Professional Documents
Culture Documents
Building Wire - Low Voltage Cable
Building Wire - Low Voltage Cable
Building Wire - Low Voltage Cable
PART 1 GENERAL
A. Building wire and low voltage cable. Wires and cables specified in this section shall
apply to all sections of these specifications.
1.03 REFERENCES
1.04 SUBMITTALS
B. Furnish products listed and classified by testing firm acceptable to authority having
jurisdiction as suitable for purpose specified and shown.
B. Submit two lengths, each 500 mm of cable assembly from each reel.
D. Where wire and cable routing is not shown, and destination only is indicated,
determine exact routing and lengths required.
1.09 COORDINATION
PART 2 PRODUCTS
B. Conductor: Copper
E. Where voltage connections are less than 100 volts, the wires or cables may be
insulated for 300 volts.
PART 3 EXECUTION
3.01 EXAMINATION
3.02 PREPARATION
3.03 INSTALLATION
B. All the wires shall be stranded. No solid conductor shall be used even if it is less than
10 AWG ( 6 mm2.)
D. Use 6mm2 (10 AWG) conductors for 20 ampere, 220 volt branch circuits longer than
61 m. For power and control minimum cable/wire size shall not be less than 4 mm².
G. Neatly train and lace wiring inside boxes, equipment, and panelboards.
J. Use split bolt connectors for copper conductor splices and taps, 6 AWG and larger.
Tape uninsulated conductors and connector with electrical tape to 150 percent of
insulation rating of conductor.
K. Use solderless pressure connectors with insulating covers for copper conductor
splices and taps, 8 AWG and smaller.
L. Use insulated spring wire connectors with plastic caps for copper conductor splices
and taps, 10 AWG and smaller.
B. Identify each conductor with its circuit number or other designation indicated on
Drawings.
C. Telephone or signal wires are included. The wiring for electric lighting, including
outlets for extension, clocks and fans, for electric power shall be furnished and
installed complete from point of service connections to all outlets indicated on
drawings.
D. Ample leads shall be provided for motor loops and service connection. Feeders shall
be of the sizes indicated on the drawings.
B. Inspect wire and cable for physical damage and proper connection.
END OF SECTION