Installation Instructions

MOSCON-F50 AC Drive
(Ver. 3.xx)

Language Page
English 3
한국어 53
English

Contents
Important User Information ............................................................................. 4
Safety Instructions .......................................................................................... 5
Receiving ......................................................................................................... 6
Nameplate information ................................................................................... 7
Installation ....................................................................................................... 8
Dimensions ..................................................................................................... 9
Connection diagram ...................................................................................... 12
Main Circuit Terminal Functions .................................................................. 14
Control Circuit Terminal Functions ................................................................ 15
Cable Specification ...................................................................................... 16
Wiring check .................................................................................................. 17
Switch Setting ............................................................................................... 18
Specifications ................................................................................................ 19
Monitoring functions of digital operator ....................................................... 28
Test Run ......................................................................................................... 29
U-Parameter: Monitoring .............................................................................. 32
B-parameter: Basic Environments Setting .................................................... 34
F-parameter: Frequency Control Setting ...................................................... 36
S-parameter: System Function Adjustment Setting ..................................... 38
C-parameter: H/W Functions Setting ........................................................... 41
H-parameter: Input/Output Control Function Setting .................................. 43
P-parameter: Protection Functions Setting .................................................. 45
Protective function/error description ........................................................... 47
Periodic inspection ........................................................................................ 51
Part replacement ........................................................................................... 52
4

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment.
There are some important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all
persons responsible for applying this equipment must satisfy themselves that each intended application of
this equipment is acceptable.
In no event will RS Automation Co., Ltd. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, RS Automation Co., Ltd. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by RS Automation Co., Ltd. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of RS Automation
Co., Ltd., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations
Identifies information about practices or circumstances that can cause an explosion in a
WARNING hazardous environment, which may lead to personal injury or death, property damage,
or economic loss.

Identifies information that is critical for successful application and understanding of the
IMPORTANT
product.
Identifies information about practices or circumstances that can lead to personal injury
ATTENTION
or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence

Moscon-F50 AC Drive
5

Safety Instructions
Please read this manual and the related documentation thoroughly and familiarize yourself with the directions
before installing, performing inspection and preventive maintenance. Make sure to follow the directions
correctly to ensure normal operation of the product and your safety.
• Before starting wiring or inspection, switch power off, wait for more than 1
WARNING minutes, and check for residual voltage between terminal P/B and N with a meter
etc, to avoid a hazard of electrical shock.
• The digital operator is detachable from the main body.
• Suitable for use in a circuit capable of delivering not more than 5kA rms
symmetrical amperes.
• Do not carry the AC Drive by holding the plastic parts, but hold the heatsink. The
heat sink may fall and cause injury.
• Use nonflammable materials such as metal for the part where the AC Drive is
installed.
• When installing several AC Drives in a single enclosed space, install a cooling fan
to keep the ambient temperature below 45°.
• Cover the AC Drive during installation to protect it from metal chip coming from
drilling
• Always turn OFF the input power supply before wiring. Otherwise, an electric shock
or fire may occur.
• Wiring must be performed by qualified personnel.
• Always check if the bolts on the main circuit and control circuit terminals are
properly tightened.
• Turn ON the AC Drive only after completely assembling the covers. Do not detach
the cover when the power is ON. Otherwise, an electric shock or fire may occur.
• Ground the ground terminal (200V class: ground to 100 ohm or less, 400V class:
ground to 10 ohm or less). Otherwise, an electric shock or fire may occur.
• Tighten all terminal screws of the main circuit and the control circuit.
• Check if the voltage of the AC Drive rated voltage satisfies with the AC power
supply voltage. Otherwise, it may cause fire or injury
• Do not perform withstand voltage test on the AC Drive. It may damage the
semi-conductor element.
• When wiring other devices read their manuals carefully. RS Automation Co., Ltd. is
not responsible for any accident resulting from user's carelessness. If not, it may
cause injury or fire.
• Do not connect electromagnetic switches or magnetic contactors to the output
circuits.
• Otherwise, it will actuate the over current protective circuit in the AC Drive.
• Never connect an AC power supply to output terminals U/T1, V/T2, and W/T3.
Otherwise, it may damage the internal circuits of the AC Drive.
• Never short or ground output terminals: the output terminals should not be touched
with bare hands and also, the output wires should not have contact with the AC
Drive case Otherwise, an electric shock or grounding may occur.

Moscon-F50 AC Drive
6

• Do not connect a phase advancing capacitor or LC/RC noise filter to an output


WARNING circuit.
• Otherwise, it may damage the AC Drive or cause a fire.
• Do not connect an electromagnetic switch or MC to an output circuit.
• Otherwise, it will actuate the over current protective circuit in the AC Drive.
• Do not disassemble the digital operator. Otherwise, it may cause a personal injury.
• Set the appropriate parameter. If not, it will not operate or trigger the protection
operation.
• Record the previous parameters (even though Moscon-F50 records the information
of the last parameter), the records can be useful in case of malfunction or errors.

Receiving
Confirm the following upon delivery of the Moscon-F50:
• Verify the model number to check if the correct item has been delivered.
• Check if any physical damage has occurred during shipping.
If there is any damage or missing part, call the place where you purchased the product
or sales office for service immediately.

Don’t install the AC Drive if there is any damage or a missing part. It may
WARNING
cause injury.

Moscon-F50 AC Drive
7

Nameplate information

Program version Hardware version

Model number MODEL : SI_20P7F50 SW: 1.0 HW:A


Input voltage Input Voltage: 3PH 200-230Vac 4.8A 50/60HZ
Output Power: 3PH 0-230Vac 1.9kVA 5.0A
output voltage IP20/UL Open-Type MASS: 0.95 Kg
SER. NO: 2XF50X013-FB0001
serial number IND. CONT. EQ.
61KJ
E226834

Rockwell Automation Korea Ltd. MADE IN KOREA

Example of nameplate

AC Drive model number

SI - 4 3P7 F50 XXX (Option)


F50 Series

voltage class Max. motor capacity Option


(P is a decimal point) None: Standard
B: 1-phase 200V 0P2: 0.2kW
2 : 3-phase 200V 0P4 : 0.4kW A: Full Function
4 : 3-phase 400V 0P7 : 0.7kW D: DeviceNet
1P5 : 1.5kW TM: Treadmil
2P2 : 2.2kW
3P7 : 3.7kW

Nameplate location
Nameplate
(located at the right side)
एँऎ࣪ऊऋࣶ࣮ࣜऔंࣱ࣬औࣱࣩ࣬࣬ࣽं࣭ࣾ࣬࣬࣬
अऌ࣮࣬ࣜअऊएऐࣽईईࣽऐअऋऊࣜࣿࣽऐँःऋऎकࣜअअࣜउࣽएएࣲࣶ࣭࣪࣬इण
ऋऱरबऱरࣜऌफळडमࣶ࣯ࣜࣜࣜࣽࣿࣜऌऄࣰࣲࣩࣜ࣬࣬ऒࣰ࣭ࣜ࣪धऒ࣭ࣽࣜ࣪ࣴࣽ
अपबऱरࣜऒफनरझणडࣶ࣯ࣜࣜࣽࣿࣜऌऄࣰࣲ࣯ࣩࣜࣴ࣬࣬ऒࣱࣲࣜ࣬࣫࣬ऄश
उऋऀँईࣶࣜࣜएअछࣰ࣬ऌࣰंࣱ࣬
FcW_kY``5ihcaUh]cb?cfYU@hX"A589=B?CF95

ऌऎःࣶ࣭࣪࣬࣬

Moscon-F50 AC Drive
8

Installation

Controlling the ambient temperature


To maintain the optimum condition, the AC Drive should be installed at the ambient
temperature –10°C to 40°C If installed in a closed environment (e.g. enclosed panel), install a
cooling fan or air conditioner to avoid any extreme temperature increases and to maintain the
internal air temperature within the range.

• If installed in a closed environment (e.g. enclosed panel), we strongly recommend the


WARNING
AC Drive to be installed on a vertical space. If it is installed on a horizontal space, its
internal temperature may increase excessively and thus, reducing its durability.
IP20 INSTALLATION CATEGORY II MASS:1.60Kg

Input Voltage : AC 3PH 380-460V 50/60Hz


SER.NO: 2XF50X005A-FB0001

Output Power : AC 3PH 0-460V 1.4kVA 1.8A

MODEL : SI_40P4F50
Rockwell Automation Korea Ltd. MADE IN KOREA

Rockwell Automation Korea Ltd. MADE IN KOREA

SER.NO: 2XF50X005A-FB0001
IP20 INSTALLATION CATEGORY II MASS:1.60Kg
Output Power : AC 3PH 0-460V 1.4kVA 1.8A
Input Voltage : AC 3PH 380-460V 50/60Hz
PRG:1.00 MODEL : SI_40P4F50
PRG:1.00

Vertical Horizontal
Installation Installation

Moscon-F50 AC Drive
9

Installation space
Install the AC Drive on a vertical surface to enhance the cooling effect. When installing the
AC Drive, always leave enough space around it to provide normal heat dissipation.

> 100mm
> 30mm > 30mm

IP20 INSTALLATION CATEGORY II MASS:1.60Kg

Input Voltage : AC 3PH 380-460V 50/60Hz


SER.NO: 2XF50X005A-FB0001

Output Power : AC 3PH 0-460V 1.4kVA 1.8A

MODEL : SI_40P4F50
Rockwell Automation Korea Ltd. MADE IN KOREA

PRG:1.00
> 100mm

Installation space

Dimensions
76 84.6 Unit: mm
128

Dimensions of 3-phase 20P2

Moscon-F50 AC Drive
MODEL : SI_40P4F50 PRG:1.00 MODEL : SI_40P4F50 PRG:1.00
InputVoltageAC: 3PH 380-460V 50/60
Hz InputVoltageAC: 3PH 380-460V 50/60
Hz
OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A
IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg
SER.NO: 2XF50X005A-FB0001 SER.NO: 2XF50X005A-FB0001

145.4
145.4

Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA
126.4

Dimension of 1-phase B0P4, B0P7 and 3-phase 21P5, 22P2, 40P4, 40P7, 41P5

Dimension of 1-phase B1P5, B2P2 and 3-phase 23P7, 42P2, 43P7


Dimension of 3-phase 20P4, 20P7
76

120

150

Moscon-F50 AC Drive
128
128
128
10
11

Dimensions of MOSCON-F50

Type MOSCON-F50
External Dimension Installation Dimension Volume (mm3) Weight
(Unit: mm) (Unit: mm) (kg)
(W x H x D) W1 x H1 x Φ
20P2 76 x 128 x 84.6 822,988.8 0.6
20P4 66 x 118, M4
76 x 128 x 126.4 1,229,619.2 0.9
20P7
B0P4
B0P7
21P5
22P2 120×128×145.4 103×118, M4 2,233,344 1.6
40P4
40P7
41P5
B1P5
1.9
B2P2
23P7 150×128×145.4 134×118, M4 2,617,200
42P2 2.0
43P7

Moscon-F50 AC Drive
12

Connection diagram
The connection diagram of the Moscon-F50 is shown below.
When using the digital operator, the motor can be operated by wiring only the main circuits.

External Braking Resistor


(optional)

B1 B2
MCCB
Motor
R/L1 U/T1
4)
S/L2 V/T2
Input power
4)

T/L3 W/T3

Digital Input
S1 R1 Multi-function
Forward run/stop contact output 1
S2
Reverse run/stop DC 30V 1Amax
S3 RC1 AC 250V 1Amax
External fault (Default: fault)
Fault reset S4
Multi-step command S5 Multi-function
R2 contact output 2
Jogging S6 DC 30V 1Amax
SC AC 250V 1Amax
RC2
(Default: In running)

Ground
2 kΩ
V+ Power for speed command
(+12V 20mA)
A1 Analog Input 1
2 kΩ
(0 to 10V 20kΩ )
AC
Analog Common
Analog Input 2
A2
(4-20mA, 0-20mA 250Ω ,
0~10V 20kΩ )
AM (0-32kHz Pulse:Option)
Analog monitor output
(0-10V)
(0 -32kHz Pulse:Option)

Connection diagram (200V/400V class 3-phase)

p
NOTE 1) : Shield wire, : Twisted pair shield wire.
2) : Main circuit terminal, : Control circuit terminal.
3) Max. current value for V+ (power for speed command) is 20mA.
4) EMI cores are recommended to the motor cables.
(refer to the diagam about installation location. TDK ZCAT3035 - 1330)

Moscon-F50 AC Drive
13

External Braking Resistor


(optional)

B1 B2
MCCB
Motor
R/L1 U/T1
Input power 4)
S/L2 V/T2
4)
W/T3

R1 Multi-function
contact output 1
1 DC 30V 1Amax
2 AC 250V 1Amax
RC1 (Default: fault)
3
Digital Input 4
5 R2
Multi-function
6
contact output 2
DC 30V 1Amax
9 AC 250V 1Amax
RC2
(Default: In running)

2 kΩ Ground

Power for speed command


V+ (+12V 20mA)

2 kΩ A1 Analog Input 1
(0 to 10V 20kΩ )
AC
Analog command

A2
Analog Input 2
(4-20mA, 0-20mA 250Ω ,
0~10V 20kΩ )
AM (0-32kHz Pulse:Option)
Analog monitor output
(0-10V)
(0 -32kHz Pulse:Option)

Connection diagram (200V class 1-phase)

p
NOTE 1) : Shield wire, : Twisted pair shield wire.
2) : Main circuit terminal, : Control circuit terminal.
3) Max. current value for V+ (power for speed command) is 20mA.
4) EMI cores are recommended to the motor cables.
(refer to the diagam about installation location. TDK ZCAT3035 - 1330)

Moscon-F50 AC Drive
14

Main Circuit Terminal Functions


200V class 1-phase main circuit terminal functions
Purpose Symbol
Main circuit power input R/L1, S/L2
Inverter outputs U/T1, V/T2, W/T3
Braking resistor connection B1, B2
Ground

3-Phase 200V/400V class main circuit terminal functions


Purpose Terminal Symbol
Main circuit power input R/L1, S/L2, T/L3
Inverter output U/T1, V/T2, W/T3
Braking resistor connection B1, B2
Ground

Moscon-F50 AC Drive
15

Control Circuit Terminal Functions


Control circuit terminal block
Terminal Function Signal level Default setting
S1 Forward run/stop command Photo-Coupler input -
+24V, 10mA
S2 Reverse run/stop command -
S3 Digital input 1 External fault
S4 Digital input 2 Fault reset
Digital input 3 Multi-step speed1
S5
command
S6 Digital input 4 Jogging command
SC Digital Common +24V Ground Sequence 0V
V+ Voltage source for freq. command +12V (Max 20mA) -

A1 Analog Input 1 for freq. commandy Voltage (DC 0 to +10V) Command Frequency

Analog Input 2 for freq. command Current (0~20, 4~20mA) Command Frequency
A2 Voltage( 0~10V),
Pulse(Option: 0~32kHz)
AC Analog Common 0V -
Analog monitor output DC 0~10V (Output frequency)
AM
Pulse(Option) 0~32kHz
Multi-function relay output 1 Contact : Fault occurred
R1, RC1 AC 250V, 1A or below
DC 30V, 1A or below
Multi-function relay output 2 Contact : In running
R2, RC2
AC 250V, 1A or below
(Option)
DC 30V, 1A or below

NOTE Be attentive to below mention when changing output frequency in using the external frequency command terminal.
• Voltage command input terminal is set as AI1 + AI2.
• Pulse IO is available from ver 2.0 and it is optional.

