GENERAL: CONCRETE SLAB: L

1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED MODIFY TYPICAL DETAILS 1. ALL REINFORCEMENT SHALL BE .019M CLEAR MINIMUM FROM TOP AND BOTTOM OF SLAB.
AS DIRECTED TO MEET SPECIAL CONDITIONS. 2. FOR TWO-WAY SLAB ALONG THE LONGER SPAN SHALL BE PLACED BELOW BARS NEAR THE SUPPORT UNLESS OTHERWISE INDICATED OR
2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS. MISCELLANEOUS IRON, PRE-CAST CONCRETE, DETAILING
SHOWN IN DETAILS THE SPACING OF THE BARS AT THE COLUMN STRIPS CAN BE APPROXIMATELY 131 OF THE MIDDLE STRIP IN NO CASE HOOK (A OR G)
ETC. SHALL BE SUBMITTED FOR ENGINEER'S APPROVAL PRIOR TO PURCHASE, FABRICATION AND INSTALLATION. DIMENSION
GREATER THAN 231 TIMES THE SLAB THICKNESS.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN. CHECK WITH SANITARY, MECHANICAL AND ELECTRICAL 3. UNLESS OTHERWISE DETAILED IN CONDITIONING SLAB HAVING SAME REINFORCEMENT RUNNING IN ONE DIRECTION, REINFORCING SHALL

EMBEDMENT
CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC., TO BE EMBEDDED IN CONCRETE.

d
BEND, EXTENDED OR CUT AS FOLLOWS:
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING AND BRACING OF THE STRUCTURE FOR ALL LOADS 4. TEMPERATURE BARS FOR SLAB SHAL BE GENERALLY PLACED NEAR THE TENSION FACE AND SHALL NOT BE LESS THAN 0.025 BT. DEPTH
THAT MAYBE IMPOSED DURING CONSTRUCTION.

J
5. UNLESS OTHERWISE NOTED, ALL BEDDED SLAB BE REINFORCED WITH 10mmØ BAR AT .25M O.C. B.W. AT CENTER OF SLAB. CONSTRUCTION D

WIDTH
JOINT FOR SLAB SHALL NOT BE MORE THAN 3.00M APART.
FOOTING:

W
L1/4
6. PROVIDE EXTRA REINFORCEMENT L1/4
AT CORNERL2/4 L2/4 DISCONTINOUS
SLAB (TWO ADJACENT L3/4 L3/4
EDGE) AS SHOWN BELOW.
1. FOOTINGS WERE DESIGNED TO REST ON SOIL WITH AN ASSUMED BEARING CAPACITY OF 5000psf. 4d OR 65 MM MIN

0.30MIN

DEPTH
2. NO FOOTING SHALL REST ON FILL.
180 DEG

t
3. MINIMUM CONCRETE PROTECTION SHALL BE .075M CLEAR FOR CONCRETE DEPOSITED AGAINST THE GROUND AND 0.05M FOR
CONCRETE DEPOSITED AGAINST THE FRAMEWORK.
DETAILING
DIMENSION
CONCRETE MIXES AND PLACINGS:
1. UNLESS OTHERWISE SPECIFIED, THE MINIMUM 28 DAYS CYLINDER COMPRESSIVE STRENGHT OF CONCRETE ARE AS FOLLOWS: L1/5 L1/5 L2/5 L2/5 L3/5 L3/5
L1 SPAN
EXTERIOR L2 SPAN
INTERIOR L3 SPAN
INTERIOR .
CANTILEVER

A OR G
LOCATION STREGHT AGGREGATE SIZE MAX. SLUMP

TYPICAL COLUMN FOOTING DETAIL


D

FOUNDATION, PILE CAP 3000 psi 3 4 IN (100mm)

