Professional Documents
Culture Documents
Applications Notes (Longcables)
Applications Notes (Longcables)
com
Application Note
Unidrive SP Operation
with Long Motor Cables
Issue:1
Contents
1 Unidrive SP Operation with Long Motor
Cables .....................................................3
1.1 Introduction ...........................................................3
1.2 Increasing the Maximum Motor Cable Length
Beyond the Standard Limits ..................................4
1.3 Multiple Motors ....................................................12
1.4 Appendix: Unidrive SP and Unidrive SPM Current
Ratings ................................................................13
1.5 Appendix: Sinusoidal Filter Components ............15
When a long motor cable is used between the motor and drive the effect 3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
of the capacitance of this cable on the drive can become significant. At SP1401 65m (210ft)
every switching edge the capacitance must be charged and SP1402 100m (330ft)
subsequently discharged on the falling edge. This leads to a capacitive SP1403 130m (425ft)
high frequency current flowing which must be supported by the inverter
SP1404
output. This charging current is sensed by the drive current sensing
circuit and may affect the drive current control system or protection, SP1405
causing a loss of torque or over-current trip. This is more of a problem SP1406 37m
50m
for small drives where the cable charging currents may be significant SP2401 75m (120ft)
100m (165ft)
compared to the drives current rating. These high frequency currents SP2402 200m 150m (245ft)
may also have heating effects on internal filter and input stage snubber (330ft)
SP2403 (660ft) (490ft)
components. Again, if excessive this results in a drive trip. This is a
SP2404
problem for drives which use a controlled rectifier as the input stage.
SP3401
Figure 1-1 below shows the path for the high frequency earth currents
SP3402
caused by the switching nature of the drives output, returning to the drive
via input cable line to earth capacitance and input stage snubber SP3403
components. SP4401
Figure 1-1 Circulating ground earth currents SP4402
90m
Snubber
SP4403
Supply cable Output cable 250m 185m 125m (295ft)
capacitance to
components
capacitance to SP5401
Switching frequency (820ft) (607ft) (410ft)
earth earth SP5402
earth currents
SP6401
SP6402
SP8411
SP8412
SP8413
Switching frequency Switching frequency Switching frequency
SP8414
500m 370m 250m
earth currents earth currents earth currents SP9411
(1640ft) (1214ft) (820ft)
Other possible paths for these high frequency currents to return to the SP9412
drive are via the line to earth capacitance of the EMC filter, via the star SP9413
point of the supply transformer if connected to earth and via the SP9414
capacitance of the internal EMC filter.
SP9415
1.1.1 Unidrive SP Maximum motor cable lengths SPMA1401
Below are the maximum motor cable lengths for Unidrive SP without SPMA1402
derating the drive or adding external components.
SPMD1401 250m 185m 125m
Table 1-1 Maximum motor cable lengths (200V drives) SPMD1402 (820ft) (607ft) (410ft)
200V Nominal AC supply voltage SPMD1403
SPMD1404
Maximum permissible motor cable length for each of
Model the following frequencies Table 1-3 Maximum motor cable lengths (575V drives)
3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
575V Nominal AC supply voltage
SP1201 65m (210ft)
Maximum permissible motor cable length for each of
SP1202 100m (330ft) the following frequencies
Model
SP1203 130m (425ft)
37m 3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
SP1204
50m (120ft) SP3501
SP2201 75m
100m (165ft) SP3502
SP2202 200m 150m (245ft)
(330ft) SP3503
SP2203 (660ft) (490ft) 200m 150m 100m 75m
SP3504
SP3201 (660ft) (490ft) (330ft) (245ft)
SP3505
SP3202
SP3506
SP4201
250m 185m 125m 90m SP3507
SP4202
(820ft) (607ft) (410ft) (295ft)
SP4203
If this data is not available from the cable supplier, we suggest using the following values: a
Screened cable with insulating jacket between cores and screen 30Ω
Unscreened cable 45Ω Z0
Screened cable with no insulating jacket between cores and screen 20Ω
Mineral insulated solid copper cable 20Ω
If there are n cables in parallel, i.e. in a star configuration from the drive, then the value for one cable must be
divided by n.
