MOSCON-F50 AC Drive
(Ver. 3.xx)
Language Page
English 3
한국어 53
English
Contents
Important User Information ............................................................................. 4
Safety Instructions .......................................................................................... 5
Receiving ......................................................................................................... 6
Nameplate information ................................................................................... 7
Installation ....................................................................................................... 8
Dimensions ..................................................................................................... 9
Connection diagram ...................................................................................... 12
Main Circuit Terminal Functions .................................................................. 14
Control Circuit Terminal Functions ................................................................ 15
Cable Specification ...................................................................................... 16
Wiring check .................................................................................................. 17
Switch Setting ............................................................................................... 18
Specifications ................................................................................................ 19
Monitoring functions of digital operator ....................................................... 28
Test Run ......................................................................................................... 29
U-Parameter: Monitoring .............................................................................. 32
B-parameter: Basic Environments Setting .................................................... 34
F-parameter: Frequency Control Setting ...................................................... 36
S-parameter: System Function Adjustment Setting ..................................... 38
C-parameter: H/W Functions Setting ........................................................... 41
H-parameter: Input/Output Control Function Setting .................................. 43
P-parameter: Protection Functions Setting .................................................. 45
Protective function/error description ........................................................... 47
Periodic inspection ........................................................................................ 51
Part replacement ........................................................................................... 52
4
Identifies information that is critical for successful application and understanding of the
IMPORTANT
product.
Identifies information about practices or circumstances that can lead to personal injury
ATTENTION
or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Moscon-F50 AC Drive
5
Safety Instructions
Please read this manual and the related documentation thoroughly and familiarize yourself with the directions
before installing, performing inspection and preventive maintenance. Make sure to follow the directions
correctly to ensure normal operation of the product and your safety.
• Before starting wiring or inspection, switch power off, wait for more than 1
WARNING minutes, and check for residual voltage between terminal P/B and N with a meter
etc, to avoid a hazard of electrical shock.
• The digital operator is detachable from the main body.
• Suitable for use in a circuit capable of delivering not more than 5kA rms
symmetrical amperes.
• Do not carry the AC Drive by holding the plastic parts, but hold the heatsink. The
heat sink may fall and cause injury.
• Use nonflammable materials such as metal for the part where the AC Drive is
installed.
• When installing several AC Drives in a single enclosed space, install a cooling fan
to keep the ambient temperature below 45°.
• Cover the AC Drive during installation to protect it from metal chip coming from
drilling
• Always turn OFF the input power supply before wiring. Otherwise, an electric shock
or fire may occur.
• Wiring must be performed by qualified personnel.
• Always check if the bolts on the main circuit and control circuit terminals are
properly tightened.
• Turn ON the AC Drive only after completely assembling the covers. Do not detach
the cover when the power is ON. Otherwise, an electric shock or fire may occur.
• Ground the ground terminal (200V class: ground to 100 ohm or less, 400V class:
ground to 10 ohm or less). Otherwise, an electric shock or fire may occur.
• Tighten all terminal screws of the main circuit and the control circuit.
• Check if the voltage of the AC Drive rated voltage satisfies with the AC power
supply voltage. Otherwise, it may cause fire or injury
• Do not perform withstand voltage test on the AC Drive. It may damage the
semi-conductor element.
• When wiring other devices read their manuals carefully. RS Automation Co., Ltd. is
not responsible for any accident resulting from user's carelessness. If not, it may
cause injury or fire.
• Do not connect electromagnetic switches or magnetic contactors to the output
circuits.
• Otherwise, it will actuate the over current protective circuit in the AC Drive.
• Never connect an AC power supply to output terminals U/T1, V/T2, and W/T3.
Otherwise, it may damage the internal circuits of the AC Drive.
• Never short or ground output terminals: the output terminals should not be touched
with bare hands and also, the output wires should not have contact with the AC
Drive case Otherwise, an electric shock or grounding may occur.
Moscon-F50 AC Drive
6
Receiving
Confirm the following upon delivery of the Moscon-F50:
• Verify the model number to check if the correct item has been delivered.
• Check if any physical damage has occurred during shipping.
If there is any damage or missing part, call the place where you purchased the product
or sales office for service immediately.
Don’t install the AC Drive if there is any damage or a missing part. It may
WARNING
cause injury.
Moscon-F50 AC Drive
7
Nameplate information
Example of nameplate
Nameplate location
Nameplate
(located at the right side)
एँऎ࣪ऊऋࣶ࣮ࣜऔंࣱ࣬औࣱࣩ࣬࣬ࣽं࣭ࣾ࣬࣬࣬
अऌ࣮࣬ࣜअऊएऐࣽईईࣽऐअऋऊࣜࣿࣽऐँःऋऎकࣜअअࣜउࣽएएࣲࣶ࣭࣪࣬इण
ऋऱरबऱरࣜऌफळडमࣶ࣯ࣜࣜࣜࣽࣿࣜऌऄࣰࣲࣩࣜ࣬࣬ऒࣰ࣭ࣜ࣪धऒ࣭ࣽࣜ࣪ࣴࣽ
अपबऱरࣜऒफनरझणडࣶ࣯ࣜࣜࣽࣿࣜऌऄࣰࣲ࣯ࣩࣜࣴ࣬࣬ऒࣱࣲࣜ࣬࣫࣬ऄश
उऋऀँईࣶࣜࣜएअछࣰ࣬ऌࣰंࣱ࣬
FcW_kY``5ihcaUh]cb?cfYU@hX"A589=B?CF95
ऌऎःࣶ࣭࣪࣬࣬
Moscon-F50 AC Drive
8
Installation
MODEL : SI_40P4F50
Rockwell Automation Korea Ltd. MADE IN KOREA
SER.NO: 2XF50X005A-FB0001
IP20 INSTALLATION CATEGORY II MASS:1.60Kg
Output Power : AC 3PH 0-460V 1.4kVA 1.8A
Input Voltage : AC 3PH 380-460V 50/60Hz
PRG:1.00 MODEL : SI_40P4F50
PRG:1.00
Vertical Horizontal
Installation Installation
Moscon-F50 AC Drive
9
Installation space
Install the AC Drive on a vertical surface to enhance the cooling effect. When installing the
AC Drive, always leave enough space around it to provide normal heat dissipation.
