Solar Lighting Base

Prolectric
16568.

Paul Dawson
September 2016
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 2C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Proposals
It is proposed to fix a 3m lighting column to two different types of precast kentledge blocks. To the top of these lighting
columns will be attached a luminaire and solar panel. These calculations are to determine the maximum horizontal wind
load for each of the kentledge blocks.

The two blocks to be considered are KM1000 and KM500 as detailed below by Elite Precast.

The lighting column is to be a BE Lighting column 3TG/FP which is a 140 dia tube with a self-weight of 29kg. To the top of
the column will be fixed a luminare 725 x 120 x 75 which weighs 3.6kg and a solar panel which is 1105 x 360 x 60 and
weighs 12kg.

Assume that the total area of the solar panel and luminare attract full wind load and the wind load on the column itself is
negligible. Ground bearing pressure is limited to 75 kN/m².;
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 3C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

KM1000

FOUNDATION ANALYSIS (EN1997-1:2004)


In accordance with EN1997-1:2004 incorporating Corrigendum dated February 2009 and the UK National Annex
incorporating Corrigendum No.1
TEDDS calculation version 3.2.07

Pad foundation details


Length of foundation; Lx = 1000 mm
Width of foundation; Ly = 750 mm
Foundation area; A = Lx  Ly = 0.750 m2
Depth of foundation; h = 750 mm
Depth of soil over foundation; hsoil = 0 mm
Level of water; hwater = 0 mm
Density of water; water = 9.8 kN/m3
Density of concrete; conc = 18.0 kN/m3

Column no.1 details


Length of column; lx1 = 200 mm
Width of column; ly1 = 200 mm
position in x-axis; x1 = 500 mm
position in y-axis; y1 = 375 mm
Soil properties
Density of soil; soil = 20.0 kN/m3
Characteristic cohesion; c'k = 0 kN/m2
Characteristic effective shear resistance angle; 'k = 25 deg
Characteristic friction angle; k = 19.3 deg
Foundation loads
Self weight; Fswt = h  conc = 13.5 kN/m2
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 4C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Column no.1 loads


Permanent load in z; FGz1 = 0.4 kN
Variable load in x; FQx1 = 0.8 kN
Variable moment in x; MQx1 = 3.1 kNm
Bearing resistance (Section 6.5.2)
Forces on foundation
Force in x-axis; Fdx = FQx1 = 0.8 kN
Force in z-axis; Fdz = A  Fswt + FGz1 = 10.5 kN
Moments on foundation
Moment in x-axis; Mdx = A  Fswt  Lx / 2 + FGz1  x1 + MQx1 + FQx1  h = 9.0 kNm
Moment in y-axis; Mdy = A  Fswt  Ly / 2 + FGz1  y1 = 3.9 kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-axis; ex = Mdx / Fdz - Lx / 2 = 354 mm
Eccentricity of base reaction in y-axis; ey = Mdy / Fdz - Ly / 2 = 0 mm
Pad base pressures
q1 = 0 kN/m2
q2 = 0 kN/m2
q3 = 2  Fdz / (3  Ly  (Lx / 2 - ex)) = 63.9 kN/m2
q4 = 2  Fdz / (3  Ly  (Lx / 2 - ex)) = 63.9 kN/m2
Minimum base pressure; qmin = min(q1, q2, q3, q4) = 0 kN/m2
Maximum base pressure; qmax = max(q1, q2, q3, q4) = 63.9 kN/m2
Presumed bearing capacity
Presumed bearing capacity; Pbearing = 75.0 kN/m2
PASS - Presumed bearing capacity exceeds design base pressure
Partial factors on actions - Combination1
Permanent unfavourable action - Table A.3; G = 1.35
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.50
Variable favourable action - Table A.3; Qf = 0.00
Partial factors for spread foundations - Combination1
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 1.2 kN
Force in z-axis; Fdz = G  (A  Fswt + FGz1) = 14.2 kN
Moments on foundation
Moment in x-axis; Mdx = G  (A  Fswt  Lx / 2 + FGz1  x1) + Q  MQx1 + (Q  FQx1)  h =
12.7 kNm
Moment in y-axis; Mdy = G  (A  Fswt  Ly / 2 + FGz1  y1) = 5.3 kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-axis; ex = Mdx / Fdz - Lx / 2 = 393 mm
Eccentricity of base reaction in y-axis; ey = Mdy / Fdz - Ly / 2 = 0 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 214 mm
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 5C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Effective width; L'y = Ly - 2  ey = 750 mm


