Culture Documents
Reply To Comments 2
Reply To Comments 2
Reply To Comments 2
Consultant: Worley
Project: Construction of 24 SF at JDH
2 Selections shall comply to operating temperature and Ambient temperature of proposed lighting
relative humidity ranges in project specifications. Refer to fixtures for indoor Ta=40°C, street light
Division 26, SECTION 260500, clause 1.7. (Lights SN 2, 4, 5, Ta=55°C. Refer to attached index.
6, and 7)
3 Include all missing fixtures found in shop drawings such as Missing items updated and added. Please find
office and toilet selections. attached datasheets.
4 Provide cut-out dimensions for recessed lights. Toilet and Updated product description for recessed
office lights shall be IP44 and low glare. downlight with the required information.
Alternate item proposed with low glare as
below:
Toilet: RAY- C CONO-DL REC- 170- IP44
Office: RAY-DAY-DL-SUR-40W-MAS, IP44
5 Provide warranty for emergency lights and their batteries We provide 3 year warranty for emergency
as per project specifications. lights after delivery and 2 years warranty
from Contractor.
6 Pump station lights shall be IP 66, low glare, 4000K. Alternate item proposed with IP66.
RAY-DAMP LED ADV-SUR -1200MM-IP66-40W
Please see attached datasheet
7 Street light and pole shall withstand wind speed of 160 Comply - CRI>80 not applicable for Street Lights
km/hr minimum and shall have CRI>80
8 Provide samples for all selections for final approval and Noted
prior to release for manufacturing.
9 Minimum lumens for toilet lights shall be 2000lm. Comply as per BOQ specs
10 Provide seismic qualification certificate samples Applicable for Street Light only.See attached Test