> 100mm
> 30mm > 30mm
MODEL : SI_40P4F50
Rockwell Automation Korea Ltd. MADE IN KOREA
PRG:1.00
> 100mm
Installation space
Dimensions
76 84.6 Unit: mm
128
Moscon-F50 AC Drive
MODEL : SI_40P4F50 PRG:1.00 MODEL : SI_40P4F50 PRG:1.00
InputVoltageAC: 3PH 380-460V 50/60
Hz InputVoltageAC: 3PH 380-460V 50/60
Hz
OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A
IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg
SER.NO: 2XF50X005A-FB0001 SER.NO: 2XF50X005A-FB0001
145.4
145.4
Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA
126.4
Dimension of 1-phase B0P4, B0P7 and 3-phase 21P5, 22P2, 40P4, 40P7, 41P5
120
150
Moscon-F50 AC Drive
128
128
128
10
11
Dimensions of MOSCON-F50
Type MOSCON-F50
External Dimension Installation Dimension Volume (mm3) Weight
(Unit: mm) (Unit: mm) (kg)
(W x H x D) W1 x H1 x Φ
20P2 76 x 128 x 84.6 822,988.8 0.6
20P4 66 x 118, M4
76 x 128 x 126.4 1,229,619.2 0.9
20P7
B0P4
B0P7
21P5
22P2 120×128×145.4 103×118, M4 2,233,344 1.6
40P4
40P7
41P5
B1P5
1.9
B2P2
23P7 150×128×145.4 134×118, M4 2,617,200
42P2 2.0
43P7
Moscon-F50 AC Drive
12
Connection diagram
The connection diagram of the Moscon-F50 is shown below.
When using the digital operator, the motor can be operated by wiring only the main circuits.
B1 B2
MCCB
Motor
R/L1 U/T1
4)
S/L2 V/T2
Input power
4)
T/L3 W/T3
Digital Input
S1 R1 Multi-function
Forward run/stop contact output 1
S2
Reverse run/stop DC 30V 1Amax
S3 RC1 AC 250V 1Amax
External fault (Default: fault)
Fault reset S4
Multi-step command S5 Multi-function
R2 contact output 2
Jogging S6 DC 30V 1Amax
SC AC 250V 1Amax
RC2
(Default: In running)
Ground
2 kΩ
V+ Power for speed command
(+12V 20mA)
A1 Analog Input 1
2 kΩ
(0 to 10V 20kΩ )
AC
Analog Common
Analog Input 2
A2
(4-20mA, 0-20mA 250Ω ,
0~10V 20kΩ )
AM (0-32kHz Pulse:Option)
Analog monitor output
(0-10V)
(0 -32kHz Pulse:Option)
p
NOTE 1) : Shield wire, : Twisted pair shield wire.
2) : Main circuit terminal, : Control circuit terminal.
3) Max. current value for V+ (power for speed command) is 20mA.
4) EMI cores are recommended to the motor cables.
(refer to the diagam about installation location. TDK ZCAT3035 - 1330)
Moscon-F50 AC Drive
13
B1 B2
MCCB
Motor
R/L1 U/T1
Input power 4)
S/L2 V/T2
4)
W/T3
R1 Multi-function
contact output 1
1 DC 30V 1Amax
2 AC 250V 1Amax
RC1 (Default: fault)
3
Digital Input 4
5 R2
Multi-function
6
contact output 2
DC 30V 1Amax
9 AC 250V 1Amax
RC2
(Default: In running)
2 kΩ Ground
2 kΩ A1 Analog Input 1
(0 to 10V 20kΩ )
AC
Analog command
A2
Analog Input 2
(4-20mA, 0-20mA 250Ω ,
0~10V 20kΩ )
AM (0-32kHz Pulse:Option)
Analog monitor output
(0-10V)
(0 -32kHz Pulse:Option)
p
NOTE 1) : Shield wire, : Twisted pair shield wire.
2) : Main circuit terminal, : Control circuit terminal.
3) Max. current value for V+ (power for speed command) is 20mA.
4) EMI cores are recommended to the motor cables.
(refer to the diagam about installation location. TDK ZCAT3035 - 1330)
Moscon-F50 AC Drive
14
Moscon-F50 AC Drive
15
A1 Analog Input 1 for freq. commandy Voltage (DC 0 to +10V) Command Frequency
Analog Input 2 for freq. command Current (0~20, 4~20mA) Command Frequency
A2 Voltage( 0~10V),
Pulse(Option: 0~32kHz)
AC Analog Common 0V -
Analog monitor output DC 0~10V (Output frequency)
AM
Pulse(Option) 0~32kHz
Multi-function relay output 1 Contact : Fault occurred
R1, RC1 AC 250V, 1A or below
DC 30V, 1A or below
Multi-function relay output 2 Contact : In running
R2, RC2
AC 250V, 1A or below
(Option)
DC 30V, 1A or below
NOTE Be attentive to below mention when changing output frequency in using the external frequency command terminal.
• Voltage command input terminal is set as AI1 + AI2.
• Pulse IO is available from ver 2.0 and it is optional.
Moscon-F50 AC Drive
16
Cable Specification
Determine the cable size for the main circuit. The line voltage drop should be within 2% of
the rated voltage. The line voltage drop is calculated as below:
–
= 10
LVD: Line Voltage Drop
CR: Cable Resistance
WL: Wiring Length
C: Current
Cable size
Circuit Model Terminal Tightening Crimping Cable Size(1) Kind of Cable
Screw Torque Nm Terminal
mm2 AWG
(1)
Earth Cable should be used with a 10.0 mm2 or thicker cable.
Moscon-F50 AC Drive
17
Wiring check
• After wiring has been complete, check the following. Do not perform a buzzer check on
WARNING
control circuit.
Moscon-F50 AC Drive
18
Switch Setting
SW1
Monitor
Select ON
SW3 1 2 3 4 5 6
SRC/SNK
Select
SW2
AI Type
Select
ATTENTION Wrong DIP SW setting makes HW problem resulted from mixed signal types.
Pay very careful attention to DIO SW settings.
Moscon-F50 AC Drive
19
Specifications
200V- 3-phase 20P2 20P4 20P7 21P5 22P2 23P7
230V
Class 1-phase - B0P4 B0P7 B1P5 B2P2 -
Max. Applicable
Motor
Moscon-F50 AC Drive
20
380V- 3-phase
460V - 40P4 40P7 41P5 42P2 43P7
Class
Max. Applicable
Motor
(1 phase)
Rated Output 3 phase, 0~460Vac (Proportional to input voltage)
Voltage[V]
Rated Output Default: 60Hz, Max. 400Hz
Frequency[Hz]
(1) The maximum applicable motor capacity is for a standard 4-pole motor. When selecting the motor and inverter, make sure
that the Inverter's rated current is applicable for the motor's rated current.