Moscon-F50 AC Drive
16

Cable Specification
Determine the cable size for the main circuit. The line voltage drop should be within 2% of
the rated voltage. The line voltage drop is calculated as below:

  =           10
LVD: Line Voltage Drop
CR: Cable Resistance
WL: Wiring Length
C: Current

Cable size
Circuit Model Terminal Tightening Crimping Cable Size(1) Kind of Cable
Screw Torque Nm Terminal
mm2 AWG

Main 20P2, M4 0.8-1.0 2-4 2 14 Power cable


Power 20P4, (600V
(R/L1, 20P7 Vinyl-sheathed
S/L2, wire or
21P5, M4 1.2-1.5 2-4 3.5 12
T/3, equivalent)
22P2
+1,+2,
P/B,N, 23P7 M4 1.2-1.5 5.5-4 5.5 10
U/T1,
B0P4 M4 0.8-1.0 2-3.5 2 14
V/T2,
W/T3) B0P7, M4 1.2-1.5 2-4 3.5 12
B1P5
B2P2 M4 1.2-1.5 5.5-4 5.5 10
40P4, M4 1.2-1.5 2-4 2 14
40P7,
41P5,
42P2,
43P7
Control All M2 0.22-0.25 - 0.5-1.2 20-16 Shielded
5 twisted-pair

(1)
Earth Cable should be used with a 10.0 mm2 or thicker cable.

Moscon-F50 AC Drive
17

Wiring check
• After wiring has been complete, check the following. Do not perform a buzzer check on
WARNING
control circuit.

• Check if all wiring is correct.


• Especially check if the power supply is connected the U/T1, V/T2, W/T3 terminal.
• Check if any wire clippings, screws or other foreign material are left.
• Check if all screws are tight.
• Check if the load status is good.
• Check if any wire ends are contacting other terminals.

Power Input Noise Filter


Model Noise Filter Maker
20P2, 20P4, 20P7 C3B2005-AR OKY
21P5, 22P2 C3B2010-AR
23P7 C3B2020-DR
40P4, 40P7, 41P5 C3B4005-AR
42P2, 43P7 C3B4010-AR
B0P4, B0P7 Ask to sales representatives
B1P5, B2P2

Moscon-F50 AC Drive
18

Switch Setting

SW1
Monitor
Select ON

SW3 1 2 3 4 5 6
SRC/SNK
Select

SW2
AI Type
Select

Function Switch DIP SW Position Number


1 2 3 4 5 6
AO Enable SW1 ON OFF ON OFF N/A N/A
(Option)
PO Enable OFF ON OFF ON N/A N/A
AI2 = Pulse (option) SW2 OFF ON OFF OFF (1) OFF

AI2 = Voltage ON OFF OFF ON OFF


AI2 = Current (default) OFF OFF ON ON ON
Termination Resistor - - - - ON -
Internal Power Source SW3 OFF OFF ON ON OFF
Internal Power Sink (default) ON ON OFF OFF OFF
External Power Source OFF OFF OFF OFF ON
(1)
Empty box is “don’t care.”

ATTENTION Wrong DIP SW setting makes HW problem resulted from mixed signal types.
Pay very careful attention to DIO SW settings.

Moscon-F50 AC Drive
19

Specifications
200V- 3-phase 20P2 20P4 20P7 21P5 22P2 23P7
230V
Class 1-phase - B0P4 B0P7 B1P5 B2P2 -

Max. Applicable
Motor

Motor 0.2 0.4 0.75 1.5 2.2 3.7


Capacity[kW](1)
Inverter
0.8 1.2 2 3.2 4.8 7.7
Capacity[kVA]
(-) (1.1) (1.9) (3) (4.5) (-)
(1 phase)
Rated Input 1.5 2.9 4.8 7.5 11.0 17.5
Current (A)
Input

Rated Input 3Phase, 200~230Vac, 50/60Hz


Voltage and
Single phase, 200~230Vac, 50/60Hz
Frequency
Allowable Voltage: -10% ~ +10%,
Fluctuation Frequency: −0.5% ~ +5%
Inverter
0.6 1.1 1.9 3 4.2 6.7
Capacity[kVA]
(-) (1.1) (1.9) (3) (4.2) (-)
(1 phase)
Rated Output
1.6 3 5 8 11 17.5
Current[A]
Output

(-) (3) (5) (8) (11) (-)


(1 phase)
Rated Output 3 phase, 200~230Vac (Proportional to input voltage)
Voltage[V]
Rated Output Default: 60Hz, Max. 400Hz
Frequency[Hz]
(1) The maximum applicable motor capacity is for a standard 4-pole motor. When selecting the motor and inverter, make sure
that the Inverter's rated current is applicable for the motor's rated current.

Note: Difference between standard and full function products


•Standard: Relay output 1 only, no pulse IO
•Full Function : Relay output 1, 2, include pulse IO

Moscon-F50 AC Drive
20

380V- 3-phase
460V - 40P4 40P7 41P5 42P2 43P7
Class
Max. Applicable
Motor

Motor 0.2 0.4 0.75 1.5 2.2 3.7


Capacity[kW](1)
Rated Input
1.5 2.8 4 5.1 9.3
Capacity[kVA]
Rated Input
1.8 3.2 4.4 5.5 8.2
Current[A]
Input

Rated Input 3-Phase, 380~460Vac, 50/60Hz


Voltage and
Frequency
Allowable Voltage: -10% ~ +10%,
Fluctuation Frequency: −0.5% ~ +5%
Inverter
1.4 2.6 3.7 4.2 6.7
Capacity[kVA]
Rated Output
Current[A] 1.8 3.4 4.8 5.5 8.6
Output

(1 phase)
Rated Output 3 phase, 0~460Vac (Proportional to input voltage)
Voltage[V]
Rated Output Default: 60Hz, Max. 400Hz
Frequency[Hz]
(1) The maximum applicable motor capacity is for a standard 4-pole motor. When selecting the motor and inverter, make sure
that the Inverter's rated current is applicable for the motor's rated current.

Moscon-F50 AC Drive
21

Modulation type Comination of sinusoidal waves PWM (Pure sinusoidal


wave modulation or Space Vector modulation - 2-phase
3-phase modulation)
Control Method V/f (Slip compensation included), Vector without PG
Frequency Control Range 0~400.00 Hz
Frequency Control Accuracy Digital: 0.05%
Analog: 0.5%
Frequency Setting Resolution Digital: 0.01Hz
Control & Performace

Analog: 0.1Hz(10-bit)
Output Frequency Resolution 0.01Hz
Accel/Decel Time 0~600.00sec (0.1sec step)
2 sets available
Carrier Frequency Control Range 1.5~11KHz (0.1kHz step)
Speed Control Range 100:1
Speed Stability 1.0%(@60:1, Slip compensation included)
Speed Responsivity 5Hz
Starting Torque 150%@1.0Hz
Torque limiting Yes (Current limiting)
Overload tolerance 150%/60sec., 200%/1sec

Moscon-F50 AC Drive
22

Input/Output Terminals
Control User I/F Operation Panel: LED Operator (4 digits + 6 keys),
Communication S/W (MosconTools)
Communication Port RS-485 with Modbus-RTU (RJ-45),
Input Analog Input Two Input, 9 functions, AI1 voltage (0-10V)
AI2: Voltage (0-10V, 0 (or 4)-20mA, 0-32kHz Pulse: option)
Zi :20 k ohm(voltage), 250 ohm(current)
external resistor : 2k ohm, min. 2W
Digital Contact Point Input 6 Input, 30 functions + power (+24V)
(fixed x 2, configurable x 4)
24V, Sink or Source
(L: 0~6V, H: 18~24V)
1 Output, 8 functions (Pulse Output 5 functions: option)
Analog Output Select Voltage (0~10V) or Pulse (0-32kHz: option)
Zo : min.1 k ohm (voltage) or max. 200 ohm (current)
Output R1 Output, 12 functions (1a relay)
(R2 Output, 12 functions (Option 1a realy)
Digital Contact Point Output
relay : 1.0A @ 30Vdc/240Vac(non-inducting), 1.0A @
30Vdc/240Vac(inducting)
1-phase power Input L1, L2
3-phase power Input L1/R, L2/S, L3/T
Power Supply Breaking resistor
B1, B2
connection
3-phase Output (Common) T1/U, T2/V, T3/W

Moscon-F50 AC Drive
23

Inverter Overload (OL2), Motor Overload (OL1), low voltage


(UV1), over voltage (OV), over current (OC), current limit
H/W protection/detection
(CLB,CLA), over torque (OL3), over heat(OH), Input power
loss(IPL: 3-phase only)
Protection

Slip protection, automatic torque compensation, Analog


input loss detection, user parameter protection, blackout
S/W compensation compensation(ready for recovery), command loss
compensation (ready for recovery), detection of command
error from external terminal blocks

Moscon-F50 AC Drive
24

5 types (integrated control panel, internal settings, Preset,


Frequency command unit
Analog input, communication)
3 types (integrated control panel, contact point input,
Run command unit
communication)
Stop method 2 types (decel, free run)
Internal setting speed
command (Preset 9 steps
command)
Restarting during rotation Yes
Automatic restarting when
Max. 10 times
there is a fault
Automatic restarting when
Application Yes
power is applied
Mechanical vibration
prevention (Frequency Max. 3 locations
Jump)
Breaking with DC current During Start and Stop
Output voltage calibration automatic
Automatic estimation of
Stop type, rotation type
motor constant(autotuning)
command frequency, Output frequency/ current/
Monitoring items voltage/power(kW), DC circuit, estimate motor speed(rpm)/
(HMI) torque,

Other features Copy user parameters by using the standard operator

Moscon-F50 AC Drive
25

Enclosure type IP20/ UL Open-Type


Installation spot Indoor (explosive gas or dust free area)
Installation altitude limit < 1000m
Max. surroungding air
-10 ~ 40 'C
temperature
Environment/ Storage temperature -40 ~ 85 'C
Safety
Relative humidity 0 ~ 90 %RH, No dew condensing
Shock and vibration 5G peak : 10ms, 1G peak : 5 Hz~2 kHz
UL 508C, CSA 22.2, CE LVD (EN61800-5-1:2003), EMC
International standard 89/336(EN61800-3:2004)
certification 200V 1 phase models: UL508C, CSA22.2, CE LVD, except for
EMC

Moscon-F50 AC Drive
26

Specifications of Inverter Fuse and Circuit Breaker


Model Circuit Breaker(1) Contactor UL Class T, CC, J Fuse(2)
(5kA 600V)
AF AT
20P2 30A 5A 5A 6A
20P4 30A 5A 10A 6A
B0P4, 20P7 30A 10A 10A 10A
B0P7, 21P5 30A 20A 20A 15A
B1P5, 22P2 30A 20A 20A 25A
B2P2, 23P7 30A 30A 20A 30A
40P4 30A 5A 10A 6A
40P7 30A 5A 10A 6A
41P5 30A 10A 10A 10A
42P2 30A 10A 10A 15A
43P7 30A 20A 10A 20A
(1) Circuit Breakers: inverse time or instantaneous trip
(2)
Fuse

- IEC-BS88(British standard) Parts 1&2, EN60269-1, Parts 1&2, type gG or equivalent should be used

Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD,

DD, ED, EFS, EF, FF, FG, GF, GG, GH.

- UL - UL Class CC, T or J must be used

Typical designations include; Type CC - KTK-R, FNQ-R, Type J - JKS, LPJ, Type T - JJS, JJN

Moscon-F50 AC Drive
27

7-segment Display: FWD LED:


Display monitoring information and parameters with 4 ON when the motor is
characters running forward (CW)

Increment/Up key:
– Increase parameter number and value REV LED:
ON when the motor is
– Shift between parameter groups running backward (CCW)

Digital volume(1):
– Frequency setting
mode (change
frequency command)
– Parameter setting
Run key: mode
Run motor in the operator CW: increment
command mode CCW: decrement
– Shift between
parameter group

Stop key:
Stop motor
Reset key:
Reset fault

Data key:
Display parameter description
Decrement/Down key:
– Decrease parameter number and value Set key:
– Set parameter to the displayed
value
Shift key:
- Select the digit to modify – After chaning the parameter,
- When U0.01 value is displayed, display the parameter number
move to command freq. edit mode
(B0.01=0 or 1 only)

(1)
Using the digital volume, a displayed data or parameter number can be changed in different rate.

Moscon-F50 AC Drive
28

Monitoring functions of digital operator

Reference Freq.
Ά͟͢͡͡ ͑

Άͣ͟͡͡ ͑ Output Freq. Άͨ͟͢͡ S/W version

Άͤ͟͡͡ ͑ Output Current Άͧ͟͢͡ ͑ Run time


[hour]

Άͥ͟͡͡ ͑ Άͦ͟͢͡ ͑ Accumulated Run time


[10 hours]
Output Voltage

Άͦ͟͡͡ ͑ DC link Voltage Άͥ͟͢͡ Inverter Temperature

Άͧ͟͡͡ ͑ Output ͑
Άͤ͟͢͡ I/O status ͑

Άͨ͟͡͡ ͑ Estimate Motor Speed Άͣ͟͢͡ ͑


[RPM]
PID output [%]
͑

Ά͟͢͢͡ ͑ PID deviation [%]


Άͩ͟͡͡ ͑ Output Torque[%]
͑

Ά͟͢͡͡ ͑ PID feedback [%]

Άͪ͟͡͡
͑
PID reference [%] ͑
Monitoring functions of digital operator

Moscon-F50 AC Drive
29

Test Run
Power ON
When pressing Shift Key, the mode is
changed to Freq. edit mode.
Floating point blinking (B0.0=0)
FWD
Digit blinking (B0.01=1)
REV
Set Command
Frequency In order to increase the value,
FWD rotate the digital volume in CW
REV
direction.
Run
Press RUN key.
FWD

REV

Stop Press STOP key.


FWD

Go to parameter no. REV

Press DATA/SET key.


FWD
Go to different REV
parameter group
Rotate the digital volume clockwise
FWD for 2 click.
Go to digit REV

to be changed
Press Right Shift Key
FWD

Increase parameter REV

subgroup number Rotate the digital volume clockwise


for 2 click.
FWD

REV
Parameter
modification Press DATA/SET key.
FWD
(Switched to DATA mode)
REV

*The reversed color digit indicates blinking.

