allowed to fall below 15% under any
circumstances.
i. To Remove Carbon Dioxide :The CO, concentrationinatmospheric
air is 0.03% by volume. It should not be allowed to rise above 5% under
any circumstance. For CO, dilution, a minimum fresh air flow of
0.2 cmm per sedentary adult is recommended.
iii. To Remove Odours : 0.42 cmm of fresh air per person is required to
remove body odours. The actual air requirement depends on room size
and level of activity.
iv. To Remove Heat and Humidity : Removal of body heat and moisture
addition by ventilation is the controlling factor.
V. To Dilute Toxicity: This is required when toxic and hazardous fumes/
particles are being generated in the space.
PART-3
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
1. Natural ventilation can generally provide a high ventilation rate more
economically, due to the use of natural forces and large openings.
2. Natural ventilation can be more energy efficient, particularly if heating
is not required.
3. Well-designed natural ventilation could be used to access higher levels
of daylight.
4. Advantage of natural ventilation is its ability to provide avery high air
change rate at low cost, with a very simple system. Although the air
3-10A (ME-Sem-7) Heat Pump and Ventilation
change rate can vary significantly, buildings with modern natural
ventilation systems can achieve very high air-change rates by natural
forces, which can greatly exceed minimum ventlation requirements.
Que 3.8. Define mechanical ventilation. What are its types ?
Answer
A. Mechanical Ventilation :
1. Mechanical ventilation systems are considered to be reliable in delivering
the designed flow rate, regardless of the impacts of variable wind and
ambient temperature. As mechanical ventilation can be integrated easily
into air-conditioning, the indoor air temperature and humidity can also
be controlled.
2. Filtration systems can be installed in mechanical ventilation so that
harmful microorganisms, particulates, gases, odours and vapours can
be removed.
3. The airflow path in mechanical ventilation systems can be controlled,
for instance allowing the air to flow from areas where there is a source
towards the areas free of susceptible individuals.
4. Mechanical ventilation can work everywhere when electricity is available.
B. Types of Mechanical Ventilation :
1. There are three types of mechanical ventilation systems:
i Exhaust-only, supply-only, and
:ii. Balanced.
2. Each system uses a combination of fans, ducting, dampers and controls.
PART-4
Questions-Answers
Answer
A. Tunnel Ventilation : It is system when exhaust fans are located at
one end of the house and two large openings are installed at the opposite
end.
HVACSystems 3-11 A (ME-Sem-7)
B. Types of Tunnel
follows :
Ventilation: Types of tunnel ventilation are as
i.
Longitudinal Ventilation :
1. Longitudinal ventilation is by far very common. It introduces in' and
removes air from' tunnel at one or more points. A
shown in Fig. 3.9.1. typical layout is
2. Fig. 3.9.1(a) shows system with jet
combination.
8
Fig. 3.9.1(b)shows a module with oneinjection
of air at one point, while
jet injection and one exhaust fan
D
Fan
AJet.
Pollutants
level
Ethaust Supply
fan fan
Jet
Pollutants
level
Exhaust
fan Exhaust air duct
PART-5
Questions-Answers
Answer
A. Air-Conditioning System: It is defined as an assembly of different
parts of the system used to produce a specified condition of air within a
required space of building.
B. Various Elements ofAir-Conditioning System: The basic
of air-conditioning system are :
elements
i. Fans:For moving air.
ii. Filters :For cleaning air, either fresh, recirculated or both.
iüi. Refrigerating Plant :Connected to heat exchange surface, such as
finned coils or chilled water sprays.
iv. Means for Warming:The air, such as hot water or steam heated coils
or electrical elements.
vi. Means for Humidification or Dehumidification.
vi. Control System : Toregulate automaticallythe amount of cooling or
warming.
Que 3.12. Explain various steps of an air conditioning plant. What
is the function of each component ?
Answer
A. Air Conditioning Cycle : An air conditioning cycle comprises the
following steps :
Supply duct Supply outlet
Heating or
cooling coil (Fan)
Air-conditioned
Secondary space
filter
(Electrostatic
or fabric type)
Self cleaning
filter
Return duct return outlet
Fig. 3.12.1. Air conditioning cycle.
3-14 A (ME-Sem-7) Heat Pump and Ventilation
the openings in
1. The fan forces air into duct-work which is connected to terminals.
outlets or
the room. These openings are commonly called
2. The duct-work directs the air to the room through
the outlets.
as required. Dust
3 The air enters the room and either heats or cools
carried along with it.
particles from the room enter the air stream and are
4 Air then flows from the room through a second
outlet (sometimes called
duct-work, where dust particles
the return outlet) and enters the return
are removed by a filter.
upon the
5 After the air is cleaned, it is either heated or cooled depending
passed over the
condition in the room. If cool air is required, the air is
through
surface of a cooling coil; if warm air required, the air is passed
a combustion chamber or over the surface of a heating coil.
6. Finally the air flows back to the fan,and the cycle is completed.
Functions :
B. Main Parts of Air Conditioning Plant and their
the room.
1 Fan:The primary function of afan is to move air to and from
fan
2. Supply Duct:The function of asupply duct is to direct the air from
short as
as
to the room. In order that air may flow freely it should be
possible and have minimum number of turns.
3. Supply Outlets: The function of supply outlets is to distribute the air
evenly in a room.
4 Space: It is very important to have an enclosed space (i.e., room) since
ifit does not exist it would be impossible tocomplete the air cycle since
conditioned air from supply outlets would flow into the atmosphere.
5.
Return Outlets : These are the openings in the room surface. They
return
are employed to allow room air to enter the return duct (i.e.,
outlets allow air to pass from the room). They are actually located at
opposite extreme of a wall or room from the supply outlet.
6 Filters: Afilter is primarily used to clean the air by removing dust and
dirt particles. They are usually located at some point in the return air
duct. They are made of any materials from spun glass to composite
plastic. Other types operate on electrostatic principle.