Moscon-F50 AC Drive
21
Analog: 0.1Hz(10-bit)
Output Frequency Resolution 0.01Hz
Accel/Decel Time 0~600.00sec (0.1sec step)
2 sets available
Carrier Frequency Control Range 1.5~11KHz (0.1kHz step)
Speed Control Range 100:1
Speed Stability 1.0%(@60:1, Slip compensation included)
Speed Responsivity 5Hz
Starting Torque 150%@1.0Hz
Torque limiting Yes (Current limiting)
Overload tolerance 150%/60sec., 200%/1sec
Moscon-F50 AC Drive
22
Input/Output Terminals
Control User I/F Operation Panel: LED Operator (4 digits + 6 keys),
Communication S/W (MosconTools)
Communication Port RS-485 with Modbus-RTU (RJ-45),
Input Analog Input Two Input, 9 functions, AI1 voltage (0-10V)
AI2: Voltage (0-10V, 0 (or 4)-20mA, 0-32kHz Pulse: option)
Zi :20 k ohm(voltage), 250 ohm(current)
external resistor : 2k ohm, min. 2W
Digital Contact Point Input 6 Input, 30 functions + power (+24V)
(fixed x 2, configurable x 4)
24V, Sink or Source
(L: 0~6V, H: 18~24V)
1 Output, 8 functions (Pulse Output 5 functions: option)
Analog Output Select Voltage (0~10V) or Pulse (0-32kHz: option)
Zo : min.1 k ohm (voltage) or max. 200 ohm (current)
Output R1 Output, 12 functions (1a relay)
(R2 Output, 12 functions (Option 1a realy)
Digital Contact Point Output
relay : 1.0A @ 30Vdc/240Vac(non-inducting), 1.0A @
30Vdc/240Vac(inducting)
1-phase power Input L1, L2
3-phase power Input L1/R, L2/S, L3/T
Power Supply Breaking resistor
B1, B2
connection
3-phase Output (Common) T1/U, T2/V, T3/W
Moscon-F50 AC Drive
23
Moscon-F50 AC Drive
24
Moscon-F50 AC Drive
25
Moscon-F50 AC Drive
26
- IEC-BS88(British standard) Parts 1&2, EN60269-1, Parts 1&2, type gG or equivalent should be used
Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD,
Typical designations include; Type CC - KTK-R, FNQ-R, Type J - JKS, LPJ, Type T - JJS, JJN
Moscon-F50 AC Drive
27
Increment/Up key:
– Increase parameter number and value REV LED:
ON when the motor is
– Shift between parameter groups running backward (CCW)
Digital volume(1):
– Frequency setting
mode (change
frequency command)
– Parameter setting
Run key: mode
Run motor in the operator CW: increment
command mode CCW: decrement
– Shift between
parameter group
Stop key:
Stop motor
Reset key:
Reset fault
Data key:
Display parameter description
Decrement/Down key:
– Decrease parameter number and value Set key:
– Set parameter to the displayed
value
Shift key:
- Select the digit to modify – After chaning the parameter,
- When U0.01 value is displayed, display the parameter number
move to command freq. edit mode
(B0.01=0 or 1 only)
(1)
Using the digital volume, a displayed data or parameter number can be changed in different rate.
Moscon-F50 AC Drive
28
Reference Freq.
Ά͟͢͡͡ ͑
Άͧ͟͡͡ ͑ Output ͑
Άͤ͟͢͡ I/O status ͑
Άͪ͟͡͡
͑
PID reference [%] ͑
Monitoring functions of digital operator
Moscon-F50 AC Drive
29
Test Run
Power ON
When pressing Shift Key, the mode is
changed to Freq. edit mode.
Floating point blinking (B0.0=0)
FWD
Digit blinking (B0.01=1)
REV
Set Command
Frequency In order to increase the value,
FWD rotate the digital volume in CW
REV
direction.
Run
Press RUN key.
FWD
REV
to be changed
Press Right Shift Key
FWD
REV
Parameter
modification Press DATA/SET key.
FWD
(Switched to DATA mode)
REV
Moscon-F50 AC Drive
30
B0.01= 0 or 1 only
Moscon-F50 AC Drive
31
Moscon-F50 AC Drive
32
U-Parameter: Monitoring
Parameter Descrpition Unit Display
U0.01 Effective Frequency Command xx.xx
0.01㎐
∼xxx.x
U0.02 Current Output Frequency xx.xx
0.01㎐
∼xxx.x
U0.03 Output Current in RMS 0.01A xx.xA
U0.04 Output Voltage in RMS 1V xxxu
U0.05 DC Bus Voltage 1V dxxx
U0.06 Output Power in 0.1kW 0.1kW Pxx.x
U0.07 Motor speed in RPM 1rpm xxxx
Monitoring
Moscon-F50 AC Drive
33
Moscon-F50 AC Drive
34
Moscon-F50 AC Drive
35
(3-phase)
B0P4(42)~
B2P2(45)
(1-phase)
B2.02 Power Capacity of the Motor 20P2(01)~
23P7(06)(3-phase)
- - X
40P4(22)~
43P7(26)(3-phase)
B2.03 Inverter control mode selection - 0∼1 1 X
B2.04 Reserved
Moscon-F50 AC Drive
36
0.00
Command of Operator Mode & 0.01㎐ 0.00 ○
∼600.0
Communication Mode
F0.02 Frequency2 to Frequency8 0.00
~F0.08 0.01㎐ 0.00 ○
∼600.0
F0.09 Jog Frequency
0.00
0.01㎐ 6.00 ○
∼600.0
~600.0
F1.04 Jump Frequency2 0.00
0.01Hz
~600.0
0.00 ○
Match Detection
0.01Hz
~600.0
0.00 ○
Moscon-F50 AC Drive
37
0.01sec 10.00 ○
~600.0
F2.03 Accel Time 2 0.00
0.01sec 10.00 ○
~600.0
F2.04 Decel Time 2 0.00
0.01sec 10.00 ○
~600.0
F2.05 Accel/Decel Time Base - 0~1 0 X
F2.06 Reserved
F3.01 S-Curve Time
Accel/Decel Time
S-Curve
0.00
0.01sec 0.20 ○
~2.50
Moscon-F50 AC Drive
38
S0.02 DC Brake
1% 0~100 50 X
Current
S0.03 DC Braking Time 0.0
0.1sec 0.0 X
at Start ~ 25.0
S0.04 DC Braking Time 0.0
0.1sec 0.5 X
at Stop ~ 25.0
S1.01 Speed Search
- 0~1 0 X
Speed Search
at Start
S1.02 Speed Search 0.00
0.01㎐ 60.00 X
Start Frequency ~600.0
S1.03 Speed Search Current 1% 0~200 100 X
S1.04 Speed Search Deceleration Time 0.1sec 0~10.0 2.0 X
S2.01 Dwell Frequency at Start 0.00
0.01Hz 0.00 X
~250.0
Dwell Operation
0.00
0.01㎐ 0.00 X
~600.0
Gain
1%
~S4.03
20% ○
Slip
Moscon-F50 AC Drive
39
Delay time 0~
1msec 20 X
9999
S6.01 Hunting
System function
% 0~100 20 ○
Prevention Gain
S6.02 Enable
- 0~1 0 X
Brake Boosting
S6.03 Reserved
Moscon-F50 AC Drive
40
(1)
Available from Ver. 2.0
Moscon-F50 AC Drive
41
~600.0
C0.05 Mid Output Frequency 0.00
0.01Hz 3.00 X
~600.0
C0.06 Mid Output Voltage 0.0
0.1V 14.0 X
~250.0
C0.07 Min Output Frequency 0.00
0.01Hz 1.50 X
~600.0
C0.08 Min Output Voltage 0.0
0.1V 8.0 X
~250.0
C1.01 PWM Frequency
Carrier Frequency
/ Modulation
1.50
0.01kHz 10.00 X
~11.00
Moscon-F50 AC Drive
42
C3.07
Data
Moscon-F50 AC Drive
43
mal)
H0.02 Function of Terminal 3 - 0~29 1 X
H0.03 Function of Terminal 4 - 0~29 2 X
H0.04 Function of Terminal 5 - 0~29 3 X
H0.05 Function of Terminal 6 - 0~29 6 X
H1.01 Select Terminal Output Type - 0~3 0 X
Multi-Function
H2.01 Reserved
H2.02 Analog Input Time Constant 1ms 0~100 20 X
H2.03 Analog Input 1 Function - 0~9 0 X
H2.04 Analog Input 1 Gain 0.1% 0.0~200.0 100.0 ○
Multi-Function Analog Input
Moscon-F50 AC Drive
44
Moscon-F50 AC Drive
45
- 0~1 0 X
1V 0~250 190 X
Moscon-F50 AC Drive
46
- 0~1 0 X
- 0~1 0 X
Moscon-F50 AC Drive
47
Moscon-F50 AC Drive
48
Moscon-F50 AC Drive
49
Moscon-F50 AC Drive
50
Moscon-F50 AC Drive
51
Daily inspection
Check the system in operation if:
• the motor vibrates or makes unusual noises.