Moscon-F50 AC Drive
30

B0.01= 0 or 1 only

Floating point blinking (B0.0


Digit blinking (B0.01=1)

Test run using digital operator


(when the inverter is in its default status)

Moscon-F50 AC Drive
31

Parameter setting method

Moscon-F50 AC Drive
32

U-Parameter: Monitoring
Parameter Descrpition Unit Display
U0.01 Effective Frequency Command xx.xx
0.01㎐
∼xxx.x
U0.02 Current Output Frequency xx.xx
0.01㎐
∼xxx.x
U0.03 Output Current in RMS 0.01A xx.xA
U0.04 Output Voltage in RMS 1V xxxu
U0.05 DC Bus Voltage 1V dxxx
U0.06 Output Power in 0.1kW 0.1kW Pxx.x
U0.07 Motor speed in RPM 1rpm xxxx
Monitoring

U0.08 Percentage Output Torque 1% oxxx


U0.09 PID Command % xxx
U0.10 PID Feedback % xxx
U0.11 PID Error % xxx
U0.12 PID Output % xxx
U0.13 Input/Output terminal status
U0.14 AC Drive Temperature °C c xxx
U0.15 Elapsed total operation time 10Hr xxxx
U0.16 Elapsed time after power on Hr xxxx
U0.17 SW revision number - r.xxx

Moscon-F50 AC Drive
33

Parameter Descrpition Unit Display


U1.01 Reference Frequency at fault xx.xx
0.01Hz
∼xxx.x
U1.02 Output Frequency at fault xx.xx
0.01Hz
∼xxx.x
U1.03 Output Current at fault 0.01A xx.xA
U1.04 Output Voltage at fault 1V xxxu
U1.05 DC Bus Voltage at fault 1V dxxx
U1.06 Output Power at fault 0.1kW Pxx.x
Last Fault

U1.07 Motor rpm at fault 1rpm xxxx


U1.08 Output Torque at fault 1% oxxx
U0.09 PID Command at fault % xxx
U0.10 PID Feedback at fault % xxx
U0.11 PID Error at fault % xxx
U0.12 PID Output at fault % xxx
U1.13 Input terminal status at fault bit
U1.14 AC drive temperature at fault °C c xxx
U1.15 Elapsed total operation time at fault 10Hr xxxx
U1.16 Elapsed time after power on at fault Hr xx.xx
U2.01 Fault (most recent) - *
Last Fault

U2.02 Fault occurred before 1 time of rotation - *


U2.03 Fault occurred before 2 times of rotation - *
U2.04 Fault occurred before 3 times of rotation - *
U3.01 Modified Parameter List - “----” (None)
Examination Result

U3.02 Fault Parameter List - “----” (None)


Parameter

Moscon-F50 AC Drive
34

B-parameter: Basic Environments Setting


Para- Name Unit Setting Factory Changeable
meter Range Setting During
operation
B0.01 Speed Reference - 0~4 0 X
B0.02 Start Source - 0~2 0 X
B0.03 Stop mode - 0~1 0 X
B0.04 Reverse Disable - 0~1 0 X
B0.05 Default Motor Direction - 0~1 0 ○
Basic Setup

B0.06 Default Monitor Item - 1~10 1 ○


B0.07 Automatic Start at Power Up - 0~1 0 ○
B0.08 Drive ID - 0~253 1 ○
B0.09 Modbus baud rate setup - 0~4 2 X
B0.10 Modbus time delay msec 2~65 5 X
B0.11 Stop mode at comm time out - 0~2 0 X
B0.12 Comm loss time sec 0~60.0 0 X
B0.13 Comm Write Mode - 0~1 0 X
B1.01 Drive Initialization - 0~9999 0000 X
System Initialization

B1.02 Check Password - 0~9999 0000 X


B1.03 Set Password
- 0~9999 0000 X

Moscon-F50 AC Drive
35

Para- Name Unit Setting Factory Changeable


meter Range Setting During
operation
B2.01 AC Drive model 20P2(01)~
Do not change the model. 23P7(06)
Wrong setting may result in (3-phase)
malfunction.
40P4(22)~
- 43P7(26) - X
System Capacity Setup

(3-phase)

B0P4(42)~
B2P2(45)
(1-phase)
B2.02 Power Capacity of the Motor 20P2(01)~
23P7(06)(3-phase)
- - X
40P4(22)~
43P7(26)(3-phase)
B2.03 Inverter control mode selection - 0∼1 1 X
B2.04 Reserved

Moscon-F50 AC Drive
36

F-parameter: Frequency Control Setting


Para- Name Unit Setting Factor Setting Changeable
meter Range During Operation
F0.01 Main Frequency
Frequency Limit Frequency/Speed Command

0.00
Command of Operator Mode & 0.01㎐ 0.00 ○
∼600.0
Communication Mode
F0.02 Frequency2 to Frequency8 0.00
~F0.08 0.01㎐ 0.00 ○
∼600.0
F0.09 Jog Frequency

0.00
0.01㎐ 6.00 ○
∼600.0

F1.01 High Speed Limit 0.1


0.1% 100.0 ○
~100.0
F1.02 Low Speed Limit

0.1% 0~99.9 0.0 ○

F1.03 Jump Frequency1 0.00


0.01Hz 0.00 ○
Jump Frequency Limit

~600.0
F1.04 Jump Frequency2 0.00
0.01Hz
~600.0
0.00 ○

F1.05 Jump Frequency3 0.00


0.01Hz 0.00 ○
~600.0
F1.06 Jump Frequency Width 0.00
0.01Hz 0.50 ○
~20.00
F1.07 Jump Mode - 0~1 0 X
F1.08 Frequency of 0.00
Frequency Detection

Match Detection
0.01Hz
~600.0
0.00 ○

F1.09 Frequency Match Detection Width 0.00


0.01Hz 0.50 ○
~20.00
F1.10 Frequency of
Accel/Decel Time Switching 0.00
0.01Hz
~600.0
0.00 ○

Moscon-F50 AC Drive
37

Para- Name Unit Setting Factor Setting Changeable


meter Range During Operation
F2.01 Accel Time 1 0.00
0.01sec 10.00 ○
~600.0
F2.02 Decel Time 1 0.00
Accel/Decel Time

0.01sec 10.00 ○
~600.0
F2.03 Accel Time 2 0.00
0.01sec 10.00 ○
~600.0
F2.04 Decel Time 2 0.00
0.01sec 10.00 ○
~600.0
F2.05 Accel/Decel Time Base - 0~1 0 X
F2.06 Reserved
F3.01 S-Curve Time
Accel/Decel Time
S-Curve

0.00
0.01sec 0.20 ○
~2.50

F4.01 Pattern Run Time 1 0.1 sec 0.0 - 999.9 0.00 ○


F4.02 Pattern Run Time 2 0.1 sec 0.0 - 999.0 0.00 ○
F4.03 Pattern Run Time 3 0.1 sec 0.0 - 999.9 0.00 ○
F4.04 Pattern Run Time 4 0.1 sec 0.0 - 999.0 0.00 ○
F4.05 Pattern Run Time 5 0.1 sec 0.0 - 999.9 0.00 ○
F4.06 Pattern Run Time 6 0.1 sec 0.0 - 999.0 0.00 ○
Pattern Run Mode

F4.07 Pattern Run Time 7 0.1 sec 0.0 - 999.9 0.00 ○


and Time(1)

F4.08 Pattern Run Time 8 0.1 sec 0.0 - 999.0 0.00 ○


F4.09 Pattern Run Mode 1 - 0 - 113 0 X
F4.10 Pattern Run Mode 2 - 0 - 113 0 X
F4.11 Pattern Run Mode 3 - 0 - 113 0 X
F4.12 Pattern Run Mode 4 - 0 - 113 0 X
F4.13 Pattern Run Mode 5 - 0 - 113 0 X
F4.14 Pattern Run Mode 6 - 0 - 113 0 X
F4.15 Pattern Run Mode 7 - 0 - 113 0 X
F4.16 Pattern Run Mode 8 - 0 - 113 0 X
(1) Available from Ver. 2.0

Moscon-F50 AC Drive
38

S-parameter: System Function Adjustment Setting


Para- Name Unit Setting Factor Setting Changeable
meter Range During Operation
S0.01 DC Brake 0.00
0.01Hz 1.50 X
Starting Frequency ~10.00
DC Braking

S0.02 DC Brake
1% 0~100 50 X
Current
S0.03 DC Braking Time 0.0
0.1sec 0.0 X
at Start ~ 25.0
S0.04 DC Braking Time 0.0
0.1sec 0.5 X
at Stop ~ 25.0
S1.01 Speed Search
- 0~1 0 X
Speed Search

at Start
S1.02 Speed Search 0.00
0.01㎐ 60.00 X
Start Frequency ~600.0
S1.03 Speed Search Current 1% 0~200 100 X
S1.04 Speed Search Deceleration Time 0.1sec 0~10.0 2.0 X
S2.01 Dwell Frequency at Start 0.00
0.01Hz 0.00 X
~250.0
Dwell Operation

S2.02 Dwell Time at Start 0.00


0.01sec 0.00 X
~25.00
S2.03 Dwell Frequency at Stop 0.00
0.01Hz 0.00 X
~25.00
S2.04 Dwell Time at Stop 0.00
0.01sec 0.00 X
~250.0
S3.01 Energy Saving Mode - 0~2 0 X
Energy Save Function

S3.02 Energy Saving Voltage Level 1% 0~100 80 X


S3.03 Energy Saving Start Frequency

0.00
0.01㎐ 0.00 X
~600.0

S4.01 Slip Compensation 0.00


Compensation

Gain
1%
~S4.03
20% ○
Slip

S4.02 Slip Compensation 0


1msec 200 X
Delay Time ~9999
S4.03 Slip Compensation Limit 1% 0~250 200 X

Moscon-F50 AC Drive
39

Para- Name Unit Setting Factor Setting Changeable


meter Range During Operation
S5.01 Torque Compensation Gain 1% 0~250 100 X
Compensation Compensation

S5.02 Torque Compensation


Torque

Delay time 0~
1msec 20 X
9999

S6.01 Hunting
System function

% 0~100 20 ○
Prevention Gain
S6.02 Enable
- 0~1 0 X
Brake Boosting
S6.03 Reserved

Moscon-F50 AC Drive
40

Para- Name Unit Setting Factor Setting Changeable


meter Range During Operation
S7.01 PID Control Mode - 0~4 0 X

S7.02 PID Acceleration/Deceleration 1sec 0~50 0 X


Time
S7.03 PID Feedback Loss Mode - 0~111 0 X

S7.04 PID Feedback Loss Lower Limit % 0.0~S7.06 0.0 X


Level
S7.05 PID Feedback Loss Lower Limit 0.1sec 0.0~20.0 1.0 X
Time
S7.06 PID Feedback Loss Higher Limit % S7.05~100. 100.0 X
Level 0
S7.07 PID Feedback Loss Higher Limit 0.1sec 0.0~20.0 1.0 X
Time
S7.08 PID Output Characteristics - 0~1 0 X
Selection
S7.09 PID P Proportioanl Gain 0.01 0.00~25.00 1.00 X
PID Control(1)

S7.10 PID I Inegration Time 0.1sec 0.0~300.0 0.0 X

S7.11 PID D Differentiation Time 0.01sec 0.0~10.00 0.0 X

S7.12 PID Error Limit 1% 0~1000 1000 X

S7.13 PID Integration Limit 0.1% 0.0~100.0 100.0 X

S7.14 PID Lower Limit 0.1% -100.0~S7. 0.0 X


15
S7.15 PID Higher Limit 0.1% S7.14~100. 100.0 X
0
S7.16 PID Delay Time 0.01sec 0.00~10.00 0.00 X

S7.17 PID Offset 0.1% -100.0~100 0.0 X


.0
S7.18 PID Output Gain 0.01 0.00~25.00 1.00 X

S7.19 PID Output Reverse Rotation - 0~1 0 X


Selection
S7.20 PID Target Selection - 0~1 0 X

S7.21 PID Target 0.0Hz 0.00~C0.02 0 X

(1)
Available from Ver. 2.0

Moscon-F50 AC Drive
41

C-parameter: H/W Functions Setting


Para- Name Unit Setting Factor Setting Changeable
meter Range During Operation
C0.01 V/f Pattern - 0~15 15 X
C0.02 Max Output Frequency 30
0.01Hz 60.00 X
~600.0
C0.03 Max Output Voltage 0.0
0.1V 200.0 X
~250.0
C0.04 Base Frequency 30.00
0.01Hz 60.00 X
V/f Setting

~600.0
C0.05 Mid Output Frequency 0.00
0.01Hz 3.00 X
~600.0
C0.06 Mid Output Voltage 0.0
0.1V 14.0 X
~250.0
C0.07 Min Output Frequency 0.00
0.01Hz 1.50 X
~600.0
C0.08 Min Output Voltage 0.0
0.1V 8.0 X
~250.0
C1.01 PWM Frequency
Carrier Frequency
/ Modulation

1.50
0.01kHz 10.00 X
~11.00

Moscon-F50 AC Drive
42

Para- Name Unit Setting Factor Setting Changeable


meter Range During Operation
C2.01 Stator Resistance 0.00
0.01Ω * X
~99.99
C2.02 Motor Iron Loss 1W 0~9999 * X
C2.03 Motor Rated Current 0.00
0.01A * X
~99.99
Motor Data

C2.04 Motor No Load Current 0.00


0.01A * X
~99.99
C2.05 Motor Rated Slip 0.00
0.01 Hz * X
~600.0
C2.06 Motor Poles - 2~39 4 X
C2.07 Magnetic flux voltage 0.1V 0.0~250.0 0 X
C2.08 Auto tuning mode selection - 0~2 0 X
C3.01~ Reserved
H/W Adjusting

C3.07
Data

Moscon-F50 AC Drive
43

H-parameter: Input/Output Control Function Setting


Para- Name Unit Setting Factor Setting Changeable
meter Range During Operation
H0.01 Select Terminal Input Type 00∼3F
- (Hexadeci 00 X
Multi-Function
Contact Inputs

mal)
H0.02 Function of Terminal 3 - 0~29 1 X
H0.03 Function of Terminal 4 - 0~29 2 X
H0.04 Function of Terminal 5 - 0~29 3 X
H0.05 Function of Terminal 6 - 0~29 6 X
H1.01 Select Terminal Output Type - 0~3 0 X
Multi-Function

H1.02 Function of Output Terminal 1 - 0~15 0 X


Contact

H1.03 Function of Output Terminal 2 - 0~15 1 X


H1.05 Pulse Counter 1(1) - 0~9999 0 X

H1.06 Pulse Counter 2(1) - 0~9999 0 X

H2.01 Reserved
H2.02 Analog Input Time Constant 1ms 0~100 20 X
H2.03 Analog Input 1 Function - 0~9 0 X
H2.04 Analog Input 1 Gain 0.1% 0.0~200.0 100.0 ○
Multi-Function Analog Input

H2.05 Analog Input 1 Bias -100.0~10


0.1% 0.0 ○
0.0
H2.06 Analog Input 2 Function - 0~9 0 X
H2.07 Analog Input 2 Gain 0.1% 0.0~200.0 100.0 ○
H2.08 Analog Input 2 Bias -100.0~10
0.1% 0.0 ○
0.0
H2.09 Analog input 2 type - 0~3 1 X
H2.10 Pulse input scale (1) 0.00kHz 1.00~32.0 1.44 ○
0
H2.11 Pulse input gain(1) 0.1% 0.0~100.0 100.0 ○

H2.12 Pulse input bias(1) 0.1% -100.0~10 0.0 ○


0.0
H2.13 Pulse input delay time(1) 0.1sec 0.00~2.00 0.10 ○

Moscon-F50 AC Drive
44

Para- Name Unit Setting Factor Setting Changeable


meter Range During Operation
H3.01 Analog Monitor Function Setting - 0~7 1 X
H3.02 Analog Monitor Gain Setting 0.0
0.1% 100.0 ○
~200.0
Multi-Function
Analog Output

H3.03 Analog Monitor Bias Setting -100.0


0.1% 0.0 ○
~100.0
H3.04 Analog Monitor Type(1) - 0~1 0 X

H3.05 Pulse Output Function(1) - 0~4 1 ○

H3.06 Pulse Output Scale(1) 0.01kHz 0.00~32.0 1.44 ○


0
H4.01 Motor Speed Form - 0~3999 30 ○
Digital Operator Setting

H4.02 Digital Operator Stop - 0~1 1 X


H4.03 Operation when Change Local
- 0~1 0 X
Remote
H4.04 Reserved
H4.05 Select Frequency Unit of Digital
- 0~1 2 ○
Volume
H4.06 Parameter Setting Method - 0~1 1 X
H4.07 Fan Operation Mode - 0~1 1 X
(1)
Available from Ver. 2.0

Moscon-F50 AC Drive
45

P-parameter: Protection Functions Setting


Para- Name Unit Setting Factor Setting Changeable
meter Range During Operation
P0.01 Select Motor Protection - 0~1 1 X
Temporary Power Loss Motor Overload Prevention

P0.02 Motor Protection Time Constants 0.0


- 1.0 X
~60.0
P0.03 Motor Selection

- 0~1 0 X

P1.01 Operation at Power Loss - 0~2 0 X


P1.02 Compensation Time of Power Loss 0.1 sec. 0.0~2.0 0.5 X
P1.03 V/f Recovery Time 0.1 sec. 0.0~2.0 0.5 X
P1.04 Undervoltage Level

1V 0~250 190 X

P2.01 Stall Prevention at Start - 0~1 1 X


P2.02 Stall Prevention Level at Start 1% 0~200 170 ○
Overtorque Detection Stall Prevention

