SattCon 05 Slimline

From Program Version 4.0

SattCon 05 Slimline is a family of com- Systems in the SattCon 05 Slimline as well as the DOX 10 and DOX 5 soft-
pact programmable controllers for small family are self-contained and handle ware packages. In addition, all original
to medium-size applications. A modular both analogue and digital control, mak- SattCon 05 expansion units may be used
configuration, offering four different ing them suitable for process and with SattCon 05 Slimline.
processor boards with four I/O units, machine control applications. In addi-
means that each system can be tailored tion to their use as stand-alone control- ● Combines a compact format with the
to meet your exact requirements. lers, SattCon 05 Slimline systems have flexibility of a modular system.
In addition to the systems described in built-in facilities for network communi- ● PID loops and arithmetic functions
this data sheet, there are versions of cation. The compact design allows the for process control.
SattCon 05 Slimline with built-in oper- most cost effective use of panel space. ● Programming using a standard VDU
ator interface (SattCon OP45/ The SattCon 05 Slimline family or a personal computer with DOX 10
SattCon OP45SB), and units which can includes I/O units for system expansion or DOX 5 software installed.
execute a BASIC program as well as (SD32D, SDA, SD24D, SD24RS and ● Serial ports for VDU, printer and
carrying out control (SattCon 05-65/ SACV) and other accessories: a backup COMLI or SattBus communication.
SattCon OP65). Details of these prod- unit (SBUP05), a battery-backed real- ● Text handling includes facilities for
ucts are presented in separate data time clock (BRT15), digital and ana- operator inputs from VDU.
sheets. logue input simulators (PTC05 and ● Powerful instruction set permits com-
ATC05), pulse encoder interface (IP05), plex applications.
System functions
Processor boards CU05-25 CU05-25SB CU05-45 CU05-45SB
VDU programming X X* X X*
Programming and documentation with PC X X* X X*
Program listing on printer X X* X X*
Max. number of expansion I/O units (in addition to 3 3 3 3
base unit I/O)
Interrupt-controlled fast loop X*** X***
Internal memory cells (reduced by no. of I/O) 3072 3072 3072 3072
Timers 64 64 64 64
Counters 64 64 64 64
Registers 28000 28000 28000 28000
Sequencers 256 256 256 256
Fast count input (2 kHz) X** X**
Time channels 16 16
PID loops 8 8
Subroutines X X X X
Shift instructions X X X X
Text messages 512 512 512 512
Operator dialogue X X X X
COMLI slave X X
COMLI master X
VDU port X X* X X*
Printer port X X* X X*
SattBus port X X
* DX232 or DX485 required.
** Only when SD32D or SDA are the base unit. DX232/DX485G cannot be used.
*** Not valid when SD24RS is used as a base unit.

I/O units SD32D SD24D SD24RS SDA SACV


Can be used as a base unit X X X X
DX232 or DX485G can be fitted in base unit X X
Fast counter input (2 kHz) X* X*
Internal power supply via the processor board X X X X X
External power supply X X
Digital inputs/outputs 32/28 24/24 24/16 16/16
Opto-isolated digital inputs X X X
Opto-isolated digital outputs X X
Transistor outputs X X X
Relay outputs X
Analogue inputs/outputs 4/2 12/4
*Only available when DX232 or DX485G is not installed.

