REVISION HISTORY:
Rev. /
Date Change Description
Vers.
0 28/09/2017 Original issue
1 27/10/2017 Issued for Design – Revised as per Client’s comments
DOCUMENT REFERENCES:
Current Rev. / Vers. of this Document 0
Referenced Documents
Document Document
Revision / Version
Name number
A00KM-
HVAC Design description 000165-MAN- 0
120-001
TABLE OF CONTENTS
8. System Description..........................................................................................................................9
1.6. PMC : -
ISHRAE (Second edition, 2014) : Indian Society of Heating, Refrigeration, and Air
Conditioning Engineer’s Hand Book
(R1)
IS 5572 (2009) : Classification of Hazardous area (other than
mines) having flammable gases and vapours for
Electrical Installation.
2.2. Statutory Requirements : The Gujarat lifts and escalators rules, 2001
2.4. In case of any conflict amongst various documents, the order of precedence shall be as
follows:
Statutory Regulations
Job Specifications
Design Basis
Standard specifications, installation standards etc.
3. Units of Measurement
Altitude : 27.5 M
SUMMER 43 25.6 24
WINTER 10 6.1 58
8. System Description
8.1. General
Direct expansion refrigeration (DX) system shall be provided which consists of Indoor
units & outdoor condensing units inter connected with refrigerant piping/cabling.
HCFC free refrigerant such as R407c & R410a shall be used for all AC system.
Indoor DX units shall either be floor mounted Package type/ Hi sensible Package /
Ductable Ceiling suspended / Cassette / Hi-wall Split AC Unit as per the requirement.
VRF (Variable Refrigerant Flow) system shall be provided for few rooms such as Plant
Maintenance Offices, Engg. Offices, Control room etc.
Fresh air shall be distributed to each air conditioned room to maintain the room under
slight positive pressure and/or to meet the fresh air requirement of occupants.
Fresh air for IRR & Control room shall be provided through Chemical Filter unit to
improve the life of their equipment & maintain the rooms at slight positive pressure.
Fresh air for balance air conditioned areas shall be provided with the help of Fan Filter
units to maintain the rooms under slight positive pressure.
Air locks provided for entry from Annex building to Plant building shall be continuously
ventilated. This is required because this passage connects the Safe area (Annex
building) to Hazardous area (Plant building).
The air locks shall be adequately ventilated at a rate of minimum 12 air changes per
hour.
Provision for overpressure control of air lock shall be provided.
Audio-visual alarm shall be provided for loss of ventilation.
a) Above areas shall be catered by dedicated Package type/ Hi sensible Package units.
b) 2 nos. x 50% capacity (i.e. 2 Working + 0 Stand-by) AC units shall be provided for
MCC room.
c) 2 nos. x 100% capacity (i.e. 1 Working + 1 Stand-by) AC units shall be provided for
VFD/UPS room and Battery room.
d) These units shall be mounted on the floor inside the rooms which are air conditioned.
Cooled and de-humidified air shall be distributed in the room through ducting.
e) Fresh air shall be supplied from the common Fan filter unit located on the roof of the
building.
f) Fresh air duct entering each room from the shaft shall be protected with the help of
Fusible link type Fire dampers.
c) The indoor units shall be suspended above the false ceiling inside the IRR room. Cooled
and de-humidified air shall be distributed in the room through ducting. Return air shall be
collected above false ceiling and routed back to the AC unit.
d) Fresh air shall be supplied from the common Chemical Filter unit located on the roof of
the building.
e) Fresh air duct entering each room from the shaft shall be protected with the help of
Fusible link type Fire dampers.
a) Control room, Plant Management office, Engineering office Engineering Spares Room,
Instruments Spares Room & Record room shall be provided with a common VRF
(Variable Refrigerant flow) system.
b) 2 nos. x 50% capacity (i.e. 2 Working + 0 Stand-by) VRF system shall be provided.
Control room shall be partially catered from both the VRF systems.
c) Indoor units for Control room & offices shall be cassette type, whereas for few rooms
such as Record room, spare room etc. indoor units shall be hi-wall type.
d) Fresh air is supplied to the individual indoor units from the common Fan filter unit
located on the roof of the building. In case of Control room, fresh air shall be supplied
from a common Chemical Filter unit located on the roof of the building.
e) Fresh air duct entering each room from the shaft shall be protected with the help of
Fusible link type Fire dampers.
a) The pressurisation unit shall be located on the roof of the building which shall supply
fresh air to the lift shaft through ducting.
a) Dedicated Fan filter units shall be provided on the roof of the building which shall supply
fresh air to the Air locks through ducting.
b) 2 nos. x 100% capacity (i.e. 1 Working + 1 Stand-by) dedicated fan filter units shall be
provided.
a) Dedicated Fan filter unit shall be provided on the roof of the building which shall supply
fresh air to the lift shaft through ducting.
b) 2 nos. x 100% capacity (i.e. 1 Working + 1 Stand-by) dedicated fan filter units shall be
provided.
9.7. Summary
Working (W)+
Area Served Proposed System
Standby (S)
MCC rooms Package Unit
2W+ 0S
(Floor Mounted)
VFD/ UPS & Battery Room Package Unit
1W+1S
(Floor Mounted)
IRR rooms Ductable Split AC unit
1W+1S
(Ceiling suspended)
Working (W)+
Area Served Proposed System
Standby (S)
Control Room, Plant Management offices,
Engineering Office, Engineering Spares VRF unit 2W+ 0S
Room, Instrument Spares Room, Spare
Room, Record Room etc.
Working (W)+
Area Served Proposed System
Standby (S)
Fresh Air for Control room Chemical filter unit (with 2 x 100 % supply
1W+0S
& IRR rooms air fans)
Exhaust Air with wall mounted propeller
Battery Room 1W+1S
fans
1W+0S,
Toilets/ Pantries In-line/ wall mounted exhaust fans
each
Lift shaft– Annex Building Fan Filter unit 1W+0S
Air locks – Annex Building Fan Filter units 1W+1S
Lift shaft– Plant Building Fan Filter units 1W+1S
b) Each AC system shall be provided with an electrical panel. This panel shall have
provision to trip the HVAC equipment on receipt of fire signal from Fire Alarm panel.
It shall have auto changeover & sequencing provision for equal run of fresh air
units.
These units shall stop on receipt of fire signal.
Loss of ventilation shall be communicated to DCS with an audio-visual alarm.
It shall have auto changeover & sequencing provision for equal run of fresh air
units.
These units shall continue to pressurise the lift shaft even during fire scenario.
Loss of ventilation shall be communicated to DCS with an audio-visual alarm.