Structural Calculations
Structural Calculations
Prolectric
16568.
Paul Dawson
September 2016
Project Job Ref.
Proposals
It is proposed to fix a 3m lighting column to two different types of precast kentledge blocks. To the top of these lighting
columns will be attached a luminaire and solar panel. These calculations are to determine the maximum horizontal wind
load for each of the kentledge blocks.
The two blocks to be considered are KM1000 and KM500 as detailed below by Elite Precast.
The lighting column is to be a BE Lighting column 3TG/FP which is a 140 dia tube with a self-weight of 29kg. To the top of
the column will be fixed a luminare 725 x 120 x 75 which weighs 3.6kg and a solar panel which is 1105 x 360 x 60 and
weighs 12kg.
Assume that the total area of the solar panel and luminare attract full wind load and the wind load on the column itself is
negligible. Ground bearing pressure is limited to 75 kN/m².;
Project Job Ref.
KM1000
KM500
3.1 / 3 = 1.03 kN horizontal force. The combined area of the solar panel and luminaire = 0.48 m².
Therefore the maximum horizontal uniformly distributed load at the top of the column will be 2.15 kN/m²
3.1 / 4 = 0.775 kN horizontal force. The combined area of the solar panel and luminaire = 0.48 m².
Therefore the maximum horizontal uniformly distributed load at the top of the column will be 1.615 kN/m²
KM500 Base
The KM500 base can resist an overturning moment of 1.75 kNm again working back to the solar panel at the top of the
column.
1.75 / 3 = 0.58 kN horizontal force. With the same arrangement of solar panel and luminaire.
Project Job Ref.
Therefore the maximum horizontally uniformly distributed load at the top of the column will be 1.215 kN/m².
Note these loads are unfactored and assume that the allowable ground
pressure exceeds 75 kN/m²