P2.03 Stall Prevention at Acc Limit 1% 0~100 50 ○


P2.04 Stall Prevention at Stop - 0~1 1 X
P2.05 Stall Prevention in Running - 0~2 1 X
P2.06 Stall Prevention Level in Running 1% 0~200 170 ○
P3.01 Overtorque Detection - 0~4 0 X
P3.02 Overtorque Detection Level 1% 0~300 180 ○
P3.03 Overtorque
Delay Time
1 sec. 0.0~10.0 0.1 X

Moscon-F50 AC Drive
46

Para- Name Unit Setting Factor Setting Changeable


meter Range During Operation
P4.01 Auto Restart Tries - 0~10 0 X
Phase Loss Detection Retry at Fault

P4.02 Relay Output Disable at Restart

- 0~1 0 X

P6.01 Input Phase Loss Detection

- 0~1 0 X

Moscon-F50 AC Drive
47

Protective function/error description


In case of the wrong parameter setting or faulty writing, the inverter and/or the motor may
not function as commanded.
The MOSCON-F50 has many protective functions, which is displayed on the digital operator
when the fault occurs.
When the fault is detected, the fault contact output operates and the inverter output to be
shut off causing the motor to stop. The stopping method can be selected for some faults.
• Refer to the table below for the fault display, cause and corrective actions.
• To reset the fault, use one of the followings:
– Press the reset key on the digital operator.
– Turn the power supply off and on again.
– Turn on the fault reset terminal

Fault display and description (Faults in inverter)


Code Meaning Cause Corrective action
OC2 The inverter output or load was • A short-circuit or ground fault Reset the fault after
Short circuit short-circuited. (caused by motor damage, worn correcting.
Error insulation, or a damaged cable) at
the inverter output.
OC1 The inverter output current • A short-circuit or ground fault Reset the fault after
Over current exceeded 200% of the rated (caused by motor damage, worn correcting.
current instantly. insulation, or a damaged cable) at
the inverter output.
• Too large load or too short
accel/decel time.
• A magnetic switch was switched
at the inverter output.
• A special-purpose motor with too
large capacity for the inverter is
used.
OH2 cooling fin exceeded • Too high ambient temperature. Install a cooling unit.
Inverter approximately 95
• Heat source nearby the inverter. Remove the heat
Over-Heated.
source.
• Inverter cooling fan is Replace the cooling
malfunctioning. fan.(Contact Samsung)
IPL Input power phase loss DC Bus ripple is increased by Check wiring and
Input Phase input phase loss voltage Input
Loss (only 3 phase models) unbalance, DC bus
Detection is impossible in light load capacitor problem

Moscon-F50 AC Drive
48

Fault display and description (Faults in inverter)


Code Meaning Cause Corrective action
OV The main circuit DC voltage • Too short deceleration time. Increase the
Main exceeded the over voltage • Too large regenerative energy from the deceleration time or
Over-Voltage. detection level. 200V class:410V. motor. connect a braking
400V class:820V. resistor (or unit).
• Too high power supply voltage. Decrease the voltage
within specification.
UV1 The main circuit DC voltage is • A open-phase occurred with the Reset the fault after
Main below the under voltage input power supply. Correction.
Under-Voltage. detection level. 200Vclass:190V. • A momentary power loss.
400Vclass:380V.
• Too large voltage fluctuation in
the input power supply.
OL3 There was output of 180% of the • Too heavy load or too rapid Set P3.02 and P3.03
Over-torque rated motor torque current acceleration. appropriately.
Det. instantly. Check the
mechanical system
and correct the cause
of the over torque.
OL2 150% output • Too heavy load. Too short Check the size of the
Inverter current of inverter accel/decel time and cycle time load, length of the
Over-load. rating lasted more accel/decel and cycle
than 1 minute, or times.
equivalent situation.
• Too high V/f pattern Check the V/f
Pattern.
• Too low inverter capacity Replace the inverter
with larger capacity.
OL1 150% motor’s • Too heavy load. Too short Check the size of the
Motor rating lasted more accel/decel time and cycle time load, length of the
Over-load. than 1 minute or accel/decel and cycle
equivalent situation. times.
• Too high V/f pattern Check the V/f
pattern.
• Wrong motor rated current setting Check C2.03 ’s rated
current).
PFL PID feedback loss PID feedback wiring problem Check wiring or
PID Feedback Feedback sensor problem sensor.
Loss
CB2 Input parameter is out of - Input the value
Parameter max/min value. within the max/min
range over. value.

Moscon-F50 AC Drive
49

Fault display and description (Faults in inverter)


Code Meaning Cause Corrective action
CB1 Error during recalling of the - Contact AB-OEMax
EEPROM preset parameter service center
failure.
EF4 Fault in external Input (Terminal 4) • An “external fault” was input from Check if the
External Fault. a multi-function input. multi-function input
(Terminal 4) is properly selected.
Remove the cause of
EF3 Fault in external Input (Terminal 3)
the external fault.
External Fault.
(Terminal 3)
EF2 Fault in external Input (Terminal 2)
External Fault.
(Terminal 2)
EF1 Fault in external input (Terminal 1)
External Fault.
(Terminal 1)
CB0 Error in leading the parameter • The check of the parameters Contact AB-OEMax
Parameter when power is applied. stored in EEPROM is failed. service center.
Fault. (The detected parameters can be
confirmed in U3.02, max. 32)
CB2 Input parameter is out of - Input the value
Parameter max/min value. within the max/min
range over. value.

Warning display and description (Warning in inverter) : Blinking display


Code Meaning Cause Corrective action
UV The main circuit DC • A open-phase occurred with the Reset the fault
Main voltage was below: input power supply. after correction.
under-Voltage. 200Vclass: 190V • A momentary power loss.
400Vclass: 380V
• Too large voltage fluctuation in the
input power supply.
OL3 There was output • Too large load. • Set P3.02 and
Over torque of180% of the rated • Too low inverter’s capacity. P3.03
detection. current instantly. appropriately.
• Check the
mechanical
system and
correct the
cause of the
over torque.

Moscon-F50 AC Drive
50

Warning display and description (Warning in inverter) : Blinking display


SE Forward/reverse run • The forward and reverse run Check the
Warning. commands input at the command input at the same time. sequence of the
same time. forward and
reverse run
commands.
BB Output block command • The base block command input.
Base block. was input from
external.
STP Motor stopped by the • In the remote mode, the local stop
Local Stopped in stop key in remote command input.
Remote Mode. mode.
OPE Fault in operator • Operator can not communicate with Reconnect operator
communication AC Drive Power recycle
CE2 PC communication loss • Communication loss in comm Check
operation mdoe communication line
with PC

Moscon-F50 AC Drive
51

Daily inspection
Check the system in operation if:
• the motor vibrates or makes unusual noises.
• there are any abnormal heat generation
• the ambient temperature is too high
• the output current value shown on the monitor display is higher than normal
• the cooling fan is operating normally.

Periodic inspection
Refer to the table below for the periodic inspection.

• Always turn off the power supply before the inspection. Otherwise, it may cause an
WARNING
electric shock.
• After turning off the main circuit power supply, wait for a while before maintenance or
inspection since it may remain charged. Otherwise, it may cause an electric shock.

Item Inspection Solution


Terminals, mounting Are all connection hardware Reconnect the loose connectors and tighten
bolts, connectors, etc. properly seated and bolts the bolts.
tightened?
Cooling fins Are the fins dirty or dusty? Clean with dry compressed air:
39.2 x 104 to 58.8 x 104 Pa (4 to 6 kg. cm2 )
PCB Is there any accumulation of Clean with dry compressed air:
conductive material or oil mist? 39.2 x 104 to 58.8 x 104 Pa (4 to 6kg. Cm2)
Replace the inverter if the board can not be
cleaned,
Cooling fan Is there any abnormal noise or Replace the cooling fan
vibration?
Power element Is there any accumulation of Clean with dry compressed air:
conductive material or oil mist? 39.2 x 104 to 58.8 x 104 Pa (4 to 6 kg.cm2)
Smoothing capacitor Is there any abnormal odor or Replace the capacitor.
discoloration?

Moscon-F50 AC Drive
52

Part replacement
Inverter is composed of many parts and these parts must function properly for normal
operation of the inverter.
To maintain normal operation of the inverter for a long period of time, it is recommended to
perform a regular inspection and replace parts.

Inspection period may vary depending on the installation environment and usage conditions.

Usage condition
WARNING
• Ambient temperature(yearly average of 30 °C)
• Load factor: 80% max.
• Operating rate: 12hrs max/day

Refer to the table below for the periodic inspection of the MOSCON-F50.

Part Standard Replacement Period Method


Cooling fan 2 to 5 yrs Replace with new part.
Breaker relays - Inspect to determine if the replacement is
required.
Aluminum capacitors 5yrs Replace with new board. Inspect to determine
on PCBs if inspection is required.
Fuses 10yrs Replace with new part.

Moscon-F50 AC Drive
한국어
목차
일러두기 ..................................................................................................... 54
일반 주의 사항 .......................................................................................... 55
안전주의사항 ............................................................................................ 55
제품 도착 시 점검사항 ........................................................................... 57
명판 표기 .................................................................................................... 58
설치 .............................................................................................................. 59
외형 치수 .................................................................................................... 60
기본배선도 ................................................................................................ 63
주회로 단자 기능 ..................................................................................... 65
제어회로 단자기능 .................................................................................. 66
전선 사양 규격 .......................................................................................... 67
배선 점검 .................................................................................................... 68
스위치 설정 ............................................................................................... 69
주요사양 ..................................................................................................... 70
디지털 오퍼레이터의 모니터링 기능 ................................................ 77
시운전 ......................................................................................................... 78
U- 정수 : 모니터링 기능 .......................................................................... 81
B- 정수 : 기본환경 설정 .......................................................................... 84
F- 정수 : 주파수 제어 설정 .................................................................... 85
S- 정수 : 시스템 기능 조정 설정 정 ..................................................... 87
C- 정수 : H/W 기능 설정 ......................................................................... 89
H- 정수 : 입출력 제어 기능 설정 .......................................................... 90
P- 정수 : 보호기능 설정 .......................................................................... 93
보호기능 / 에러 설명 .............................................................................. 94
일상점검 ..................................................................................................... 98
정기적인 검사 ........................................................................................... 98
부품 교환 .................................................................................................... 99
54

일러두기
이 문서에서 설명하는 제품은 다양한 설비에 사용될 수 있습니다. 본 제품의 적용 설비가 다
양하므로 본 제품의 모든 사용자와 관리자는 사용하고자 하는 설비와 관련된 운전 및 안전상
의 제 법령 및 규정과 준수사항을 반드시 확인하고 지켜야합니다.

사용자가 본 제품을 사용 및 응용함에 따른 직접 또는 간접적인 손상에 대해서 알에스오토메


이션(주)는 그 책임을 지지 않습니다.

이 문서에 사용된 예제, 삽화, 도표, 데이터 등은 설명을 위한 예시적인 자료일 뿐입니다. 제품
이 설치 및 사용되는 구체적인 상황에 따라 많은 변수와 충족되어야 할 전제 조건들이 있습
니다. 이러한 사유로 이 문서에서 제시된 예시, 도표 및 데이터의 사용 및 이에 따른 직간접적
결과에 대해 알에스오토메이션(주)는 그 책임을 지지 않습니다.

알에스오토메이션(주)는 본 매뉴얼에 포함된 소프트웨어, 장비, 회로 또는 정보 사용에 대해


특허 책임을 지지 않습니다.

알에스오토메이션(주)의 서면 승인 없이 본 매뉴얼의 내용 전부 또는 일부를 복제하는 것은


금지됩니다.

사용자의 안전 및 효과적인 정보 전달을 위해 이 문서는 다음 기호들을 사용하고 있습니다.

주어진 정보 또는 절차를 잘못 취급할 경우, 사망, 중상 또는 재산상의 손


경고
실을 야기할 수 있음을 나타냅니다.

주어진 정보가 제품을 이해하고 활용함에 있어 중요한 정보임을 나타냅


중요
니다.

주어진 정보 또는 절차를 잘못 취급할 경우, 경상 또는 재산상의 손실을 야


주의
기할 수 있음을 나타냅니다. 그렇지만, 상황에 따라서 심각한 결과를 가져
올 수도 있습니다.

이 표시는 장비(예: 드라이브, 모터)의 내부 또는 외부에 있으며 전압이 높


감전 위험
아 위험할 수 있음을 알려줍니다.

이 표시는 장비(예: 드라이브, 모터)의 내부 또는 외부에 있으며 장비 표면


화상 위험
의 온도가 높아 위험할 수 있음을 알려줍니다.

Moscon-F50 AC Drive
55

일반 주의 사항
매뉴얼 중의 그림은 대부분 커버나 보호장치가 열린 상태에서 설명되고 있으며, 제품에 대해
상세하게 설명되어 있습니다. 설치 및 배선이 끝난 후 커버나 보호장치를 닫아주시기 바랍니
다.

제품개선, 혹은 매뉴얼 재편집으로 내용이 변동이 생길 경우 별도의 통보를 하지 않습니다.


변동된 내용은 수정된 매뉴얼의 번호에서 표기됩니다.

매뉴얼을 분실 혹은 파손한 경우 대리점 혹은 가까운 판매점에 문의하시기 바랍니다.

사용자의 임의 조작으로 발생된 제품파손은 유지보수범위에 포함되지 않으며 이에 대해 책


임을 지지 않습니다.

안전주의사항
설치
• 전원 차단후 1분이상 지난후에 내부의 "CHARGE" 램프가 Off 상태임을 확
주의
인 후 점검을 진행하며 그렇지 않을 경우, 감전사고가 발생할 수 있습
니다.

• 인버터는 불연 재질(이를테면 금속)표면에 고정해야 하며 그렇지 않을


경고
경우, 화재위험이 있습니다.
• 동일한 캐비닛에 여러 개의 인버터를 설치할 경우 냉각팬을 설치하여
인버터 주위온도를 40℃ 이하로 유지하도록 하십시오.
• 설치 드릴 작업 시 생기는 금속가루가 인버터에 들어가는 것을 방지하
기 위해 인버터 커버를 덮어 주어야 합니다.

Moscon-F50 AC Drive
56

배선
• 입력전원이 완전 차단 상태임을 확인한 후 배선 작업을 진행하여야 하
주의
며 그렇지 않을 경우, 감전사고가 발생할 수 있습니다.
• 전기공사 전문가에게 의뢰하여 배선작업을 진행하여야 합니다.
• 배선 작업 시 메인 회로와 제어회로 단자 나사를 단단히 조여 줍니다.
• 인버터 커버를 확실하게 닫은 다음 전원을 넣어야 하며, 전원 투입 중
에 커버를 여는 것을 금지합니다. 감전사고가 발생할 위험이 있습니다.
• 접지 단자를 접지합니다.(200V: 접지저항 100Ω 이하, 400V급: 접지저항
10Ω 이하) 그렇지 않을 경우, 감전사고나 화재가 발생할 위험이 있습니
다.

• 대인사고나 화재가 발생하는 것을 방지하기 위해 교류전원이 인버터


경고
의 정격입력전압과 동일한지의 여부를 확인합니다.
• 인버터의 내전압 시험은 하지 마십시오. 반도체 소자가 파손할 가능성
이 있습니다.
• 기타 설비의 배선작업 시 사용자 매뉴얼을 숙지하여 화재나 대인사고
의 발생을 미연에 방지합니다.
• 교류전원을 U/T1, V/T2 및 W/T3 출력단자에 연결하지 마십시오. 인버터
가 파손될 수 있습니다.
• 출력터미널을 단락 혹은 접지해서는 안됩니다. 또한 출력터미널을 손
으로 직접 만져서는 안되며 출력케이블이 인버터와 접촉해서도 안됩
니다.
• 역률 개선용 진상콘덴서나 LC/RC노이즈 필터를 출력회로에 연결하지
마십시오. 인버터의 파손 혹은 화재가 발생하게 됩니다.
• 전자 접촉기(MC)나 스위치를 출력회로에 연결하지 마십시오.

