Name: PLC date: Number of faults: 0

LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0


Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

Nov 22, 2023

16:19:13.413 Preheating Message 2 - On


16:19:13.402 P126 Flow monitoring engine circuit Message 2 - Running
16:19:11.613 Jacket water circuit pump Message 2 - On
16:19:11.613 Speed governor Message 2 - On
16:19:11.612 Ignition Message 2 - On
16:19:11.602 Auxilaries test mode Message - Off
16:19:11.512 Genset operation mode Message - Auto
16:18:54.886 GK control valve limit stop warm Message 2 - Appears
16:18:47.686 HK control valve limit stop warm Message 2 - Appears
16:17:41.086 GK control valve limit stop cold Message 2 - Disap.

16:17:38.185 HK control valve limit stop cold Message 2 - Disap.


16:17:27.486 GK control valve limit stop cold Message 2 - Appears
16:17:23.586 HK control valve limit stop cold Message 2 - Appears
16:16:13.986 HK control valve limit stop warm Message 2 - Disap.
16:16:13.186 GK control valve limit stop warm Message 2 - Disap.
16:15:59.686 GK control valve limit stop warm Message 2 - Appears
16:15:55.886 HK control valve limit stop warm Message 2 - Appears
16:15:50.302 P126 Flow monitoring engine circuit Message 2 - Stopped
16:15:29.534 System message: 0xb0000000 System -
16:14:46.486 HK control valve limit stop cold Message 2 - Disap.

16:14:45.886 GK control valve limit stop cold Message 2 - Disap.


16:14:33.286 GK control valve limit stop cold Message 2 - Appears
16:14:20.086 HK control valve limit stop cold Message 2 - Appears
16:14:13.129 System message: 0xb0000000 System -
16:13:18.986 GK control valve limit stop warm Message 2 - Disap.
16:13:10.686 HK control valve limit stop warm Message 2 - Disap.
16:13:03.514 Jacket water circuit pump Message 2 - Off
16:13:03.514 Preheating Message 2 - Off
16:13:03.513 Speed governor Message 2 - Off
16:13:03.513 Ignition Message 2 - Off

16:13:03.502 Auxilaries test mode Message - On


16:12:56.813 Genset operation mode Message - Manual
16:12:45.386 E596 Circuit breaker auxiliaries Fault - Acknowledged
16:12:45.386 Acknowledge (fault) Message 2 - Acknowledged
16:10:20.486 E596 Circuit breaker auxiliaries Message 2 - Off
16:10:20.385 E596 Circuit breaker auxiliaries Message 2 - On
16:10:08.585 E596 Circuit breaker auxiliaries Message 2 - Off
16:10:08.486 E596 Circuit breaker auxiliaries Message 2 - On
16:09:55.086 E596 Circuit breaker auxiliaries Message 2 - Off
16:09:53.386 E596 Circuit breaker auxiliaries Message 2 - On

16:09:52.885 E596 Circuit breaker auxiliaries Message 2 - Off


16:09:28.385 E596 Circuit breaker auxiliaries Fault - Appears
--> 16:12:45.386 E596 Circuit breaker auxiliaries Fault - Acknowledged
16:09:27.786 E596 Circuit breaker auxiliaries Message 2 - On
11:50:59.187 GK control valve limit stop warm Message 2 - Appears
11:49:45.287 GK control valve limit stop cold Message 2 - Disap.
11:49:43.688 P309 Flow monitoring intercooler circuit Message 2 - Stopped
11:49:40.715 Intercooler circuit pump Message 2 - Off
11:45:05.287 GK control valve limit stop cold Message 2 - Appears
11:36:40.387 GK control valve limit stop warm Message 2 - Disap.
11:30:38.794 Lifting knock level warm-up active Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

11:20:32.514 Bridge Δp-monitoring in the AWT circuit Message 2 - Off


11:19:51.104 Ignition enable Message 2 - Disabled
11:19:42.600 Gas mixer limit stop lean Message 2 - Appears
11:19:41.016 Prelubrication pump Message 2 - Off
11:19:40.904 Ignition enable Message 2 - Enabled
11:19:40.611 E199.7 Demand active Message 2 - Disap.
11:19:40.587 E100 Demand Message 2 - Off
11:19:34.408 Gas mixer start position OK Message 2 - Appears
11:19:33.001 Gas mixer limit stop lean Message 2 - Disap.
11:19:32.815 Reset emergency stop module Message 2 - Off

11:19:32.515 Prelubrication pump Message 2 - On


11:19:32.315 Bridge Δp-monitoring in the AWT circuit Message 2 - On
11:19:32.315 Reset emergency stop module Message 2 - On
11:19:32.301 Start Message - On
11:19:32.207 E199.7 Demand active Message 2 - Appears 100.0 % 30.0 %
11:19:32.188 E100 Demand Message 2 - On
11:19:15.988 P309 Flow monitoring intercooler circuit Fault - Acknowledged
11:19:15.988 Acknowledge (fault) Message 2 - Acknowledged
11:18:37.488 P309 Flow monitoring intercooler circuit Message 2 - Running
11:17:03.188 P309 Flow monitoring intercooler circuit Message 2 - Stopped

11:17:00.388 P309 Flow monitoring intercooler circuit Message 2 - Running


11:16:52.992 P196 Lube oil before filter Fault - Acknowledged
11:16:52.992 Acknowledge (fault) Message 2 - Acknowledged
11:16:38.914 Bridge Δp-monitoring in the AWT circuit Message 2 - Off
11:16:37.788 P309 Flow monitoring intercooler circuit Message 2 - Stopped
11:16:35.188 P309 Flow monitoring intercooler circuit Message 2 - Running
11:16:33.304 Ignition enable Message 2 - Disabled
11:16:19.488 P309 Flow monitoring intercooler circuit Message 2 - Stopped
11:16:19.107 E199.7 Demand active Message 2 - Disap.
11:16:19.087 E100 Demand Message 2 - Off

11:16:17.499 ZA Ignites Message 2 - Off


11:16:17.288 P309 Flow monitoring intercooler circuit Message 2 - Running
11:16:15.000 Gas mixer limit stop lean Message 2 - Appears
11:16:13.715 Prelubrication pump Message 2 - Off
11:16:13.213 Gas valve A2 Message 2 - Off
11:16:13.213 Gas valve A1 Message 2 - Off
11:16:13.117 Net starting device Message 2 - Off
11:16:13.116 Starter Message 2 - Off
11:16:13.092 P196 Lube oil before filter Fault - Appears 0.02 bar 0.30 bar
--> 11:16:52.992 P196 Lube oil before filter Fault - Acknowledged
11:16:13.088 P309 Flow monitoring intercooler circuit Fault -
--> 11:19:15.988 P309 Flow monitoring intercooler circuit Fault - Acknowledged