System configuration The facilities provided by the various I/O signals can be used to start a fast
A SattCon 05 Slimline system compris- processor boards and I/O units are sum- loop capable of executing a section of
es a base unit and up to three expansion marised in the tables above. A table at the PLC program with a cycle time as
I/O units, together with any accessories the end of this data sheet shows all per- short as 1ms. (This function is not pro-
required. The base unit consists of an missible combinations of processor vided by CU0525SB and CU05-45SB.)
I/O unit where a processor board is built board, I/O unit and communications The system can handle analogue
in. A communications board (DX232 or board. inputs and outputs. In addition to the
DX485G) can also be built in, if PID loops provided on certain versions,
required. Memory the PLC program can be used to imple-
There are five I/O units (SD32D, The program memory is battery backed ment alarms, ramp functions etc. There
SDA, SACV, SD24D, SD24RS), pro- CMOS RAM; the area used for the con- are 28000 16-bit registers available for
viding different combinations of digital trol program is 25 kbytes. An external common use.
and analogue I/O, and four processor Flash EPROM memory unit (SBUP05)
boards (CU05-25, CU05-25SB, CU05- is also available. Timers and counters
45, CU05-45SB). Every version of SattCon 05 Slimline
CU05-45 and CU05-45SB provide a Program functions has 64 timers and 64 counters. The PLC
full range of facilities for process con- The main part of the control software in program has access to timer and counter
trol including PID loops and time chan- SattCon 05 Slimline is the PLC pro- presets to allow re-use with different
nels, while CU05-25 and CU05-25SB gram. As well as providing functions values of operator adjustment.
are intended more for machine control for logic and interlocking, there are
and do not support these functions. arithmetic and data handling instruc- Time channels
CU05-25 and CU05-45 support tions, three levels of subroutines, shift 16 programmable time channels in
COMLI communication; CU05-25SB registers and 256 sequencers with 100 CU05-45 and CU05-45SB can be used
and CU05-45SB have an integral steps each. to start and stop activities at predeter-
SattBus port. mined times and days.
PID controllers Using either SattBus or COMLI, sig- up program development. When the
CU05-45 and CU05-45SB have 8 pro- nal status, register values and other data program has been transferred to the
grammable loop controllers with P, PI, can be transferred to and from other sys- SattCon 05 Slimline, it can be super-
PD or PID functions which can also be tems. A personal computer can be used vised on-line via DOX 10/DOX 5,
cascaded. Functions such as setpoint to upload/download data and programs. which still shows identifiers etc.
ramping and gain scheduling may be On-line programming and program For programming via the SattBus net-
implemented using the PLC program. changes can be performed via the net- work, a personal computer running
work (not valid for DOX 10). DOX 5 is connected via an SBC con-
Text handling and dialogue nector (see separate data sheet).
512 lines of text, each 32 characters Programming and documentation SattCon OP45SB must be equipped
long, can be used for events, alarms and The minimum requirement for pro- with a DX232 or DX485 communica-
dialogue messages. The messages can gramming SattCon 05 Slimline is a tion board, if it is to be programmed via
also include the date, time and process VDU terminal. All programmed func- a VDU or DOX 10.
values. tions can be listed on a printer.
Large numerical values, and values CU05-25SB and CU05-45SB require a Allowed combinations of
with up to five decimal places can be DX232 or DX485G to provide the VDU boards
handled if several consecutive registers and printer ports. Any CPU board can be mounted in any
are used. An IBM compatible personal compu- of the I/O units SD32D, SDA, SD24D
Numerical information may be scaled ter with the DOX 10 or DOX 5 software or SD24RS to make a base unit. SACV
automatically and displayed in physical package serves as an enhanced pro- must constitute an expansion unit of its
units with up to 5 decimal places. Limit gramming and documentation tool. Pro- own and cannot be combined with a
checking of min./max. values is per- grams can be developed off-line using CPU board.
formed at input. identifiers (signal names rather than The communication boards DX232
Text can be displayed at a VDU, print- numeric addresses) and comments. and DX485G can only be mounted in
er, or both. Control codes can be easily Function block library handling speeds the I/O units SD32D and SDA.
inserted into messages to provide cursor
positioning, flashing, high intensity text
etc. on a VT100-compatible VDU.
Any ASCII character can be printed
out from a register or from the text line.
A DX232 or DX485G communica-
tion board is required to use VDU and/
or printer with a SattBus system.