• there are any abnormal heat generation
• the ambient temperature is too high
• the output current value shown on the monitor display is higher than normal
• the cooling fan is operating normally.
Periodic inspection
Refer to the table below for the periodic inspection.
• Always turn off the power supply before the inspection. Otherwise, it may cause an
WARNING
electric shock.
• After turning off the main circuit power supply, wait for a while before maintenance or
inspection since it may remain charged. Otherwise, it may cause an electric shock.
Moscon-F50 AC Drive
52
Part replacement
Inverter is composed of many parts and these parts must function properly for normal
operation of the inverter.
To maintain normal operation of the inverter for a long period of time, it is recommended to
perform a regular inspection and replace parts.
Inspection period may vary depending on the installation environment and usage conditions.
Usage condition
WARNING
• Ambient temperature(yearly average of 30 °C)
• Load factor: 80% max.
• Operating rate: 12hrs max/day
Refer to the table below for the periodic inspection of the MOSCON-F50.
Moscon-F50 AC Drive
한국어
목차
일러두기 ..................................................................................................... 54
일반 주의 사항 .......................................................................................... 55
안전주의사항 ............................................................................................ 55
제품 도착 시 점검사항 ........................................................................... 57
명판 표기 .................................................................................................... 58
설치 .............................................................................................................. 59
외형 치수 .................................................................................................... 60
기본배선도 ................................................................................................ 63
주회로 단자 기능 ..................................................................................... 65
제어회로 단자기능 .................................................................................. 66
전선 사양 규격 .......................................................................................... 67
배선 점검 .................................................................................................... 68
스위치 설정 ............................................................................................... 69
주요사양 ..................................................................................................... 70
디지털 오퍼레이터의 모니터링 기능 ................................................ 77
시운전 ......................................................................................................... 78
U- 정수 : 모니터링 기능 .......................................................................... 81
B- 정수 : 기본환경 설정 .......................................................................... 84
F- 정수 : 주파수 제어 설정 .................................................................... 85
S- 정수 : 시스템 기능 조정 설정 정 ..................................................... 87
C- 정수 : H/W 기능 설정 ......................................................................... 89
H- 정수 : 입출력 제어 기능 설정 .......................................................... 90
P- 정수 : 보호기능 설정 .......................................................................... 93
보호기능 / 에러 설명 .............................................................................. 94
일상점검 ..................................................................................................... 98
정기적인 검사 ........................................................................................... 98
부품 교환 .................................................................................................... 99
54
일러두기
이 문서에서 설명하는 제품은 다양한 설비에 사용될 수 있습니다. 본 제품의 적용 설비가 다
양하므로 본 제품의 모든 사용자와 관리자는 사용하고자 하는 설비와 관련된 운전 및 안전상
의 제 법령 및 규정과 준수사항을 반드시 확인하고 지켜야합니다.
이 문서에 사용된 예제, 삽화, 도표, 데이터 등은 설명을 위한 예시적인 자료일 뿐입니다. 제품
이 설치 및 사용되는 구체적인 상황에 따라 많은 변수와 충족되어야 할 전제 조건들이 있습
니다. 이러한 사유로 이 문서에서 제시된 예시, 도표 및 데이터의 사용 및 이에 따른 직간접적
결과에 대해 알에스오토메이션(주)는 그 책임을 지지 않습니다.
Moscon-F50 AC Drive
55
일반 주의 사항
매뉴얼 중의 그림은 대부분 커버나 보호장치가 열린 상태에서 설명되고 있으며, 제품에 대해
상세하게 설명되어 있습니다. 설치 및 배선이 끝난 후 커버나 보호장치를 닫아주시기 바랍니
다.
안전주의사항
설치
• 전원 차단후 1분이상 지난후에 내부의 "CHARGE" 램프가 Off 상태임을 확
주의
인 후 점검을 진행하며 그렇지 않을 경우, 감전사고가 발생할 수 있습
니다.
Moscon-F50 AC Drive
56
배선
• 입력전원이 완전 차단 상태임을 확인한 후 배선 작업을 진행하여야 하
주의
며 그렇지 않을 경우, 감전사고가 발생할 수 있습니다.
• 전기공사 전문가에게 의뢰하여 배선작업을 진행하여야 합니다.
• 배선 작업 시 메인 회로와 제어회로 단자 나사를 단단히 조여 줍니다.
• 인버터 커버를 확실하게 닫은 다음 전원을 넣어야 하며, 전원 투입 중
에 커버를 여는 것을 금지합니다. 감전사고가 발생할 위험이 있습니다.
• 접지 단자를 접지합니다.(200V: 접지저항 100Ω 이하, 400V급: 접지저항
10Ω 이하) 그렇지 않을 경우, 감전사고나 화재가 발생할 위험이 있습니
다.
정수 설정
• 적절한 정수를 입력해야 합니다. 부적절한 정수 입력은 인버터 가동과
주의
작업에 영향을 미칠 수 있습니다.