7. Cooling Coil and Heating Coil or Combustion Chamber: The
cooling coil and heating coil or combustion chamber can be located either
ahead or after the fan, but should always be located after the filter. A
filter ahead of the coil is necessary to prevent the excessive dirt, dust
and dirt particles from covering the coil surface.
8 Summer Operation : The air-conditioning cycle cools the air during
summer operation. Return air from the room passes over the surface of
cooling coil, and the air cooled to the required temperature. If there is
too much moisture present, it is removed automatically as the air is
cooled by the coil.
HVAC Systems 3-15 A (ME-Sem-7)
9. Winter Operation:The air conditioning cycle adds heat to the air
during winter operation. This is achieved by passing the return air from
the room over the surface of a heating coil, etc.
PART-6
Unitary System, Central Air Conditioning System, Directs
Expansion System.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
A Unitary :
1 Unitary systems are packaged units in which all the equipments and
controls, for fulfilling the requirements of air-conditioning, are assembled
in a single casing with decorative covering. The components are factory
assembled, tested and balanced.
2 They can be directly installed in or near the vicinity to be air-conditioned.
The only utility required is a source of electricity, and for water-cooled
units,a supply of cooling water.
3 Various factory assembled units available are:
Attic Fans : An attic or exhaust fan isa cooling unit without any heat
transfer element such as a cooling coil.
ii. Remnote Units :A system in which air handling unit is separated from
the condensing unit is called a remote system.
ii. Self Contained Units: In aself contained unit the condensing unit
and other functional elements (such as coils and fans) are encased in
the same cabinet.
iv. Room Air-conditioners: Fig.3.13.1 shows a unit air-conditioner for
mounting in a window or wall bracket.
V. Unit Air-coolers: Aunit air-cooler is a special application of remote
units. It primarily reduces the temperature in insulated and sealed
storage rooms.
3-16 A (ME-Sem-7) Heat Pump and Ventilation
Air filter
Direct
expansion Return air
intake
cooling coil
Fresh air
Drip tray
intake
if required
Condenser
Access
Cooling water panel
inlet
Compressor
2. The central systems are generally employed for the loads above 25
tonnes of refrigeration and 2500m³/min of conditioning air.
HVAC Systems 3-17A (ME-Sem-7)
PART-7
AllWater System, All Air System, Air Water System.
Questions-Answers
Answer
1. In an all air system air is used as the media that transports energy from
the conditioned space to the A/C plant.
2. In these systems air is processed in the A/C plant and this processed air
is then conveyed to the conditioned space through insulated ducts using
blowers and fans.
3. This air extracts (or supplies in case of winter) the required amount of.
sensible and latent heat from the conditioned space.
3-20 A (ME-Sem-7) Heat Pump and Ventilation
4. The return air from the conditioned space is conveyed back to the plant,
where it again undergoes the required processing thus completing the
cycle. No additional processing of air is required in the conditioned space.
5. All air systems can be further classified into :
i. Single duct systems, or
Dual duct systems
6
The single duct systems can provide either cooling or heating using the
same duct, but not both heating and cooling simultaneously.
7 The dual duct systems can provide both cooling and heating
simultaneously.
Que 3.19. Mention advantages, disadvantages and application of
all air systems.
Answer
A. Advantages of AllAir Systems:
1 All air systems offer the greatest potential for energy conservation by
utilizing the outdoor air effectively.
2. By using high-quality controls it is possible to maintain the temperature
and relative humidity of the conditioned space within +0.15°C (DBT)
and + 0.5%, respectively.
3 Building pressurization can be achieved easily.
4 The complete air conditioning plant including the supply and return air
fans can be located away from the conditioned space. Due to this it is
possible to use a wide variety of air filters and avoid noise in the conditioned
space.
B. Disadvantages of All Air Systems :
1. They occupy more space and thus reduce the available floor space in the
buildings.
2. Retrofitting may not always be possible due to the space requirement.
3. Balancing of air in large and particularly with variable air volume
systems could be difficult.
C. Applications of all air systems : All air systems can be used in both
comfort as well as industrial air conditioning applications. They are
especially suited to buildings that require individual control of multiple
zones, such as office buildings, classrooms, laboratories, hospitals, hotels,
ships etc.
HVAC Systems 3-21 A (ME-Sem-7)
Answer
1. In air-water systems both air and water are used for providing required
conditions in the conditioned space.
2 The air and water are cooled or heated in a central plant. The air supplied
to the conditioned space from the central plant is called as primary air,
while the water supplied from the plant is called as secondary water.
3. The complete system consists of a central plant for cooling or heating of
water and air, ducting system with fans for conveying air, water pipelines
and pumps for conveying water and a roomn terminal.
4 The room terminal may be in the form of a fan coil unit, an induction
unit or a radiation panel.
CONTENTS
Part-l : Load Calculation : Solar Radiation, ....4-2A to 4 4A
Heat Gain through Glass :
Calculation of Solar Heat Gain
through Ordinary Glass Tables
Part-2 Shading Devices : Effect of Shading . . 44A to 4-6A
Devices, Fabric Heat Gain
Part-3 : Over All Heat Transfer 4-6A to 4-11A
Coefficient, Periodic Heat
Transfer through Walls and Roofs,
Empirical Methods to Calculate
Heat Transfer through Walls and
Roofs using Decrement Factor
and Time Lag Method
Part-4 : Infiltration : Stack Effect, Wind .4-11Ato 4-14A
Effect, Infiltration Load
Part-5 : Internal Heat Loads, System Heat ...4-14A to 4-17A
Gains, Break up of Ventilation and
Efective Sensible Heat Factor
Part-6 : Cooling and Heating Load .4-17A to 4-19A
Estimation, Psychrometric
Calculation for Cooling, Selection
of Air Conditioning Apparatus
Part-7 : Evaporative Cooling, Building 4-19A to 4-22A
Requirements and Energy
Conservation in Air Conditioning
Buildings
4-1A (ME-Sem-7)
Load Calculation
4-2A (ME-Sem-7)
PART-1
Load Calculation : Solar Radiation, Heat Gain through Glass :
Calculation of Solar Heat Gain through Ordinary Glass Tables.