12d
4 IN (19mm) REINFORCING STEEL BARS 2
BEAMS, GIRDERS 3000 psi 3
4 IN (19mm) 4 IN (100mm) S-01 Scale: 1:30
1. ALL REINFORCING STEEL SHALL BE NEW BILLET, HOT ROLLED, WELDABLE, DEFORMED BARS CONFORMING
COLUMN, STAIR 3000 psi 3
4 IN (19mm) 4 IN (100mm) TO THE SPECIFICATIONS OF PNS 49; 1986 (ASTM 615), Fy= 60,000 psi (413.79 Mpa) FOR SIZES >12 AND Fy =
SUSPENDED SLAB 3000 psi 3 4 IN (100mm) 40,000 psi (275.86 Mpa) FOR SIZES ≤12. CL
4 IN (19mm)
2. ALL CONCRETE REINFORCEMENT SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED, AND SPACED 90 DEG C
L
VERIFY
SHEARWALL/RET. WALL 3000 psi 3
4 IN (19mm) 4 IN (100mm) IN FORMS, SECURED IN THE REQUIRED LOCATION IN ACCORDANCE WITH THE PROCEDURES AND CL
REQUIREMENTS OUTLINED IN THE LATEST EDITION OF THE BUILDING CODE AND THE MANUAL OF STANDARD STANDARD HOOKS
SLAB ON GRADE 2500 psi 3
4 IN (19mm) 4 IN (100mm) PRACTICE FOR DETAILED REINFORCED CONCRETE STRUCTURES. RC WALL
3. ALL REINFORCING STEEL BARS SHALL BE THOUROUGHLY CLEANED OF ALL LOOSE RUST, SOIL OR OTHER
2. ALL CONCRETE MUST BE DEPOSITED, VIBRATED AND CURED ACCORDING TO THE ACI STANDARDS. CORROSIVE MATERIAL IMMEDIATELY PRIOR TO PLACING OF CONCRETE. CHB WALL INTERIOR CHB

3. STRIPPING OF FORMS AND SHORES SHALL BE AS FOLLOWS: 12d FOR 25 MM


6d FOR 10, 12, 16 MM
DEVELOPMENT LENGTH, (Ld), IN TENSION FOR RC BEAMS LENGTH OF LAP COMPRESSION SPLICES (mm) 10Ø TRANSVERSE

A OR G
FOUNDATION 1 DAY

HOOK
U-BARS @ 300 O.C.
AND GIRDERS (PRISMATIC OR NON-PRISMATIC) BAR SIZE fc'=21MPa fc'=28MPa fc'=34.5MPa
BEAMS, GIRDERS 21 DAYS
TENSION LENGTH
fc'=21MPa (3000psi) fc'=28MPa (4000psi) fc'=34.5MPa(5000psi) (mm) (3000psi) (4000psi) (5000psi)
COLUMN & WALLS 3 DAYS BAR SIZE
TOP BARS BOT BARS TOP BARS BOT BARS TOP BARS BOT BARS

100
SUSPENDED SLAB 17 DAYS (mm) 16Ø 420 390 360

DETAILING DIMENSION

600 (MINIMUM)
(mm) (mm) (mm) (mm) (mm) (mm) REFER TO DWG. NO. S-01 10Ø TRANSVERSE BARS
D

FOR NOTES ON PREPARATION @ 300 O.C.


SHEARWALL/RET. WALL 3 DAYS 20Ø 540 510 450 OF SOIL SUB-BASE.

100
16Ø 730 560 630 480 560 430
25Ø 720 600 540
RC STAIRS 17 DAYS

200
3-10Ø LONGITUDINAL BARS REFER TO DWG. NO. S-01
20Ø 1090 840 940 730 840 650 TIE BEAM
(CONT.) WITH TENSION SPLICE FOR NOTES ON PREPARATION
28Ø 810 720 690 J OF SOIL SUB-BASE.
25Ø 1820 1400 1570 1210 1410 1080 100 500 100 300
4. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, RE-HANDLING, OR 4. 32Ø 900 780 720 REFER TO DWG. NO. S-01
FLOWING. PLACING OF CONCRETE SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS, OR WHEEL 28Ø 2340 1800 1980 1520 1765 1360 REFER TO DWG. NO. S-01 FOR NOTES ON PREPARATION 3-10Ø LONGITUDINAL BARS
36Ø 990 900 810 FOR NOTES ON PREPARATION OF SOIL SUB-BASE.
(CONTINUOUS) WITH TENSION SPLICE
BARROWS. NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUGGIES, D