정수 설정
• 적절한 정수를 입력해야 합니다. 부적절한 정수 입력은 인버터 가동과
주의
작업에 영향을 미칠 수 있습니다.
• 변경한 정수는 기록하여 두십시오.( MOSCON-F50이 앞의 상수를 기록한
경우 포함) 이런 기록은 고장과 착오 발생시 빠른 처리를 가능하게 합
니다.
• 파라미터 변경은 지정된 범위(사용자 매뉴얼 F50-UM001A-KO-P 5장 참조
)에서만 가능합니다. 특히 모터, V/f 변경 혹은 최대출력 주파수 조정 시
주의를 기울여야 하며, 그렇지 않을 경우, 인버터와 모터를 파손 시킬
수 있습니다.

Moscon-F50 AC Drive
57

유지보수와 검사
• 인버터는 고압부분를 가지고 있으므로 전원 투입 중에는 감전되기 쉽
주의
습니다.
• 인버터에 전원 투입 중 커버를 열지 마십시오.
• 주회로 콘덴서에 잔류전압이 존재함으로 인버터의 주회로 전원 차단
후 일정한 시간이 경과 후 유지보수와 검사작업을 실시하여야 합니다.
• 전기공사 전문가에 위탁하여 유지보수, 검사 혹은 부품교체를 합니다.
그렇지 않을 경우, 대인사고 혹은 대물사고가 발생할 가능성이 존재합
니다.
• 유지보수, 검사 혹은 부품교체 전 소지하고 있는 금속품 이를 테면 시
계, 반지 등을 모두 제거하고 별도로 보관하십시오. 동시에 적당한 절
연공구를 사용하여 작업하여야 합니다. 그렇지 않을 경우 감전사고가
발생할 위험이 있습니다.
• 검사 전 전원을 반드시 차단하여야 하며 그렇지 않을 경우, 감전사고
발생의 위험이 있습니다.

• 본체 내부의 CMOS직접회로를 손으로 직접 만져서는 안됩니다. 정전기


경고
에 의해 파손될 위험이 있습니다.
• 주회로 콘덴서에 전류가 잔존해 있음으로 인버터 주회로 전원을 차단
하여 일정시간이 경과 후 유지보수와 검사작업을 실시하여야 합니다.

매뉴얼은 http://www.oemax.co.kr에서 보거나 다운로드할 수 있습니다. 매뉴얼의 인


쇄본을 주문하려면 해당 지역 Allen-Bradley OEMax 취급 대리점 또는 판매 담당자에
게 문의하십시오.

제품 도착 시 점검사항
MOSCON-F50이 도착되면 다음 사항을 점검해 주십시오.

• 주문서와 제품이 일치하는지 확인합니다.


• 운반과정에서 발생한 제품파손의 유무를 점검해 주십시오.
제품 파손이나 부품 누락 등이 있을 경우 즉시 당사의 대리점 또는 영업소에
연락하여 주십시오.

손상되어 있거나 부품이 빠져있는 인버터는 설치하지 마십시오.


경고
부상의 위험이 있습니다.

Moscon-F50 AC Drive
58

명판 표기
프로그램 버전 HW 버전

모델번호
MODEL : SI_20P7F50 SW: 1.0 HW:A
입력사양 Input Voltage: 3PH 200-230Vac 4.8A 50/60HZ
Output Power: 3PH 0-230Vac 1.9kVA 5.0A
출력사양 IP20/UL Open-Type MASS: 0.95 Kg
Serial number SER. NO: 2XF50X013-FB0001 IND. CONT. EQ.
61KJ
E226834

Rockwell Automation Korea Ltd. MADE IN KOREA

명판 표기예

인버터 형식 설명

SI - 4 3P7 F50 XXX (Option)


F50 Series

전압 최대적용 모터용량 Option


B: 단상 200V (P는 소수점을 나타냅니다.) None: Standard
2 : 3상 200V 0P2: 0.2kW A: Full Function
4 : 3상 400V 0P4 : 0.4kW D: DeviceNet (개발중)
0P7 : 0.7kW TM: Treadmil
1P5 : 1.5kW
2P2 : 2.2kW
3P7 : 3.7kW

명판 부착위치

명판
(제품의 우측면에 부착)
एँऎ࣪ऊऋࣶ࣮ࣜऔंࣱ࣬औࣱࣩ࣬࣬ࣽं࣭ࣾ࣬࣬࣬
अऌ࣮࣬ࣜअऊएऐࣽईईࣽऐअऋऊࣜࣿࣽऐँःऋऎकࣜअअࣜउࣽएएࣲࣶ࣭࣪࣬इण
ऋऱरबऱरࣜऌफळडमࣶ࣯ࣜࣜࣜࣽࣿࣜऌऄࣰࣲࣩࣜ࣬࣬ऒࣰ࣭ࣜ࣪धऒ࣭ࣽࣜ࣪ࣴࣽ
अपबऱरࣜऒफनरझणडࣶ࣯ࣜࣜࣽࣿࣜऌऄࣰࣲ࣯ࣩࣜࣴ࣬࣬ऒࣱࣲࣜ࣬࣫࣬ऄश
उऋऀँईࣶࣜࣜएअछࣰ࣬ऌࣰंࣱ࣬
FcW_kY``5ihcaUh]cb?cfYU@hX"A589=B?CF95

ऌऎःࣶ࣭࣪࣬࣬

Moscon-F50 AC Drive
59

설치

주변온도
판넬과 같이 밀폐된 환경에 설치하게 될 경우 인버터의 주위온도가 -10℃~40℃를 유
지할 수 있도록 해주십시오. 또한 과열을 방지하기 위하여 냉각 팬 혹은 에어컨을 설
치하여 내부 온도를 유지하십시오.

냉각 효율을 높이기 위해 반드시 수직으로 인버터를 설치하십시오. 그렇지


경고
않을 경우, 내부가 과열되어 내구성이 떨어지게 됩니다.
IP20 INSTALLATION CATEGORY II MASS:1.60Kg

Input Voltage : AC 3PH 380-460V 50/60Hz


SER.NO: 2XF50X005A-FB0001

Output Power : AC 3PH 0-460V 1.4kVA 1.8A

MODEL : SI_40P4F50
Rockwell Automation Korea Ltd. MADE IN KOREA

Rockwell Automation Korea Ltd. MADE IN KOREA

SER.NO: 2XF50X005A-FB0001
IP20 INSTALLATION CATEGORY II MASS:1.60Kg
Output Power : AC 3PH 0-460V 1.4kVA 1.8A
Input Voltage : AC 3PH 380-460V 50/60Hz
PRG:1.00 MODEL : SI_40P4F50
PRG:1.00

수직설치 수평설치

Moscon-F50 AC Drive
냉각 효율을 높이기 위해 반드시 수직으로 설치하고, 아래 그림과 같이 주위 공간을

(단위: mm)
MODEL : SI_40P4F50 PRG:1.00
Input Voltage : AC 3PH 380-460V 50/60Hz
Output Power : AC 3PH 0-460V 1.4kVA 1.8A

84.6
IP20 INSTALLATION CATEGORY II MASS:1.60Kg
SER.NO: 2XF50X005A-FB0001
Rockwell Automation Korea Ltd. MADE IN KOREA

3상 20P2의 외형치수
100

설치공간
100
30

76
확보해 주십시오(단위:mm).

30

Moscon-F50 AC Drive
외형 치수
설치 공간

128
60
Moscon-F50 AC Drive
61

MODEL : SI_40P4F50 PRG:1.00


InputVoltageAC: 3PH 380-460V 50/60
Hz
OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A
IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg
SER.NO: 2XF50X005A-FB0001

145.4
Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA
MODEL : SI_40P4F50 PRG:1.00
InputVoltageAC: 3PH 380-460V 50/60
Hz
OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A
IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg
SER.NO: 2XF50X005A-FB0001
145.4

Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA

단상 B0P4, B0P7 및 3상 21P5, 22P2, 40P4, 40P7, 41P5의 외형치수


145.4

단상 B1P5, B2P2 및 3상 23P7, 42P2, 43P7의 외형치수


3상 20P4, 20P7의 외형치수
76

150
120
128

128

128
62

기종 MOSCON-F50

외형사이즈 mm 설치사이즈
부피(㎣) 무게(㎏)
(W×H ×D) W1×H1, Φ
20P2 76 x 128 x 84.6 66 x 118, M4 822,988.8 0.6
20P4 76 x 128 x 126.4 1,229,619.2 0.9
20P7
B0P4 120×128×145.4 103×118, M4 2,233,344 1.6
B0P7
21P5
22P2
40P4
40P7
41P5
B1P5 150×128×145.4 134×118, M4 2,617,200 1.9
B2P2
23P7
42P2 2.0

43P7

Moscon-F50 AC Drive
63

기본배선도
MOSCON-F50의 기본배선도는 아래와 같습니다.

디지털 오퍼레이터를 사용할 경우 주회로만 배선하여 모터를 운전할 수 있습니다.

제동저항(선택사항)

배선용차단기 B1 B2
(MCCB)
R/L1 전동기
U/T1
4)
S/L2 V/T2
입력전원
4)

T/L3 W/T3

다기능 접점 입력 다기능 접점 출력 1
S1 R1
정회전운전/정지 최대 직류 30V 1A
S2 최대 교류 250V 1A
역회전운전/정지
(기본설정: 이상발생)
S3
외부 이상 RC1
이상 Reset S4
S5
다단속 지령1 R2 다기능 접점 출력 2 (옵션)
Jogging S6
최대 직류 30V 1A
SC 최대 교류 250V 1A
RC2 (기본설정: 운전중)

E
접지
2 kΩ
속도지령 설정용 전원
V+ (+12V 20mA)

2 kΩ A1 아날로그 입력 1
(0~10V 20kΩ )
AC
아날로그 Common
A2
아날로그 입력 2
(4-20mA, 0-20mA 250Ω 또는
AM 0~10V 20kΩ )
(0-32kHz Pulse:Option)
아날로그 모니터 출력
(0-10V)
(0-32kHz Pulse:Option)

기본배선도(3상 200V/400V급)

방사노이즈를 대비하여 모터 케이블에 상기 다이어그램과 같이 EMI 코어를 설치해


주시기 바랍니다. (TDK ZCAT3035-1330)

Moscon-F50 AC Drive
64

제동저항(선택사양)

배선용차단기 B1 B2
(MCCB)
R/L1 U/T1
전동기
입력전원 4)
S/L2 V/T2
4)
W/T3

다기능 접점 입력 R1 다기능 접점 출력1


1 최대 직류 30V 1A
정회전운전/정지
2 최대 교류 250V 1A
역회전운전/정지 RC1
외부 이상 3 (기본설정: 이상발생)
이상 Reset 4
5 R2
다단속 지령1 다기능 접점 출력 2 (옵션)
Jogging 6 최대 직류 30V 1A
9 최대 교류 250V 1A
RC2
(기본설정: 운전중)

E
접지
2 kΩ

속도지령 설정용 전원
V+ (+12V 20mA)

2 kΩ 아날로그 입력 1
A1
(0~10V 20kΩ )
AC
아날로그 Common

아날로그 입력 2
A2 (4-20mA, 0-20mA 250Ω 또는
0~10V 20kΩ )
AM (0-32kHz Pulse:Option)
아날로그 모니터 출력
(0-10V)
(0-32kHz Pulse:Option)

기본배선도(단상 200V급)
주: 1) 는 실드선 는 트위스트 페어 실드선입니다.
p

2) 표시는 주회로단자, 표시는 제어회로 단자를 나타냅니다.


3) 아날로그 입력 설정용 전원 V+의 최대 전류 용량은 20㎃입니다.
4) 방사노이즈를 대비하여 모터 케이블에 상기 다이어그램과 같이 EMI 코어를 설치하시기 바랍니다.
(TDK ZCAT3035-1330)

Moscon-F50 AC Drive
65

주회로 단자 기능

용 도 단 자 부 호

주회로 전원입력 R/L1, S/L2

인버터 출력 U/T1, V/T2, W/T3

제동 저항 접속 B1, B2

접지

용 도 단 자 부 호

주회로 전원입력 R/L1, S/L2, T/L3

인버터 출력 U/T1, V/T2, W/T3

제동 저항 접속 B1, B2

접지

Moscon-F50 AC Drive
66

제어회로 단자기능

단자 단 자 기 능 신호레벨 초기 설정값
S1 정회전 운전/정지 지령 포토 커플러 입력 -
+24V, 10mA
S2 역회전 운전/정지 지령 -

S3 다기능 입력 1 외부이상
S4 다기능 입력 2 이상 Reset
S5 다기능 입력 3 다단속 1지령
S6 다기능 입력 4 조깅(Jogging) 지령
SC 시퀀스 제어 입력 +24V Ground 시퀀스 0V
Common
V+ 속도지령 설정용 전원 +12V(Max 20mA) -

A1 속도지령 1 전압 (DC 0~+10V) 지령 주파수

A2 속도지령 2 전류 (4~20mA, 0~20mA) 지령 주파수


전압 ( 0~10V),
펄스(0~32kHz:Option)
AC 아날로그 Common 0V -

AM 아날로그 모니터 출력 DC 0~10V (출력 주파수)


펄스(Option):0~32kHz
R1, RC1 다기능 접점 출력 1 접점 용량: 이상발생
AC 250V, 1A 이하
DC 30V, 1A 이하

R2, RC2 다기능 접점 출력 2 접점 용량: 운전중


(옵션) AC 250V, 1A 이하
DC 30V, 1A 이하

주) 외부 주파수 지령단자를 이용하여 주속 주파수를 바꾸는 경우는 다음 사항에 주의하십시


오.
• 공장 출하 시는 전압 지령은 AI1과 AI2의 합으로 되어 있습니다.
• 펄스 입출력은 FW Ver 2.0부터 가능하며 Option으로 추가기능임

Moscon-F50 AC Drive
67

전선 사양 규격
주회로의 전선 사이즈를 결정할 때 '선 전압강하'는 정격 전압의 2% 이내에
들도록 전선을 선택 하여야 합니다. '선전압강하'의 계산방법은 다음과 같습니다.

㍶G 㩚㞫ṫ䞮O}Pd G G G ZG G Ý G 㩚 ㍶ 㩖 䟃 Oȳ V’” PGÝ G ⺆ ㍶ ₎ 㧊 O” PÝ G G


G
㩚⮮OhPGÝGXW TZ

전선 Size(1)
터미널 단자대 전선의
회로 모델 토크(Nm) 압착단자 종류
나사 2 AWG
mm

주회로(R/L1, 20P2, M4 0.8-1.0 2-4 2 14 전력용


S/L2, 20P4, 20P7 케이블
T/3, (600V
21P5, 22P2 M4 1.2-1.5 2-4 3.5 12
+1,+2, 비닐
P/B,N, 23P7 M4 1.2-1.5 5.5-4 5.5 10 전선 등)
U/T1, B0P4 M4 0.8-1.0 2-3.5 2 14
V/T2,
W/T3) B0P7, B1P5 M4 1.2-1.5 2-4 3.5 12
B2P2 M4 1.2-1.5 5.5-4 5.5 10
40P4, 40P7, 41P5, M4 1.2-1.5 2-4 2 14
42P2, 43P7

제어회로 전모델 M2 0.22-0.25 - 0.5-1.25 20-16 트위스트


실드선
(1)
어스 케이블은 10.0 mm2 이상의 케이블을 사용하여 주십시오.

Moscon-F50 AC Drive
68

배선 점검
배선작업이 완료되면 다음 사항을 확인해 주십시오.
경고
단, 제어회로의 부져 점검은 하지 마십시오.