Diagnostics I/O units


SattCon 05 Slimline has a number of
built-in functions for error detection and
50-pin connector
fault-finding. These include automatic
detection of analogue input/output 32 Inputs 28 Outputs
faults, and dynamic display of program,
I/O status and sequence steps. 00
01
40
41
02 42
Inputs

03 43
Communication 04 44
45
05
As standard, CU05-25 and CU05-45 06 46
47
07
have an opto-isolated serial port for pro- 48 +
gramming or COMLI communication, 10
49 0V

and a second port for a printer. Commu- 11


12 50
Inputs

51
nication is via an RS232 interface or 13
14 52
53
electrically isolated RS485 (2-wire), but 15
16 54
the printer interface is RS232 only. 17 55
56
Electronics
Adding a DX232 or DX485G commu- 57
20
nication board provides programming, 21
58 +
59 0V
22
printer and two separate COMLI chan-
Inputs

23
60
24
nels. DX232 has two RS232 interfaces 25
61
62
26
and DX485G two electrically isolated 27
63
64
RS485 channels (4-wire). 65
66
The text handling includes facilities 30 67
31
for interface to Hayes modem. 32 70
Inputs

33 71
CU05-25SB and CU05-45SB com- 34 72
35 73
municate via SattBus instead of 36
37 78 +
COMLI. SattBus is a two wire asyn- F1 Automatic 79 0V
+24V 38
chronous token passing bus. A maxi- 0V 39 0,5A 24V

mum of 120 nodes may be connected 0V

over a maximum length of 2000 m. In a


SattBus network at least one of the 50-pin connector for next expansion unit
nodes must include the supervisor func-
tion, e.g. SattBus Connector (SBC),
since the function is not provided in SD32D outputs (12–50 VDC). When used in a
SattCon 05 Slimline. SD32D is a digital I/O unit with 32 SattCon 05 Slimline base unit, DX232/
inputs (16–32 VDC) and 28 transistor DX485G can also be fitted.
SDA
A combination of digital and analogue
50-pin connector
I/Os can be connected to SDA: 16 opto- Inputs Outputs
isolated digital outputs (12–50 VDC),
4 analogue inputs with common signal Power supply to sensor F2 0,5AT 5x20 mm Analogue power supply
+24V 00 30 +24V
ground (0–5 V/1–5 V/0–10 V/ AI00 + 01 F3 0,315 AT 31 0V
0–20 mA/4–20 mA) and 2 analogue 0V 02 µ ƒuse internal 32 PGND
AI04 + 03 33 0V
+24VI
outputs (0 10 V/0 20 mA/4–20 mA). 0V 04 Analogue
mA
34 +AO40
+24V 05 circuits 35 +AO60
When used in a SattCon 05 Slimline AI10 + 06 36 0V
0V 07 +24V0 V 37 +AO40
base unit, DX232/DX485G can also be AI14 + 08 38 +AO60
0VA
0V 09 39 0V
fitted. 10k 1µ
40 D20

D00 10 41 D21
D01 11

Optocoupler
D02 12 42 D22

Inputs
D03 13
D04 14 Electronics 43 D23
D05 15

Optocoupler
D06 16 44 D24
D07 17
+24V 18 45 D25
0V 19
20M 0,01µ
46 D26

D10 20 47 D27
D11 21 48 +D20-27
D12 22 20M 49 0V D20-27

Optocoupler
0,01µ

Inputs
D13 23
D14 24 D30
PNP 50
D15 25 D31
51

coupler
D16 26 D32
52

Opto-
D17 27 D33
XJ4 53
+24V 28
54 D34
0V 29 0V
55 D35
20M 0,01µ D36
56
F1 +24V 57 D37
20M +D30-37
58
0,5AT 5x20 mm 0,01µ 59 0V D30-37

50-pin connector for next expansion unit

SD24D
SD24D is a digital I/O unit with 24
50-pin connector
opto-isolated inputs (16-32 VDC) and
24 opto-isolated transistor outputs 24 Inputs 24 Outputs
(12-50 VDC). A1
A2
A3
A4
00 40
01 41
02
Optocoupler

