Enclosure Heat Dissipation

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

Enclosure

Pesa = k x S x ΔT

Required Loss in W 377


451.44 Pesa
5.5 k
4.56 S
18 ΔT
35 Temp Inside
17 Temp Outside

H W D
HE208 1.15 0.85 0.27 3.035
HE207 0.95 0.7 0.27 2.221
HE206 0.85 0.6 0.27 1.803
HE205 0.75 0.55 0.27 1.527
HE204 0.65 0.45 0.27 1.179
HE203 0.55 0.4 0.27 0.953
HE202 0.45 0.3 0.27 0.675
HE201 0.35 0.25 0.27 0.499
Custom 1.8 0.6 0.5 4.56

Forced Ventilation
V = (3.1 x Pexhaust) / ΔT

0V
0 Pexhaust
18 ΔT

No. of Fans
FF08 10 m3/hr 0
FF12 18 m3/hr 0
FF15 115 m3/hr 0
FF20 520 m3/hr 0
Enclosure

Power dissipated from within the enclosure via exposed surface area in W (Watts)
Heat transfer coefficient [sheet metal ~ 5.5W/m2K, plastic ~ 3.5W/m2K ]
Corrected enclosure surface area of the enclosure, in m2 in accordance with IEC890.
Temperature differential (inside enclosure - outside ambient), in °C
Can't be more than manufacturers requirements or 40C.

m2
m2
m2
m2
m2
m2
m2
m2
m2

Forced Ventilation

Volume of air flow required, in m3/hr


Power exhausted from within the enclosure, in W (Watts)
Temperature differential (inside enclosure - outside ambient), in °C
23-016-P-UNIDO Panel heat calculation

EWD Tag Product No Panel Heat Loss [W] EWD Tag Product No Panel Heat Loss [W]
100Q0 3VA1063-2ED32-0AA0 1 17.31 101G0 6EP1434-2BA20 2 2.07
100P0 7KM3220-1BA01-1EA0 1 101F1 5SL4110-7 2 1.2
100F0 5SL4302-7 1 1.2 130F0 5SL4202-7 2 1.2
100F1 5SL4202-7 1 1.2 130F1 5SL4202-7 2 1.2
100F2 5SL4310-7 1 1.2 130F2 5SL4202-7 2 1.2
100F3 5SL4210-7 1 1.2 130F3 5SL4202-7 2 1.2
100F4 5SL4202-7 1 1.2 130F4 5SL4202-7 2 1.2
100F5 5SY4211-7 1 1.2 130F5 5SL4202-7 2 1.2
100F6 5SL4201-7 1 1.2 130F6 5SL4202-7 2 1.2
100F7 3NP1133-1CA10 1 51 130F7 5SL4202-7 2 1.2
101Q0 3RV2011-1DA10 1 7.25 ALL LZS:RT4A4L24 2 9.2
200BF1 5SL4310-8 2 1.2
TOTAL HEAT LOSS FOR PANEL 1 83.96 102BU1 FC-202P4K0 2 124
201BF1 5SL4310-8 2 1.2
102BU2 FC-202P4K0 2 124
202AQ1 3RV2021-4EA10 2 13.5
202AK1 3RT2027-1NB30 2 63
203AQ1 3RV2011-1KA10 2 9.25
203AK1 3RT2023-1NB30 2 1.4
204AQ1 3RV2011-1KA10 2 9.25
204AK1 3RT2023-1NB30 2 1.4
EWD Tag Product No Panel Heat Loss [W] 300F1 5SL4410-7 2 0.9
CPU S71500 3 5.7 300K1 3RT2023-1NB30 2 1.4
DI 6ES7521-1BH00-0AB0 3 2.6 301F1 5SY7504-7CC 2 1.3
DO 6ES7522-1BF00-0AB0 3 6.8 302F1 5SY7504-7CC 2 1.3
AI x 2 6ES7531-7KF00-0AB0 3 5.4 303F1 5SY7504-7CC 2 1.3
AO 6ES7532-5HD00-0AB0 3 4 304F1 5SY7504-7CC 2 1.3

TOTAL HEAT LOSS FOR PANEL 3 24.5 TOTAL HEAT LOSS FOR PANEL 2 377.77
FORMULA

V = airflow in m3/h
V =(f x Q) / (Ti - Ta)

Where:
V = airflow in m3/h
f = factor in m3.K/Wh
Q = total heat to be transferred in W
Ti = temperature inside the enclosure in °C
Ta = ambient temperature in °C
f = cp x ρ (specific heat of air x density of air)

Assumptions
Ti = 35 & Ta = 23

Air flow required for panel 1: 21.69 m3/hr


Air flow required for panel 2: 97.59 m3/hr
Air flow required for panel 3: 6.33 m3/hr

Air flow required for panel 1: 12.78 CFM


Air flow required for panel 2: 57.48 CFM
Air flow required for panel 3: 3.73 CFM

Formulas used are taken from the Danfoss Frequency Drive (VLT AQUA FC202) Design Guide, Section 3.13 Cooling.