Questions-Answers
Answer
1. The solar radiation intensity normal to the sun's rays incident upon a
plane surface situated in the limits of the earth's atmosphere, varies
with the time of the year as the distance of the earth from the sun
changes. Its value when the earth is at its mean distance from the sun
is called the 'solar constant'.
The normal value of the solar constant is assumed as 5045 kJ/m²-h.
2.
Radiation received at the surface of the earth is much less because,
much of it, while passing through earth's atmosphere, is scattered and
absorbed by dust and vapour particles and the gases in the atmosphere.
3. The solar heat reaches part of the earth's surface in the form of two
radiations:
Beam or Direct Radiation : The part of the sun's radiation which
travels through the atmosphere and reaches the earth's surface directly
is called Beam or direct radiation.
ii. Diffuser Sky Radiation :A large part of thesun's radiation is scattered,
reflected back into space and absorbed by the earth's atmosphere. A
part of this radiation is re-radiated and reaches the earth's surface
uniformly from all directions. It is called diffuse or sky radiation.
4 The total solar radiation reaching a surface is equal to the sum of the
direct and diffuse radiation.
Answer
1. Glass which is major material ofmost buildings provides the most direct
route for entry of solar radiation. For these reasons, the proper estimation
of heat gain through glass is necessary.
2 Heat transmitted through a glass surface depends on the wavelength of
radiation and physical and chemical characteristics of the glass. Part of
the radiation is absorbed, part is reflected and the rest is transmitted.
HVAC Systems 43A (ME-Sem-7)
3 Glass is opaque to the radiant energy emitted from sources below 200°C.
Thus glass has high transmissivity for short wavelength and low
transmissivity for long wave length radiation.
4 Direct solar heat gain can be reduced by using different type of glass,
glass construction and shades as follows:
Double pan glass reduces the solar heat by 10 %to 20%.
Special heat absorbing glass reduces the solar heat by 25 %.
iiü. Stained glass can reduce it upto 65 %depending upon its colour.
iv. Shading devices installed on the outside of windows reduce sun load
upto 15 %.
V.
Vertilation blinds and curtain shades reduce it by 30 %to 35 %.
5. Heat gain of aspace through glass then comprises:
E:
F: All the transmitted radiation.
A part of the absorbed radiation that travels to the room.
Heat transmitted due to the difference between the outside and inside
temperature.
Que 4.3. Calculate solar heat gain through ordinary glass tables.
Answer
1 The absorbed radiation raises the temperature of glass, and the glass
then transmits this heat partly to the outside and partly to the inside.
2 Thus from Fig. 4.3.1, T,
8 represents the temperature of glass, then the
heat gain of the space is given by,
Incident Glass at T,
Radiation
Absorbed Radiation
Entering Space
Outside at To Inside at T;
Reflected
Radiation Transmitted
Radiation
Inside film
Outside film.
coefficient fo coefficient f
UA(T,-T)
...(4.3.1)
Where f.=Inside film-coofficient of heat transfer,
subseripts Dand d denote the terms for direct and diffuse radiations
respectively,
A,=Glass area directly exposed to the sun and A
total glas8 area.
3 Writing a steady state energy balance for the gla88 sheet itself, we have
.(4.3.2)
where fo = outside film-coefficient of heat transfer.
4 In eq. (4.3.1) the left-hand side represents the heat gain of glass due to
absorption, and the right-hand side represents the heat loss by convection
and radiation from its two surfaces.
5 In this equation, the thermal resistance of glass has been neglected.
Eliminating , between eq. (4.3.1) and eq. (4.3.2), we get for the heat
gain of space
Q=A,un p+At,lj)+ np + UA(T, - T) ..4.3.3)
PART-2
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Z, is transmissivity
Glass Venetian
Blinds
Fig. 4.5.1. Heat gain of space through glass with venetian blinds shading.
PART-3
Over All Heat Transfer Coefficient, Periodie Heat Transfer
through Walls and Roofs, Empirical Methods to Caleulate
Heat Transfer through Walls and Roofs using Decrement Factor
and Time Lag Method.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
1. A wall may be composite, consisting of many sections of different
construction and insulating materials.
2. Also, the outside and inside wall surfaces may exchange heat by
convection and radiation with the surrounding atmosphere.
3. Thus, there will be more than one thermal resistance to heat transfer.
4. Taking into account the number of layers of different materials with
varying thickness Ax and thermal conductivity k, we have for the overall
heat transfer coefficient and overall thermal resistance R.
AT
q= UN= ...(4.7.1)
T1
T T
Wall
k
Air film
(1) 2 3
-f
T 1 2 3
f
k T;
Fig. 4.8.1. (c) Heat transfer through a composite wall air space.
5 The overall coefficient of heat transmission is given by,
1
U=
1 1
f k
"6. When air space is provided between the material as shown in
Fig. 4.8.1c), then the overall coefficient of heat transmission is given by,
1
U=
1 1
+...+
f.
Where, k = Thermal conductance of air space.
7. In case of interior walls or partitions, floors and ceilings, the temperature
in the adjoining unconditioned space is usually 5° to 10° below the outdoor
design temperatures but for kitchen, boiler rooms ete, it is often higher
than the outdoor temperature.
HVAC Systems 4-9A (ME-Sem-7)
Answer
1. Heat transmission through the walls and roofs of building structures is
not steady and is therefore, difficult to evaluate.
2. The two principal factors causing this are:
The variation of the outside air temperature-over a period of 24
hours.
The variation of the solar radiation intensity that is incident upon
the surface over a period of 24 hours.
3. The phenomenon is further complicated by the fact that a wall has a
thermal capacity due to which acertain amount of heat passing through
it is stored and is transmitted to the outside and/or inside at some later
time.