42
Optocoupler

03
Inputs

43
04 44
05 45
06 46
07 47
+C 08 0,01µ 48 +C
0V 09 20M 0,01µ 49 0V
10 20M 50
11 51
Optocoupler

12 52
Optocoupler
Inputs

13 Electronics 53
14 54
15 55
16 56
17 57
+C 18 0,01µ 58 +C
0V 19 20M 0,01µ 59 0V
20 20M 60
21 61
Optocoupler

Optocoupler

22 62
Inputs

23 63
24 64
25 65
26 0V 66
27 67
+C 28 XJ1 68 +C
0V 29 0V 69 0V
0,01µ 0,01µ 20M
20M
F1 +24V
0,5AT

50-pin connector for next expansion unit


SD24RS
SD24RS is a digital I/O unit with 24
opto-isolated inputs (16–32 VDC) and 50-pin connector
16 relay outputs. 24 Inputs 16 Outputs

00 40
Relay 40
01 Electronics C40
02 Relay 41 40
03 C41
04 Relay 42 41
05 C42
06 Relay 43 42
07 C43
C08 Relay 44 43
0V09 20M 0,01µ C44
Relay 45 44
10 C45
11 Relay 46 45
12 C46
13 Relay 47 46
14 C47
15 47
16
17 Relay 50 C50
C18 50
0V19 Relay 51
20M 0,01µ C51
Relay 52 51
20 C52
21 52
22 Relay 53
C53
23 53
24 Relay 54
C54
25 54
26 Relay 55
C55
27 55
Relay 56
C28 0V C56
Relay 57
0V29
XJ1 56
0V
57
20M

F1 +24V C57
0,01µ 57
0,5 AT

50-pin connector for next expansion unit

SACV
SACV is an analogue I/O unit having 12 50-pin connector
Inputs Outputs
analogue inputs with common signal
ground (0-20 mA/4-20 mA/0-10 V) and
4 analogue outputs (0-20 mA/4-20 mA/ Power supply for sensors
F1 0.5 AT
0-10 V). SACV must constitute an +24V 00
S1 +24V AI
30
expansion unit of its own and cannot be AI00 +
0V
01
02
31
32
combined with a CPU board in a base AI04 + 03 33
0V 04 34
unit. +24V 05
S2 35
AI10 + 06 36
0V 07
AI14 + 08 Current
0V 09 0V 40 +AO00
41 0V
42 +AO20
43 0V
+24V 10 S3 44 +AO40
AI20 + 11 45 0V
0V 12 46 +AO60
AI24 + 13 47 0V
0V 14 48 0V
+24V 15
S4 49 0V
AI30 + 16
0V 17 Voltage
50 +AO00
AI34 + 18 0V
51
0V 19 +AO20
52
53 0V
54 +AO40
+24V 20
S5 55 0V
56 +AO60
AI40 + 21
57 0V
0V 22
58 0V
AI44 + 23
59 0V
0V 24
S6
+24V 25 Internal pow-
AI50 + 26 er supply F2 1.0 AT
0V 27 60 +24 V DC
AI54 + 28
0V 29 61 0 V
0V
62 Protective
ground

50-pin connector to next expansion unit


Accessories IOCOP cable PTC05 digital input simulator
Communication boards Each expansion unit is supplied with a PTC05 connects directly to the inputs of
DX232 and DX485G provide two addi- short ribbon cable (0.1 m) for connec- an I/O unit. It can be used to simulate
tional serial ports each, RS232 and tion between I/O units. Cables with 0.3, the status of eight inputs while testing
RS485 respectively. When connected to 1.0 respective 2.0 m length can be the operation of the control program.
CU05-25 or CU05-45 these ports are ordered as accessory items. The total
used for COMLI communication. When cable length between base unit and the
connected to CU05-25SB or CU05- I/O units must not exceed 2.7 m.
45SB they provide ports for a VDU and
a printer.

