BI-16

LATCHING AUXILIARY RELAYS AND


MASTER TRIP RELAYS

APPLICATIONS MAIN FEATURES


 Latching relays and master trip relays with  No consumption in permanence.
sixteen changeover contacts, mounted on  Front indication on the nameplate.
“I” boxes, able to be plugged into the
 Large variety of assemblies with front and
various types of “I” sockets.
rear connection sockets by screw or fast-
on clip and flush mounting option socket.
 The design, durability and quality of these
relays guarantee their application in high
responsibility controls such as power
stations, substations, railway, industries of
continuous processes (petrochemical,
rolling mills, cement and chemical
industries), etc.
 According to the most demanding test
standards: IEC, EN, IEEE, and bearing the
CE mark.
 The great power of the output contacts
makes possible direct action on HV and
MV switchgear, because their
making/breaking capacities, continuous
through-current and overvoltage capacity
guarantee perfect insulation.
 Absolutely reliable for use in salty, tropical
atmospheres, and in general in those
atmospheres which need protection with
transparent cover.

www.arteche.com 1
TECHNICAL SPECIFICATIONS

Electrical Characteristics
BI-16 Standard
BI-16RP BI-16RP HB
BI-16BB*
24, 48, 72, 110, 125, 220
Vdc/Vac; 50/60 Hz
Standard voltages (UN) 110, 125, 220 Vdc
(Other voltages upon
request)
Voltage range +10% -20% Un
Voltage range and
consumptions Consumption in the
24 W 60 W 150 W
conmutation
Pick-up time < 20 ms < 10 ms
Permanent current 10 A
80 A/200 ms
Instantaneous current
150 A/10 ms
Contacts
Making capacity 40 A/0,5 s/110 Vdc
Breaking capacity See curves
Umax, opened contact 250Vdc/400 Vac
Mechanical life 107 operations
Operating temperature -10°C +70°C
Operating humidity 93%/40°C
high burden
Low burden configuration according to ESI 48- configuration
High/Low burden configuration
4 EB1 according to ESI
48-4 EB2

Construction Standards
Dielectric test 2 kV/50 Hz/1 min
Electrical test
Surge withstand 5 kV/1,2/50 μs
IEC60255
Insulation > 2000 MΩ/500 Vdc
Plastic materials
Inflammability tests
IEC 60692-2-1 UL94: V0
IEC 60695: 850ºC/30s
Cover protection degree IEC60529, EN60529: IP40

* Coil overvoltage protection

www.arteche.com 2
DIMENSIONS
Relay I-DE Socket

I-TR, I-TR2C Socket I-TRC Socket

I-EMP Socket

CONNECTIONS
BI-16 BI-16BB BI-16RP

www.arteche.com 3
OTHER CHARACTERISTICS

Kind of sockets
Screw Faston Double Faston
Front connection I-DE
Rear connection I-TR I-TRC I-TR2C
Flush mounting I-EMP

Weight
BI-16 1400 g.
I-DE 1000 g.
I-TR, I-TRC, I-TR2C 500 g.
I-EMP 500 g.

BREAKING CAPACITY CURVES

107

106

105

104
0 1 2 3 4 5 6 7 8 9 10

110 Vdc. 0ms


110 Vdc. 40ms

107

106

105

104
0,00 0,20 0,40 0,60 0,80 1,00 1,20 1,40 1,60

220 Vdc. 0ms


220 Vdc. 40ms

www.arteche.com 4