700
600 40
500
I 4
400 30 T,
300
200 20
100
10
4 12 4 12
Noon
Midnight Solar time Midnight
Fig. 4.9.1. Typical variation of solar radiation and
Outside air temperature during day.
Load Calculation
4-10 A (ME-Sem-7)
after solar
5. The maximum temperatures usually occur just 2-3 hours
noon while the minimum temperatures occur just before sunrise.
The
6. The outside air temperature t, follows nearly a harmonic variation.
mean line is shown at temperature tom':
Que 4.10. Discuss in brief empirical methods to calculate heat
transfer through walls and roofs. Explain any one.
Answer
A Empirical Methods to Calculate Heat Transfer through Walls
and Roofs :
transfer
1 There are two approaches to empirical calculations of heat
through walls and roofs. They are :
i The decrement factor and time lag method.
iü. The equivalent temperature differential method.
2 Both the methods use analytical-experimental results for their
formulations.
commonly used
3 The equivalent temperature differential method is more
by the air- conditioning engineers as it is also applicable to
sunlit walls
and roofs.
B. Decrement Factor and Time Lag:
instantaneous
1 If the thermal capacity of the wall is ignored, then the
rate of heat transfer through the wall at any time t is given by
(4.10.1)
Q= UA(T,-T)
2. On an average basis, the mean heal flow is given by,
Qm = UA(Tm-T) (4.10.2)
P1
< 2k
0g0/ m
Time
log,
hours+ 2 0- 0
1 8 0 0
15 1 8 0- 0
2 4 0 0
10
0 15 30 45 60
Thickness Ax, cm
Fig. 4.10.1. Time log of walls.
8. Considering the effect of thermal capacity, the actual heat transfer at
any time t is
Q, = UA(Tem - T) + UA(T--Tim) ...(4.10.2)
Where T = Sol-air temperature at time t- ¢, i.e. 6 hours
before the heat transfer is to be calculated.
9 A comparison of Eq. (4.10.2) with Eq. (4.10.1) shows that Q. can be
greater or less than Qmean depending on whether T-is greater or
less than t,m hours before.
10. The second term in Eq. (4.10.2) therefore, represents the periodic
component.
PART-4
Questions-Answers
Long Answer Type and Medium Answer Type Questions
4-12A (ME-Sem-7) Load Calculation
LWHA, m'/min
60
Where, L= Room length in metres,
W= Room width in metres,
4-13 A (ME-Sem-7)
HVAC Systems
H=Room height in metres, and
A, = Air changes per hour.
Que 4.13. Write short note on stake effect.
Answer
humidities, differences
1. Due to differences between temperatures and
buildings are
in the densities of air between the outside and inside of the
flow of air
produced. Consequently pressure differences occurs causing
known as Chimney or stack effect.
stack effect
2. When the inside temperature is lower than the outside, the
negative inside
produces positive inside pressure at lower levels and
pressure at higher levels.
and the
3. As a result, the outward flow of air takes place at lower levels
The
inward flow at higher levels, with the neutral zone in the middle.
reverse is true when inside is at a higher temperature than the outside.
4. Thus in summer infiltration is at the top and exfiltration at the bottom.
the
Similarly in winter infiltration is at the bottom and exfiltration at
top.
Que 4.14. Discuss in brief about wind effect.
Answer
1. Wind driven ventilation is one of two methods of providing natural
ventilation. When wind blows against a barrier, it is deflected around
and above the barrier (in this case, a building).
2. Wind causes a positive pressure on the windward side and a negative
pressure on the leeward side of buildings. To equalize pressure, outdoor
air will enter through available openings on the windward side and
eventually be exhausted through the leeward side.
3 Pressure is not uniformly distributed over the entire windward face, but
diminishes outwards from the pressure zone. The pressure difference
between any two points on the building envelope will determine the
potential for ventilation, if openings were provided at these two points.
The airflow is directly proportional to the effective area ofinlet openings,
wind speed, and wind direction.
4 The occurrence and change of wind pressures on building surfaces
depend on:
Wind speed and wind direction relative to the building.
The location,shape, orientation and surrounding environment of
the building.
ii. Window typologies and operation.
iv. Other aperture types (doors, chimneys).
4-14 A (ME-Sem-7) Load Calculation
Answer
1. When an amount of air is enter in to the conditioned room through
doors, windows. This is due to the pressure difference on two sides of
doors, window etc. this type of passing air is known as infiltrated air, this
type of effect is caused due to the stack effect, wind pressure.
2. This type of pressure difference and passing through different types of
entries is known as air infiltration.
3. When the load developed by the infiltration phenomenon is known as
infiltration load.
PART-5
Internal Heat Loads, System Heat Gains, Break up of Ventilation
and Efective Sensible Heat Factor.
Questions-Answers
Answer
application. The
1. The ventilation air requirements depends on individual
minimum requirement is taken as 0.2 cmm per person.
person and a
2 This is based on a population density of 5 to 7.5 m² per
ceiling height of 2.4 m.
3. When people are snmoking, the minimum ventilation
requirement is 0.4
to 0.7 cmm per person.
4. Bypass factor of the cooling equipment affects the position ofthe grand
sensible heat factor line.
5.
The effect of the bypass factor (BPF) is such as to add (X) (m) amount
of the outside air directly to the room, and to allow only (1-X) (m,) to
pass through the apparatus.
6.
Although the room air is also bypassed, this does not affect the break-up
of the load as the room air going to the room does not change the load
situation.
7. Thus, we can say that a part of the ventilation load forms a component
of the room load.
8 This bypassed outside air load is proportional to the bypass factor X.
9. It has both sensible and latent beat components. The other part which is
proportional to1-X, both sensible and latent which is bypassed around
the apparatus, is added so the equipment load.
10. Thus the bypassed outside air loads on the room are :
SH = (0ASH) outside air sensible heat (BPF)
LH= (0ALH) outside air latent heat (BPF)
11. These loads are imposed on the room in exactly the same manner as the
infiltration load.