2. Estimate the maximum operating d.c. link voltage Vdc.
If there is no requirement for rapid deceleration or braking then the value is given from the highest a.c. supply
voltage multiplied by a factor of √2. b
Vdc
If rapid deceleration is likely then use the maximum d.c. link voltage of 415V for a 200V drive, 830V for a 400V,
990V for a 575V drive and 1175V for a 690V drive.
3. Estimate the peak charging current from:
Vdc I ch
I ch =
Z0
4. Estimate the maximum required motor current. This must allow for any required short-term overload capability.
(Note that the drive is designed for up to 175% short-term current in Heavy Duty rating, and up to 120% in Normal Im
Duty rating.)
5. The required peak current rating of the drive is given by:
I ch Id
Id = Im +
2
6. Select the drive, using the data provided in section 4.1 Unidrive SP and Unidrive SPM Current Ratings on page
Id
11. is the appropriate peak current (closed-loop or open-loop), for Heavy Duty, or 1.1 times the maximum
continuous output current, for Normal Duty.
a. The values are valid for conventional cables in the range 1mm2 to 10mm2. Above 10mm2 use 70% of the values given. This data is not
generally available, but fortunately for mechanical reasons it does not vary greatly over the most common cable sizes.
b. This is the light-load value; it applies even at maximum output current when the speed is low.
I mrg = 2 .(2.1I n − kI nm )
For Normal rating:
I mrg = 2 .(1.85 I n − kI nm )
where:
In
is the nominal rated r.m.s. drive output current in the relevant rating I mrg
I nm
is the nominal r.m.s. motor current at rated load
k is the required short-term overload factor.
Typical values of k are:
Normal duty operation (no torque transients) 1.1
Heavy duty open-loop 1.5
Heavy duty closed-loop 1.75
To prevent nuisance tripping from normal fluctuations around the normal maximum torque, k should never be less
than 1.1.
The factors 2.1 and 1.85 in the expressions above apply to Unidrive SP. For other drives the corresponding
factors must be applied.
4. Estimate the maximum operating d.c. link voltage Vdc.
If there is no requirement for rapid deceleration or braking then the value is given from the highest a.c. supply
voltage multiplied by a factor of √ 2. a
Vdc
If rapid deceleration is likely then use the maximum d.c. link voltage of 415V for a 200V drive, 830V for a 400V,
990V for a 575V drive and 1175V for a 690V drive.
5. The minimum value of inductance to allow the drive to work with this cable capacitance is given by:
2
2CTOT ⎡ Vdc ⎤
Lmin = ⎢ ⎥
3 ⎣⎢ I mrg ⎦⎥ 2Lmin
Using standard iron-cored line inductors the inductance at the high frequencies involved will be rather lower than
the specified 50/60Hz inductance. We suggest specifying an inductance of twice that determined by this
2Lmin
calculation, i.e.
xVac
Lmax =
2πf 0 3I nm
where:
x = acceptable inductor voltage fraction, e.g. for 5% use 0.05
Vac Lmax
= motor voltage rating (line-to-line)
f0
= maximum drive output frequency
I nm
= nominal motor current at maximum continuous load
Since the inductor voltage is inductive, it does not subtract directly from the motor terminal voltage. A value of
x of 0.05 gives a voltage reduction of between 2% and 3%, which is generally acceptable. If the application is
very critical with regard to obtaining full rated torque at full speed then it may be advisable to apply a lower value
of
x , e.g. 0.02.
7. 2 Lmin < Lmax
It will usually be found that and then any value between these limits can be used.
If there is a need to minimise the high frequency current for other reasons, for
example to prevent premature operation of thermal relays, then the highest value should be used. L
2 Lmin > Lmax
If then an inductor cannot be used alone, and a de-rating of the drive is also required. The
above procedure must be repeated with the proposed alternative drive rating.
8. Consideration must now be given to the high frequency power losses in the output line inductors. The loss in each
phase inductor can be estimated from the following expression:
where
f o (max)
= maximum output frequency
I nchk
= inductor rated nominal current at intended operating frequency
10. If the loss exceeds this limit, the following measures should be considered:
Reduce switching frequency
Use a larger inductor
Add a damping resistor
The resistor should be connected in parallel with each inductor to extract some of the power.
The resistor value is given by:
2L
R=
CTOT
The value is not critical and variations of ± 50% are acceptable. The power rating of the resistor should be at least
0.8P. Provision must be made for the resistor to dissipate this power without over-heating itself or nearby
equipment. Values of 100W per phase are not uncommon.
a. This is the light-load value; it applies even at maximum output current when the speed is low.