• 상호배선에 잘못이 없는가?


특히 U/T1, V/T2, W/T3 단자에 전원이 접속되어 있는가?
• 전선 부스러기 등으로 단락 상태가 되어 있지 않은가?
• 단자의 볼트는 느슨하지 않는가? 배선처리는 좋은가?
• 부하상태는 양호한가?
• 배선이 합선되어 있지는 않은가?

전원 입력 노이즈 필터

모델 노이즈 필터 제조사
20P2, 20P4, 20P7 C3B2005-AR OKY
21P5, 22P2 C3B2010-AR
23P7 C3B2020-DR
40P4, 40P7, 41P5 C3B4005-AR
42P2, 43P7 C3B4010-AR
B0P4, B0P7 대리점에 문의하십시오.
B1P5, B2P2

Moscon-F50 AC Drive
69

스위치 설정

SW1
Monitor
Select ON

SW3 1 2 3 4 5 6
SRC/SNK
Select

SW2
AI Type
Select

기능 스위치 DIP SW 번호
구분
1 2 3 4 5 6
AO Enable SW1 ON OFF ON OFF N/A N/A
PO Enable (옵션) OFF ON OFF ON N/A N/A

AI2 = 펄스 (옵션) SW2 OFF ON OFF OFF (1) OFF

AI2 = 전압 ON OFF OFF ON OFF

AI2 = 전류 (초기설정) OFF OFF ON ON ON

종단 저항 - - - - ON -

내부 전원 소스 SW3 OFF OFF ON ON OFF

내부 전원 싱크 (초기설정) ON ON OFF OFF OFF

외부 전원 소스 OFF OFF OFF OFF ON

(1) 상기 표에서 모든 빈 박스는 ON/OFF 여부에 관계없다는 것을 의미합니다.

주의 DIP SW 설정을 잘못하면 신호 종류가 혼합되어 하드웨어적 문


제가 발생할수 있으므로 정확한 설정을 해주십시오.

Moscon-F50 AC Drive
70

주요사양
3상 20P2 20P4 20P7 21P5 22P2 23P7
200-230V급
단상 - B0P4 B0P7 B1P5 B2P2 -

모터 최대 모터 용량[kW] 0.2 0.4 0.75 1.5 2.2 3.7

전원 입력 전력 용량[kVA] 0.8 1.2 2 3.2 4.8 7.7


(단상) (-) (1.1) (1.9) (3) (4.5) (-)

정격 입력 전류(A) 1.5 2.9 4.8 7.5 11.0 17.5

정격 입력전압[V] 3상 교류 200~230V, 50/60Hz


단상 교류 200~230V, 50/60Hz

허용 전압 변동범위 -10% ~ +10%

허용 주파수 -5% ~ +5%


변동범위
출력 전력 용량[kVA] 0.6 1.1 1.9 3 4.2 6.7
(단상) (-) (1.1) (1.9) (3) (4.2) (-)

정격 출력전류[A] 1.6 3 5 8 11 17.5


(단상) (-) (3) (5) (8) (11) (-)

출력 전압범위[V] 3상교류 0~230V (입력전압 대응)

정격 출력주파수[Hz] 기본값 60Hz, 최대 400Hz까지 설정 가능

전력손실 소모량[W] 20 40 60 90 160


(단상) (40) (60) (90)

외함 및 중량 Frame size A B C
(3상) 제품 본체[kg] 0.6 0.9 1.6 2

포장 상태[kg] 0.9 1.2 2.2 2.6

외함 및 중량 Frame size B C
(단상) 제품 본체[kg] 1.6 1.9

포장 상태[kg] 2.2 2.5

주) Standard와 Full Function 제품의 차이

• Standard: 릴레이 출력1만 있음, 펄스 입출력 없음


• Full Function : 릴레이 출력1, 2, 펄스 입출력 지원

Moscon-F50 AC Drive
71

380-460V급 3상 - 40P4 40P7 41P5 42P2 43P7

용량 [kW] 0.2 0.4 0.75 1.5 2.2 3.7

입력 정격 입력용량[kVA] 1.5 2.8 4 5.1 9.3

정격 입력전류[A] 1.8 3.2 4.4 5.5 8.2

정격 입력전압[V] 3상 교류 380~460V, 50/60Hz

허용 전압 변동범위 -10% ~ +10%

허용 주파수 변동범위 -5% ~ +5%

출력 전력 용량[kVA] 1.4 2.6 3.7 4.2 6.7

정격 출력전류[A] 1.8 3.4 4.8 5.5 8.6

정격 출력전압[V] 3상 교류 0~460V (입력전압 대응)

정격 출력주파수[Hz] 기본값 60Hz, 최대 400Hz까지 설정 가능

전력손실 소모량[W] 40 60 90 120 145

외함 및 중량 Frame size B C

제품 본체[kg] 1.7 2

포장 상태[kg] 2.2 2.6

Moscon-F50 AC Drive
72

공통
H/W구성 직류 리액터 적용 불가 (교류 리액터 사용)

회생제동장치 내장 (제동 저항은 별도 설치)

EMC 필터 별치 (선택)

변조방식 정현파 조합 PWM (순 정현파 변조 또는


Space Vector 변조 (2상 /3상 변조))

제어방식 V/f (슬립보상 포함), PG 없는 벡터

주파수 제어범위 0 ~400.00 Hz

주파수 제어 정도 0.05% : 디지탈 지령, 0.5% : 아날로그 지령

주파수 설정 정도 0.01 Hz : 디지탈 지령, 0.1 Hz : 아날로그 지령(10 bit)

주파수 출력 정도 0.01Hz
적용 대상
가감속 시간 범위 0~600.00초, 0.01초 간격 (독립설정 가능한 2개 가감
인버터의
제어 & 성능 속 시간 set 구비)

캐리어 주파수 제어범위 1.5~11kHz (0.1kHz 단위로 설정)

속도제어 범위 100:1

속도 안정성 1.0% (@ 60:1, 슬립보상 포함)

속도 응답성 5 Hz

기동 토오크 150% @ 1.0 Hz

토오크 제한기능 가능 (전류제한으로 가능)

과부하 내량 150%/ 60초, 200%/ 1초

Moscon-F50 AC Drive
73

입출력 단자

제어 사용자 I/F 자체 조작반 : LED 오퍼레이터(4 digits + 6 keys),


통신 S/W (MosconTools)

통신 포트 RS-485 with Modbus-RTU (RJ-45)

입력 아날로그 입력 2개 입력, 9개 기능, AI1 전압(0-10V)


AI2 : 전압(0-10V, 0(or 4)-20mA, 0-32kHz Pulse: 옵션)

Zi :20 k ohm(전압), 250 ohm(전류)


외부 볼륨 : 2k ohm, 최소 2W 이상

디지탈 접점 입력 6개 입력, 30개 기능, 전원 (+24V)


(전용 x 2, 설정 가능 x 4)

24V, Sink 또는 Source


(L: 0 : 0~6V, H: 18~24V)

출력 아날로그 출력 1개 출력, 8개 기능 (펄스 출력 5개 기능: 옵션)


전압 (0~10V) / 펄스 (0~32kHz: 옵션) 중 선택

Zo : 최소1 k ohm (전압) (또는 0~32kHz 펄스: 옵션)

디지탈 접점 출력 R1 출력, 12개 기능(1a 릴레이)


R2 출력, 12개 기능(옵션 1a 릴레이)

릴레이 : 1.0 A @ 30Vdc/240Vac(비유도성), 1.0 A @


30Vdc/240Vac(유도성)

전원부 단상 전원 입력용 L1, L2

삼상 전원 입력용 L1/R, L2/S, L3/T

제동저항 연결용 B1, B2

삼상 출력용 공통 T1/U, T2/V, T3/W

보호기능 H/W 보호/검출 기능 인버터 과부하 (OL2), 전동기 과부하 (OL1), 부족전
압 (UV1), 과전압 (OV), 과전류 (OC), 전류제한
(CLB,CLA), 과 토오크 (OL3),과열방지(OH), 입력 전원
결상(IPL:3상 제품만)

S/W 보상 기능 실속 방지, 자동 토오크 보상, 아날로그 입력 상실


검출, 사용자 정수 보호, 정전 보상(복전 대기), 지
령손실 보상 (복구 대기), 외부 단자대 지령이상 검

Moscon-F50 AC Drive
74

주파수 지령 가능장치 5개 종류 (내장 조작반, 내부 설정치, 다단속, 아날


로그 입력, 통신)

운전 지령 가능장치 3개 종류 (내장 조작반, 접점 입력, 통신)

정지 방법 2개 종류 (감속, 프리런)

내부 설정 속도지령 (다 9단
단속지령)

회전 중 재시동 가능

이상발생시 자동 재시동 최대 10 회까지

전원투입시 자동 기동 가능

응용기능 기계계 진동방지(주파수 최대 3 개소


점프)

DC 전류인가 제동 기능 시동 및 정지시

출력전압 보정 자동

전동기 상수 자동 추정( 정지식, 회전식


오토튜닝)

모니터 항목 지령 주파수, 출력 주파수/ 전류/ 전압/전력(kW),


(사용자 표시장치) 직류회로 전압, 추정 모터속도(rpm)/ 토크,
입력단자상태, 누적 통전 시간, S/W 개정번호,

기타 특징 표준 장착된 Operator를 사용하여 사용자 정수의


복사 가능

외함 형식 IP20/ UL Open-Type

설치장소 실내 (폭발성 가스 및 분진이 없는 곳)

설치 고도 제한 1000m 이하

사용시 주변온도 -10 ~ 40 'C

보관시 주변온도 -40 ~ 85 'C


환경/안전
상대 습도 0 ~ 90 %RH, 이슬 맺힘 없을 것

충격 및 진동 5G peak : 10ms, 1G peak : 5 Hz~2 kHz

국제 표준규격 인증 UL 508C, CSA 22.2, CE LVD (EN61800-5-1:2003), EMC


89/336(EN61800-3:2004)
200V 단상모델: UL508C, CSA22.2, CE LVD만 취득, EMC
는 제외

Moscon-F50 AC Drive
75

인버터 Fuse 및 회로 차단기 규격

모델 차단기(1) 전자 접촉기 UL Class T, CC, J (2)


AF AT (5kA 600V)

20P2 30A 5A 5A 6A
20P4 30A 5A 10A 6A
B0P4, 20P7 30A 10A 10A 10A
B0P7, 21P5 30A 20A 20A 15A
B1P5, 22P2 30A 20A 20A 25A
B2P2, 23P7 30A 30A 20A 30A
40P4 30A 5A 10A 6A
40P7 30A 5A 10A 6A
41P5 30A 10A 10A 10A
42P2 30A 10A 10A 15A
43P7 30A 20A 10A 20A

(1)
차단기: inverse time 또는 instantaneous trip
(2)
휴즈

- IEC-BS88(British standard) Parts 1&2, EN60269-1, Parts 1&2, type gG 또는 동등품 사용

일반적으로 다음을 포함하지만 제한되지 않을수도 있습니다. Parts 1 & 2: AC, AD, BC, BD, CD,

DD, ED, EFS, EF, FF, FG, GF, GG, GH.

- UL - UL Class CC, T 또는 J를 반드시 사용합니다.

일반적으로 다음을 포함한다. Type CC - KTK-R, FNQ-R, Type J - JKS, LPJ, Type T - JJS, JJN

Moscon-F50 AC Drive
76

7-Segment Display : FWD LED :


점등:정회전(CW)
모니터링 및 정수관련 데이터 표시

Increment/Up key : REV LED :


- 정수 번호 및 값 증가 점등: 역회전(CCW)
- 정수 그룹간 이동

Digital Volume(1)
- 주파수설정모드
RUN key : · 주파수 지령변경
Operator 조작모드에서 - 정수설정모드
모터 기동 · 시계방향:증가
· 반시계방향:감소
- 정수그룹간 이동

STOP key :
모터 정지

RESET key :
이상 상태 해제
DATA key :
Decrement/Down key : 정수내용 표시
- 정수 번호 및 값 감소
- 정수 그룹간 이동 SET key :
- 표시된 값으로 정수변경 설정
SHIFT keys : - 정수변경후 정수번호 표시
- 변경할 Digit 선택
- U0.01의 값을 보고 있을때
지령 주파수 수정모드로 이동
(B0.01= 0 또는 1일 경우만)

(1)
표시된 정수나 데이터는 디지털 볼륨으로 변경할 수 있습니다.

Moscon-F50 AC Drive
77

디지털 오퍼레이터의 모니터링 기능

지령주파수
Ά͑͟͢͡͡

Άͣ͟͡͡ ͑ 출력주파수 Άͨ͟͢͡ S/W 버전

Άͤ͟͡͡ ͑ 출력전류 Άͧ͟͢͡ ͑ 운전시간


[시간]

Άͥ͟͡͡ ͑ Άͦ͟͢͡ ͑ 누적운전시간


[10시간]
출력전압

Άͦ͟͡͡ ͑ DC 링크 전압 Άͥ͟͢͡ 인버터 온도

Άͧ͟͡͡ ͑ 출력
͑
Άͤ͟͢͡ I/O 상태 ͑

͑
Άͨ͟͡͡
추정 모터 속도[RPM] Άͣ͟͢͡ ͑ PID 출력[%] ͑

Ά͟͢͢͡ ͑ PID 편차[%]


͑
Άͩ͟͡͡ 출력 토오크[%]
͑

Ά͟͢͡͡ ͑ PID 피드백[%]

Άͪ͟͡͡
͑
PID 목표치[%] ͑
디지털 오퍼레이터의 모니터링 기능

Moscon-F50 AC Drive
78

시운전

전원 ON Shift 키 한번 누르면
(B0.01= 0 또는 1일때만)
주파수 수정모드로 들어갑니다.
소숫점 깜박임(B0.01=0)
자리수 깜박임(B0.01=1)
FWD

REV
값 증가 시
운전주파수 설정
디지털 볼륨을
시계방향으로 회전
FWD

REV

운전 RUN 키를 누름

FWD

REV
정지 STOP 키를 누름

FWD

REV

정수 번호로 이동
DATA/SET 키를 누름

FWD

REV
다른 정수그룹으로 이동 시계방향으로 2
클릭 돌림
FWD

REV

변경할 Digit로 이동
Shift 키를 누름

FWD

REV
시계방향으로 2
정수 소그룹 증가 클릭 돌림

FWD

REV
DATA/SET 키를 누름
정수 수정 (DATA MODE으로 전환)

FWD

REV

주) 반전된 Digit는 점멸상태를 나타냄

Moscon-F50 AC Drive
79

Shift 키를 누름
Digit 변경

FWD

REV 값 감소시
디지털 볼륨을
숫자 감소 반 시계방향으로 회전

FWD

REV
DATA/SET 키를 누름
표시된 정수 저장 (현재 F2.01=3.00)

FWD

REV
DATA/SET 키를 누름
다음 Level로 이동 (Data 모드로부터 이탈)

FWD

REV
Digit 변경 Shift 키를 2번 누름

FWD

REV
다른 정수그룹으로 반시계방향으로 2
이동 클릭 돌림

FWD

REV
DATA/SET 키를 누름
정수 수정 (U.0.01의 내용 확인)

FWD Shift 키 한번 누르면


(B0.01= 0 또는 1일때만)
REV 주파수 수정모드로 들어갑니다.
소숫점 깜박임(B0.01=0)
운전 자리수 깜박임(B0.01=1)

FWD

REV
UP 키를 누름
U0.02로 이동 (출력주파수 표시)