12. Accordingly,the effective room loads are modified as follows :
Effective room sensible heat
ERSH = RSH + (ASH) (BPF)
Effective room latent heat
ERLH = RLH + (OALH) (BPF)
13. The effective sensible heat factor (ESHF) is the ratio of the effective
room sensible heat to the effective room total heat
4-17A (ME-Sem-7)
HVAC Systems
ERSH ERSH
ESHF = ERSH + ERLH ERTH
PART-6
Questions-Answers
Answer
A Cooling Loads :
1 The total heat required to be removed from the space in order to bring
it at the desired temperature by the air conditioning and refrigeration
equipment is known as cooling load.
2 For air conditioning the cooling loads can be classified as follows :
Room Load:
1. These are the loads which fall on the room directly.
2 Room Joads are further classified into two categories as follows:
i. Room Sensible Heat (RSH) : It occurs due to:
1. Solar andtransmission heat gain through walls,roof, glass
etc.
2 Transmission gain through partition walls, ceiling, floor
etc.
3. Infiltration.
4 Internal heat gain from people and power appliances.
5. The heat gain from the fan work.
ii. Room Latent Heat (RLH):It occurs due to :
1. The heat gain due to moisture in the outside air entering
by infiltration.
2. Vapour transmission.
3. The heat gain due to condensation of moisture from
occupants.
b. Total Load :
1. Thege are the loads which fall on the air conditioning apparatus.
2. Total load are further classified into twocategories as follows:
Load Calculation
4-18A (ME-Sem-7)
i. Sensible Heat: It occurs due to :
1 Effective room sensible heat.
2 Sensible heat of the outside air that is not by-passed.
3. Return duct heat gain, return duct leakage gain,
dehumidifier pump power and dehumidifier and piping
losses.
ii. Latent Heat : It occurs due to :
1 Effective room latent heat.
2. Latent heat of outside air which is not by-passed.
3. Return duct leakage gain.
B. Heating Loads:
loss
1 Heating loads are prepared on the basis ofmaximum probable heat
of the room or space to be heated.
2. Heating loads are classified as follows :
a.
Transmission Heat Loss: The transmission heat loss from walls,
roof, etc., is calculated on the basis of just the outside and inside
temperature difference.
b Solar Radiation: Normally there is no solar radiation present
and hence no solar heat gain at the time of the peak load which
normally occurs in the early morning hours.
Internal Heat Gains: The heating requirement is reduced due to
internal heat gain from occupants, light, motors and machinery
etc.
GSHF
line
2b
|w
|2 RSHF line
21
BPF (1-BPF)
T DP
Fig. 4.20.1. Effect of bypass factor.
HVAC Systems 4-19 A (ME-Sem-7)
2. The condition line 1-2 represents the psychrometric process in the air
conditioning apparatus, and hence the GSHF (ground sensible heat
factor) line.
3. Further, the leaving air state 2is governed by the BPF of the apparatus,
although, at the same time, it must lie on the RSHF (room sensible heat
factor) line 1-2.
4. Accordingly, the dehumidified air quantity can be caleulated either from
room sensible heat balance, viz. process s - i in the room.
RSH
(Cmm)a= 0.0204 (T -T)
5. From total sensible heat balance, viz, process 1-2 in the apparatus
TSH
(Cmm), = 0.0204 (T,-T,)
Que 4.21. What are the various factors on which selection of air
PART-7
Questions-Answers
CONTENTS
Part-1 : Air Distribution: Room Air .5-2A to 5-3A
Distribution, Types of Supply Air Outlets
Part-2 : Mechanism of Flow through 5-3A to 5-6A
Outlets, Selection and Location of
Outlets, Distribution Pattern of Outlets
Part-3 : Ducts : Definition and Types, **be*.**** 5-6A to 5-14A
Materials for Ducts and its
Specification, Friction Loss in
Ducts, Grills, Diffusers,
Registers, Rectangular
Equivalent of Circular Duct
Part-4 : Air Duct Designs, Duct 5-14A to 5-17A
Construction, Duct Design
Procedures : Equal Friction
Method, Static Regain Method,
Velocity Reduction Method
Part-5: Air Conditioning Apparatus ....5-17A to 5-23A
Fans and Blowers, Types of Fans,
Fan Characteristic, Centrifugal Fans,
Axial Fans, Fan Arrangements
Part-6 : Suction Line, Discharge Line..... .5-23A to 5-26A
(Hot-Gas Line), Liquid Line
Part-7: Location and Arrangement of........ 5-26A to 5-28A
Piping, Vibration and Noise in
Piping, Basic Elements of
Control System
5-1A (ME-Sem-7)
5-2A (ME-Sem-7) Air Distribution
PART- 1
Air Distribution : Room Air Distribution, Types of Supply Air
Outlets.
Questions-Answers
Answer
A Requirements of Good Room Air Distribution :
1. The primary requirement of good room air distribution is to create a
proper combination of temperature, humidity and air motion in the
occupied zone which is normally at 1.8 mabove the floor level.
2 The maximum variation in temperature in a single room should not be
more than 1°C, and within rooms, 2 °C. The desirable air velocity is 7.5
to 9 m/min.
B. Draft:
1 It is defined as any localized feeling of coolness or warmth of any portion
of the body due to both air movement and air temperature with humidity
and radiation, considered constant.
2 The warmth or coolness ofa draft is measured above or below the
controlled room condition of 24.4 °C DBT at the centre of the room and
air moving at approximately 9 m/min.
Que 5.2. What are the various types of supply air outlets ?
Answer
Various types of supplyair outlets are as follows:
i. Grille Outlets :
1 Grilles with fixed bars can give direction at the outlet and gives a constant
capacity at the outlet. This can be used where air capacity can be
determined accurately and is not likely to change.