OF SOIL SUB-BASE.
32Ø 2990 2300 2600 1985 2300 1780 DET. OF CHB ON SLAB THICKENING
WHELL BARROWS, OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED 6.0M IN AGGREGATE LENGHT. DETAIL OF WALL FOOTING
36Ø 3770 2900 3280 2520 2930 2250 DET. OF CHB ON TIE BEAM (FOR INTERIOR WALL)
NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS, UNLESS
AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR USUAL CONDITIONS WHERE VIBRATOR IS (FOR EXTERIOR WALL)
TENSION SPLICE CLASSIFICATION:
EXTREMELY DIFFICULT TO ACCOMPLISH.
CLASS A = 1.00Ld 90 DEG

BEAMS AND GIRDERS:


CLASS B = 1.33Ld
3 WALL FOOTING DETAILS ON CHB

DETAILING DIMENSIONA OR G
MASONRY AND CONCRETE BLOCKS: S-01 Scale: 1:30

HOOK
1. UNLESS OTHERWISE NOTED IN THE PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AT LEAST 6mm FOR 1. ALL NON-LOAD BEARING TYPE CONCRETE BLOCKS SHALL HAVE A UNIT WEIGHT NOT TO EXCEED 80 PCF. FOR LOAD BEARING TYPE
EVERY 3.0M OF SPAN EXCECPT FOR CANTILEVERS FOR WHICH THE CAMBER SHALL BE AS NOTED IN THE CONCRETE BLOCKS, A MINIMUM COMPRESSIVE STRENGHT OF 6.90 Mpa SHALL BE DEVELOPED.

150
6D
PLANS OR AS ORDERED BY THE STRUCTURAL ENGINEER BUT IN NO CASE LESS THAN 19mm FOR EVERY 3.0M 2. PROVIDE 1-16Ø VERTICAL BARS AT CORNERS, INTERSECTIONS, END OF WALLS AND EACH SIDE OF MASONRY WALL OPENING. 10 MMØ NOSING BARS
OF FREE SPAN. 3. LINTEL BEAMS SHALL BEAR AT LEAST 8 INCHES (200mm) ON EACH SIDE OF MASONRY WALL OPENING.

H
2. IF THERE ARE TWO OR MORE LAYERS OF LONGITUDINAL REINFORCING BARS IN A BEAM OR ORDER, USE 4. UNLESS OTHERWISE INDICATED IN THE PLANS, WALL REINFORCEMENT SHALL BE AS FOLLOWS: D
10 MMØ TEMP. BAR 10 MMØ TEMP.
SEPERATORS OF A SIZE NOT LESS THAN 25mm BARS SPACED ABOUT 0.90M ON CENTER. IN NO CASE SHALL PLACE AS SHOWN 200 BAR @ 220MM O.C.
THERE LESS THAN TWO (2) SEPERATORS BETWEEN LAYERS OF BARS. CONCRETE HOLLOW BLOCKS REINFORCEMENT
3. LONGITUDINAL REINFORCING BARFS SHALL BE PLACED SYMMETRICALLY ABOUT THE VERTICAL CENTER
D

10 MMØ @ 12 MMØ @ 175MM O.C.


REINFORCEMENT NOTES
LINE OF THE BEAM OR GIRDER SECTION WHERE POSSIBLE WITH UPPER LAYER BARS PLACED DIRECTLY 200MM O.C.

100
ABOVE THOSE IN THE BOTTOM LAYER. t (mm) A.MIN. LAP SPLICE = 0.25M
TOP & BOT. MAIN SEE SUSPENDED SLAB SCHED.

600
HORIZONTAL VERTICAL E.F. REBARS TYP.

150
4. MINIMUM CONCRETE PROTECTION OF REINFORCING BARS SHALL BE 38mm, B. PROVIDE RIGHT ANGLE REINFORCEMENT AT CORNER
5. BEAM REINFORCING BARS BOTH TOP AND BOTTOM TERMINATING IN A WALL SHALL EXTEND AT THE MOST 75 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C. 0.90M LONG. 135 DEG 10 MMØ NOSING BARS
50mm FROM THE FAR FACE OF THE WALL AND SHALL TERMINATE IN A STANDARD 90° HOOK.
12 MMØ @ 200MM O.C. E.F. 12 MM Ø @ 175 MM