11:16:13.018 Gas valve A2 Message 2 - On


11:16:13.018 Gas valve A1 Message 2 - On
11:16:13.000 ZA Ignites Message 2 - On
11:16:12.606 Ignition enable Message 2 - Enabled
11:16:09.215 Net starting device Message 2 - On
11:16:09.214 Starter Message 2 - On
11:16:08.088 P309 Flow monitoring intercooler circuit Message 2 - Stopped
11:15:46.715 Preheating Message 2 - On
11:15:42.604 P126 Flow monitoring engine circuit Message 2 - Running
11:15:41.088 P309 Flow monitoring intercooler circuit Message 2 - Running
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

11:15:40.815 Intercooler circuit pump Message 2 - On


11:15:40.807 Gas mixer start position OK Message 2 - Appears
11:15:39.815 Jacket water circuit pump Message 2 - On
11:15:39.400 Gas mixer limit stop lean Message 2 - Disap.
11:15:39.220 Reset emergency stop module Message 2 - Off
11:15:38.915 Prelubrication pump Message 2 - On
11:15:38.794 Lifting knock level warm-up active Message 2 - On
11:15:38.716 Bridge Δp-monitoring in the AWT circuit Message 2 - On
11:15:38.715 Reset emergency stop module Message 2 - On
11:15:38.701 Start Message - On

11:15:38.606 E199.7 Demand active Message 2 - Appears 100.0 % 30.0 %


11:15:38.587 E100 Demand Message 2 - On
10:21:30.488 GK control valve limit stop warm Message 2 - Appears
10:21:09.188 P309 Flow monitoring intercooler circuit Message 2 - Stopped
10:21:06.615 Intercooler circuit pump Message 2 - Off
10:10:52.105 P126 Flow monitoring engine circuit Message 2 - Stopped
10:07:35.316 Jacket water circuit pump Message 2 - Off
09:57:56.689 P309 Flow monitoring intercooler circuit Fault - Acknowledged
09:57:56.689 Acknowledge (fault) Message 2 - Acknowledged
09:57:32.988 P309 Flow monitoring intercooler circuit Message 2 - Running

09:57:08.188 P309 Flow monitoring intercooler circuit Fault -


--> 09:57:56.689 P309 Flow monitoring intercooler circuit Fault - Acknowledged
09:57:03.188 P309 Flow monitoring intercooler circuit Message 2 - Stopped
09:54:11.788 HK control valve limit stop warm Message 2 - Appears
09:51:37.115 Bridge Δp-monitoring in the AWT circuit Message 2 - Off
09:51:08.317 Engine running Message - Stopped
09:51:08.102 Gas mixer limit stop lean Message 2 - Appears
09:50:57.599 ZA Ignites Message 2 - Off
09:50:57.204 Ignition enable Message 2 - Disabled
09:50:37.115 Gas valve A2 Message 2 - Off
09:50:37.115 Gas valve A1 Message 2 - Off

09:50:36.988 Island operation mode Message - On


09:50:36.916 Bridge Δp-monitoring in the AWT circuit Message 2 - On
09:50:36.889 G106 Power switch Message - Off
09:50:36.817 Power switch enable Message - Off
09:49:51.589 S101 Speed Minus Message 2 - Off
09:49:51.090 S101 Speed Minus Message 2 - On
09:49:49.089 S101 Speed Minus Message 2 - Off
09:49:48.588 S101 Speed Minus Message 2 - On
09:49:46.588 S101 Speed Minus Message 2 - Off
09:49:46.088 S101 Speed Minus Message 2 - On

09:49:44.089 S101 Speed Minus Message 2 - Off


09:49:43.589 S101 Speed Minus Message 2 - On
09:49:41.589 S101 Speed Minus Message 2 - Off
09:49:41.089 S101 Speed Minus Message 2 - On
09:49:39.088 S101 Speed Minus Message 2 - Off
09:49:38.589 S101 Speed Minus Message 2 - On
09:49:38.206 E198.2 Actual power Message 2 - Disap.
09:49:36.588 S101 Speed Minus Message 2 - Off
09:49:36.089 S101 Speed Minus Message 2 - On
09:49:34.089 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:49:33.588 S101 Speed Minus Message 2 - On


09:49:31.589 S101 Speed Minus Message 2 - Off
09:49:31.089 S101 Speed Minus Message 2 - On
09:49:29.089 S101 Speed Minus Message 2 - Off
09:49:28.588 S101 Speed Minus Message 2 - On
09:49:26.588 S101 Speed Minus Message 2 - Off
09:49:26.089 S101 Speed Minus Message 2 - On
09:49:24.088 S101 Speed Minus Message 2 - Off
09:49:23.589 S101 Speed Minus Message 2 - On
09:49:21.588 S101 Speed Minus Message 2 - Off

09:49:21.088 S101 Speed Minus Message 2 - On


09:49:19.089 S101 Speed Minus Message 2 - Off
09:49:18.589 S101 Speed Minus Message 2 - On
09:49:18.508 E199.7 Demand active Message 2 - Disap.
09:49:18.488 E100 Demand Message 2 - Off
09:49:16.589 S101 Speed Minus Message 2 - Off
09:49:16.089 S101 Speed Minus Message 2 - On
09:49:14.088 S101 Speed Minus Message 2 - Off
09:49:13.589 S101 Speed Minus Message 2 - On
09:49:11.588 S101 Speed Minus Message 2 - Off

09:49:11.089 S101 Speed Minus Message 2 - On


09:49:09.089 S101 Speed Minus Message 2 - Off
09:49:08.590 S101 Speed Minus Message 2 - On
09:49:06.589 S101 Speed Minus Message 2 - Off
09:49:06.088 S101 Speed Minus Message 2 - On
09:48:59.089 S101 Speed Minus Message 2 - Off
09:48:58.589 S101 Speed Minus Message 2 - On
09:48:49.089 S101 Speed Minus Message 2 - Off
09:48:48.589 S101 Speed Minus Message 2 - On
09:48:44.089 S101 Speed Minus Message 2 - Off

09:48:43.589 S101 Speed Minus Message 2 - On


09:48:34.089 S101 Speed Minus Message 2 - Off
09:48:33.589 S101 Speed Minus Message 2 - On
09:48:04.088 S101 Speed Minus Message 2 - Off
09:48:03.590 S101 Speed Minus Message 2 - On
09:47:54.089 S101 Speed Minus Message 2 - Off
09:47:53.589 S101 Speed Minus Message 2 - On
09:47:51.588 S101 Speed Minus Message 2 - Off
09:47:51.089 S101 Speed Minus Message 2 - On
09:47:49.089 S101 Speed Minus Message 2 - Off

09:47:48.589 S101 Speed Minus Message 2 - On


09:47:46.589 S101 Speed Minus Message 2 - Off
09:47:46.089 S101 Speed Minus Message 2 - On
09:47:44.088 S101 Speed Minus Message 2 - Off
09:47:43.589 S101 Speed Minus Message 2 - On
09:47:41.588 S101 Speed Minus Message 2 - Off
09:47:41.089 S101 Speed Minus Message 2 - On
09:47:39.088 S101 Speed Minus Message 2 - Off
09:47:38.588 S101 Speed Minus Message 2 - On
09:47:36.589 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:47:36.089 S101 Speed Minus Message 2 - On