• 변경한 정수는 기록하여 두십시오.( MOSCON-F50이 앞의 상수를 기록한
경우 포함) 이런 기록은 고장과 착오 발생시 빠른 처리를 가능하게 합
니다.
• 파라미터 변경은 지정된 범위(사용자 매뉴얼 F50-UM001A-KO-P 5장 참조
)에서만 가능합니다. 특히 모터, V/f 변경 혹은 최대출력 주파수 조정 시
주의를 기울여야 하며, 그렇지 않을 경우, 인버터와 모터를 파손 시킬
수 있습니다.
Moscon-F50 AC Drive
57
유지보수와 검사
• 인버터는 고압부분를 가지고 있으므로 전원 투입 중에는 감전되기 쉽
주의
습니다.
• 인버터에 전원 투입 중 커버를 열지 마십시오.
• 주회로 콘덴서에 잔류전압이 존재함으로 인버터의 주회로 전원 차단
후 일정한 시간이 경과 후 유지보수와 검사작업을 실시하여야 합니다.
• 전기공사 전문가에 위탁하여 유지보수, 검사 혹은 부품교체를 합니다.
그렇지 않을 경우, 대인사고 혹은 대물사고가 발생할 가능성이 존재합
니다.
• 유지보수, 검사 혹은 부품교체 전 소지하고 있는 금속품 이를 테면 시
계, 반지 등을 모두 제거하고 별도로 보관하십시오. 동시에 적당한 절
연공구를 사용하여 작업하여야 합니다. 그렇지 않을 경우 감전사고가
발생할 위험이 있습니다.
• 검사 전 전원을 반드시 차단하여야 하며 그렇지 않을 경우, 감전사고
발생의 위험이 있습니다.
제품 도착 시 점검사항
MOSCON-F50이 도착되면 다음 사항을 점검해 주십시오.
Moscon-F50 AC Drive
58
명판 표기
프로그램 버전 HW 버전
모델번호
MODEL : SI_20P7F50 SW: 1.0 HW:A
입력사양 Input Voltage: 3PH 200-230Vac 4.8A 50/60HZ
Output Power: 3PH 0-230Vac 1.9kVA 5.0A
출력사양 IP20/UL Open-Type MASS: 0.95 Kg
Serial number SER. NO: 2XF50X013-FB0001 IND. CONT. EQ.
61KJ
E226834
명판 표기예
인버터 형식 설명
명판 부착위치
명판
(제품의 우측면에 부착)
एँऎ࣪ऊऋࣶ࣮ࣜऔंࣱ࣬औࣱࣩ࣬࣬ࣽं࣭ࣾ࣬࣬࣬
अऌ࣮࣬ࣜअऊएऐࣽईईࣽऐअऋऊࣜࣿࣽऐँःऋऎकࣜअअࣜउࣽएएࣲࣶ࣭࣪࣬इण
ऋऱरबऱरࣜऌफळडमࣶ࣯ࣜࣜࣜࣽࣿࣜऌऄࣰࣲࣩࣜ࣬࣬ऒࣰ࣭ࣜ࣪धऒ࣭ࣽࣜ࣪ࣴࣽ
अपबऱरࣜऒफनरझणडࣶ࣯ࣜࣜࣽࣿࣜऌऄࣰࣲ࣯ࣩࣜࣴ࣬࣬ऒࣱࣲࣜ࣬࣫࣬ऄश
उऋऀँईࣶࣜࣜएअछࣰ࣬ऌࣰंࣱ࣬
FcW_kY``5ihcaUh]cb?cfYU@hX"A589=B?CF95
ऌऎःࣶ࣭࣪࣬࣬
Moscon-F50 AC Drive
59
설치
주변온도
판넬과 같이 밀폐된 환경에 설치하게 될 경우 인버터의 주위온도가 -10℃~40℃를 유
지할 수 있도록 해주십시오. 또한 과열을 방지하기 위하여 냉각 팬 혹은 에어컨을 설
치하여 내부 온도를 유지하십시오.
MODEL : SI_40P4F50
Rockwell Automation Korea Ltd. MADE IN KOREA
SER.NO: 2XF50X005A-FB0001
IP20 INSTALLATION CATEGORY II MASS:1.60Kg
Output Power : AC 3PH 0-460V 1.4kVA 1.8A
Input Voltage : AC 3PH 380-460V 50/60Hz
PRG:1.00 MODEL : SI_40P4F50
PRG:1.00
수직설치 수평설치
Moscon-F50 AC Drive
냉각 효율을 높이기 위해 반드시 수직으로 설치하고, 아래 그림과 같이 주위 공간을
(단위: mm)
MODEL : SI_40P4F50 PRG:1.00
Input Voltage : AC 3PH 380-460V 50/60Hz
Output Power : AC 3PH 0-460V 1.4kVA 1.8A
84.6
IP20 INSTALLATION CATEGORY II MASS:1.60Kg
SER.NO: 2XF50X005A-FB0001
Rockwell Automation Korea Ltd. MADE IN KOREA
3상 20P2의 외형치수
100
설치공간
100
30
76
확보해 주십시오(단위:mm).
30
Moscon-F50 AC Drive
외형 치수
설치 공간
128
60
Moscon-F50 AC Drive
61
145.4
Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA
MODEL : SI_40P4F50 PRG:1.00
InputVoltageAC: 3PH 380-460V 50/60
Hz
OutputPow er AC: 3PH 0-460V VA
1.4k
1.8A
IP20 INS
TALLATIONCATEGORY II
M ASS:1.60
Kg
SER.NO: 2XF50X005A-FB0001
145.4
Rockw ell
Automation Ko
reaLtd. M ADE IN
KOREA
150
120
128
128
128
62
기종 MOSCON-F50
외형사이즈 mm 설치사이즈
부피(㎣) 무게(㎏)
(W×H ×D) W1×H1, Φ
20P2 76 x 128 x 84.6 66 x 118, M4 822,988.8 0.6
20P4 76 x 128 x 126.4 1,229,619.2 0.9
20P7
B0P4 120×128×145.4 103×118, M4 2,233,344 1.6
B0P7
21P5
22P2
40P4
40P7
41P5
B1P5 150×128×145.4 134×118, M4 2,617,200 1.9
B2P2
23P7
42P2 2.0
43P7
Moscon-F50 AC Drive
63
기본배선도
MOSCON-F50의 기본배선도는 아래와 같습니다.