300
C. WHERE CHB WALLS ADJOINING COLUMN, R.C. BEAM,
100 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C. 10 MMØ TEMP. BAR @ O.C. B.W. TOP & BOT.
6. BEAM REINFORCING BARS BOT TOP AND BOTTOM TERMINATING IN A COLUMN, SHALL EXTERND TO THE WALL DOWEL W/ SAME SIZE AS VERTICAL OR HORIZONTAL STIRRUP AND TIE-HOOKS 4-12 MMØ 12 MM Ø @ 200MM O.C. TO ALL
FAR FACE OF THE CONFINED CONCRETE CORE OF THE COLUMN AND TERMINATED BY A STANDARD 90° REINFORCEMENT SHALL BE PROVIDED. 600 220 MM O.C. LANDING REBARS
HOOK. 150 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C. CONTINUOUS STAIRS

150
7. GENERALLY NO LAP SLPLICE SHALL BE PERMITTED ON BEAMS AND GIRDERS AT POINTS WHERE CRITICAL 200 10Ø @ 0.60m O.C. 10Ø @ 0.60m O.C.
BENDING STRESSES OCCUR. IN ADDITION, FOR GIRDERS, NO LAP SPLICE SHALL BE LOCATED WITHIN THE
JOINTS OR WITHIN THE DISTANCE EQUAL TO TWICE THE DEPTH OF THE MEMBER FROM THE FACE OF THE
JOINT. 4 TYP. STAIR FOUNDATION DETAIL 5 TYP. STAIR FLR LVL DETAIL
8. PROVIDE LAP SPLICES ON GIRDER WITH HOOP REINFORCEMENT OVER THE LENGHT OF THE LAPPED BARS CONCRETE WALLS: S-01 Scale: NTS S-01 Scale: NTS
SPACED NO FARTHER THAN ONE-FOURTH OF THE NOMINAL DEPTH OR 100mm. UNLESS OTHERWISED INDICATED IN THE PLANS, WALL REINFORCEMENT
9. SEE MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR ALL SUSPENDED PIPE SHALL BE FOLLOWED ACCORDING TO THE FOLLOWING SCHEDULE
AND EMBEODED PIPINGS, CONDUITS, DUCTWORKS, ETC.
REINFORCEMENT
WALL VERTICAL
STANDARD HOOKS STIRRUP AND TIE-HOOKS THK. REMARKS SECTION
HORIZONTAL VERTICAL
D 180 DEG 90 DEG D 90 DEG 135 DEG HOR. & CENTER VERT.
BAR SIZE BAR SIZE 0.102m 10Ø @ 0.25m O.C. 10Ø @ 0.30m O.C.

D
(MM) A OR G J A OR G (MM) A OR G A OR G H BARS STAGGERED OUTSIDE

VAR.
10Ø 60 125 60 150 10Ø 40 105 105 65 0.127m 10Ø @ 0.20m O.C. 10Ø @ 0.25m O.C. - DO -
12Ø 80 150 105 200 12Ø 50 115 115 80 BOTH FACES HOR. B

VAR.
0.152m 12Ø @ 0.25m O.C. 12Ø @ 0.30m O.C. SHALL BE INSIDE
16Ø 95 175 130 250
0.178m 12Ø @ 0.23m O.C. 12Ø @ 0.25m O.C. - DO -
20Ø 125 225 175 350
12Ø @ 0.30m O.C. BOTH FACES HOR.
25Ø 155 275 205 425 0.208m 12Ø @ 0.30m E.F. SHALL BE OUTSIDE