09:47:34.088 S101 Speed Minus Message 2 - Off
09:47:33.589 S101 Speed Minus Message 2 - On
09:47:31.589 S101 Speed Minus Message 2 - Off
09:47:31.088 S101 Speed Minus Message 2 - On
09:47:29.088 S101 Speed Minus Message 2 - Off
09:47:28.589 S101 Speed Minus Message 2 - On
09:47:26.588 S101 Speed Minus Message 2 - Off
09:47:26.089 S101 Speed Minus Message 2 - On
09:47:24.089 S101 Speed Minus Message 2 - Off

09:47:23.588 S101 Speed Minus Message 2 - On


09:47:21.588 S101 Speed Minus Message 2 - Off
09:47:21.089 S101 Speed Minus Message 2 - On
09:47:19.089 S101 Speed Minus Message 2 - Off
09:47:18.589 S101 Speed Minus Message 2 - On
09:47:16.589 S101 Speed Minus Message 2 - Off
09:47:16.089 S101 Speed Minus Message 2 - On
09:47:14.089 S101 Speed Minus Message 2 - Off
09:47:13.589 S101 Speed Minus Message 2 - On
09:47:11.588 S101 Speed Minus Message 2 - Off

09:47:11.088 S101 Speed Minus Message 2 - On


09:47:09.089 S101 Speed Minus Message 2 - Off
09:47:08.589 S101 Speed Minus Message 2 - On
09:47:06.589 S101 Speed Minus Message 2 - Off
09:47:06.088 S101 Speed Minus Message 2 - On
09:47:04.089 S101 Speed Minus Message 2 - Off
09:47:03.588 S101 Speed Minus Message 2 - On
09:47:01.589 S101 Speed Minus Message 2 - Off
09:47:01.089 S101 Speed Minus Message 2 - On
09:46:59.089 S101 Speed Minus Message 2 - Off

09:46:58.589 S101 Speed Minus Message 2 - On


09:46:56.589 S101 Speed Minus Message 2 - Off
09:46:56.088 S101 Speed Minus Message 2 - On
09:46:54.088 S101 Speed Minus Message 2 - Off
09:46:53.589 S101 Speed Minus Message 2 - On
09:46:51.588 S101 Speed Minus Message 2 - Off
09:46:51.089 S101 Speed Minus Message 2 - On
09:46:49.089 S101 Speed Minus Message 2 - Off
09:46:48.589 S101 Speed Minus Message 2 - On
09:46:46.588 S101 Speed Minus Message 2 - Off

09:46:46.088 S101 Speed Minus Message 2 - On


09:46:44.089 S101 Speed Minus Message 2 - Off
09:46:43.588 S101 Speed Minus Message 2 - On
09:45:44.088 S101 Speed Minus Message 2 - Off
09:45:43.689 S101 Speed Minus Message 2 - On
09:45:31.588 S101 Speed Minus Message 2 - Off
09:45:31.189 S101 Speed Minus Message 2 - On
09:45:26.588 S101 Speed Minus Message 2 - Off
09:45:26.188 S101 Speed Minus Message 2 - On
09:45:24.089 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:45:23.689 S101 Speed Minus Message 2 - On


09:45:14.088 S101 Speed Minus Message 2 - Off
09:45:13.688 S101 Speed Minus Message 2 - On
09:45:09.089 S101 Speed Minus Message 2 - Off
09:45:08.689 S101 Speed Minus Message 2 - On
09:45:06.589 S101 Speed Minus Message 2 - Off
09:45:06.189 S101 Speed Minus Message 2 - On
09:45:04.088 S101 Speed Minus Message 2 - Off
09:45:03.689 S101 Speed Minus Message 2 - On
09:45:01.589 S101 Speed Minus Message 2 - Off

09:45:01.189 S101 Speed Minus Message 2 - On


09:44:59.089 S101 Speed Minus Message 2 - Off
09:44:58.689 S101 Speed Minus Message 2 - On
09:44:56.589 S101 Speed Minus Message 2 - Off
09:44:56.188 S101 Speed Minus Message 2 - On
09:44:54.089 S101 Speed Minus Message 2 - Off
09:44:53.688 S101 Speed Minus Message 2 - On
09:44:51.689 S101 Speed Minus Message 2 - Off
09:44:51.189 S101 Speed Minus Message 2 - On
09:44:49.189 S101 Speed Minus Message 2 - Off

09:44:48.689 S101 Speed Minus Message 2 - On


09:44:46.689 S101 Speed Minus Message 2 - Off
09:44:46.189 S101 Speed Minus Message 2 - On
09:44:44.188 S101 Speed Minus Message 2 - Off
09:44:43.689 S101 Speed Minus Message 2 - On
09:44:41.689 S101 Speed Minus Message 2 - Off
09:44:41.189 S101 Speed Minus Message 2 - On
09:44:39.189 S101 Speed Minus Message 2 - Off
09:44:38.688 S101 Speed Minus Message 2 - On
09:44:36.688 S101 Speed Minus Message 2 - Off

09:44:36.188 S101 Speed Minus Message 2 - On


09:44:34.189 S101 Speed Minus Message 2 - Off
09:44:33.689 S101 Speed Minus Message 2 - On
09:44:31.689 S101 Speed Minus Message 2 - Off
09:44:31.189 S101 Speed Minus Message 2 - On
09:44:29.189 S101 Speed Minus Message 2 - Off
09:44:28.689 S101 Speed Minus Message 2 - On
09:44:26.688 S101 Speed Minus Message 2 - Off
09:44:26.189 S101 Speed Minus Message 2 - On
09:44:24.189 S101 Speed Minus Message 2 - Off

09:44:23.689 S101 Speed Minus Message 2 - On


09:44:21.689 S101 Speed Minus Message 2 - Off
09:44:21.188 S101 Speed Minus Message 2 - On
09:44:19.188 S101 Speed Minus Message 2 - Off
09:44:18.689 S101 Speed Minus Message 2 - On
09:44:16.689 S101 Speed Minus Message 2 - Off
09:44:16.189 S101 Speed Minus Message 2 - On
09:44:14.189 S101 Speed Minus Message 2 - Off
09:44:13.689 S101 Speed Minus Message 2 - On
09:44:11.688 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:44:11.189 S101 Speed Minus Message 2 - On


09:44:09.188 S101 Speed Minus Message 2 - Off
09:44:08.690 S101 Speed Minus Message 2 - On
09:44:06.688 S101 Speed Minus Message 2 - Off
09:44:06.188 S101 Speed Minus Message 2 - On
09:44:04.189 S101 Speed Minus Message 2 - Off
09:44:03.688 S101 Speed Minus Message 2 - On
09:44:01.689 S101 Speed Minus Message 2 - Off
09:44:01.189 S101 Speed Minus Message 2 - On
09:43:59.189 S101 Speed Minus Message 2 - Off

