Module Manual - MOO-ARIOMU-V1.1-2305US - 230519 - W
Module Manual - MOO-ARIOMU-V1.1-2305US - 230519 - W
Module Manual - MOO-ARIOMU-V1.1-2305US - 230519 - W
www.autonics.com
Preface
Preface
Thank you for purchasing Autonics product.
Please familiarize yourself with the information contained in the Safety Considerations section
before using this product.
This user manual contains information about the porduct and its proper use, and should be kept in a place
where it will be easy to access.
※1 Annotation mark.
Safety Considerations
▪ Please observe all safety considerations for safe and proper product operation to avoid hazards.
▪ Safety considerations consist of ‘warning’ and ‘caution. The following symbols represent caution due to
particular circumstances in which hazards may occur.
Caution Failure to follow instructions can lead to a minor injury or product damage.
▪ Fail-safe device must be installed when using the unit with machinery that may cause serious injury or
substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft,
combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire.
▪ Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant
heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in explosion or fire.
▪ Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire.
▪ Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in fire.
▪ Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
Table of Contents
Preface .............................................................................................................................................. iii
Module Manual Guide.......................................................................................................................iv
Module Manual Symbols ...................................................................................................................v
Safety Considerations ......................................................................................................................vi
Caution during Use ..........................................................................................................................vii
Table of Contents ........................................................................................................................... viii
1 Reference manuals
Refer to the following manuals to use the ARIO system stably and safely.
Instruction manual It describes an overview of ARIO system, installation environment, and maintenance, etc.
It describes the overview of each communication, specifications, dimensions, memory map and
Coupler manual
troubleshooting.
Module manual It describes the dimensions, specifications, and connections of each module.
You can use module setting, real-time control of input/output signal, and monitoring/diagnosis
DAQMaster
function (except ARIO-C-PN and ARIO-C-PB) via DAQMaster. Also, the virtual mode and
user manual
recommended sorting provides an arrangement the coupler and modules.
2.1 Specifications
Type Digital input module Digital output module
4CH ARIO-S-DI04N ARIO-S-DI04P ARIO-S-DO04N ARIO-S-DO04P
Model
8CH ARIO-S-DI08N ARIO-S-DI08P ARIO-S-DO08N ARIO-S-DO08P
Insulation resistance 100MΩ (at 500VDCᜡ megger), I/O to inner circuit: photocoupler insulated
Noise immunity ±500VDCᜡ the square wave noise (pulse width: 1 ㎲) by the noise simulator
Vibration 0.7mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration (malfunction) 0.5mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min
Ambient temperature -10 to 55℃, storage: -25 to 70℃ (a non-freezing or condensation environment)
※1. Power supply is from ARIO-P Series. Normal operation is available when I/O power voltage is supplied.
※ For connecting the modules, consider power concumption of the sensors and drivers connected the ARIO coupler.
In case of one coupler module connecting, the ARIO digital module is available to connect up to 8 units.
2.2 Dimensions
(Unit: mm)
2.3 Indicators
(1) Status indicator
Stop operating,
Normal operation Operational readiness of
Green communication error,
Internal network (ABUS) is operating Internal network (ABUS)
module failure
Module failure,
Red error in module components Normal operation Internal network (ABUS) error
(error in main and auxiliary MCU)
ARIO-S-DI04N ARIO-S-DI04P
ARIO-S-DI08N ARIO-S-DI08P
ARIO-S-DO04N ARIO-S-DO04P
ARIO-S-DO08N ARIO-S-DO08P
3.1 Specifications
(1) Analog input module
2CH ARIO-S-AI02V1 ARIO-S-AI02V2 ARIO-S-AI02C1 ARIO-S-AI02C2
Model
4CH ARIO-S-AI04V1 ARIO-S-AI04V2 ARIO-S-AI04C1 ARIO-S-AI04C2
Rated
-10 to 10VDCᜡ 0 to 10VDCᜡ 0 to 20mA 4 to 20mA
Input range
range Allowable
-11 to 11VDCᜡ -1.0 to 11VDCᜡ 0 to 22mA 2.4 to 21.6mA
range
Accuracy Room temp.: ±0.3% F.S. / Out of room temp.: ±0.6% F.S.
Resolution 12bit
Internal transmission
4Mbps
speed
Power consumption ABUS: 5VDCᜡ, Max. 180mA (Max. 0.9W), I/O: 24VDCᜡ, Max. 15mA (Max. 0.36W)
≤-1VDCᜡ
Status indicator ON ≥1VDCᜡ ≥1mA ≥4mA
or ≥1VDCᜡ
Accuracy Room temp.: ±0.3% F.S. / Out of room temp.: ±0.6% F.S.
Resolution 12bit
Internal transmission
4Mbps
speed
ABUS: 5VDCᜡ, Max. 180mA (Max. 0.9W) ABUS: 5VDCᜡ, Max. 100mA (Max. 0.5W)
Power consumption
I/O: 24VDCᜡ, Max. 15mA (Max. 0.36W) I/O: 24VDCᜡ, Max. 60mA (Max. 1.44W)
≤-1VDCᜡ
Status indicator ON ≥1VDCᜡ ≥1mA Always on
or ≥1VDCᜡ
Noise immunity ±500VDCᜡ the square wave noise (pulse width: 1 ㎲) by the noise simulator
Vibration 0.7mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration (malfunction) 0.5mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min
Ambient temperature -10 to 55℃, storage: -25 to 70℃ (a non-freezing or condensation environment)
※ Power supply is from I/O power of coupler or ARIO-P-F Series. Normal operation is available when I/O power voltage is supplied.