D
32Ø 275 425 335 550 0.229m 12Ø @ 0.20m O.C. 12Ø @ 0.25m O.C. E.F. - DO -

0.254m 12Ø @ 0.30m O.C. E.F. 12Ø @ 0.30m O.C. E.F. - DO - 7 DETAIL OF SLAB ON FILL / GRADE
S-01 Scale: 1:10
COLUMN: 0.275m 12Ø @ 0.25m O.C. E.F. 12Ø @ 0.30m O.C. E.F. - DO -
1. WHERE COLUMNS CHANGE IN SIZE, VERTICAL REINFORCEMENTS SHALL BE OFFSET AT A SLOPE NOT MORE THAN 1 IN 6. PROVIDE
TRANSVERSE REINFORCEMENT (JOINT HOOPS) AS PER FIGURE PROVIDED IN SHEET NO. 2. 0.305m 12Ø @ 0.23m O.C. E.F. 12Ø @ 0.27m O.C. E.F. - DO - 6 TIE BEAM (TB) DETAIL
2. LAP SPLICES, WHEN REQUIRED, ARE PERMITTED ONLY WITHIN THE CENTER HALF OF TEH COLUMN LENGHT AND SHALL BE PROPORTIONED S-01 Scale: 1:20
AS TENSION SPLICES. IN NO CASE SHALL THE LAP SPLICE BE LOCATED CLOSER THAT A DISTANCE EQUAL TO THE MAXIMUM COLUMN 0.356m 12Ø @ 0.20m O.C. E.F. 12Ø @ 0.25m O.C. E.F. - DO -
DIMENSION FROM THE FACE OF THE BEAM-COLUMN JOINT. PROVIDE EXTRA TRANSVERSE REINFORCEMENT OF THE SAME SIZE ARRANGEMENT
0.406m 12Ø @ 0.25m O.C. E.F. 12Ø @ 0.30m O.C. E.F. - DO -
INDICATED IN THE COLUMN SCHEDULE SPACED AT MOST ONE-FOURTH OF THE MINIMUM COLUMN DIMENSION THROUGHOUT THE LENGHT
OF THE SPLICE OR 100mm.
3. FOR ALL TIED COLUMNS, PROVIDE TRANSVERSE REINFORCEMENTS OF THE SAME SIZE AND ARRANGEMENT INDICATED IN THE COLUMN
SECTION SCHEDULE AND SPACED NO GREATER THAN ONE QUARTER THE MINIMUM COLUMN SECTION DIMENSION NOR 100mm. OVER A
DISTANCE FROM EACH JOINT FACE OF LESS NOT LESS THAN THE LARGER OF THE MAXIMUM COLUMN SECTION DIMENSION, OR ONE SIXTH
OF THE CLEAR HEIGHT OF THE COLUMN OR 450mm.
4. UNLESS OTHERWISE DETAILED, TYPICAL BAR DETAILS FOR TIED COLUMNS ARE AS SHOWN IN FIGURE PROVIDED IN SHEET. NO. 2.

1 STRUCTURAL NOTES
S-01 Scale: NTS
8 TYPICAL BEAM DETAIL
S-01 Scale: NTS

PROJECT TITLE : OWNER: SHEET CONTENTS : REVISIONS: SHEET NO. :


DRAWN BY:
REPUBLIC ACT 9266 SECTION 33 (IV)

ALVIN N. DELIRO
ARCHITECT/ENGINEER
OWNERS OF PLANS, SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS

DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS DULY


SIGNED STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE, ARE THE
PROPOSED TWO-STOREY
MS. ROSALINDA U. BANTOC STRUCTURAL NOTES
CONSTRUCTION DETAILS CHECKED BY:
S-1
INTELLECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT, WHETHER THE COMMERCIAL/ RESIDENTIAL LOCATION: BLK 6 LOT 6 ,BEVERLY HOMES,BRGY. HUGO PEREZ,TRECE
OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. IT SHALL BE UNLAWFUL MARTIRES CITY,CAVITE DATE : PAGE NO. :
REG NO.: 0102124 PTR NO.: 5745705
FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS. FOR
USE IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS, WHETHER
BUILDING WITH ROOF DECK APPROVED BY:
PL. ISS.: TANZA, CAVITE
TIN: 238730704
DATE ISS.: JAN. 03, 2023
EXECUTED PARTLY OR IN WHOLE, WITHOUT THE WRITTEN CONSENT OF THE
ARCHITECT OR AUTHOR OF SAID DOCUMENTS.
LOCATION: BLK 5 LOT 1 ,BEVERLY HOMES,BRGY. HUGO PEREZ,TRECE MARTIRES CITY,CAVITE OWNER / REPRESENTATIVE PROJ. NO. :
1/3
 



 





 



10 MMØ TEMP. BAR PLACE AS SHOWN

150
10 MMØ NOSING BARS
12 MMØ @ 175 MM O.C. TOP & BOT.
MAIN REBARS TYP. TO ALL STAIRS
  SEE SUSPENDED
SLAB SCHED.