09:43:58.688 S101 Speed Minus Message 2 - On


09:43:56.688 S101 Speed Minus Message 2 - Off
09:43:56.189 S101 Speed Minus Message 2 - On
09:43:54.189 S101 Speed Minus Message 2 - Off
09:43:53.689 S101 Speed Minus Message 2 - On
09:43:51.689 S101 Speed Minus Message 2 - Off
09:43:51.188 S101 Speed Minus Message 2 - On
09:43:49.189 S101 Speed Minus Message 2 - Off
09:43:48.688 S101 Speed Minus Message 2 - On
09:43:46.689 S101 Speed Minus Message 2 - Off

09:43:46.189 S101 Speed Minus Message 2 - On


09:43:44.188 S101 Speed Minus Message 2 - Off
09:43:43.689 S101 Speed Minus Message 2 - On
09:43:41.688 S101 Speed Minus Message 2 - Off
09:43:41.189 S101 Speed Minus Message 2 - On
09:43:39.189 S101 Speed Minus Message 2 - Off
09:43:38.688 S101 Speed Minus Message 2 - On
09:43:36.689 S101 Speed Minus Message 2 - Off
09:43:36.189 S101 Speed Minus Message 2 - On
09:43:34.189 S101 Speed Minus Message 2 - Off

09:43:33.688 S101 Speed Minus Message 2 - On


09:43:31.688 S101 Speed Minus Message 2 - Off
09:43:31.189 S101 Speed Minus Message 2 - On
09:43:29.188 S101 Speed Minus Message 2 - Off
09:43:28.689 S101 Speed Minus Message 2 - On
09:43:26.689 S101 Speed Minus Message 2 - Off
09:43:26.189 S101 Speed Minus Message 2 - On
09:43:24.189 S101 Speed Minus Message 2 - Off
09:43:23.689 S101 Speed Minus Message 2 - On
09:43:21.689 S101 Speed Minus Message 2 - Off

09:43:21.188 S101 Speed Minus Message 2 - On


09:43:19.188 S101 Speed Minus Message 2 - Off
09:43:18.688 S101 Speed Minus Message 2 - On
09:43:16.689 S101 Speed Minus Message 2 - Off
09:43:16.189 S101 Speed Minus Message 2 - On
09:43:14.189 S101 Speed Minus Message 2 - Off
09:43:13.688 S101 Speed Minus Message 2 - On
09:43:11.688 S101 Speed Minus Message 2 - Off
09:43:11.189 S101 Speed Minus Message 2 - On
09:43:09.190 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:43:08.689 S101 Speed Minus Message 2 - On


09:43:06.689 S101 Speed Minus Message 2 - Off
09:43:06.189 S101 Speed Minus Message 2 - On
09:43:04.188 S101 Speed Minus Message 2 - Off
09:43:03.688 S101 Speed Minus Message 2 - On
09:43:01.689 S101 Speed Minus Message 2 - Off
09:43:01.189 S101 Speed Minus Message 2 - On
09:42:59.189 S101 Speed Minus Message 2 - Off
09:42:58.689 S101 Speed Minus Message 2 - On
09:42:56.688 S101 Speed Minus Message 2 - Off

09:42:56.189 S101 Speed Minus Message 2 - On


09:42:54.189 S101 Speed Minus Message 2 - Off
09:42:53.689 S101 Speed Minus Message 2 - On
09:42:51.689 S101 Speed Minus Message 2 - Off
09:42:51.189 S101 Speed Minus Message 2 - On
09:42:49.189 S101 Speed Minus Message 2 - Off
09:42:48.689 S101 Speed Minus Message 2 - On
09:42:46.689 S101 Speed Minus Message 2 - Off
09:42:46.189 S101 Speed Minus Message 2 - On
09:42:44.189 S101 Speed Minus Message 2 - Off

09:42:43.689 S101 Speed Minus Message 2 - On


09:42:41.689 S101 Speed Minus Message 2 - Off
09:42:41.188 S101 Speed Minus Message 2 - On
09:42:39.188 S101 Speed Minus Message 2 - Off
09:42:38.689 S101 Speed Minus Message 2 - On
09:42:36.689 S101 Speed Minus Message 2 - Off
09:42:36.188 S101 Speed Minus Message 2 - On
09:42:34.189 S101 Speed Minus Message 2 - Off
09:42:33.688 S101 Speed Minus Message 2 - On
09:42:31.688 S101 Speed Minus Message 2 - Off

09:42:31.189 S101 Speed Minus Message 2 - On


09:42:29.189 S101 Speed Minus Message 2 - Off
09:42:28.688 S101 Speed Minus Message 2 - On
09:42:26.689 S101 Speed Minus Message 2 - Off
09:42:26.189 S101 Speed Minus Message 2 - On
09:42:24.188 S101 Speed Minus Message 2 - Off
09:42:23.690 S101 Speed Minus Message 2 - On
09:42:21.689 S101 Speed Minus Message 2 - Off
09:42:21.188 S101 Speed Minus Message 2 - On
09:42:19.189 S101 Speed Minus Message 2 - Off

09:42:18.689 S101 Speed Minus Message 2 - On


09:42:16.689 S101 Speed Minus Message 2 - Off
09:42:16.189 S101 Speed Minus Message 2 - On
09:42:14.189 S101 Speed Minus Message 2 - Off
09:42:13.689 S101 Speed Minus Message 2 - On
09:42:11.689 S101 Speed Minus Message 2 - Off
09:42:11.189 S101 Speed Minus Message 2 - On
09:42:09.189 S101 Speed Minus Message 2 - Off
09:42:08.689 S101 Speed Minus Message 2 - On
09:42:06.689 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:42:06.189 S101 Speed Minus Message 2 - On


09:42:04.189 S101 Speed Minus Message 2 - Off
09:42:03.689 S101 Speed Minus Message 2 - On
09:42:01.689 S101 Speed Minus Message 2 - Off
09:42:01.189 S101 Speed Minus Message 2 - On
09:41:59.189 S101 Speed Minus Message 2 - Off
09:41:58.689 S101 Speed Minus Message 2 - On
09:41:56.688 S101 Speed Minus Message 2 - Off
09:41:56.189 S101 Speed Minus Message 2 - On
09:41:54.189 S101 Speed Minus Message 2 - Off

09:41:53.688 S101 Speed Minus Message 2 - On


09:41:51.689 S101 Speed Minus Message 2 - Off
09:41:51.189 S101 Speed Minus Message 2 - On
09:41:49.189 S101 Speed Minus Message 2 - Off
09:41:48.689 S101 Speed Minus Message 2 - On
09:41:46.689 S101 Speed Minus Message 2 - Off
09:41:46.189 S101 Speed Minus Message 2 - On
09:41:44.189 S101 Speed Minus Message 2 - Off
09:41:43.688 S101 Speed Minus Message 2 - On
09:41:41.688 S101 Speed Minus Message 2 - Off