ATC05 analogue input simulator


ATC05 connects directly to the inputs
on an SDA I/O unit. It provides four
0–10 V signals to simulate signals from
SBUP05 backup unit the process.
The contents of the program memory
can be stored in the SBUP05 backup
DXDSUB-SL connector unit, which uses a Flash PROM memo-
A box with two D-sub connectors, ry. This is a type of non-volatile, electri-
DXDSUB-SL, is available for external cally erasable EPROM. If SBUP05 is
connection of the communication ports. permanently connected, and the switch
This unit is connected via a ribbon cable is in the position "1", the SattCon 05
to DX232 or DX485G. Slimline's RAM memory is automati-
cally loaded from the SBUP05 on pow-
er-up and program execution starts. An
adapter cable is required for use
with a SattCon OP45 base unit.

IP05 pulse encoder interface


The IP05 pulse encoder interface can be
connected to base units with CU05-25
or CU05-45 processors and SD32D or
SDA I/O units. Pulse encoders with or
without zero pulse and with one or two
pulse trains may be used.

DOX 10/DOX 5 software packages


BRT15, battery-backed real time DOX10/DOX 5 software packages can
clock be installed in IBM compatible personal
BRT15 maintains the correct date and computers. Programming and docu-
time even when the power is discon- mentation of SattCon 05 Slimline func-
nected. tions without a control system connect-
ed are then possible (DOX 5 with some
limitations). The software packages can
also be used for commissioning and
fault-finding in existing programs.
CU05-25SB and CU05-45SB require a
DX232/DX485G if the personal com-
puter is to be connected directly to the
control system. Communication can
take place via DOX 10/DOX 5 alterna-
tively via the SattBus network using an
SBC connector.
Technical data, Processor boards and I/O units
CPU Dallas 80C320 or equivalent Digital inputs
Program memory 25 kbytes available for the PLC pro- SD32D 32 separate groups. 16–32 VDC,
gram; CMOS RAM with battery back- 10 mA. Switching level <6 V=
up, battery life approx. 3 years in logic 0, >13 V= logic 1. Filter constant
operation and 5 years in storage 10 ms, max. 50 Hz square wave
(25°C) SD24D 24 in 3 separate groups. Opto-
Instruction time Bit instructions: typically 1.2 µs/ isolated. Other data as SD32D
instruction. Word instructions: typical- SD24RS See SD24D data
ly 20 µs/instruction
SDA 16 in 2 separate groups. Opto-
Working memory Total of 3072 bits, this number is isolated. Other data as SD32D
reduced by the number of inputs/out-
puts used by the application. 60 bits Digital Outputs
are battery backed SD32D 28 in 3 groups. 12–50 VDC, max.
Timers 64 pcs. 0.1 s–9 h 6 m 7 s 0.8 A/output, max. 3.2 A/group, max.
6 A/unit. Transient current max. 2 A
Counters 64 pcs 65535 steps, up/down counter for 50 ms. Peak voltage max. 75 VDC
Registers (16-bit) 28000 pcs (average max. 50 VDC). Fused exter-
Sequencers 256 pcs. with 100 steps each nal
Time channels 16 pcs. programmable. Not valid for SD24D 24 in 3 groups. Opto-isolated. Other
CU05-25/25SB data as SD32D
Text messages 512 x 32 characters. Time, date and SD24RS 16 relay outputs.
process values can be included. AC: Max. 250 V, max. 5 A resistive
Texts can also be sent to printer. Text load.
handling includes dial-up function for DC: Max. 120 V, max.4 A (24 VDC
Hayes modem +20%), max. 0.6 A (48 VDC +20%),
resitive load.
Controllers 8 programmable P, PI, PD or PID. Not See the Installation and Maintenance
valid for CU05-25/25SB manual for more information.
Pulse input On/off switching delay max. 15/
CU05-25 and Max. 2 kHz. Only if the base unit is a 10 ms. type 8/4 ms
CU05-45 SD32D or a SDA. Not valid if a com- SDA 16 in 2 groups. Opto-isolated. Other
munication board (DX232 or data as SD32D
DX485G) is fitted in the base unit Analogue inputs