제동저항(선택사항)
배선용차단기 B1 B2
(MCCB)
R/L1 전동기
U/T1
4)
S/L2 V/T2
입력전원
4)
T/L3 W/T3
다기능 접점 입력 다기능 접점 출력 1
S1 R1
정회전운전/정지 최대 직류 30V 1A
S2 최대 교류 250V 1A
역회전운전/정지
(기본설정: 이상발생)
S3
외부 이상 RC1
이상 Reset S4
S5
다단속 지령1 R2 다기능 접점 출력 2 (옵션)
Jogging S6
최대 직류 30V 1A
SC 최대 교류 250V 1A
RC2 (기본설정: 운전중)
E
접지
2 kΩ
속도지령 설정용 전원
V+ (+12V 20mA)
2 kΩ A1 아날로그 입력 1
(0~10V 20kΩ )
AC
아날로그 Common
A2
아날로그 입력 2
(4-20mA, 0-20mA 250Ω 또는
AM 0~10V 20kΩ )
(0-32kHz Pulse:Option)
아날로그 모니터 출력
(0-10V)
(0-32kHz Pulse:Option)
기본배선도(3상 200V/400V급)
Moscon-F50 AC Drive
64
제동저항(선택사양)
배선용차단기 B1 B2
(MCCB)
R/L1 U/T1
전동기
입력전원 4)
S/L2 V/T2
4)
W/T3
E
접지
2 kΩ
속도지령 설정용 전원
V+ (+12V 20mA)
2 kΩ 아날로그 입력 1
A1
(0~10V 20kΩ )
AC
아날로그 Common
아날로그 입력 2
A2 (4-20mA, 0-20mA 250Ω 또는
0~10V 20kΩ )
AM (0-32kHz Pulse:Option)
아날로그 모니터 출력
(0-10V)
(0-32kHz Pulse:Option)
기본배선도(단상 200V급)
주: 1) 는 실드선 는 트위스트 페어 실드선입니다.
p
Moscon-F50 AC Drive
65
주회로 단자 기능
용 도 단 자 부 호
제동 저항 접속 B1, B2
접지
용 도 단 자 부 호
제동 저항 접속 B1, B2
접지
Moscon-F50 AC Drive
66
제어회로 단자기능
단자 단 자 기 능 신호레벨 초기 설정값
S1 정회전 운전/정지 지령 포토 커플러 입력 -
+24V, 10mA
S2 역회전 운전/정지 지령 -
S3 다기능 입력 1 외부이상
S4 다기능 입력 2 이상 Reset
S5 다기능 입력 3 다단속 1지령
S6 다기능 입력 4 조깅(Jogging) 지령
SC 시퀀스 제어 입력 +24V Ground 시퀀스 0V
Common
V+ 속도지령 설정용 전원 +12V(Max 20mA) -
Moscon-F50 AC Drive
67
전선 사양 규격
주회로의 전선 사이즈를 결정할 때 '선 전압강하'는 정격 전압의 2% 이내에
들도록 전선을 선택 하여야 합니다. '선전압강하'의 계산방법은 다음과 같습니다.
전선 Size(1)
터미널 단자대 전선의
회로 모델 토크(Nm) 압착단자 종류
나사 2 AWG
mm
Moscon-F50 AC Drive
68
배선 점검
배선작업이 완료되면 다음 사항을 확인해 주십시오.
경고
단, 제어회로의 부져 점검은 하지 마십시오.
전원 입력 노이즈 필터
모델 노이즈 필터 제조사
20P2, 20P4, 20P7 C3B2005-AR OKY
21P5, 22P2 C3B2010-AR
23P7 C3B2020-DR
40P4, 40P7, 41P5 C3B4005-AR
42P2, 43P7 C3B4010-AR
B0P4, B0P7 대리점에 문의하십시오.
B1P5, B2P2
Moscon-F50 AC Drive
69
스위치 설정
SW1
Monitor
Select ON
SW3 1 2 3 4 5 6
SRC/SNK
Select
SW2
AI Type
Select
기능 스위치 DIP SW 번호
구분
1 2 3 4 5 6
AO Enable SW1 ON OFF ON OFF N/A N/A
PO Enable (옵션) OFF ON OFF ON N/A N/A
종단 저항 - - - - ON -
Moscon-F50 AC Drive
70
주요사양
3상 20P2 20P4 20P7 21P5 22P2 23P7
200-230V급
단상 - B0P4 B0P7 B1P5 B2P2 -
외함 및 중량 Frame size A B C
(3상) 제품 본체[kg] 0.6 0.9 1.6 2
외함 및 중량 Frame size B C
(단상) 제품 본체[kg] 1.6 1.9
Moscon-F50 AC Drive
71
외함 및 중량 Frame size B C
제품 본체[kg] 1.7 2
Moscon-F50 AC Drive
72
공통
H/W구성 직류 리액터 적용 불가 (교류 리액터 사용)
EMC 필터 별치 (선택)
주파수 출력 정도 0.01Hz
적용 대상
가감속 시간 범위 0~600.00초, 0.01초 간격 (독립설정 가능한 2개 가감
인버터의
제어 & 성능 속 시간 set 구비)
속도제어 범위 100:1
속도 응답성 5 Hz
Moscon-F50 AC Drive
73
입출력 단자
보호기능 H/W 보호/검출 기능 인버터 과부하 (OL2), 전동기 과부하 (OL1), 부족전
압 (UV1), 과전압 (OV), 과전류 (OC), 전류제한
(CLB,CLA), 과 토오크 (OL3),과열방지(OH), 입력 전원
결상(IPL:3상 제품만)
Moscon-F50 AC Drive
74
정지 방법 2개 종류 (감속, 프리런)
내부 설정 속도지령 (다 9단
단속지령)
회전 중 재시동 가능
전원투입시 자동 기동 가능
DC 전류인가 제동 기능 시동 및 정지시
출력전압 보정 자동
외함 형식 IP20/ UL Open-Type
설치 고도 제한 1000m 이하
Moscon-F50 AC Drive
75
20P2 30A 5A 5A 6A
20P4 30A 5A 10A 6A
B0P4, 20P7 30A 10A 10A 10A
B0P7, 21P5 30A 20A 20A 15A
B1P5, 22P2 30A 20A 20A 25A
B2P2, 23P7 30A 30A 20A 30A
40P4 30A 5A 10A 6A
40P7 30A 5A 10A 6A
41P5 30A 10A 10A 10A
42P2 30A 10A 10A 15A
43P7 30A 20A 10A 20A
(1)
차단기: inverse time 또는 instantaneous trip
(2)
휴즈
일반적으로 다음을 포함하지만 제한되지 않을수도 있습니다. Parts 1 & 2: AC, AD, BC, BD, CD,
일반적으로 다음을 포함한다. Type CC - KTK-R, FNQ-R, Type J - JKS, LPJ, Type T - JJS, JJN
Moscon-F50 AC Drive
76
Digital Volume(1)
- 주파수설정모드
RUN key : · 주파수 지령변경
Operator 조작모드에서 - 정수설정모드
모터 기동 · 시계방향:증가
· 반시계방향:감소
- 정수그룹간 이동
STOP key :
모터 정지
RESET key :
이상 상태 해제
DATA key :
Decrement/Down key : 정수내용 표시
- 정수 번호 및 값 감소
- 정수 그룹간 이동 SET key :
- 표시된 값으로 정수변경 설정
SHIFT keys : - 정수변경후 정수번호 표시
- 변경할 Digit 선택
- U0.01의 값을 보고 있을때
지령 주파수 수정모드로 이동
(B0.01= 0 또는 1일 경우만)
(1)
표시된 정수나 데이터는 디지털 볼륨으로 변경할 수 있습니다.