Effective area; A' = L'x  L'y = 0.161 m2
Pad base pressure
Design base pressure; fdz = Fdz / A' = 88.5 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 1.2 kN
Force in z-axis; Fdz = Gf  (A  Fswt + FGz1) = 10.5 kN
Sliding resistance verification (Section 6.5.3)
Horizontal force on foundation; H = abs(Fdx) = 1.2 kN
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(k / ') = 3.7 kN
PASS - Foundation is not subject to failure by sliding
Partial factors on actions - Combination2
Permanent unfavourable action - Table A.3; G = 1.00
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.30
Variable favourable action - Table A.3; Qf = 0.00
Partial factors for spread foundations - Combination2
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 1.1 kN
Force in z-axis; Fdz = G  (A  Fswt + FGz1) = 10.5 kN
Moments on foundation
Moment in x-axis; Mdx = G  (A  Fswt  Lx / 2 + FGz1  x1) + Q  MQx1 + (Q  FQx1)  h =
10.1 kNm
Moment in y-axis; Mdy = G  (A  Fswt  Ly / 2 + FGz1  y1) = 3.9 kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-axis; ex = Mdx / Fdz - Lx / 2 = 460 mm
Eccentricity of base reaction in y-axis; ey = Mdy / Fdz - Ly / 2 = 0 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 80 mm
Effective width; L'y = Ly - 2  ey = 750 mm
Effective area; A' = L'x  L'y = 0.060 m2
Pad base pressure
Design base pressure; fdz = Fdz / A' = 174.5 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 1.1 kN
Force in z-axis; Fdz = Gf  (A  Fswt + FGz1) = 10.5 kN
Sliding resistance verification (Section 6.5.3)
Horizontal force on foundation; H = abs(Fdx) = 1.1 kN
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(k / ') = 2.9 kN
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 6C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

PASS - Foundation is not subject to failure by sliding

KM500

FOUNDATION ANALYSIS (EN1997-1:2004)


In accordance with EN1997-1:2004 incorporating Corrigendum dated February 2009 and the UK National Annex
incorporating Corrigendum No.1
TEDDS calculation version 3.2.07

Pad foundation details


Length of foundation; Lx = 1000 mm
Width of foundation; Ly = 500 mm
Foundation area; A = Lx  Ly = 0.500 m2
Depth of foundation; h = 400 mm
Depth of soil over foundation; hsoil = 0 mm
Level of water; hwater = 0 mm
Density of water; water = 9.8 kN/m3
Density of concrete; conc = 24.0 kN/m3

Column no.1 details


Length of column; lx1 = 200 mm
Width of column; ly1 = 200 mm
position in x-axis; x1 = 500 mm
position in y-axis; y1 = 250 mm
Soil properties
Density of soil; soil = 20.0 kN/m3
Characteristic cohesion; c'k = 0 kN/m2
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 7C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Characteristic effective shear resistance angle; 'k = 25 deg


Characteristic friction angle; k = 19.3 deg
Foundation loads
Self weight; Fswt = h  conc = 9.6 kN/m2
Column no.1 loads
Permanent load in z; FGz1 = 0.4 kN
Variable load in x; FQx1 = 0.6 kN
Variable moment in x; MQx1 = 1.8 kNm
Bearing resistance (Section 6.5.2)
Forces on foundation
Force in x-axis; Fdx = FQx1 = 0.6 kN
Force in z-axis; Fdz = A  Fswt + FGz1 = 5.2 kN
Moments on foundation
Moment in x-axis; Mdx = A  Fswt  Lx / 2 + FGz1  x1 + MQx1 + FQx1  h = 4.6 kNm
Moment in y-axis; Mdy = A  Fswt  Ly / 2 + FGz1  y1 = 1.3 kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-axis; ex = Mdx / Fdz - Lx / 2 = 381 mm
Eccentricity of base reaction in y-axis; ey = Mdy / Fdz - Ly / 2 = 0 mm
Pad base pressures
q1 = 0 kN/m2
q2 = 0 kN/m2
q3 = 2  Fdz / (3  Ly  (Lx / 2 - ex)) = 58.3 kN/m2
q4 = 2  Fdz / (3  Ly  (Lx / 2 - ex)) = 58.3 kN/m2
Minimum base pressure; qmin = min(q1, q2, q3, q4) = 0 kN/m2
Maximum base pressure; qmax = max(q1, q2, q3, q4) = 58.3 kN/m2
Presumed bearing capacity
Presumed bearing capacity; Pbearing = 75.0 kN/m2
PASS - Presumed bearing capacity exceeds design base pressure
Partial factors on actions - Combination1
Permanent unfavourable action - Table A.3; G = 1.35
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.50
Variable favourable action - Table A.3; Qf = 0.00
Partial factors for spread foundations - Combination1
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 0.9 kN
Force in z-axis; Fdz = G  (A  Fswt + FGz1) = 7.0 kN
Moments on foundation
Moment in x-axis; Mdx = G  (A  Fswt  Lx / 2 + FGz1  x1) + Q  MQx1 + (Q  FQx1)  h =
6.5 kNm
Moment in y-axis; Mdy = G  (A  Fswt  Ly / 2 + FGz1  y1) = 1.8 kNm
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 8C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Eccentricity of base reaction