Vdc I ch
I ch =
Z0 157.6A
4. Estimate the maximum required motor current. This must allow for any required short-term overload capability.
(Note that the drive is designed for 175% short-term current in Heavy Duty rating, and 110% in Normal Duty Im
rating.)
8 x 2.02 x 1.1 17.8A
5. The required peak current rating of the drive is given by:
I ch Id
Id = Im +
2 129.2A
6. Select the drive, using the data provided in section 4.1 Unidrive SP and Unidrive SPM Current Ratings on page
Id
11. is the appropriate peak current (closed-loop or open-loop), for Heavy Duty, or 1.1 times the maximum
continuous output current, for Normal Duty.
This peak current is clearly completely impracticable, as it would require a SP5401 (55kW/75kW) to obtain
the required peak current for Normal Duty.
a. This is the light-load value, it applies even at maximum output current when the speed is low.
I mrg = 2 .(2.1I n − kI nm )
For Normal rating:
I mrg = 2 .(1.85 I n − kI nm )
where:
In
is the nominal rated r.m.s. drive output current in the relevant rating I mrg
I nm
is the nominal r.m.s. motor current at rated load 14.9A
k is the required short-term overload factor.
Typical values of k are:
Normal duty operation (no torque transients) 1.1
Heavy duty open-loop 1.5
Heavy duty closed-loop 1.75
To prevent nuisance tripping from normal fluctuations around the normal maximum torque, k should never be less
than 1.1.
The factors 2.1 and 1.85 in the expressions above apply to Unidrive SP. For other drives the corresponding
factors must be applied.
SP 2401 Normal Duty: √2 x (1.85 x 15.3 – 1.1 x 16.16)
4.
Decide the maximum DC link voltage where the drive is required to produce full torque. This is the same as step Vdc
2 in the de-rating procedure above.
591V
5. The minimum value of inductance to allow the drive to work with this cable capacitance is given by:
2
2CTOT ⎡ Vdc ⎤
Lmin = ⎢ ⎥
3 ⎣⎢ I mrg ⎦⎥
2Lmin
Using standard iron-cored line inductors the inductance at the high frequencies involved will be rather lower than
the specified 50/60Hz inductance. We suggest specifying an inductance of twice that determined by this 0.322 mH
2Lmin
calculation, i.e.
Lmin = 2/3 x 153.6 nF x (591/14.9)2 = 0.161 mH
2L min = 0.322 mH
fs
= switching frequency
The factor 0.8 is a rough estimate of the fraction of the total losses which are dissipated in the inductor. Note that
the loss is proportional to the switching frequency so the lowest acceptable frequency should be selected.
9. It is now necessary to decide whether the output line inductor is able to tolerate this loss, which will appear prima-
rily as additional iron loss to that which the designer expected. This is a difficult judgement since it depends on the
closeness of its operating temperature to its material limits. As an approximate rule, the loss should not exceed
0.1 of the VA in the inductor at maximum speed, i.e.:
P ≤ 0.2πf o (max) LI nm
2
where
f o (max)
= maximum output frequency
P≤16.4W so 258W is excessive
Change to 3kHz switching, bringing loss down to 129W
10. If the loss exceeds this limit, and it is not possible to reduce the switching frequency, then a resistor should be
connected in parallel with each inductor to extract some of the power.
The resistor value is given by:
2L
R=
CTOT
The value is not critical and variations of ± 50% are acceptable. The power rating of the resistor should be at least
0.8P. Provision must be made for the resistor to dissipate this power without over-heating itself or nearby
equipment. Values of 100W per phase are not uncommon.
R = 161Ω use 150Ω rated at 103W minimum (use 150W)
Therefore the solution is to use a SP2401 and a 2mH inductor. A 150Ω, 150W resistor should also be fitted in parallel with each phase of the
inductor to reduce the power dissipated by the inductor.
When using multiple motors with Unidrive SP, the drive should be set in
open loop mode with one of the fixed V/F modes (Pr 5.14 = Fd or SrE) Motor protection
selected. relay
Motor protection Figure 1-6 Incorrect wiring for multiple parallel cable run
relay
Motor protection
relay
Star connection