Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Tap Changer Control & Transformer Monitoring System

- Fx8000A

Digital RTCC

Contact Us
11, Star Industrial Estate, Near Sakinaka Telephone Exchange,
Kurla- Andheri Road, Sakinaka, Andheri(E), Mumbai -400072
Tel: 022 2859 3377 /6550, 2859 3000, Mob: 09820 595476
Email: www.info@pradeepsales.com
Website: www.pradeepsales.co.in
Tap Changer Control & Transformer Monitoring System
- Fx8000A

Sr
No
Parameters Specifications

1 Large Display LCD ( 20 x 4)

2 Keypad Touch Sense Keypad, Alpha Numeric


32 nos freely programmable inputs
3 Binary Inputs
Optional : Additional upto 48 at extra cost
4 Binary Relay Outputs 14 nos Freely programmable outputs
32 nos BI – 10 nos AI 4-20mA freely programmable inputs
Optional
48 nos BI – 18 nos AI 4-20mA freely programmable inputs
5 Analog Inputs
(at extra cost)
48 nos BI – 28 nos AI 4-20mA freely programmable inputs
(at extra cost)
6 Analog Outputs 5 nos 4–20mA freely programmable inputs
Fiber Optic
7 IEC 61850
Optional Ethernet RJ 45
Modbus Protocol with RS 485 port,
8 PC Software
Optional RS 232 port
9 Operational Mode Master, Follower, Independent, OFF mode

10 Optional Facility GSM


Transformer Life Calculation, Apparent, real and reactive
metering values, Overload Temperature & Time, Hotspot
11 Other Features Temperature,Data & event Recording with time stamp &
report, Predictive Calculation of Winding Temperature,
System Healthy Status
12 Auxiliary Supply 90V-260V AC/DC , 50Hz, 15VA

13 PT supply 110V AC ± 10% , 50 Hz, 2.5 VA

14 CT Supply 1–5A

15 Basic Voltage Adjustment BVA between 50V-140V AC

16 Sensitivity (DBA) Adjustable around BVA from 0.5 to 9.9% in steps of 0.1%
Voltage Independent time delay adjustable from 1 to 999
17 Time Delay Setting
secs
Under Voltage Blocking & Blocking from under voltage set to 70 – 99% & restoration
18
Restoration setting at 85% of BVA adjustment
One pair of normally open, potential free contacts rated at
19 Control Output 5A, 230V AC for Raise & Lower Auto/ Manual, CF, UV, OV,
OC functions
20 Operating Temperature -40˚C to 60˚C

21 Line Drop Compensator 0 to ± 25V of regulating value continuously adjustable

22 Panel Cutout in mm 485 x 134


Overall Dimensions in mm
23 489 x 134 x 272
LxWxD
24 Weight kg 5 kg approx
2 kV AC for 1 min for 1st time, further only 80% should be
25 Dielectric Strength
applied