Part D3D29 Construction of Exits - NCC
Part D3D29 Construction of Exits - NCC
Part D3D29 Construction of Exits - NCC
(2) Where the lowest level of the window opening is less than 1.7 m above the floor, a
window opening covered by (1) must comply with the following:
(3) A barrier with a height not less than 865 mm above the floor is required to an
openable window—
https://ncc.abcb.gov.au/editions/ncc-2022/adopted/volume-one/d-access-and-egress/part-d3-construction-exits 1/2
2023/9/21 Part D3 Construction of exits | NCC
(a) fire-isolated stairways , fire-isolated ramps and other areas used primarily for
emergency purposes, excluding external stairways and external ramps; and
(b) Class 7 (other than carparks ) and Class 8 buildings and parts of buildings
containing those classes,