Moscon-F50 AC Drive
77
지령주파수
Ά͑͟͢͡͡
Άͧ͟͡͡ ͑ 출력
͑
Άͤ͟͢͡ I/O 상태 ͑
͑
Άͨ͟͡͡
추정 모터 속도[RPM] Άͣ͟͢͡ ͑ PID 출력[%] ͑
Άͪ͟͡͡
͑
PID 목표치[%] ͑
디지털 오퍼레이터의 모니터링 기능
Moscon-F50 AC Drive
78
시운전
전원 ON Shift 키 한번 누르면
(B0.01= 0 또는 1일때만)
주파수 수정모드로 들어갑니다.
소숫점 깜박임(B0.01=0)
자리수 깜박임(B0.01=1)
FWD
REV
값 증가 시
운전주파수 설정
디지털 볼륨을
시계방향으로 회전
FWD
REV
운전 RUN 키를 누름
FWD
REV
정지 STOP 키를 누름
FWD
REV
정수 번호로 이동
DATA/SET 키를 누름
FWD
REV
다른 정수그룹으로 이동 시계방향으로 2
클릭 돌림
FWD
REV
변경할 Digit로 이동
Shift 키를 누름
FWD
REV
시계방향으로 2
정수 소그룹 증가 클릭 돌림
FWD
REV
DATA/SET 키를 누름
정수 수정 (DATA MODE으로 전환)
FWD
REV
Moscon-F50 AC Drive
79
Shift 키를 누름
Digit 변경
FWD
REV 값 감소시
디지털 볼륨을
숫자 감소 반 시계방향으로 회전
FWD
REV
DATA/SET 키를 누름
표시된 정수 저장 (현재 F2.01=3.00)
FWD
REV
DATA/SET 키를 누름
다음 Level로 이동 (Data 모드로부터 이탈)
FWD
REV
Digit 변경 Shift 키를 2번 누름
FWD
REV
다른 정수그룹으로 반시계방향으로 2
이동 클릭 돌림
FWD
REV
DATA/SET 키를 누름
정수 수정 (U.0.01의 내용 확인)
FWD
REV
UP 키를 누름
U0.02로 이동 (출력주파수 표시)
FWD
REV
시계방향으로 2
U0.04로 이동 클릭 돌림
FWD
REV
Moscon-F50 AC Drive
80
그룹변경 소그룹변경
F(주파수) - 정수그룹
ஔ|SGiSGmSGzSGjSGoSGw
C(제어) - 정수그룹
H(I/O) - 정수그룹
정수번호 변경
XY - 01 정수
G
P(보호) - 정수그룹
XY - 02 정수
G
데이터 변경모드
xxx.x
(정수내용)
XY - n 정수
Y : 0, 1, 2 ~ 최대값
G 수치 변경
* UP/Down Key로
* Shift Key로 숫자 위치 변경
정수설정 방법
Moscon-F50 AC Drive
81
U-정수: 모니터링 기능
정수 표시
번호 명칭 내용 단위 형태
인버터 U0.01 주속지령주파수 현재 유효한 0.01㎐ xx.xx
운전상태 주속 주파수 지령값 ∼xxx.x
Moscon-F50 AC Drive
82
정수 표시
번호 명칭 내용 단위 형태
최종이상 U1.01 주속지령주파수 최종 이상 발생시의 0.01Hz xx.xx
발생시 주속 주파수 지령값 ∼xxx.x
운전 상태 U1.02 출력주파수 최종 이상 발생시의 0.01Hz xx.xx
출력 주파수 ∼xxx.x
Moscon-F50 AC Drive
83
정수 표시
번호 명칭 내용 단위 형태
시스템 U2.01 이상발생 이력 1 (최근) 가장 최근에 발생한 이상 내용 - *
보호 기능 U2.02 이상발생 이력 2 1회 전에 발생한 이상 내용 - *
Moscon-F50 AC Drive
84
B-정수: 기본환경 설정
정수 출하 시 운전 중 사용자
명칭 단위 설정 범위
번호 설정 변경 여부 설정값
기본설정 B0.01 주파수 지령 선택 - 0~4 0 X
B0.13 통신 쓰기 모드 - 0~1 0 X
B2.04 추후 사용(Reserved)
Moscon-F50 AC Drive
85
F-정수: 주파수 제어 설정
Moscon-F50 AC Drive
86
F2.06 추후 사용(Reserved)
S-curve F3.01 S-Curve 시간 0.01sec 0.00 0.20 ○
가감속 ~2.50
시간
패턴 F4.01 패턴 운전 시간 1 0.1 sec 0.0 - 999.9 0.00 ○
운전 모드 및 F4.02 패턴 운전 시간 2 0.1 sec 0.0 - 999.0 0.00 ○
시간(1)
F4.03 패턴 운전 시간 3 0.1 sec 0.0 - 999.9 0.00 ○
F4.04 패턴 운전 시간 4 0.1 sec 0.0 - 999.0 0.00 ○
F4.05 패턴 운전 시간 5 0.1 sec 0.0 - 999.9 0.00 ○
F4.06 패턴 운전 시간 6 0.1 sec 0.0 - 999.0 0.00 ○
F4.07 패턴 운전 시간 7 0.1 sec 0.0 - 999.9 0.00 ○
F4.08 패턴 운전 시간 8 0.1 sec 0.0 - 999.0 0.00 ○
F4.09 패턴 운전 모드 1 - 0 - 113 0 X
F4.10 패턴 운전 모드 2 - 0 - 113 0 X
F4.11 패턴 운전 모드 3 - 0 - 113 0 X
F4.12 패턴 운전 모드 4 - 0 - 113 0 X
F4.13 패턴 운전 모드 5 - 0 - 113 0 X
F4.14 패턴 운전 모드 6 - 0 - 113 0 X
F4.15 패턴 운전 모드 7 - 0 - 113 0 X
F4.16 패턴 운전 모드 8 - 0 - 113 0 X
Moscon-F50 AC Drive
87
S-정수: 시스템 기능 조정 설정 정
S0.02 직류 제동 전류 1% 0~100 50 X
Moscon-F50 AC Drive
88
Moscon-F50 AC Drive
89
C-정수: H/W 기능 설정
C2.08 오토 튜닝 모드 실행 - 0~2 0 X
H/W 조정 C3.01~C3.07 공장 설정 정수
관련 임의 수정시 오동작
데이터 발생
Moscon-F50 AC Drive
90
H-정수: 입출력 제어 기능 설정
Moscon-F50 AC Drive
91
Moscon-F50 AC Drive
92
H4.07 팬 운전 모드 - 0~1 1 X
(1)
Ver. 2.0 부터 가능
Moscon-F50 AC Drive
93
P-정수: 보호기능 설정
정수 출하 시 운전중 사용자
설정 범위
번호 명칭 단위
설정 변경여부 설정값
모터 과부하 P0.01 모터 보호 선택 - 0~1 1 X
보호 P0.02 모터보호 시 정수 - 0.0~60.0 1.0 X
P0.03 모터 선택 - 0~1 0 X
순시 정전 P1.01 정전 시 운전 - 0~2 0 X
결상 보호 P6.01 입력 결상 보호 - 0~1 0 X
Moscon-F50 AC Drive
94
보호기능/에러 설명
기동 및 운전시 정수 설정 및 배선 등의 잘못으로 인버터와 모터가 원하는 명령대로
작동하지 않을 수 있습니다.