2 Adjustable bar grilles provide for varying the air quantity if required.
ii. Slot Diffuser Outlets :
1 Slotted outlets have performance similar to bar grilles.
HVAC Systems 53A (ME-Sem-7)
2. Long narrow slots give better induction of room air and mixing is perfected
in a short throw.
3. They suit mostly to window outlets and linear design of architecture.
ii. Ceiling Diffuser Outlets:
1, These outlets supply air in multiple layers and induction is rapid at a
short distance after the air leaves the outlets.
2. They may also be fitted with dampers.
iv. Perforated Ceiling Panels:
1 These are particularly suited to low ceilings.
2. It offers unobstructive appearance and acts as sound absorbing device.
PART-2
Mechanism of Flow through Outlets, Selection and Location of
Outlets, Distribution Pattern of Outlets.
Questions-Answers
Answer
1 The mechanism of flow of air from the duct and through the outlet to
the room is shown in Fig. 5.3.1.
2. A,is the core area or the area of grille opening in which the air flows
with a velocity C, A, is the free area of the grille through which air can
pass.
3. The ratío AJA, is R, so that C=C/Rf
A CPrimary air
Secondary air,
Vena contracts
X
Fig. 5.3.1. Mechanism of flow of air through a duct outlet.
54A (ME-Sem-7) Air Distribution
4. A, is the area at the vena contracta formed outside the grille. IfC, is the
discharge coefficient of the outlet, and C, is the velocity at the vena
contracta.
C = A, A, ...(5.3.1)
Af A,R
CA. C ...(5.3.2)
A, CRe
5 The zone of interest is at 25 to 100 times the diameter or width of the
outlet in the x direction. In this zone, the velocity at any x is given by
C, KD, KyA,
3. During heating, the total air, after reaching the floor, returns back
towards the ceiling. There is no stagnation zone.
iüi. Low Sidewall Outlets Discharging Air Horizontally :
1 As is seen from Fig. 5.5.3, the total air during cooling remains near the
floor level resulting in low temperature in the occupied zone and alarge
stagnation zone above.
2. During heating, the warm air rises and temperature equalization takes
place except in the region of total air.
3. These outlets discharge air directly into the occupied zone with high
velocity.
4 They are not recommended for comfort air conditioning.
PART-3
Ducts :Definition and Types, Materials for Ducts and its
Specification, Friction Loss in Ducts, Grills, Diffusers,
Registers, Rectangular Equivalent of Circular Duct.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
A. Ducts :
1 Ducts are conduits or passage used in heating and ventilation.
2 The function of a duct is to convey the air between two points, such as
between the air handling unit or air washer and the room to be
conditioned.
3. It also carries the room air back to the air conditioning apparatus.
HVAC Systems 5-7A (ME-Sem-7)
Que 5.7. Discuss materials used for ducts and its specification.
Answer
Materials used for ducts are as follows :
1 Galvanized Steel : It is a standard, most common material used in
fabricating ductwork for most comfort air conditioning systems, The
specifications for galvanized steel sheet are ASTM A653, coating G90.
2, Aluminium : It is widely used in clean room applications. These are
also preferred systems for moisture laden air, special exhaust systems
and ornamental duct systems. The specifications for Aluminium sheet
are ASTM B209, alloy 1100, 3003 or 5052.
3. Stainless Steel:It is used in duct systems for kitchen exhaust, moisture
laden air, and fume exhaust. The specifications for stainless steel sheet
are ASTM A167, Class 302 or 304; Condition A(annealed) Finish No. 4
for exposed ducts and Finish No. 2B for concealed duct.
4 Carbon Steel (Black Iron):It is widely used in applications involving
flues, stacks, hoods, other high temperature and special coating
requirements for industrialuse.
5. Copper:It ismainly used for certain chemical exhaust and ornamental
ductwork.
Answer
A. Frictional LOsses :
1 When air flows through a duct, there is a loss of pressure due to friction
between the moving particles of air and the interior surfaces of a duct.
When the loss of pressure occurs in a straight duct, it is usually termed
as friction loss.
B. Dynamic Losses:
1. When the pressure is lost dynamically at the changes of direction such
as in bends,elbows etc., and at the changes of eross-section of the duct,
the pressure loss is usually termed as dynamic loss.
Que 5.9. Explain with neat sketch the various losses in the duct.
Answer
Various losses in the duct are as follows :
i. Pressure Loss due to Friction in Ducts :
1 The pressure loss due to friction in ducts may be obtained by using the
D'Arcy's formula or the Fanning's equation as follows :
fLp, v² ...(5.9.1)
P= 2m
Where, p,= Pressure loss due to friction (N/m2).
f= Friction factor depending upon the surface of
the duct,
L= Length of the duct (m),
V= Mean velocity of the air flowing through the
duct (m/s), and
m = Hydraulicmean depth in (m).
=
Cross -sectional area of the duct (A)
Wetted perimeter of the duct (P)
2 In air conditioning, the pressure loss due to friction in ducts is generally
expressed in mm of water. From eq. (5.9.1), we get
L p,v?
P= m -x p, mm of water ...(5.9.2)
2 m
3 We know that
- mm of water
2 4.04 )
Thus eg. (5.9.2) may be written as
2
P= m 4.04 mm of water
IVAC Syatemn 6-9A (ME-Sem-7)
Now, theo proanure losu due to friction in the duct when the air is at
temperature T"C, in given by,
273 +20 )
m\4.04) 273 T
293
mm of wator
273 +T
ii. Pressure Loss due toEnlargoment in Aren and StatieRegain:
Wherever there in anenlargement in a duct-run, thÍ velocity of fluid
decreanen nnd there in nconversion of velocity prossure into static
proumuro.
I B
V, A i
V,
Pa2
Eddies
(A,
Where, A, = CroB8-sectional area of the duct at section 1-1,
A,, = Cros8-8ectional area of the duct at section 2-2.
and
V, Velocity of air at section 2-2.
iii. Pressure Loss due to Contraction in Area :
1 Consider aduct ABC having sudden contraction at B as shown in
Fig. 5.9,2.