09:41:41.189 S101 Speed Minus Message 2 - On


09:41:39.188 S101 Speed Minus Message 2 - Off
09:41:38.689 S101 Speed Minus Message 2 - On
09:41:36.688 S101 Speed Minus Message 2 - Off
09:41:36.189 S101 Speed Minus Message 2 - On
09:41:34.188 S101 Speed Minus Message 2 - Off
09:41:33.689 S101 Speed Minus Message 2 - On
09:41:31.688 S101 Speed Minus Message 2 - Off
09:41:31.189 S101 Speed Minus Message 2 - On
09:41:29.188 S101 Speed Minus Message 2 - Off

09:41:28.689 S101 Speed Minus Message 2 - On


09:41:26.689 S101 Speed Minus Message 2 - Off
09:41:26.189 S101 Speed Minus Message 2 - On
09:41:24.189 S101 Speed Minus Message 2 - Off
09:41:23.688 S101 Speed Minus Message 2 - On
09:41:21.688 S101 Speed Minus Message 2 - Off
09:41:21.189 S101 Speed Minus Message 2 - On
09:41:19.188 S101 Speed Minus Message 2 - Off
09:41:18.689 S101 Speed Minus Message 2 - On
09:41:16.689 S101 Speed Minus Message 2 - Off

09:41:16.189 S101 Speed Minus Message 2 - On


09:41:14.189 S101 Speed Minus Message 2 - Off
09:41:13.688 S101 Speed Minus Message 2 - On
09:41:11.689 S101 Speed Minus Message 2 - Off
09:41:11.189 S101 Speed Minus Message 2 - On
09:41:09.189 S101 Speed Minus Message 2 - Off
09:41:08.689 S101 Speed Minus Message 2 - On
09:41:06.689 S101 Speed Minus Message 2 - Off
09:41:06.189 S101 Speed Minus Message 2 - On
09:41:04.189 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:41:03.688 S101 Speed Minus Message 2 - On


09:41:01.689 S101 Speed Minus Message 2 - Off
09:41:01.189 S101 Speed Minus Message 2 - On
09:40:59.189 S101 Speed Minus Message 2 - Off
09:40:58.689 S101 Speed Minus Message 2 - On
09:40:56.689 S101 Speed Minus Message 2 - Off
09:40:56.189 S101 Speed Minus Message 2 - On
09:40:54.189 S101 Speed Minus Message 2 - Off
09:40:53.688 S101 Speed Minus Message 2 - On
09:40:51.688 S101 Speed Minus Message 2 - Off

09:40:51.188 S101 Speed Minus Message 2 - On


09:40:49.188 S101 Speed Minus Message 2 - Off
09:40:48.688 S101 Speed Minus Message 2 - On
09:40:46.689 S101 Speed Minus Message 2 - Off
09:40:46.188 S101 Speed Minus Message 2 - On
09:40:44.189 S101 Speed Minus Message 2 - Off
09:40:43.688 S101 Speed Minus Message 2 - On
09:40:41.689 S101 Speed Minus Message 2 - Off
09:40:41.189 S101 Speed Minus Message 2 - On
09:40:39.188 S101 Speed Minus Message 2 - Off

09:40:38.689 S101 Speed Minus Message 2 - On


09:40:36.689 S101 Speed Minus Message 2 - Off
09:40:36.188 S101 Speed Minus Message 2 - On
09:40:34.188 S101 Speed Minus Message 2 - Off
09:40:33.689 S101 Speed Minus Message 2 - On
09:40:31.689 S101 Speed Minus Message 2 - Off
09:40:31.189 S101 Speed Minus Message 2 - On
09:40:29.189 S101 Speed Minus Message 2 - Off
09:40:28.689 S101 Speed Minus Message 2 - On
09:40:26.689 S101 Speed Minus Message 2 - Off

09:40:26.188 S101 Speed Minus Message 2 - On


09:40:24.188 S101 Speed Minus Message 2 - Off
09:40:23.689 S101 Speed Minus Message 2 - On
09:40:21.689 S101 Speed Minus Message 2 - Off
09:40:21.189 S101 Speed Minus Message 2 - On
09:40:19.189 S101 Speed Minus Message 2 - Off
09:40:18.689 S101 Speed Minus Message 2 - On
09:40:16.689 S101 Speed Minus Message 2 - Off
09:40:16.189 S101 Speed Minus Message 2 - On
09:40:14.189 S101 Speed Minus Message 2 - Off

09:40:13.689 S101 Speed Minus Message 2 - On


09:40:11.689 S101 Speed Minus Message 2 - Off
09:40:11.188 S101 Speed Minus Message 2 - On
09:40:09.189 S101 Speed Minus Message 2 - Off
09:40:08.689 S101 Speed Minus Message 2 - On
09:40:06.688 S101 Speed Minus Message 2 - Off
09:40:06.189 S101 Speed Minus Message 2 - On
09:40:04.189 S101 Speed Minus Message 2 - Off
09:40:03.689 S101 Speed Minus Message 2 - On
09:39:54.189 S101 Speed Minus Message 2 - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:39:53.689 S101 Speed Minus Message 2 - On


09:39:34.189 S101 Speed Minus Message 2 - Off
09:39:33.689 S101 Speed Minus Message 2 - On
09:38:59.188 S101 Speed Minus Message 2 - Off
09:38:58.688 S101 Speed Minus Message 2 - On
09:38:34.189 S101 Speed Minus Message 2 - Off
09:38:33.689 S101 Speed Minus Message 2 - On
09:38:31.689 S101 Speed Minus Message 2 - Off
09:38:31.189 S101 Speed Minus Message 2 - On
09:38:29.189 S101 Speed Minus Message 2 - Off

09:38:28.688 S101 Speed Minus Message 2 - On


09:38:26.689 S101 Speed Minus Message 2 - Off
09:38:26.189 S101 Speed Minus Message 2 - On
09:38:24.188 S101 Speed Minus Message 2 - Off
09:38:23.689 S101 Speed Minus Message 2 - On
09:38:21.689 S101 Speed Minus Message 2 - Off
09:38:21.189 S101 Speed Minus Message 2 - On
09:38:19.188 S101 Speed Minus Message 2 - Off
09:38:18.689 S101 Speed Minus Message 2 - On
09:38:16.688 S101 Speed Minus Message 2 - Off

09:20:03.090 Gas Pressure Low Alarm - Acknowledged


09:19:44.189 Gas Pressure Low Alarm -
--> 09:20:03.090 Gas Pressure Low Alarm - Acknowledged
09:13:30.890 Gas Pressure Low Alarm - Acknowledged
09:13:01.589 Gas Pressure Low Alarm -
--> 09:13:30.890 Gas Pressure Low Alarm - Acknowledged
09:11:19.690 Gas Pressure Low Alarm - Acknowledged
09:11:02.389 Gas Pressure Low Alarm -
--> 09:11:19.690 Gas Pressure Low Alarm - Acknowledged
09:07:53.490 Gas Pressure Low Alarm - Acknowledged
09:07:37.089 Gas Pressure Low Alarm -
--> 09:07:53.490 Gas Pressure Low Alarm - Acknowledged
08:54:49.591 Gas Pressure Low Alarm - Acknowledged
08:53:58.990 Gas Pressure Low Alarm -
--> 08:54:49.591 Gas Pressure Low Alarm - Acknowledged