MOSCON-F50은 많은 보호기능을 갖고 있으며, 이상 발생시 디지털 오퍼레이터상
에 표시됩니다.
에러 표시 및 설명
항목 지시내용 원 인 조 치
OC2 인버터의 출력 인버터 출력측에서 단락이나 접지이 원인조사, 조치후 리셋
단락 에러 또는 부하측 상 발생(단락이나 접지사고는 모터 트 실시
단락 가 타서 손상을 입었거나 절연이 약
화 되었거나 케이블이 손상되었을
때 발생할 수 있습니다.)
OC1 인버터의 출력 • 인버터 출력에 단락이나 접지 이 원인조사, 조치후 리셋
과전류 전류가 상 발생(단락이나 접지 이상은 모 트 실시
순시 정격 전류 터가 타서 손상을 입거나 절연 약
의 200% 초과 화, 케이블이 손상되었을 때 발생)
• 부하가 너무 크거나 가속/감속 시
간이 너무 짧습니다.
• 특수 모터나 인버터에 비해 너무
큰 용량을 가진 모터가 사용됩니
다.
• 인버터 출력에서 마그네틱 스위
치가 전환됩니다.
OH2 인버터 방열 핀 주위환경온도가 지나치게 높습니다. 냉각장치 설치
인버터 온도 약 95℃ 초
과열 인버터 근처에 발열체가 있습니다. 발열체 제거
과
인버터 냉각팬 고장이 생겼습니다. 냉각팬 교체
(서비스센터에 문의)
Moscon-F50 AC Drive
95
에러 표시 및 설명
항목 지시내용 원 인 조 치
OV 주회로 DC전압 • 감속시간이 너무 짧습니다. 감속시간을 길게 하거
주회로 이 과전압 감지 • 모터로부터 회생 에너지가 너무 나 제동저항기(또는
과전압 레벨을 초과 큽니다. unit)를 연결
200V급:410V
전원전압이 너무 높습니다. 전압을 전원사양 범위
400V급:820V
내로 낮춘다.
UV1 주회로 DC 전압 • 입력전원의 결상 발생입니다. 원인조사, 조치후 리셋
주회로 이 저전압 감지 • 순시정전이 발생됐습니다. 트 실시
저전압 레벨
• 입력전원의 전압변동이 큽니다.
이하
200V급: 190V
400V급: 380V
OL3 모터 토크전류 부하과중 또는 급속한 가속입니다. P3.02와P3.03를 적절하
과토크 가 설정 레벨을 게 설정
검출 초과 기계상태 점검과
모터 정격 토크 과토오크 원인을 조치
전류 100% 기준
OL2 인버터 정격에 부하가 너무 큽니다. 가속시간 감속 부하의 크기를 점검하
인버터 비해 150%의 시간 그리고 사이클 시간이 너무 고 가속, 감속 및 사이
과부하 출력전류가 짧습니다. 클시간의 길이를 점검
1분이상 지속 합니다.
Moscon-F50 AC Drive
96
에러 표시 및 설명
항목 지시내용 원 인 조 치
CB2 입력 정수의 상하한값 범위내 입력
정수 범위 상하한 값 초과
초과
CB1 설정입력된 정 서비스센터에 문의
EEPROM 수 확인중 에러
이상
EF4 외부입력 이상 외부이상이 다기능 입력단자로부터 • 다기능 입력의 적절
외부이상 (터미널 4) 입력되었습니다. 한 선택여부 점검
(터미널4) • 외부이상원인 제거
EF3 외부입력 이상
외부이상 (터미널 3)
(터미널3)
EF2 외부입력 이상
외부이상 (터미널 2)
(터미널2)
EF1 외부입력 이상
외부이상 (터미널 1)
(터미널1)
CB0 전원투입시 설 EEPROM에 저장된 사용자 정수의 서비스센터에 문의
정수이상 정 정수의 전원 투입은 기검사시 이상이 검출
에러발생 되었습니다.(U3.02에서 검출된 정수
의 번호확인가능, 최대32개)
IPL 입력 전원 결상 • 입력전원 결상으로 DC Bus 리플이 • 입력 배선, 전압 점
입력 결상 커질경우 검출을 합니다. (3상 모 검
델만) • 삼상 언벨런스, 콘
• 부하가 작을 경우 검출이 않됨 덴서 열화된 경우
검출할수 있음
Moscon-F50 AC Drive
97
항목 지시내용 원 인 조 치
Moscon-F50 AC Drive
98
일상점검
다음은 시스템 운전 중에 검사합니다.
정기적인 검사
• 정기점검에 대해 다음의 표를 참조하십시오.
항목 검사 조치
단자, 취부볼 모든 부품의 연결 부분과 느슨하게 된 연결부품을 다시 조립하고 볼트
트,커넥터등 볼트가 적절하게 체결되어 를 단단하게 조입니다.
있습니까?
Moscon-F50 AC Drive
99
부품 교환
인버터는 여러 개의 부품으로 구성되어 있고 이들 부품들이 적절한 기능을 발휘하
여야 인버터의 정상운전이 가능합니다.
사용조건
경고
• 주변온도: 연평균 30℃
• 부 하 율: 최대 80%
• 운 전 율: 1일 최대 12시간
부품 표준 교환주기 교환 방법
냉각 팬 2~5 년 새 부품으로 교환
휴즈 10년 새 부품으로 교환
Moscon-F50 AC Drive
Publication: MosconF50-IN002A-F50-EK - November 2010