FWD

REV
시계방향으로 2
U0.04로 이동 클릭 돌림

FWD

REV

Moscon-F50 AC Drive
80

그룹변경 소그룹변경

U(제어) - 정수그룹 X 0 - 소그룹

B(기본) - 정수그룹 X 1 - 소그룹

F(주파수) - 정수그룹

S(시스템) - 정수그룹 X n - 소그룹

ஔ|SGiSGmSGzSGjSGoSGw
C(제어) - 정수그룹

H(I/O) - 정수그룹
정수번호 변경

XY - 01 정수
G
P(보호) - 정수그룹

XY - 02 정수
G

데이터 변경모드

xxx.x
(정수내용)
XY - n 정수

Y : 0, 1, 2 ~ 최대값

G 수치 변경
* UP/Down Key로
* Shift Key로 숫자 위치 변경

정수설정 방법

Moscon-F50 AC Drive
81

U-정수: 모니터링 기능

정수 표시
번호 명칭 내용 단위 형태
인버터 U0.01 주속지령주파수 현재 유효한 0.01㎐ xx.xx
운전상태 주속 주파수 지령값 ∼xxx.x

U0.02 출력주파수 현재 출력되고 있는 주파수 0.01㎐ xx.xx


∼xxx.x
U0.03 출력전류 현재 출력되고 있는 0.01A xx.xA
교류 전류의 실효치
U0.04 출력전압 현재 출력되고 있는 1V xxxu
교류 전압의 실효치
U0.05 직류전압 현재 인버터 내에 1V dxxx
충전되어 있는 전압
U0.06 출력전력계산치 현재 인버터가 0.1kW Pxx.x
출력하고 있는 전력 계산치
U0.07 추정모터속도 부하 상태로부터 추정한 1rpm xxxx
현재의 모터 속도
U0.08 추정모터토크 출력 전류로부터 계산한 1% oxxx
모터의 출력토오크
U0.09 PID 지령 PID 목표값 % xxx

U0.10 PID 피드백 PID 피드백 % xxx

U0.11 PID 편차 PID 목표값 - PID 피드백 % xxx

U0.12 PID 출력 PID 제어를 통해 % xxx


결정된 출력값
U0.13 입출력 단자 상태 현재 입출력 단자의 C||||||
상태를 표시
U0.14 인버터 온도 현재 인버터 검출 온도 ℃ c xxx

U0.15 누적 통전시간 인버터 생산 후 10Hr xxxx


현재까지의
경과시간 (10Hr 단위)
U0.16 전원투입후 전원 투입 후 Hr xxxx
경과 시간 현재까지의
경과 시간 (Hr 단위)
U0.17 S/W 개정번호 현재 탑재된 S/W의 - r.xxx
개정번호

Moscon-F50 AC Drive
82

정수 표시
번호 명칭 내용 단위 형태
최종이상 U1.01 주속지령주파수 최종 이상 발생시의 0.01Hz xx.xx
발생시 주속 주파수 지령값 ∼xxx.x
운전 상태 U1.02 출력주파수 최종 이상 발생시의 0.01Hz xx.xx
출력 주파수 ∼xxx.x

U1.03 출력전류 최종 이상 발생시의 0.01A xx.xA


출력 교류전류의 실효치
U1.04 출력전압 최종 이상 발생시의 1V xxxu
출력 교류전압의 실효치
U1.05 직류전압 최종 이상 발생시의 1V dxxx
충전 전압
U1.06 출력전력계산치 최종 이상 발생시의 0.1kW Pxx.x
출력 전력 계산치
U1.07 추정모터속도 최종 이상 발생시의 1rpm xxxx
추정 모터 속도
U1.08 추정모터토크 최종 이상 발생시의 1% oxxx
모터의 추정 토오크
U1.09 PID 지령 이상시 PID 목표값 % xxx

U1.10 PID 피드백 이상시 PID 피드백 % xxx

U1.11 PID 에러 이상시 PID 목표값 - PID 피드백 % xxx

U1.12 PID 출력 이상시 PID 제어를 통해 % xxx


결정된 출력값
U1.13 입출력 단자 최종 이상 발생시 C||||||
상태 입출력 단자 상태 (On:Close)
U1.14 인버터 온도 이상시 인버터 온도 ℃ c xxx
U1.15 누적 통전시간 출하 후 최종 이상 10Hr xxxx
발생시까지의 경과 시간
U1.16 전원 투입후 경과시간 이상시 전원 투입후 경과시간 Hr xx.xx

Moscon-F50 AC Drive
83

정수 표시
번호 명칭 내용 단위 형태
시스템 U2.01 이상발생 이력 1 (최근) 가장 최근에 발생한 이상 내용 - *
보호 기능 U2.02 이상발생 이력 2 1회 전에 발생한 이상 내용 - *

U2.03 이상발생 이력 3 2회 전에 발생한 이상 내용 - *

U2.04 이상발생 이력 4 3회 전에 발생한 이상 내용 - *

정수 검사 U3.01 변경된 정수 초기 설정과 다른 값을 - “---"


결과 목록 가지는 정수들의 (무)
전체 목록
U3.02 이상발생 정수 목록 초기 전원투입시의 - “---"
정수 값 유효성 검사에서 (무)
실패한 정수들의 목록

Moscon-F50 AC Drive
84

B-정수: 기본환경 설정

정수 출하 시 운전 중 사용자
명칭 단위 설정 범위
번호 설정 변경 여부 설정값
기본설정 B0.01 주파수 지령 선택 - 0~4 0 X

B0.02 운전지령 방법선택 - 0~2 0 X

B0.03 정지방법 선택 - 0~1 0 X

B0.04 역회전 금지 선택 - 0~1 0 X

B0.05 모터 회전방향 설정 - 0~1 0 ○


B0.06 전원 인가시의 모니터 - 1~16 1 ○
항목 설정
B0.07 전원인가시 자동 기동 - 0~1 0 ○

B0.08 인버터 식별 ID - 0~253 1 ○

B0.09 모드버스 Baud rate 설정 - 0~4 2 X

B0.10 모드버스 지연시간 msec 2~65 5 X

B0.11 통신손실시 정지모드 - 0~2 0 X

B0.12 통신손실시간 sec 0~60.0 0 X

B0.13 통신 쓰기 모드 - 0~1 0 X

시스템 B1.01 인버터 초기화 - 0~9999 0000 X


초기화 B1.02 패스워드확인 - 0~9999 0000 X
B1.03 패스워드설정 - 0~9999 0000 X

시스템 B2.01 인버터의 용량 - 20P2(01)~23P7( - X


용량 (공장 설정 정수이므로 06)(삼상)
설정 사용자가 임의 변경하 40P4(22)~43P7(
면 인버터 오동작을 야 26)(삼상)
기합니다.) B0P4(42)~B2P2
(45)(단상)
B2.02 모터의 용량 - 20P2(01)~23P7( - X
06)(삼상)
40P4(22)~43P7(
26)(삼상)
B2.03 인버터 제어 모드 선택 - 0∼1 1 X

B2.04 추후 사용(Reserved)

Moscon-F50 AC Drive
85

F-정수: 주파수 제어 설정

정수 명칭 단위 설정 출하시 운전중 사용자


번호 범위 설정 변경여부 설정값

주파수/ F0.01 오퍼레이터 및 0.01㎐ 0.00 0.00 ○


아날로그 입 통신에 의한 ∼600.0
력 운전의 주속지령
주파수
F0.02 주파수 지령 2∼8 0.01㎐ 0.00 0.00 ○
∼F0.08 ∼600.0
F0.09 Jog 주파수 지령 0.01㎐ 0.00 6.00 ○
∼600.0

주파수 F1.01 주파수 지령 상한 0.1% 0.1 100.0 ○


지령 범위 ~100.0
제한 F1.02 주파수 지령 하한 0.1% 0~99.9 0.0 ○

주파수 F1.03 금지 주파수 1 0.01Hz 0.00 0.00 ○


출력 대역 ~600.0
제한 F1.04 금지 주파수 2 0.01Hz 0.00 0.00 ○
~600.0
F1.05 금지 주파수 3 0.01Hz 0.00 0.00 ○
~600.0
F1.06 금지 주파수 대역폭 0.01Hz 0.00 0.50 ○
~20.00
F1.07 출력금지 범위 - 0~1 0 X
고정값 1

주파수 F1.08 검출 주파수 0.01Hz 0.00 0.00 ○


검출기능 ~600.0
F1.09 주파수 검출 폭 0.01Hz 0.00 0.50 ○
~20.00
F1.10 가감속 절체 주파수 0.01Hz 0.00 0.00 ○
~600.0

Moscon-F50 AC Drive
86

정수 명칭 단위 설정 출하시 운전중 사용자


번호 범위 설정 변경여부 설정값

가감속 F2.01 가속 시간 1 0.01sec 0.00 10.00 ○


시간 ~600.0
F2.02 감속 시간 1 0.01sec 0.00 10.00 ○
~600.0
F2.03 가속 시간 2 0.01sec 0.00 10.00 ○
~600.0
F2.04 감속 시간 2 0.01sec 0.00 10.00 ○
~600.0
F2.05 시간 단위 선택 - 0~1 0 X

F2.06 추후 사용(Reserved)
S-curve F3.01 S-Curve 시간 0.01sec 0.00 0.20 ○
가감속 ~2.50
시간
패턴 F4.01 패턴 운전 시간 1 0.1 sec 0.0 - 999.9 0.00 ○
운전 모드 및 F4.02 패턴 운전 시간 2 0.1 sec 0.0 - 999.0 0.00 ○
시간(1)
F4.03 패턴 운전 시간 3 0.1 sec 0.0 - 999.9 0.00 ○
F4.04 패턴 운전 시간 4 0.1 sec 0.0 - 999.0 0.00 ○
F4.05 패턴 운전 시간 5 0.1 sec 0.0 - 999.9 0.00 ○
F4.06 패턴 운전 시간 6 0.1 sec 0.0 - 999.0 0.00 ○
F4.07 패턴 운전 시간 7 0.1 sec 0.0 - 999.9 0.00 ○
F4.08 패턴 운전 시간 8 0.1 sec 0.0 - 999.0 0.00 ○
F4.09 패턴 운전 모드 1 - 0 - 113 0 X

F4.10 패턴 운전 모드 2 - 0 - 113 0 X

F4.11 패턴 운전 모드 3 - 0 - 113 0 X

F4.12 패턴 운전 모드 4 - 0 - 113 0 X

F4.13 패턴 운전 모드 5 - 0 - 113 0 X

F4.14 패턴 운전 모드 6 - 0 - 113 0 X

F4.15 패턴 운전 모드 7 - 0 - 113 0 X

F4.16 패턴 운전 모드 8 - 0 - 113 0 X

(1) Ver. 2.0 부터 가능

Moscon-F50 AC Drive
87

S-정수: 시스템 기능 조정 설정 정

정수 명칭 단위 설정 범위 출하시 운전중 사용자


번호 설정 변경여부 설정값
직류제동 S0.01 직류 제동 개시주파수 0.01Hz 0.00~10.00 1.50 X

S0.02 직류 제동 전류 1% 0~100 50 X

S0.03 시동시 직류 제동시간 0.1sec 0.0~ 25.0 0.0 X

S0.04 정지시 직류 제동시간 0.1sec 0.0~ 25.0 0.5 X

속도서치 S1.01 기동시 속도 서치 - 0~1 0 X

S1.02 속도서치 개시주파수 0.01㎐ 0.00~600.0 60.00 X

S1.03 속도서치 가동전류 1% 0~200 100 X

S1.04 속도서치 감속시간 0.1sec 0~10.0 2.0 X

Dwell 운전 S2.01 기동시 순간 유지 0.01Hz 0.00 0.00 X


조작 주파수 ~250.0

S2.02 기동시 순간 유지 시간 0.01sec 0.00 ~25.00 0.00 X

S2.03 정지 순간 유지 주파수 0.01Hz 0.00 0.00 X


~25.00
S2.04 정지시 순간 유지 시간 0.01sec 0.00 0.00 X
~250.0

에너지 S3.01 에너지 절약 모드 - 0~2 0 X


절감기능 S3.02 에너지 절약 운전 레벨 1% 0~100 80 X
조작
S3.03 에너지 절약 0.01㎐ 0.00 0.00 X
운전 개시 주파수 ~600.0

슬립 보상 S4.01 슬립보상게인 1% 0.00~S4.03 20% ○


S4.02 슬립보상 지연 시간 1msec 0~9999 200 X

S4.03 슬립보상 제한 1% 0~250 200 X

토오크 S5.01 토오크 보상 게인 1% 0~250 100 X


자동 보상 S5.02 토오크 보상 지연시간 1msec 0~9999 20 X

시스템 S6.01 난조 방지 게인 % 0~100 20 ○


오차보상 S6.02 추후 사용 (Reserved)
S6.03 추후 사용(Reserved)

Moscon-F50 AC Drive
88

정수 명칭 단위 설정 범위 출하시 운전중 사용자


번호 설정 변경여부 설정값

PID 제어(1) S7.01 PID 제어모드 - 0~4 0 X

S7.02 PID용 가감속 시간 1sec 0~50 0 X

S7.03 PID 피드백 상실 모드 - 0~111 0 X

S7.04 PID 피드백 상실 하한 레벨 % 0.0~S7.06 0.0 X

S7.05 PID 피드백 상실 하한 시간 0.1sec 0.0~20.0 1.0 X

S7.06 PID 피드백 상실 상한 레벨 % S7.05~100.0 100.0 X

S7.07 PID 피드백 상실 상한 시간 0.1sec 0.0~20.0 1.0 X

S7.08 PID 출력 특성 선택 - 0~1 0 X

S7.09 PID P 비례 게인 0.01 0.00~25.00 1.00 X

S7.10 PID I 적분 시간 0.1sec 0.0~300.0 0.0 X

S7.11 PID D 미분 시간 0.01sec 0.0~10.00 0.0 X

S7.12 PID 에러 제한 1% 0~1000 1000 X

S7.13 PID 적분 제한 0.1% 0.0~100.0 100.0 X

S7.14 PID 하한치 0.1% -100.0~S7.15 0.0 X

S7.15 PID 상한치 0.1% S7.14~100.0 100.0 X

S7.16 PID 지연 시간 0.01sec 0.00~10.00 0.00 X

S7.17 PID 옵셋 0.1% -100.0~100.0 0.0 X

S7.18 PID 출력 게인 0.01 0.00~25.00 1.00 X

S7.19 PID 출력 역회전 선택 - 0~1 0 X

S7.20 PID 목표치 선택 - 0~1 0 X

S7.21 PID 목표치 0.0Hz 0.00~C0.02 0 X

(1) Ver. 2.0 부터 가능

Moscon-F50 AC Drive
89

C-정수: H/W 기능 설정

정수 명칭 단위 설정 출하시 운전중 사용자


번호 범위 설정 변경여부 설정값

V/f 설정 C0.01 V/f 패턴 - 0~15 15 X

C0.02 최대 출력 주파수 0.01Hz 30~600.0 60.00 X

C0.03 최대 출력 전압 0.1V 0.0~250.0 200.0 X

C0.04 기저 주파수 0.01Hz 30.00 60.00 X


(최대접압주파수) ~600.0

C0.05 중간 출력 주파수 0.01Hz 0.00 3.00 X


~600.0
C0.06 중간 출력 주파수 전압 0.1V 0.0~250.0 14.0 X

C0.07 최저 출력 주파수 0.01Hz 0.00 1.50 X


~600.0
C0.08 최저 출력 주파수 전압 0.1V 0.0~250.0 8.0 X

Carrier C1.01 Carrier 주파수 0.01kHz 1.50 10.00 X


주파수 ~11.00
관련 설정

주 모터 C2.01 고정자 저항 0.01Ω 0.00 * X


관련 ~99.99
데이터 C2.02 철손 설정 1W 0~9999 * X

C2.03 정격출력 전류 0.01A 0.00 * X


~99.99
C2.04 무부하전류 0.01A 0.00 * X
~99.99
C2.05 모터 정격 슬립 0.01 Hz 0.00 * X
~600.0
C2.06 모터 극 수 설정 - 2~39 4 X