08:45:12.491 Gas Pressure Low Alarm - Acknowledged


08:44:56.089 Gas Pressure Low Alarm -
--> 08:45:12.491 Gas Pressure Low Alarm - Acknowledged
07:44:39.190 Gas Pressure Low Alarm - Acknowledged
07:44:14.789 Gas Pressure Low Alarm -
--> 07:44:39.190 Gas Pressure Low Alarm - Acknowledged
07:26:41.754 Island operation mode Message - Off
01:44:31.651 Island operation mode Message - On

Nov 21, 2023

23:05:36.953 Island operation mode Message - Off


23:04:51.452 Island operation mode Message - On
23:04:51.352 Island operation mode Message - Off
22:46:22.752 Island operation mode Message - On
21:06:58.253 Island operation mode Message - Off
21:06:58.253 G106 Power switch Message - On
21:06:10.080 Power switch enable Message - On
21:05:55.282 Engine running Message - Running
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

21:05:18.066 Start Message - On


21:04:32.259 Safety chain Fault - Acknowledged

21:04:32.257 E121 Generator protection Fault - Acknowledged


21:04:32.255 Generator Protection Fault - Acknowledged
21:04:32.254 P309 Flow monitoring intercooler circuit Fault - Acknowledged
21:04:31.954 Gas Pressure Low Alarm - Acknowledged
21:04:06.880 Engine running Message - Stopped
21:03:41.053 P309 Flow monitoring intercooler circuit Fault -
--> 21:04:32.254 P309 Flow monitoring intercooler circuit Fault - Acknowledged
21:03:34.181 Power switch enable Message - Off
21:03:34.156 Safety chain Fault -
--> 21:04:32.259 Safety chain Fault - Acknowledged
21:03:34.155 E121 Generator protection Fault -
--> 21:04:32.257 E121 Generator protection Fault - Acknowledged
21:03:34.154 Generator Protection Fault -
--> 21:04:32.255 Generator Protection Fault - Acknowledged

21:03:34.153 G106 Power switch Message - Off


21:03:28.769 Maximum knocking force B side Message - Disap.
21:03:28.769 Maximum knocking force A side Message - Disap.
21:03:28.569 Maximum knocking force B side Message - Appears 27 % 20 %
21:03:28.468 Maximum knocking force A side Message - Appears 34 % 20 %
21:03:24.953 Gas Pressure Low Alarm -
--> 21:04:31.954 Gas Pressure Low Alarm - Acknowledged
21:02:48.769 Maximum knocking force B side Message - Disap.
21:02:48.768 Maximum knocking force B side Message - Disap.
21:02:48.668 Maximum knocking force A side Message - Disap.
21:02:48.668 Maximum knocking force A side Message - Disap.

21:02:48.569 Maximum knocking force B side Message - Appears 42 % 40 %


21:02:48.468 Maximum knocking force A side Message - Appears 48 % 40 %
21:02:48.468 Maximum knocking force B side Message - Appears 23 % 20 %
21:02:48.368 Maximum knocking force A side Message - Appears 38 % 20 %
20:04:37.453 Island operation mode Message - On
11:10:40.538 Gas Pressure Low Alarm - Acknowledged
11:09:52.336 Gas Pressure Low Alarm -
--> 11:10:40.538 Gas Pressure Low Alarm - Acknowledged
10:49:45.537 Gas Pressure Low Alarm - Acknowledged
10:49:28.436 Gas Pressure Low Alarm -
--> 10:49:45.537 Gas Pressure Low Alarm - Acknowledged
07:50:07.639 Gas Pressure Low Alarm - Acknowledged

07:49:52.537 Gas Pressure Low Alarm -


--> 07:50:07.639 Gas Pressure Low Alarm - Acknowledged
07:43:04.438 Gas Pressure Low Alarm - Acknowledged
07:42:28.137 Gas Pressure Low Alarm -
--> 07:43:04.438 Gas Pressure Low Alarm - Acknowledged
07:26:17.410 Island operation mode Message - Off

Nov 20, 2023


Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

19:57:45.506 Island operation mode Message - On


17:43:22.036 Gas Pressure Low Alarm - Acknowledged
17:43:02.430 Gas Pressure Low Alarm -
--> 17:43:22.036 Gas Pressure Low Alarm - Acknowledged
17:28:00.643 Gas Pressure Low Alarm - Acknowledged
17:27:36.050 Gas Pressure Low Alarm -
--> 17:28:00.643 Gas Pressure Low Alarm - Acknowledged
17:24:57.600 Gas Pressure Low Alarm - Acknowledged
17:24:41.103 Gas Pressure Low Alarm -
--> 17:24:57.600 Gas Pressure Low Alarm - Acknowledged
16:58:31.673 Island operation mode Message - Off
15:04:42.881 G106 Power switch Message - On
15:04:16.107 Power switch enable Message - On

15:04:01.215 Engine running Message - Running


15:03:24.593 Start Message - On
15:03:18.081 P309 Flow monitoring intercooler circuit Fault - Acknowledged
15:03:09.884 Safety chain Fault - Acknowledged
15:03:09.883 E121 Generator protection Fault - Acknowledged
15:03:09.881 Generator Protection Fault - Acknowledged
14:55:31.807 Engine running Message - Stopped
14:55:05.981 P309 Flow monitoring intercooler circuit Fault -
--> 15:03:18.081 P309 Flow monitoring intercooler circuit Fault - Acknowledged
14:54:58.183 Safety chain Fault -
--> 15:03:09.884 Safety chain Fault - Acknowledged
14:54:58.181 Island operation mode Message - On

14:54:58.180 G106 Power switch Message - Off


14:54:58.108 Power switch enable Message - Off
14:54:58.082 E121 Generator protection Fault -
--> 15:03:09.883 E121 Generator protection Fault - Acknowledged
14:54:58.080 Generator Protection Fault -
--> 15:03:09.881 Generator Protection Fault - Acknowledged
14:54:27.981 Island operation mode Message - Off
14:54:27.980 G106 Power switch Message - On
14:54:19.808 Power switch enable Message - On
14:54:05.107 Engine running Message - Running
14:53:28.394 Start Message - On
14:53:28.184 Safety chain Fault - Acknowledged