Eccentricity of base reaction in x-axis; ex = Mdx / Fdz - Lx / 2 = 424 mm
Eccentricity of base reaction in y-axis; ey = Mdy / Fdz - Ly / 2 = 0 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 153 mm
Effective width; L'y = Ly - 2  ey = 500 mm
Effective area; A' = L'x  L'y = 0.076 m2
Pad base pressure
Design base pressure; fdz = Fdz / A' = 91.8 kN/m2
Sliding resistance (Section 6.5.3)
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 0.9 kN
Force in z-axis; Fdz = Gf  (A  Fswt + FGz1) = 5.2 kN
Sliding resistance verification (Section 6.5.3)
Horizontal force on foundation; H = abs(Fdx) = 0.9 kN
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(k / ') = 1.8 kN
PASS - Foundation is not subject to failure by sliding
Partial factors on actions - Combination2
Permanent unfavourable action - Table A.3; G = 1.00
Permanent favourable action - Table A.3; Gf = 1.00
Variable unfavourable action - Table A.3; Q = 1.30
Variable favourable action - Table A.3; Qf = 0.00
Partial factors for spread foundations - Combination2
Bearing - Table A.5; R.v = 1.00
Sliding - Table A.5; R.h = 1.00
Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 0.8 kN
Force in z-axis; Fdz = G  (A  Fswt + FGz1) = 5.2 kN
Moments on foundation
Moment in x-axis; Mdx = G  (A  Fswt  Lx / 2 + FGz1  x1) + Q  MQx1 + (Q  FQx1)  h =
5.2 kNm
Moment in y-axis; Mdy = G  (A  Fswt  Ly / 2 + FGz1  y1) = 1.3 kNm
Eccentricity of base reaction
Eccentricity of base reaction in x-axis; ex = Mdx / Fdz - Lx / 2 = 496 mm
Eccentricity of base reaction in y-axis; ey = Mdy / Fdz - Ly / 2 = 0 mm
Effective area of base
Effective length; L'x = Lx - 2  ex = 9 mm
Effective width; L'y = Ly - 2  ey = 500 mm
Effective area; A' = L'x  L'y = 0.004 m2
Pad base pressure
Design base pressure; fdz = Fdz / A' = 1155.6 kN/m2
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 9C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Sliding resistance (Section 6.5.3)


Forces on foundation
Force in x-axis; Fdx = Q  FQx1 = 0.8 kN
Force in z-axis; Fdz = Gf  (A  Fswt + FGz1) = 5.2 kN
Sliding resistance verification (Section 6.5.3)
Horizontal force on foundation; H = abs(Fdx) = 0.8 kN
Sliding resistance (exp.6.3a); RH.d = Fdz  tan(k / ') = 1.4 kN
PASS - Foundation is not subject to failure by sliding

KM1000 Base 3m High Column


The KM1000 base can resist an overturning moment of 3.1 kNm working back to the solar panel at the top of the column.

3.1 / 3 = 1.03 kN horizontal force. The combined area of the solar panel and luminaire = 0.48 m².

Therefore the maximum horizontal uniformly distributed load at the top of the column will be 2.15 kN/m²

Basic Wind Velocity BS EN1991-1-4


Fw = cscd cf qb(ze) Aref = 1.03 kN; 1.03 = 1 x 1.8 x qb (ze) x 0.48; Therefore qb (ze) = 1192 N/m² qb = 0.613 vb2

Basic Wind velocity vb = 44.1 m/s

KM1000 Base 4m High Column


The KM1000 base can resist an overturning moment of 3.1 kNm working back to the solar panel at the top of the column.

3.1 / 4 = 0.775 kN horizontal force. The combined area of the solar panel and luminaire = 0.48 m².

Therefore the maximum horizontal uniformly distributed load at the top of the column will be 1.615 kN/m²

Basic Wind Velocity BS EN1991-1-4


Fw = cscd cf qb(ze) Aref = 0.775 kN; 0.775 = 1 x 1.8 x qb (ze) x 0.48; Therefore qb (ze) = 896 N/m² qb = 0.613 vb2

Basic Wind velocity vb = 38.2 m/s

KM500 Base
The KM500 base can resist an overturning moment of 1.75 kNm again working back to the solar panel at the top of the
column.
1.75 / 3 = 0.58 kN horizontal force. With the same arrangement of solar panel and luminaire.
Project Job Ref.

Solar Lighting Base 16568


28 Old Church Road
Section Sheet no./rev.
Clevedon
BS21 6LY Lighting Base 10 C
www.dea-llp.co.uk Calc. by Date Chk'd by Date App'd by Date

PD 13/7/17 ph 13/7/17 ph 13/7/17

Therefore the maximum horizontally uniformly distributed load at the top of the column will be 1.215 kN/m².

Basic Wind Velocity BS EN1991-1-4


Fw = cscd cf qb(ze) Aref = 0.58 kN; 0.58 = 1 x 1.8 x qb (ze) x 0.48; Therefore qb (ze) = 671 N/m² qb = 0.613 vb2

Basic Wind velocity vb = 33.08 m/s

Note these loads are unfactored and assume that the allowable ground
pressure exceeds 75 kN/m²