Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SPECIFICATION :

1. ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH


THESE PLANS AND SPECIFICATIONS, THE APPLICABLE PROVISIONS OF THE LATEST
EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE RULES AND REGULATIONS OF THE
LOCAL ENFORCING AUTHORITY, AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY.
LEGEND : 2.
3.

THE ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY


LICENSED PROFESSIONAL OR REGISTERED ELECTRICAL ENGINEER.
THE ELECTRICAL SERVICE VOLTAGE SHALL BE SINGLE PHASE, 2 WIRE, 60HZ,
BUILDING DISTRIBUTION VOLTAGE SHALL BE SINGLE PHASE, 2-WIRE, 220V, 60HZ
MOUNTED TRANSFORMER, SUBSTATION TYPE.
CIRCUIT BREAKER 4. WIRING SYSTEM INSTALLATION SHALL BE DONE IN POLYVINYL CHLORIDE(uPVC) CONDUIT,
SCHEDULE 40, MINIMUM SIZE FOR uPVC SHALL BE 20mm DIAMETER ELECTRICAL TRADE
SIZE, ATLANTA BRAND SHALL BE USED, WHERE IN CONDUIT MAY BE SUBJECT MECHANICAL
M
KWHRMETER DAMAGE, INTERMEDIATE METAL CONDUIT (IMC) SHALL BE USED, MATSUSHITA OR MC GILL
BRAND.
18 watts PL LAMP 5. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THHN / THWN" UNLESS
OTHERWISE INDICATED. THE MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 3.5mm,
32 watts CIRCULAR LAMP CONTROL WIRES SHALL BE AS INDICATED OR AS SPECIFIED ELSEWHERE ON PLANS.
PHELPS DODGE, OR DURAFLEX BRAND SHALL BE USED.
2 GANG CONVENIENCE OUTLET 6. THE CONTRACTOR SHALL VERIFY AND ORIENT ACTUAL LOCATION OF SERVICE ENTRANCE
REF
REFRIGERATOR OUTLET CONNECTION TO THE POWER SUPPLY, AND AUXILIARY SYSTEM ENTRANCE FOR CONNECTION
TO LOCAL UTILITY COMPANIES.
R
GAS RANGE OUTLET 7. ALL PIPES SLEEVES SHALL BE PROVIDED WITH PROPER SUPPORT OR ANCHORAGE NECESSARY
FOR PERMANENT CONNECTION WITH CONCRETE WALLING OR BEAM.
WP
WATER PROOF CONV. OUTLET 8. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANELBOARDS, LIGHTING FIXTURES AND ALL
NON-CURRENT CARRYING METAL PARTS SHALL BE PROPERLY GROUNDED IN ACCORDANCE
CT
COUNTER TOP CONV. OUTLET WITH THE PHILIPPINE ELECTRICAL CODE.
PANELBOARD 9. ALL 20-AMPERE CIRCUIT HOMERUNS TO PANELBOARDS OF MORE THAN 30 METERS IN
LENGTH SHALL BE 5.5mm.
CIRCUIT HOMERUN 10. ANY DISCREPANCY IN LOCATION AND RATINGS OF EQUIPMENT AND APPARATUS SHALL BE
VERIFIED WITH THE OWNER/ENGINEER OR ANY OF HIS REPRESENTATIVE SO CHANGES
SHALL BE MADE ACCORDINGLY.
SPECIFICATION : 11. ALL MATERIALS TO BE USED AND EQUIPMENT TO BE INSTALLED SHALL BE BRAND NEW
AND MUST BE OF THE APPROVED TYPE FOR THE PARTICULAR LOCATION AND PURPOSE
INTENDED UNLESS OTHERWISE INDICATED.
THESE DRAWINGS DULY STAMPED OR
SEALED, AS INSTRUMENTS OF SERVICE,
GL COLASITO ARE THE PROPERTY OF GENEVEVE
ARCHITECTURE AND DESIGN COLASITO. UNDER REPUBLIC ACT 9266,
IT IS UNLAWFULL FOR ANY PERSONS
TO MAKE COPIES OF THIS DRAWINGS
FOR USE IN THE REPETITION OF AND
OTHER PROJECTS WITHOUT THE WRITTEN
CONSENT OF GENEVEVE COLASITO.

You might also like