2. It may be noted that turbulence (formation of
eddies) occurs at two
places, viz., at the shoulders of the contraction in the large section, and
at a section shortly after the vena contracta.
5-10A (ME-Sem-7) Air Distribution
A
B
Vena
contracta
3. It may be observed that the major source of pressure loss is at the neck.
Thus, the loss corresponds to that of sudden expansion from the velocity
V, at the vena contracta to the downstream velocity V,.
4 If A, and A, are the crosS-sectional areas at sections 1-1 and 2-2
respectively, then pressure loss due to sudden contraction,
4.04
iv. Pressure Loss at Suction and Discharge of a Duct:
1 The pressure loss at suction to the duct is given by,
Ky² m of air
2g
Pa Nm?
2
=K mm of water
4.04
Where, V= Velocity of air in the duct, m/s, and
K= Loss coefficient.
Duct
Air flow
A=0
(a) Abrupt suction opening. (6) Flanged entrance. (c) Formed entrance.
Fig. 5.9.3.
HVACSystems 5-11 A (ME-Sem-7)
2. The pressure loss at the discharge or exit of a
duct is given by,
(PDis = 2g m of air
N/m'= mm of water
2Pa 4.04
Que 5.10. Define grills, diffusers and
registers.
Answer
i. Grills :
1 Grilles are defined as air devices that are
back to the fan or to exhaust air from typically used to return air
a space.
2 Grilles are generally not used in supply
tocontrol the air. distribution
due to their inability
3. Registers look like grilles but are
adjustable air stream deflectors andcomprised
dampers
of one-way or tw0-way
to restrict the amount of
air flow required to be returned, supplied or
ii. Diffusers :
exhausted.
1. Diffusers are the terminal devices that supply air in various
through the use of their deflecting vanes. directions
2. These are designed to promote the mixing of conditioned air with the
already in the space. air
P=
fLp,C_fLp,
2m 2m
...(5.11.1)
2 2
32 a+6
or,
ea ab
32a'%3 qus
Or, Deg = n²(a + b) =1.265 a+b) ...(5.11.3)
ii. When the Velocity of Air Passing through the Rectangular and
Circular Ducts is Same:
1 Let,C=Velocity of air passing through the rectangular and circular
ducts.
2 Pressure loss due to friction for a circular duct,
Lp,C² ...(5.11.4)
2
fLp,C(P
cir fLp,C'(Prect
2 A 2
Aect
Or, Pet
Aar A,et
2(a + b)
0r, TDeg axb
4
2(a x b) 2a
or, ...(5.11.6)
a+b
a
Where is known as Aspect ratio".
1 N/m'= mm of water
9.81
PART-4
Air Duct Design, Duct Construction, Duct Design Procedures : Equal
Friction Method, Static Regain Method, Velocity Reduction Method.
HVACSystems 5-15 A (ME-Sem-7)
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Que 5.13. What are the general rules considered in air duct design?
Answer
Afew general rules are stated as follows which should be followed in the
design of ducts :
1 Air should be conveyed as directly as possible to economise on power,
material and space.
2. Sudden changes in direction should be avojded. When bends are essential,
turning vanes should be used to minimise the pressure loss.
3. Air velocities in ducts should be within permissible limits to minimise
noise.
4 Diverging sections should be made gradual. The angle of divergence
should not exceed 20.
5. Rectangular ducts should be made as nearly square as possible. This will
ensure minimum duct surface, and hence cost, for the same air-carrying
capacity. An aspect ratio of less than 4:1should be maintained.
6 Ducts should be made of smooth materials such as galvanized iron (GI)
or aluminium sheet metals. Whenever other materials are used,
allowance should be made for the roughness of the material.
7 Dampers should be provided in each branch outlet for balancing the
system.
8 Avoid duct obstructions.
(i) Grooved seam (ii) Drive slip joint (ii) Flat joint
Fig. 5.14.1.
PART-5
Air Conditioning Apparatus : Fans and Blowers, Types of Fans, Fan
Characteristic, Centrifugal Fans, Axial Fans, Fan Arrangements.
Questions-Answers
Answer
1 Afan is rotodynamie machine which propels air or other gas continuously.
2 Fans find extensive use in air-conditioning and refrigeration plants for
moving or circulating air over air-cooled condensers and evaporator
coils.
5-18 A (ME-Sem-7) Air Distribution
3. While a pump or a compressor develops higher fluid pressures, the fans
can develop comparatively low pressures. The pressure developed by
the fan being very low, is expressed in "mm of water".
4. According to the maximum total pressures they can safely develop, fans
may be classified as follows :
Maximum pressure upto 95 mm water gauge Class I.
ii. Maximum pressure upto 171 mm water gauge Class II.
ii. Maximum pressured upto 311 mm water gauge Class III.
iv. Maximum pressure over 31l mm water gauge Class IV.
Que 5.17. Write short note on blowers.
Answer
1 Blowers serve three main functions : heating, cooling and air flow.
2 Although unit designs range from simple and complex, most blowers
usually consist of some type of fan-like apparatus. Some blowers also
use pressure pumps to move air or gases.
3 Heating blowers direct warm or hot air into cooler areas.
4. The blower fan is located in the inside portion of your air conditioner it
is responsible for blowing the air to the ductwork in your system which
then allows for the distribution of the air throughout your home.
Que 5.18. Describe centrifugal fans with the help of neat sketch.
Answer
1. A centrifugal or radial flow fan is one in which air enters the impeller
axially and is discharged radially from the impeller.
2. Centrifugal fans are used for the air-conditioning and ventilation
purposes.
3. Depending upon the inclination (inclination determines the performance
characteristics of the fan) of the fan blades, the centrifugal fans are
further classified as:
i Forward-Curved Fans: Refer Fig. 5.18.1.
