Wiring

NOTICE
INCORRECT VOLTAGE
• Supply the control supply terminals CL1 / CL2 within a range of 110...230
Vac only
• In case of migration from ATS48●●●Q to ATS480●●●Y, adapt the control
supply transformer
Failure to follow these instructions can result in equipment damage.

Tightening Min relay output Other min wire Max connection Stripping length
torque max wire cross cross section capacity mm (in)
N.m (lbf.in) section mm² (AWG) mm² (AWG)
mm² (AWG) Min Max

0.5 (4.4) 0.75 (18) 0.5 (20) 2.5 (13) 5.5 (0.2) 7.5 (0.3)

Those values are given for a single wire per terminal. Use a shunt to create a
bridge between terminals if necessary.

Control Block Wiring Diagram

AQ1

COM
R2C

R3C

PTC2

PTC3
R2A

R3A

PTC1
AI1
R1C
R1A

0-10 Vdc (b)


x-20 mA

ATS480
STOP

RUN
DQ+
DQ1

DQ2
CL1

CL2

+24
DI3

DI4

0V

24 V

+24 V

110...230Vac (a) 0V

• (a): Control supply 110...230 Vac


• (b): 2 wire PTC/PT100
PT100 Thermal Probe 3 Wires:
PTC2

PTC3
PTC1
AI1

(c)

(c): 3 wire PT100

NNZ85515.04 – 07/2023 45