For connecting the modules, consider power concumption of the sensors and drivers connected the ARIO coupler and power
modules. In case of one coupler connecting, the ARIO analog module is available to connect up to 4 units.
3.2 Dimensions
(Unit: mm)
3.3 Indicators
(1) Status indicator
Stop operating,
Normal operation Operational readiness of
Green communication error,
Internal network (ABUS) is operating Internal network (ABUS)
module failure
Module failure,
Red error in module components Normal operation Internal network (ABUS) error
(error in main and auxiliary MCU)
ARIO-S-AI02V1/V2 ARIO-S-AI04V1/V2
ARIO-S-AI02C1/C2 ARIO-S-AI04C1/C2
ARIO-S-AO02V1/V2 ARIO-S-AO04V1/V2
ARIO-S-AO02C1/C2 ARIO-S-AO04C1/C2
4.1 Specifications
Type Temperature input module
Power consumption ABUS: 5VDCᜡ, Max. 180mA (Max. 0.9W), I/O: 24VDCᜡ, Max. 15mA (Max. 0.36W)
Internal transmission
4Mbps
speed
Installation method DIN rail mounting
Insulation resistance 100MΩ (at 500VDCᜡ megger), I/O to inner circuit: photocoupler insulated
Noise immunity ±500VDCᜡ the square wave noise (pulse width: 1 ㎲) by the noise simulator
Vibration 0.7mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration (malfunction) 0.5mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min.
Ambient temperature -10 to 55℃, storage: -25 to 70℃ (a non-freezing or condensation environment)
※ Power supply is from I/O power of coupler or ARIO-P-F Series. Normal operation is available when I/O power voltage is supplied.
For connecting the modules, consider power concumption of the sensors and drivers connected the ARIO coupler and power
modules.In case of one coupler connecting, the ARIO analog module is available to connect up to 4 units.
4.2 Dimensions
(Unit: mm)
4.3 Indicators
(1) Status indicator
Stop operating,
Normal operation Operational readiness of
Green communication error,
Internal network (ABUS) is operating Internal network (ABUS)
module failure
Module failure,
Red error in module components Normal operation Internal network (ABUS) error
(error in main and auxiliary MCU)
4.5 Parameter
Parameter Descriptions Setting range Factory defaults
J (IC)
-200.0 to 800.0 -2000 to 8000
E (CR)
R (PR)
0.0 to 1750.0 0 to 17500
TC S (PR)
C (TT)※1
0.0 to 2300.0 0 to 23000
G (TT)※2
Cu 50 Ω
-200.0 to 200.0 -2000 to 2000
Cu 100 Ω
DPt 50 Ω
-200.0 to 650.0 -2000 to 6500
DPt 100Ω
RTD JPt 50 Ω
-200.0 to 650.0 -2000 to 6500
JPt 100 Ω
Nickel 100 Ω
Nickel 1000 Ω
※1. Same as existing W5(TT).
※2. Same as existing W(TT).
5.1 Specifications
(1) Slim Remote ABUS Power Module
Model ARIO-P-B
ABUS
24VDCᜡ, max. 320mA (max. 7.5W, max. 160mA/CH, 2CH/COM)
Power (external consumption)
supply ABUS
5VDCᜡ, max. 1,500mA (max. 7.5W)
(internal supply)
Installation method DIN rail mounting
Noise immunity ±500VDCᜡ the square wave noise (pulse width: 1 ㎲) by the noise simulator
0.7mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction
Vibration
for 1 hour
0.5mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction
Vibration (malfunction)
for 10 min.
Shock 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times.
Certification
※ The ARIO digital module is available to connect up to 8 units, and the ARIO analog and special module are
available to connect up to 4 units.
※ For connecting the modules, consider power concumption of the sensors and drivers connected the ARIO
power module.
No. of 24V 6 2 8 4
I/O supply
power※1 0V 2 6 4 8
Noise immunity ±500VDCᜡ the square wave noise (pulse width: 1 ㎲) by the noise simulator
0.7mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z
Vibration
direction for 1 hour
0.5mm amplified at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z
Vibration (malfunction)
direction for 10 min.
Shock 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
※1. For more information on the number of I/O supply power, see “5.4 Wiring diagram.”
※ For connecting the modules, consider power concumption of the sensors and drivers connected
the ARIO power module.
5.2 Dimensions
(Unit: mm)
ARIO-P-B
6 Ground / Shield
12 Ground / Shield
ARIO-P-F1 ARIO-P-F2
1 24VDC 1 0VDC
2 24VDC 2 0VDC
3 0VDC 3 24VDC
4 24VDC 4 0VDC
7 24VDC 7 0VDC
8 24VDC 8 0VDC
9 0VDC 9 24VDC
10 24VDC 10 0VDC
ARIO-P-T1 ARIO-P-T2
1 24VDC 1 0VDC
2 24VDC 2 24VDC
3 0VDC 3 0VDC
4 24VDC 4 0VDC
5 24VDC 5 24VDC
6 0VDC 6 0VDC
7 24VDC 7 0VDC
8 24VDC 8 24VDC
9 0VDC 9 0VDC
10 24VDC 10 0VDC
11 24VDC 11 24VDC
12 0VDC 12 0VDC