Blade bas no
curvature, fixed radially
Rotation
is fxed
1. Radial blade has no curvature and the blade is straight and
radially.
cooling.
2. These fans are generally used in electric motors for internalmotors.
The blades are built into the rotor itself in case of small-sized
motor shaft
3. For bigger-sized motors, a separate fan is fixed on the
(within the body).
iii. Backward-Curved Fans : Refer Figs. 5.18.3 and Fig. 5.18.4.
Answer
1. When the air flows parallel to the axis of impeller, it is called an axial
flow fan.
2. Following are the three types of axial-flow fans:
i. Propeller Fans : Refer to Fig. 5.19.1.
3. Since these fans produce high noise level, therefore, their use is limited
to applications where the noise level is not of much importance.
iii. Vane Axial Fans : Refer to Fig. 5.19.3.
Impeller - -Guide vanes
1 These are tube axial fans with vanes. The vanes located at the leaving
side of the wheel help to straighten out the spiral flow of air coming out
of an axial fan. The straight line flow leaving the fan assures quiet
operation.
2 The efficiency of operation and the pressure characteristics are better
than those of tube axial fan.
(Pran-3.
Fig.5.20.1. Fans in series.
5-22 A (ME-Sem-7) Air Distribution
i. The overall fan total pressure (pn is equal to the sum of the fan total
pressures developed by the individual fans i.e.,
(pran = (prfan- 1+(Ppan-2+Pr'an-3
ii. Fans in Parallel :
1 Fig. 5.20.2 shows fans connected in parallel.
2 In this case :
i The fan total pressure (pe of each fan is same,i.e.,
(Pp'an-1=(Pr'an-2=(Pran-3
The total volume delivered (Q) is equal to the sum of the volumes
delivered by the individual fans, i.e.,
Q=Q,+Q, +Q3
Fan-1
Fan-2
Fan-3
-(Praun
Fig. 5.20.2. Fans in Parallel.
Que 5.21. Describe fan and system characteristic with neat sketch.
Answer
1. System characteristic is the change in pressure loss or resistance with
the change in flow rate. It is independent of the fan used in that system.
2. The system resistance (R) or pressure loss (p,) of any fixed system
varies as square of the flow rate,
i.e., K or P, = KQ?
3 When Ror p, is plotted against Q, a curve (a parabola) such as OA,as
shown in Fig. 5.21.1, is obtained; the curve is usually known as a system
characteristic curve.
HVAC Systems 5-23 A (ME-Sem-7)
4 The operation of a fan in conjunction with a particular system must
fulfill the condition that the loss of total pressure in the system at a
given volume flow must be equal to the total pressure developed by the
fan (i.e., fan total pressure) at the same volume.
A
B Fan total pressure
System
resistance
(R)
D
Operating pressure
Fan performance
S y s t e
cmh a r a c t e r i s
c tui c
rsv e
curve
C
k-Volume delivered
Volume flow rate (Q)
Fig.5.21.1. Fan and system characteristic.
PART-6
Suction Line, Discharge Line (Hot-Gas Line); Liquid Line.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Answer
1. The larger line typicaly carries a cool gas and is insulated. This is
commonly referred to as the suction line.
2. Suction lines are the most critical from the viewpoints of design and
construction. The considerations involved are the following :
i Correct size for practical pressure drop.
ii. Capability to return oil to the compressor by entrainment by the
suction vapour under minimum loading conditions, especially in
the case of fluorocarbons.
ii. If there are suction risers, gas velocities to ensure oil return have
to be increased. Thus a minimum tonnage is prescribed in suction
risers.
iv. Double-suction risers may be used for full-load operation and single
risers for part-load operation as shown in Fig. 5.22.1.
To compressor
suction
Double suction
riser
Evaporator
Oil seal at
part load
U-bend
Fig, 5.22.1. Double-suction riser.
Answer
lines) allow refrigerant
Discharge gas lines (often referred to as hot-gas
1
to the inlet of the condenser.
toflow from the discharge of the compressor
the discharge lines should
2. Even though a low pressure drop is desired, velocities are reduced so
not be oversized to the extent that the gas carry along the entrained
much that the refrigerant will not be able to
oil.
prevent the refrigerant
3. They should be so designed and constructed as to to the compressor,
and oil in the line from condensing and draining backambient where long
especially during shutdown or operation at low condensers.
outdoor discharge lines are required as in evaporative
4. Whenever the condenser is located above the compressor, the discharge
line should loop to the floor before rising to the compressor.
to 1 or 2 °C in the
5. It is not desirable to exceed a pressure drop equivalent efficiency
saturation temperature because of the penalty on volumetric
and hence the capacity of the compressor.
6 Discharge lines should be selected on the basis of 0.45 to 0.67 bar per
100 m pressure drop.
Answer
1 The smaller uninsulated line typically carries a warm liquid. It is most
often called the liquid line.
2 The liquid line presents fewest problems. It is desirable to have a slightly
subcooled liquid reach the liquid-feed device to prevent the formation of
flash gas.
3 The flash gas in the liquid line causes an increase in the pressure drop
and further flashing, reduction in the capacity of the expansion device,
noise and erratic control of the liquid refrigerant entering the evaporator.
4 The pressure drop in turn is due to friction as well as decrease in the
static head due to the elevation of the evaporator above the condenser.
5. Generally, liquid always leaves the condenser in a subcooled state. An
additional refrigerant charge will increase subcooling.
6. Shell-and-tube condensers are designed to maintain a liquid level in the
shellwhich can provide for subcooling.
7. The construction of the aircooled condensers is also such that the liquid
is in contact with the cooling air surface until it gets subeooled and
leaves.
5-26 A (ME-Sem-7) Air Distribution
PART-7
Location and Arrangement of Piping, Vibration and Noise in Piping,
Basic Elements of Control System.
Questions-Answers
Long Answer Type and Medium Answer Type Questions
Sensing
element
Fig. 5.27.1.
5-28 A (ME-Sem-7) Air Distribution