Expansion Max. 3 I/O units in addition to the SDA 4 inputs, common signal ground.
base unit 0–5/1–5/ 0-10 V (> 1 MΩ, max. 15 V
Communication continuous) or 0–20 mA/4–20 mA
CU05-25 One serial port, COMLI slave. RS232 (max. 250 Ω, max. 30 mA continu-
or RS485 (galv. separated). With ous). 10 bit resolution. Filter constant
DX232 or DX485G, a total of two 100 ms. Accuracy ±0.5% of full scale
COMLI ports deflection (0–50°C)
CU05-45 One serial port, optional COMLI mas- SACV 12 inputs 0-10 V (> 1 MΩ, max. 15 V
ter/slave. RS232 or RS485 (galv. continuous) or 0–20 mA/4–20 mA
separated). With DX232 or DX485G, (max. 50 Ω, max. 50 mA continuous).
a total of two COMLI ports Accuracy ±0.4% of full scale deflec-
tion (0–50°C). Other data as SDA
CU05-25SB and SattBus connection. Does not have
CU05-45SB supervisor function. 120 nodes, max. Analogue outputs
2000 m SDA 2 outputs, 0–10 V max. 10 mA or
Programming 0–20 mA/4–20 mA (external load
<750 Ω). 8 bit resolution. Accuracy
CU05-25 and ±0.5% of full scale deflection
CU05-45 VDU or PC with DOX10/DOX 5 (0–50°C)
CU05-25SB and DX232 or DX485G is required to SACV 4 outputs 0-10 V/0-20 mA/4-20 mA.
CU05-45SB allow programming via terminal. Other data as SDA
PC and DOX 10/DOX 5 can be used
for programming via SattBus Power consumption Refer to the Installation and
I/O units Maintenance manual
DOX 5 Software for personal computer.
Off-line programming with IDF and Environment Industrial premises
comments Electrical Fulfils Low Voltage Directive
DOX 10 Software for off-line programming environment 73/23/EEC and
with personal computer. Graphic pro- ElectroMagnetic Compatibility, EMC,
gramming is possible Directive 89/336/EEC
Backup Total with SBUP05, DOX 10 and Protection class IP20
DOX 5 Ambient temperature Operating: 0–50°C
Printer connection Non-operating: -25 to +70°C
CU05-25/45 RS232 via 25-pole D type connector. Relative humidity 10–95%, non-condensing.
For SDA and SACV 10–85%,
CU05-25SB/45SB DX232 or DX485G is required non-condensing
Power supply 24 V DC -15% +20%. Max. ripple 5% Dimensions W342 X H200 X D47 mm
(100–120 Hz). No additional supply
for I/O units is normally required. Weight Max. 2.2 kg
SDA and SACV require however
24 V DC -15% +20%
Power consumption Ca. 3 W (processor board only). For
details, refer to the Installation and
Maintenance manual
Technical data, accessories
DX232 Pulse frequency To IP05: max. 4 kHz
Baud rate Max. 19200 baud From IP05: max. 2 kHz
Cable Screened multicore, max. length Power supply From base unit, pulse encoder
15 m at 19200 baud powered from terminal +12 V,
max. 100 mA
Power consumption 1.0 W (+24 V DC)
Power consumption 2.5 W (+24 V DC)
Power supply +5 VDC from CU05
Dimensions (incl.
DX485G cable) W45 X H110 X D70 mm
Baud rate Max. 19200 baud PTC05
Cable Screened multicore, max. length Output 8
1200 m
Power supply From base unit with cable supplied
Power consumption 2.8 W (+24 V DC)
Protection class. IP10
Power supply +5 VDC and +24 VDC from CU05
Dimensions W85 X H41 X D28 mm
SBUP05
ATC05
Memory 128 kbytes Flash EPROM
Outputs 4.0–10 V
Power consumption 0.6 W (+24 V DC)
Power supply Direct from SDA or SACV
Power supply From base unit
Dimensions W70 X H50 X D30 mm
Dimensions W135 X H75 X D35 mm
BRT15 The following applies to all units unless stated otherwise:
Accuracy ±1 min. per month at 25°C Ambient temperature
IP05 Operating 0–50°C
Pulse encoder inputs 3 for incremental pulse encoders Non-operating -25°C to +70°C
(channel 1, 2 plus zero pulse).
1 input for ZER0 ENABLE. Differen- Relative humidity 10–95%
tial or single-ended signals. Single- Protection class IP20
ended signals: active high or active Environment Industrial premises
low
Electrical Fulfils Low Voltage Directive
Input voltage 12–24 VDC environment 73/23/EEC and
Pulse rate Selectable from pulse encoder x1, ElectroMagnetic Compatibility, EMC,
x2 pr x0.5 Directive 89/336/EEC

