Professional Documents
Culture Documents
De-Rate Pages
De-Rate Pages
HOME
De-Rate for differing ambient conditions
D909 / D910 / FL1011F / FM1011F / FL2011F / FM2011F / FL912
Above 30°C & 100m, de-rate will apply as per Chart A
BF6L913C
Above 30°C & 100m, de-rate will apply as per Chart C
BF4/6M1012/2012/C-1013E/EC
Please refer to Chart D
BF6M1015
Air temperature = 6.5% per 10°C above 30°C
Altitude above sea level = 0.9% per 100m above 100m
BF6/8M1015C/C2*/G2
Air temperature = 4.0% per 10°C above 30°C
Altitude above sea level = 0.9% per 100m above 100m
BF6/8M 1015CP
Air temperature = 4.0% per 10°C above 40°C
Altitude above sea level = 0.9% per 100m above 1000m
For air on fan temperatures above 45°C on all genset engines please refer to DEUTZ UK.
*BF6/8M1015C2 engines only available with NT cooling packs. For air on fan temperatures above 40°C
Please refer to DEUTZ UK.
** TBD 620 engines have air to water charge coolers, temperature refers to the charge air coolant temperature,
the differential between this and air onto fan is dependent on the cooling pack design. For Covrad coolers it is
o o
15 C. Therefore at 40 C air temperature onto fan the anticipated charge air coolant temp with Covrad cooling
o
pack would be 55 C. If clarification required Consult DEUTZ UK.
o
TBD 616/620 Engines are available with different cooling packs, standard pack for air on rad of 40 C,
Please refer to DEUTZ UK above this temperature.
14/01/04
DEUTZ.GenMotor.
HOME
DE-RATING BASED ON AMBIENT CONDITIONS
Naturally-Aspirated Genmotor Engines Stationary - FL/M1011F-FL/M2011F-FL912 - CHART A
1.00
o
0 C
o
0.90 10 C
o
20 C
0.80
Correction Factor
o
30 C
0.70
40oC
0.60 50oC
0.50
0.40
0 500 1000 1500 2000 2500 3000 3500 4000
Altitude (m)
1.00
0oC
0.90
10oC
0.80 20oC
Correction Factor
30oC
0.70
40oC
0.60 50oC
0.50
0.40
0 500 1000 1500 2000 2500 3000 3500 4000
Altitude (m)
14/01/04
DEUTZ.GenMotor.
HOME
DE-RATING BASED ON AMBIENT CONDITIONS
Turbocharged Engines with Charge Air Cooler Genmotor Engines Stationary - BF6L913C - CHART C
1.00
o
0 C
0.90 o
10 C
o
20 C
0.80
Correction Factor
0 o
30 C
o
0.70 40 C
o
50 C
0.60
0.50
0.40
0 500 1000 1500 2000 2500 3000 3500 4000
Altitude (m)
External cooling system with DEUTZ radiator - Cooling system layout for 45oC ambient temperature and 500m above sea level -
GenMotor Engines
Temperature (oC)
Altitude 0 5 10 15 20 25 30 35 40 45 50 55 60
(m)
1000 1 1 1 0.98 0.95 0.91 0.88 0.85 0.83 0.80 0.77 0.75 0.71
1500 1 1 0.97 0.93 0.90 0.87 0.84 0.81 0.79 0.76 0.73 0.71 0.68
2000 1 0.96 0.92 0.89 0.86 0.83 0.80 0.77 0.74 0.72 0.70 0.67 0.65
2500 0.94 0.90 0.87 0.84 0.81 0.78 0.75 0.73 0.70 0.68 0.66 0.63 0.61
3000 0.89 0.85 0.82 0.79 0.76 0.73 0.71 0.68 0.66 0.64 0.62 0.59 0.57
3500 0.83 0.80 0.77 0.74 0.71 0.69 0.66 0.64 0.62 0.59 0.57 0.55 0.53
4000 0.77 0.74 0.72 0.69 0.66 0.64 0.62 0.59 0.57 0.55 0.53 0.51 0.49
4500 0.72 0.69 0.66 0.64 0.61 0.59 0.57 0.55 0.53 0.51 0.49 0.47 0.45
5000 0.66 0.63 0.61 0.58 0.56 0.54 0.52 0.50 0.48 0.46 0.44 0.43 0.41
14/01/04