14:53:28.183 E121 Generator protection Fault - Acknowledged


14:53:28.181 Generator Protection Fault - Acknowledged
14:52:37.507 Engine running Message - Stopped
14:52:05.283 Safety chain Fault -
--> 14:53:28.184 Safety chain Fault - Acknowledged
14:52:05.280 Island operation mode Message - On
14:52:05.280 G106 Power switch Message - Off
14:52:05.207 Power switch enable Message - Off
14:52:05.182 E121 Generator protection Fault -
--> 14:53:28.183 E121 Generator protection Fault - Acknowledged
14:52:05.180 Generator Protection Fault -
--> 14:53:28.181 Generator Protection Fault - Acknowledged
14:51:36.981 Island operation mode Message - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

14:51:36.980 G106 Power switch Message - On


14:51:24.307 Power switch enable Message - On
14:51:09.606 Engine running Message - Running
14:50:32.993 Start Message - On
14:50:29.881 P309 Flow monitoring intercooler circuit Fault - Acknowledged
14:50:27.583 E121 Generator protection Fault - Acknowledged
14:50:27.581 Generator Protection Fault - Acknowledged
14:48:23.107 Engine running Message - Stopped
14:48:03.782 Safety chain Fault - Acknowledged
14:47:57.780 P309 Flow monitoring intercooler circuit Fault -
--> 14:50:29.881 P309 Flow monitoring intercooler circuit Fault - Acknowledged

14:47:49.811 Power switch enable Message - Off


14:47:49.784 Safety chain Fault -
--> 14:48:03.782 Safety chain Fault - Acknowledged
14:47:49.783 E121 Generator protection Fault -
--> 14:50:27.583 E121 Generator protection Fault - Acknowledged
14:47:49.782 Generator Protection Fault -
--> 14:50:27.581 Generator Protection Fault - Acknowledged
14:47:49.781 Island operation mode Message - On
14:47:49.781 G106 Power switch Message - Off
14:47:12.081 Island operation mode Message - Off
14:47:12.081 G106 Power switch Message - On
14:47:09.907 Power switch enable Message - On
14:46:55.410 Engine running Message - Running

14:46:18.393 Start Message - On


14:46:15.697 P126 Flow monitoring engine circuit Fault - Acknowledged
14:46:15.283 T206 Jacket water engine outlet Alarm - Acknowledged
14:46:11.184 T206 Jacket water engine outlet Fault - Acknowledged
14:46:11.181 P309 Flow monitoring intercooler circuit Fault - Acknowledged
14:44:26.296 P126 Flow monitoring engine circuit Fault - Appears
--> 14:46:15.697 P126 Flow monitoring engine circuit Fault - Acknowledged
14:37:07.784 Safety chain Fault - Acknowledged
14:37:07.783 E121 Generator protection Fault - Acknowledged
14:37:07.781 Generator Protection Fault - Acknowledged
14:34:29.682 T206 Jacket water engine outlet Fault - Appears 99.5 °C 99.0 °C
--> 14:46:11.184 T206 Jacket water engine outlet Fault - Acknowledged

14:34:24.782 T206 Jacket water engine outlet Alarm - Appears 98.5 °C 98.0 °C
--> 14:46:15.283 T206 Jacket water engine outlet Alarm - Acknowledged
14:33:42.207 Engine running Message - Stopped
14:33:15.080 P309 Flow monitoring intercooler circuit Fault -
--> 14:46:11.181 P309 Flow monitoring intercooler circuit Fault - Acknowledged
14:33:08.809 Power switch enable Message - Off
14:33:08.783 Safety chain Fault -
--> 14:37:07.784 Safety chain Fault - Acknowledged
14:33:08.782 E121 Generator protection Fault -
--> 14:37:07.783 E121 Generator protection Fault - Acknowledged
14:33:08.781 Generator Protection Fault -
--> 14:37:07.781 Generator Protection Fault - Acknowledged
14:33:08.780 G106 Power switch Message - Off
14:33:05.880 Island operation mode Message - On
11:06:13.582 Gas Pressure Low Alarm - Acknowledged
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

11:05:59.681 Gas Pressure Low Alarm -


--> 11:06:13.582 Gas Pressure Low Alarm - Acknowledged
10:11:46.417 Gas Pressure Low Alarm - Acknowledged
10:10:18.241 Gas Pressure Low Alarm -
--> 10:11:46.417 Gas Pressure Low Alarm - Acknowledged
08:26:21.162 Gas Pressure Low Alarm - Acknowledged
08:24:39.362 Gas Pressure Low Alarm -
--> 08:26:21.162 Gas Pressure Low Alarm - Acknowledged
08:04:50.562 Gas Pressure Low Alarm - Acknowledged
08:04:24.861 Gas Pressure Low Alarm -
--> 08:04:50.562 Gas Pressure Low Alarm - Acknowledged
07:25:01.661 Island operation mode Message - Off
04:41:44.961 Island operation mode Message - On
03:19:43.761 Island operation mode Message - Off

03:00:14.961 Island operation mode Message - On


02:06:10.161 Island operation mode Message - Off
02:06:10.161 G106 Power switch Message - On
02:05:49.790 Power switch enable Message - On
02:05:35.591 Engine running Message - Running
02:04:58.374 Start Message - On
01:52:17.974 Start Message - On
01:51:36.675 Start Message - On
01:51:36.462 Generator Protection Fault - Acknowledged
01:51:36.063 E121 Generator protection Fault - Acknowledged

01:49:21.962 P309 Flow monitoring intercooler circuit Fault - Acknowledged


01:49:21.364 Safety chain Fault - Acknowledged
01:49:09.888 Engine running Message - Stopped
01:48:45.762 P309 Flow monitoring intercooler circuit Fault -
--> 01:49:21.962 P309 Flow monitoring intercooler circuit Fault - Acknowledged
01:48:38.790 Power switch enable Message - Off
01:48:38.764 Safety chain Fault -
--> 01:49:21.364 Safety chain Fault - Acknowledged
01:48:38.763 E121 Generator protection Fault -
--> 01:51:36.063 E121 Generator protection Fault - Acknowledged
01:48:38.762 Generator Protection Fault -
--> 01:51:36.462 Generator Protection Fault - Acknowledged
01:48:38.761 G106 Power switch Message - Off

Nov 19, 2023

19:42:48.041 Island operation mode Message - On


15:42:26.642 Gas Pressure Low Alarm - Acknowledged
15:41:52.442 Gas Pressure Low Alarm -
--> 15:42:26.642 Gas Pressure Low Alarm - Acknowledged
15:38:37.742 Island operation mode Message - Off
15:38:37.741 G106 Power switch Message - On
15:38:12.443 Gas Pressure Low Alarm - Acknowledged
15:38:10.068 Power switch enable Message - On
15:37:55.867 Engine running Message - Running
15:37:53.642 Gas Pressure Low Alarm -
--> 15:38:12.443 Gas Pressure Low Alarm - Acknowledged
15:37:22.926 System message: 0xb0000000 System -
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

15:37:18.755 Start Message - On


15:37:07.277 System reset Fault - Acknowledged
15:36:53.642 Black start Message - Off
15:36:53.641 Island operation mode Message - On
15:36:16.344 Black start Message - On
15:36:16.344 Island operation mode Message - Off
15:36:16.343 E596 Circuit breaker auxiliaries Fault - Acknowledge
system
15:36:15.936 Pre-heating enable ON Command - Enabled
15:36:15.736 System reset Fault - Appears 0 0
--> 15:37:07.277 System reset Fault - Acknowledged
15:36:13.263 System message: 0xe5050010 System -