Dimensions
Ø 6,5

Ø12
47
20

276
15

PWR 24V
25

00 40
01 41
02 42
03 43
04 44
05 45
06 46
07 47
10 48
11 49
12 50
13 51
14 52
15 53
16 54
17 55
150

200

20 56
21 57
22 58
23 59
24 60
25 61
26 62
27 63
30 64
31 65
00000. AE Andersson Grafiska AB. Printed in Sweden 1995.

32 66
33 67
34 70
35 71
36 72
37 73
38 78
25

39 79
INPUT OUTPUT

300
320
342

Telephone: HEAD OFFICE: Malmö, Sweden: +46 40 222000, fax: +46 40 219539, intmarketing@automation.alfalaval.se. ARGENTINA: Buenos Aires: +54 1 7462300, AUSTRIA: Wien: +43 1 6155511, BELGIUM: Brys-
9512 Ver. 1-1
493-0676-11

sels: +32 2 7283802, BRAZIL: Sao Paulo: +55 11 5481311, CANADA: Scarborough: +1 416 2996101, CHINA: Beijing: +86 10 3475661, CZECK REPUBLIC: Praha: +42 2 7812882, DENMARK: København: +45 42 848844,
Silkeborg: +45 86 822811, FINLAND: Espoo: +358 0 804041, FRANCE: Les Clayes-Sous-Bois: +33 1 30818181, GERMANY: München: +49 89 84000-0, Berlin: +49 30 4211371, Chemnitz: +49 371 304712, Glinde:
+49 40 727409, Haan: +49 2129 9357-0, HONG KONG: +852 2857 6600, HUNGARY: Budapest: +36 1 1536647, INDIA: Puna: +91 212 776321, IRELAND: Dublin: +353 1 4573399, ITALY: Monza: +39 39 27071, NETHERLANDS:
Etten-Leur: +31 76 5086200, NORWAY: Oslo: +47 63 878730, Larvik: +47 33 185765, Trondheim: +47 74 826962, POLAND: Warzaw: +48 22 266570, PORTUGAL: Carnaxide: +351 417 3358, SINGAPORE: Jurong:
+65 862 2711, SLOVAK REPUBLIC: Bratislava: +42 7 27094310, SOUTH AFRICA: Johannesburg: +27 11 3921602/16, SPAIN: Madrid: +34 1 3790663, SWEDEN: Göteborg: +46 31 582441, Karlskoga: +46 586 39330, Stock-
holm: +46 8 53066100, Sundsvall: +46 60 129381, SWITZERLAND: Kloten: +41 1 8046600, UNITED KINGDOM: Northwich: + 44 1606 49935, USA: Pleasant Prairie: +1 414 9472423.
Alfa Laval Automation reserves the right to change specifications given in text and pictures, without notice., Copyright © 1995 Alfa Laval Automation AB. Printed in Sweden.