Esquema Soft3
Application Diagrams
Connection In Line, With Line Contactor, No Bypass, Type 1 or 2
Coordination, 2-wire or 3-wire control
Line contactor controlled by Power ON and Power OFF push-buttons or on detected error
This application diagram is well adapted to local control using inputs of ATS480. It requires a local intervention to restart after the error
reset even in case of remote control: press S3 push button to restart. Use relay output R1 set to [Operating State Fault] FLT (factory
setting) to turn Off the soft starter when an error is detected.
13
-Q1
14
S1
1
S2
-Q1
6
2
13
(3)
-Q2 S3 -KM1
-Q4
1 -T1
14
2 1 2 R1A
A1
3 4
(2)
1
R1C
-KM1
A1
2
-Q5 -KM1
(5)
A2
Q3
2
(1)
(3)
1/L1
3/L2
5/L3
CL1
CL2
A1
PTC1/AI1
STOP
PTC2
PTC3
+24V
COM
RUN
DQ+
DQ1
DQ2
2/T1
4/T2
6/T3
R1C
R2C
R3C
AQ1
R1A
R2A
R3A
DI4
DI3
S4
S5
STOP
STOP
+24V
+24V
RUN
W1
U1
V1
(4)
M
3
S6
(4) (4)
• (1) Installation of additional fast-acting fuses is mandatory to upgrade to type 2 coordination according to IEC 60947–4–2.
• (2) Take into account the electrical characteristics of the relays, refer to Control Terminal Characteristics, page 46.
• (3) The transformer must supply 110...230 Vac +10% - 15%, 50/60Hz.
• (4) 3–wire control, 2–wire control and fieldbus control. Refer to RUN and STOP Management, page 47.
• (5) To select the appropriate voltage surge suppressor refer to Relay Contacts Wiring, page 49.
Q2 Circuit breaker Short circuit protection device for the primary of the transformer
Q3 Fast acting fuses Short circuit protection device of the soft starter to be used only when type 2
coordination
Q4 Circuit breaker Short circuit protection device for the secondary of the transformer
Q5 Circuit breaker Short circuit protection device for the control part of the soft starter
52 NNZ85515.04 – 07/2023