C2.07 정격 자속 전압 설정 0.1V 0.0~250.0 0 X

C2.08 오토 튜닝 모드 실행 - 0~2 0 X

H/W 조정 C3.01~C3.07 공장 설정 정수
관련 임의 수정시 오동작
데이터 발생

Moscon-F50 AC Drive
90

H-정수: 입출력 제어 기능 설정

정수 명칭 단위 설정 출하시 운전중 사용자


번호 범위 설정 변경여부 설정값

다기능 접점 H0.01 단자대 입력 형태 선택 - 00∼ 00 X


입력 3F
(16진
법)
H0.02 단자 3의 입력기능 - 0~29 1 X

H0.03 단자 4의 입력기능 - 0~29 2 X

H0.04 단자 5의 입력기능 - 0~29 3 X

H0.05 단자 6의 입력기능 - 0~29 6 X

다기능 접점 H1.01 접점출력 형태 선택 - 0~3 0 X


출력 H1.02 출력 단자1의 기능 - 0~15 0 X

H1.03 출력 단자2의 기능 - 0~15 1 X

H1.05 펄스 카운터 1(1) - 0~9999 0 X

H1.06 펄스 카운터 2(1) - 0~9999 0 X

Moscon-F50 AC Drive
91

정수 명칭 단위 설정 출하시 운전중 사용자


번호 범위 설정 변경여부 설정값

다기능 H2.01 추후 사용 (Reserved)


아날로그 H2.02 Analog입력시 정수 1ms 0~100 20 X
입력
H2.03 다기능 아날로그 - 0~9 0 X
입력 1 단자 기능
H2.04 다기능 아날로그 0.1% 0.0~20 100.0 ○
입력 1 게인 0.0

H2.05 다기능 아날로그 0.1% -100.0 0.0 ○


입력 1 바이어스 ~100.0

H2.06 다기능 아날로그 - 0~9 0 X


입력 2 단자 기능
H2.07 다기능 아날로그 0.1% 0.0~20 100.0 ○
입력 2 게인 0.0

H2.08 다기능 아날로그 0.1% -100.0 0.0 ○


입력 2 바이어스 ~100.0

H2.09 아날로그 입력 2 타입(1) - 0~3 1 X

H2.10 펄스 입력 스케일(1) 0.00kHz 1.00~3 1.44 ○


2.00
H2.11 펄스 입력 게인(1) 0.1% 0.0~10 100.0 ○
0.0
H2.12 펄스 입력 바이어스(1) 0.1% -100.0 0.0 ○
~100.0
H2.13 펄스 입력 지연시간 0.1sec 0.00~2. 0.10 ○
00

다기능 H3.01 아날로그 모니터 - 0~7 1 X


아날로그 기능 설정
출력 H3.02 아날로그 모니터 게인 0.1% 0.0 100.0 ○
설정 ~200.0

H3.03 아날로그 모니터 0.1% -100.0 0.0 ○


바이어스 설정 ~100.0

H3.04 아날로그 모니터 타입(1) - 0~1 0 X

H3.05 펄스 출력 기능(1) - 0~4 1 ○

H3.06 펄스 출력 스케일(1) 0.01kHz 0.00~3 1.44 ○


2.00

Moscon-F50 AC Drive
92

정수 명칭 단위 설정 출하시 운전중 사용자


번호 범위 설정 변경여부 설정값

디지털 H4.01 U0.07 화면표시 형태 - 0~3999 30 ○


오퍼레이터 H4.02 디지털 오퍼레이터 정지 - 0~1 1 X
설정
H4.03 로컬원격 변경시 운전 - 0~1 0 X

H4.04 미사용 (Reserved)


H4.05 디지털 볼륨의 주파수 - 0~1 2 ○
단위 선정
H4.06 정수 설정 모드 - 0~1 1 X

H4.07 팬 운전 모드 - 0~1 1 X

(1)
Ver. 2.0 부터 가능

Moscon-F50 AC Drive
93

P-정수: 보호기능 설정

정수 출하 시 운전중 사용자
설정 범위
번호 명칭 단위
설정 변경여부 설정값
모터 과부하 P0.01 모터 보호 선택 - 0~1 1 X
보호 P0.02 모터보호 시 정수 - 0.0~60.0 1.0 X

P0.03 모터 선택 - 0~1 0 X

순시 정전 P1.01 정전 시 운전 - 0~2 0 X

P1.02 순시정전 보상 시간 0.1초 0.0~2.0 0.5 X

P1.03 V/f 복구 시간 0.1초 0.0~2.0 0.5 X

P1.04 저전압 감지 레벨 1V 0~250 190 X

스톨방지 P2.01 가속중 스톨방지 - 0~1 1 X

P2.02 가속중 스톨 방지 레벨 1% 0~200 170 ○


P2.03 가속중 스톨 방지 제한 1% 0~100 50 ○
P2.04 감속중 스톨 방지 - 0~1 1 X

P2.05 운전중 스톨 방지 - 0~2 1 X

P2.06 운전중 스톨 방지 1% 0~200 170 ○

과토오크 P3.01 과토오크 검출 - 0~4 0 X


검출 P3.02 과토오크 검출 레벨 1% 0~300 180 ○
P3.03 과토오크 지연시간 1초 0.0~10.0 0.1 X

이상 재시도 P4.01 이상 재시도 횟수 - 0~10 0 X

P4.02 단자출력 유무 - 0~1 0 X

결상 보호 P6.01 입력 결상 보호 - 0~1 0 X

Moscon-F50 AC Drive
94

보호기능/에러 설명
기동 및 운전시 정수 설정 및 배선 등의 잘못으로 인버터와 모터가 원하는 명령대로
작동하지 않을 수 있습니다.
MOSCON-F50은 많은 보호기능을 갖고 있으며, 이상 발생시 디지털 오퍼레이터상
에 표시됩니다.

이상이 검출되면 이상접점출력이 작동되고 인버터 출력은 차단되어 모터가 정지됩


니다. 정지방법은 이상의 종류에 따라 다르게 선택할 수 있습니다.

• 이상이 발생하면 다음의 표에서 원인과 조치 내용을 참조하십시오.


• 다음 방법중 하나를 사용하여 이상을 리셋한 후 재기동하십시오.
– 디지털 오퍼레이터의 리셋트 키를 누릅니다 .
– 전원을 껐다가 다시 켭니다 .
– 이상 리셋트 단자를 ON 합니다 .

에러 표시 및 설명
항목 지시내용 원 인 조 치
OC2 인버터의 출력 인버터 출력측에서 단락이나 접지이 원인조사, 조치후 리셋
단락 에러 또는 부하측 상 발생(단락이나 접지사고는 모터 트 실시
단락 가 타서 손상을 입었거나 절연이 약
화 되었거나 케이블이 손상되었을
때 발생할 수 있습니다.)
OC1 인버터의 출력 • 인버터 출력에 단락이나 접지 이 원인조사, 조치후 리셋
과전류 전류가 상 발생(단락이나 접지 이상은 모 트 실시
순시 정격 전류 터가 타서 손상을 입거나 절연 약
의 200% 초과 화, 케이블이 손상되었을 때 발생)
• 부하가 너무 크거나 가속/감속 시
간이 너무 짧습니다.
• 특수 모터나 인버터에 비해 너무
큰 용량을 가진 모터가 사용됩니
다.
• 인버터 출력에서 마그네틱 스위
치가 전환됩니다.
OH2 인버터 방열 핀 주위환경온도가 지나치게 높습니다. 냉각장치 설치
인버터 온도 약 95℃ 초
과열 인버터 근처에 발열체가 있습니다. 발열체 제거

인버터 냉각팬 고장이 생겼습니다. 냉각팬 교체
(서비스센터에 문의)

Moscon-F50 AC Drive
95

에러 표시 및 설명
항목 지시내용 원 인 조 치
OV 주회로 DC전압 • 감속시간이 너무 짧습니다. 감속시간을 길게 하거
주회로 이 과전압 감지 • 모터로부터 회생 에너지가 너무 나 제동저항기(또는
과전압 레벨을 초과 큽니다. unit)를 연결
200V급:410V
전원전압이 너무 높습니다. 전압을 전원사양 범위
400V급:820V
내로 낮춘다.
UV1 주회로 DC 전압 • 입력전원의 결상 발생입니다. 원인조사, 조치후 리셋
주회로 이 저전압 감지 • 순시정전이 발생됐습니다. 트 실시
저전압 레벨
• 입력전원의 전압변동이 큽니다.
이하
200V급: 190V
400V급: 380V
OL3 모터 토크전류 부하과중 또는 급속한 가속입니다. P3.02와P3.03를 적절하
과토크 가 설정 레벨을 게 설정
검출 초과 기계상태 점검과
모터 정격 토크 과토오크 원인을 조치
전류 100% 기준
OL2 인버터 정격에 부하가 너무 큽니다. 가속시간 감속 부하의 크기를 점검하
인버터 비해 150%의 시간 그리고 사이클 시간이 너무 고 가속, 감속 및 사이
과부하 출력전류가 짧습니다. 클시간의 길이를 점검
1분이상 지속 합니다.

V/f 특성 전압이 너무 높습니다. V/f 특성을 점검

인버터 용량이 너무 낮습니다. 인버터를 더 큰 용량으


로 교체

OL1 모터 모터 정격에 비 부하가 너무 큽니다. 가속시간 감속 부하의 크기를 점검하


과부하 해150%의 시간 그리고 사이클 시간이 너무 고 가속, 감속 및 사이
출력이 짧습니다. 클시간의 길이를 점검
1분이상 지속
V/f 특성 전압이 너무 높습니다. V/f특성을 점검

모터 정격 전류 설정(C2.03)이 부정확 모터의 정격 전류 설정


합니다. (C2.03)을 점검
PFL PID 피드백 PID 피드백이 검출되지 않음 입력 배선 점검
PID 피드백 로스 피드백 센서 문제 발생 피드백 센서 점검
로스
CB3 외부아날로그 배선교환
아날로그 속도제어용 배 (서비스센터에 문의)
속도 선 연결불량
명령이상

Moscon-F50 AC Drive
96

에러 표시 및 설명
항목 지시내용 원 인 조 치
CB2 입력 정수의 상하한값 범위내 입력
정수 범위 상하한 값 초과
초과
CB1 설정입력된 정 서비스센터에 문의
EEPROM 수 확인중 에러
이상
EF4 외부입력 이상 외부이상이 다기능 입력단자로부터 • 다기능 입력의 적절
외부이상 (터미널 4) 입력되었습니다. 한 선택여부 점검
(터미널4) • 외부이상원인 제거
EF3 외부입력 이상
외부이상 (터미널 3)
(터미널3)
EF2 외부입력 이상
외부이상 (터미널 2)
(터미널2)
EF1 외부입력 이상
외부이상 (터미널 1)
(터미널1)
CB0 전원투입시 설 EEPROM에 저장된 사용자 정수의 서비스센터에 문의
정수이상 정 정수의 전원 투입은 기검사시 이상이 검출
에러발생 되었습니다.(U3.02에서 검출된 정수
의 번호확인가능, 최대32개)
IPL 입력 전원 결상 • 입력전원 결상으로 DC Bus 리플이 • 입력 배선, 전압 점
입력 결상 커질경우 검출을 합니다. (3상 모 검
델만) • 삼상 언벨런스, 콘
• 부하가 작을 경우 검출이 않됨 덴서 열화된 경우
검출할수 있음

Moscon-F50 AC Drive
97

항목 지시내용 원 인 조 치

UV경고 주회로 • 입력전원 투입시 조치후


주회로 DC전압의 저전압 감 결상 발생입니다. 리셋트 실시
저전압 지 레벨 • 순시 정전 발생
이하 되었습니다.
200V급: 190V
• 입력전원의
400V급: 380V
전압변동이 큽니다.
OL3 순시정격전류의 • 부하가 너무 큽니다. P3.02와P3.03를 적절하게 설정 기
과토오크 180% 출력 • 인버터 용량이 계상태 점검과 과토오크 원인을
검출 작습니다. 조치

SE 정방향/역방향 운전 정방향, 역방향 운전명 정방향/역방향 운전명령의 시


경고 명령이 동시에 령이 동시에 입력됩니 퀀스를 점검
입력 됨 다.
BB 베이스블록 명령이 베이스 블록 지령 입력
베이스블록 외부에서 입력 이 됩니다.
STP 원격모드에서 정지 원격모드에서
경고 키에 의한 로컬정지 명령이
모터 정지 입력 되었습니다.
OPE 오퍼레이터 오퍼레이터와 인버터 • 오퍼레이터 재장착
이상 통신 이상 간에 통신이 안됨 • 전원 재투입
CE2 PC통신 유지 시간 초 통신지령 모드에서 통 PC 통신 라인에 이상이 없는지
경고 과 신이 지정시간동안 유 점검
지 되지 않음

Moscon-F50 AC Drive
98

일상점검
다음은 시스템 운전 중에 검사합니다.

• 모터의 진동과 이상한 소음


• 비정상적인 열발생
• 주변온도의 이상 고온
• 모니터상에 정상 출력 전류값 보다 높은 값 표시(U0.05 참조)
• 냉각팬의 정상적인 가동 여부

정기적인 검사
• 정기점검에 대해 다음의 표를 참조하십시오.

• 검사전 전원을 차단하여 주십시오. 감전의 위험이 있습니다.


주의
• 주회로 콘덴서에 잔류전압이 존재하므로 인버터의 주회로 전원 차단후
일정 시간 경과 후 유지보수와 검사작업을 실시하여야 합니다.

항목 검사 조치
단자, 취부볼 모든 부품의 연결 부분과 느슨하게 된 연결부품을 다시 조립하고 볼트
트,커넥터등 볼트가 적절하게 체결되어 를 단단하게 조입니다.
있습니까?

방열 핀 핀이 더럽거나 먼지가 묻지 압력 39.2×104∼58.8×104 Pa(4∼6kg.㎠)의 건조


않았습니까? 한 공기를 사용하여 에어 건으로 제거합니다.
PCB 도전성 물질이나 오일분무가 압력 39.2×104∼58.8×104 Pa(4∼6kg.㎠)의 건조
쌓여 있습니까? 한 공기를 사용하여 에어 건으로 깨끗하게 청
소합니다.

냉각 팬 이상음이나 진동이 있습니까? 냉각 팬을 교체합니다.

전원 소자 도전성 먼지나 기름 찌꺼기 압력 39.2×104∼58.8×104 Pa(4∼6kg.㎠)의 건조


등이 소자에 묻어 있지는 않 한 공기를 사용하여 에어 건으로 제거합니다.
습니까?

주회로 변색이나 악취 같은 이상한 콘덴서를 교환합니다.


콘덴서 것들이 없습니까?

Moscon-F50 AC Drive
99

부품 교환
인버터는 여러 개의 부품으로 구성되어 있고 이들 부품들이 적절한 기능을 발휘하
여야 인버터의 정상운전이 가능합니다.

인버터가 장시간 정상적인 운전이 유지되려면 주기적인 점검과 수명에 따라 부품


을 교환할 필요가 있습니다.

점검주기는 설치환경과 사용조건에 따라 다릅니다.

사용조건
경고
• 주변온도: 연평균 30℃
• 부 하 율: 최대 80%
• 운 전 율: 1일 최대 12시간

MOSCON-F50의 정기점검을 위해서는 아래 표를 참조하십시오.

부품 표준 교환주기 교환 방법

냉각 팬 2~5 년 새 부품으로 교환

브레이커 릴레이 - 교환이 필요할 경우 점검 후 결정

PCB의 알루미늄 5년 새 보드로 교환


컨덴서 (교환이 필요할 경우 점검 후 결정)

휴즈 10년 새 부품으로 교환

Moscon-F50 AC Drive
Publication: MosconF50-IN002A-F50-EK - November 2010
*RA68_000205*
*RA68_000205*

Copyright © 2010 RS Automation Co., Ltd. All rights reserved.