115
1 TYP. STAIR START-UP DETAIL
S-02 Scale: NTS

10 MMØ NOSING BARS

150
12 MM Ø @ 175 VERIFY
  MM O.C. TOP &

150
BOT. MAIN
REBARS TYP. TO
3 TRUSS DETAILS ALL STAIRS
12 MMØ @ 175 MM O.C. B.W. TOP &

150
S-02 Scale: NTS BOT. LANDING REBARS

2 TYP. STAIR LANDING DETAIL


S-02 Scale: NTS

PROJECT TITLE : OWNER: SHEET CONTENTS : REVISIONS: SHEET NO. :


DRAWN BY:
REPUBLIC ACT 9266 SECTION 33 (IV)

ALVIN N. DELIRO
ARCHITECT/ENGINEER
OWNERS OF PLANS, SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS

DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS DULY


SIGNED STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE, ARE THE
PROPOSED TWO-STOREY
MS. ROSALINDA U. BANTOC STRUCTURAL SCHEDULE
CONSTRUCTION DETAILS CHECKED BY:
S-2
INTELLECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT, WHETHER THE COMMERCIAL/ RESIDENTIAL LOCATION: BLK 6 LOT 6 ,BEVERLY HOMES,BRGY. HUGO PEREZ,TRECE
OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. IT SHALL BE UNLAWFUL MARTIRES CITY,CAVITE DATE : PAGE NO. :
REG NO.: 0102124 PTR NO.: 5745705
FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS. FOR
USE IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS, WHETHER
BUILDING WITH ROOF DECK APPROVED BY:
PL. ISS.: TANZA, CAVITE
TIN: 238730704
DATE ISS.: JAN. 03, 2023
EXECUTED PARTLY OR IN WHOLE, WITHOUT THE WRITTEN CONSENT OF THE
ARCHITECT OR AUTHOR OF SAID DOCUMENTS.
LOCATION: BLK 5 LOT 1 ,BEVERLY HOMES,BRGY. HUGO PEREZ,TRECE MARTIRES CITY,CAVITE OWNER / REPRESENTATIVE PROJ. NO. :
2/3
SECOND FLOOR THIRD FLOOR ROOF

1 FOUNDATION PLAN 2 FRAMING PLAN 3 FRAMING PLAN 4 FRAMING PLAN


S-03 Scale: 1:100 S-03 Scale: 1:100 S-03 Scale: 1:100 S-03 Scale: 1:100

PROJECT TITLE : OWNER: SHEET CONTENTS : REVISIONS: SHEET NO. :


DRAWN BY:
REPUBLIC ACT 9266 SECTION 33 (IV)

ALVIN N. DELIRO
ARCHITECT/ENGINEER
OWNERS OF PLANS, SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS

DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS DULY


SIGNED STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE, ARE THE
PROPOSED TWO-STOREY
MS. ROSALINDA U. BANTOC FOUNDATION PLAN
FLOOR FRAMING PLAN
ROOF FRAMING PLAN
CHECKED BY:
S-3
INTELLECTUAL PROPERTY AND DOCUMENTS OF THE ARCHITECT, WHETHER THE COMMERCIAL/ RESIDENTIAL LOCATION: BLK 6 LOT 6 ,BEVERLY HOMES,BRGY. HUGO PEREZ,TRECE
OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. IT SHALL BE UNLAWFUL MARTIRES CITY,CAVITE DATE : PAGE NO. :
REG NO.: 0102124 PTR NO.: 5745705
FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS. FOR
USE IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS, WHETHER
BUILDING WITH ROOF DECK APPROVED BY:
PL. ISS.: TANZA, CAVITE
TIN: 238730704
DATE ISS.: JAN. 03, 2023
EXECUTED PARTLY OR IN WHOLE, WITHOUT THE WRITTEN CONSENT OF THE
ARCHITECT OR AUTHOR OF SAID DOCUMENTS.
LOCATION: BLK 5 LOT 1 ,BEVERLY HOMES,BRGY. HUGO PEREZ,TRECE MARTIRES CITY,CAVITE OWNER / REPRESENTATIVE PROJ. NO. :
3/3