15:35:58.175 System message: 0x01000001 System -


15:32:52.190 E149 Voltage supply Alarm - Appears 8.6 V 22.0 V
15:32:52.180 E149 Voltage supply Alarm - Appears 8.6 V 20.0 V
15:31:01.823 System message: 0xb0000000 System -
15:30:40.278 System reset Fault - Acknowledged
15:30:40.242 H117 Ext. quick stop without heat removal Fault - Acknowledged
15:30:40.241 E121 Generator protection Fault - Acknowledged
15:30:40.239 Emergency Stop Fault - Acknowledged
15:30:40.238 MCB Busber U Trip Fault - Acknowledged
15:30:40.237 Generator Protection Fault - Acknowledged

15:30:40.235 Collective fault CAN-Bus Fault - Acknowledged


15:30:39.934 I/O-C: -30K01 (COS) Alarm - Acknowledged
15:30:33.233 E596 Circuit breaker auxiliaries Fault - Appears
--> 15:36:16.343 E596 Circuit breaker auxiliaries Fault - Acknowledge system
15:30:32.634 Black start Message - Off
15:30:32.634 Island operation mode Message - On
15:29:55.323 E596 Circuit breaker auxiliaries Fault - Acknowledge system
15:29:54.917 Pre-heating enable ON Command - Enabled
15:29:54.717 System reset Fault - Appears 0 0
--> 15:30:40.278 System reset Fault - Acknowledged
15:29:52.242 System message: 0xe5050010 System -
15:29:37.171 System message: 0x01000001 System -

15:28:34.747 E149 Voltage supply Alarm - Appears 16.8 V 22.0 V


15:28:34.737 E149 Voltage supply Alarm - Appears 16.8 V 20.0 V
15:28:33.737 Black start Message - On
15:28:33.736 Island operation mode Message - Off
15:28:33.734 Collective fault CAN-Bus Fault - 0 0
--> 15:30:40.235 Collective fault CAN-Bus Fault - Acknowledged
15:28:33.533 MCB Busber U Trip Fault -
--> 15:30:40.238 MCB Busber U Trip Fault - Acknowledged
15:28:33.530 I/O-C: -30K01 (COS) Alarm - Appears 12544 0
--> 15:30:39.934 I/O-C: -30K01 (COS) Alarm - Acknowledged
15:28:33.035 H117 Ext. quick stop without heat removal Fault -
--> 15:30:40.242 H117 Ext. quick stop without heat removal Fault - Acknowledged
15:28:33.034 E121 Generator protection Fault -
--> 15:30:40.241 E121 Generator protection Fault - Acknowledged
15:28:33.033 Emergency Stop Fault -
--> 15:30:40.239 Emergency Stop Fault - Acknowledged
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

15:28:33.032 Generator Protection Fault -


--> 15:30:40.237 Generator Protection Fault - Acknowledged
15:25:25.360 Engine running Message - Stopped
15:24:51.833 Island operation mode Message - On
15:24:51.733 G106 Power switch Message - Off
15:24:51.660 Power switch enable Message - Off
15:24:51.632 E596 Circuit breaker auxiliaries Fault - Appears
--> 15:29:55.323 E596 Circuit breaker auxiliaries Fault - Acknowledge
system
14:40:56.130 Gas Pressure Low Alarm - Acknowledged
14:40:28.236 Gas Pressure Low Alarm -
--> 14:40:56.130 Gas Pressure Low Alarm - Acknowledged
11:37:15.318 Gas Pressure Low Alarm - Acknowledged
11:37:01.017 Gas Pressure Low Alarm -
--> 11:37:15.318 Gas Pressure Low Alarm - Acknowledged

07:43:41.421 Island operation mode Message - Off


07:43:41.421 G106 Power switch Message - On
07:42:06.748 Power switch enable Message - On
07:41:52.652 Engine running Message - Running
07:41:14.634 Start Message - On

Nov 18, 2023

13:27:05.797 P126 Flow monitoring engine circuit Fault - Acknowledged


11:04:12.298 P126 Flow monitoring engine circuit Fault - Appears
--> 13:27:05.797 P126 Flow monitoring engine circuit Fault - Acknowledged
08:06:12.685 P309 Flow monitoring intercooler circuit Fault - Acknowledged
08:05:37.912 Engine running Message - Stopped
08:05:08.912 Power switch enable Message - Off
08:05:08.885 P309 Flow monitoring intercooler circuit Fault -
--> 08:06:12.685 P309 Flow monitoring intercooler circuit Fault - Acknowledged
08:05:01.085 G106 Power switch Message - Off
08:04:30.785 Island operation mode Message - On
08:04:30.085 Island operation mode Message - Off
08:04:30.085 G106 Power switch Message - On

08:03:18.812 Power switch enable Message - On


08:03:14.086 Gas Pressure Low Alarm - Acknowledged
08:02:58.410 Engine running Message - Running
08:02:54.985 Gas Pressure Low Alarm -
--> 08:03:14.086 Gas Pressure Low Alarm - Acknowledged
08:02:20.198 Start Message - On
05:46:59.214 Engine running Message - Stopped
05:46:27.987 Island operation mode Message - On
05:46:27.886 G106 Power switch Message - Off
05:46:27.817 Power switch enable Message - Off
02:45:43.990 Island operation mode Message - Off

02:45:43.989 G106 Power switch Message - On


02:45:24.617 Power switch enable Message - On
02:45:07.818 Engine running Message - Running
02:44:30.503 Start Message - On
01:45:40.518 Engine running Message - Stopped
01:45:09.091 Island operation mode Message - On
01:45:08.991 G106 Power switch Message - Off
01:45:08.919 Power switch enable Message - Off
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

Nov 17, 2023

17:33:37.105 Island operation mode Message - Off


16:40:00.546 Island operation mode Message - On
16:40:00.446 Island operation mode Message - Off
16:38:58.428 Island operation mode Message - On
16:38:58.329 Island operation mode Message - Off
16:21:20.711 Island operation mode Message - On
13:53:29.961 Island operation mode Message - Off
13:52:02.761 Island operation mode Message - On
13:52:02.461 Island operation mode Message - Off
13:39:41.261 G106 Power switch Message - On

13:38:40.289 Power switch enable Message - On


13:38:25.989 Engine running Message - Running
13:37:49.175 Start Message - On
13:36:54.488 Engine running Message - Stopped
13:36:52.375 Start abortion Message - On 4 0
13:36:44.487 Engine running Message - Running
13:36:16.189 Engine running Message - Stopped
13:36:14.874 Start abortion Message - On 4 0
13:36:08.487 Engine running Message - Running
13:35:31.075 Start Message - On

13:35:28.579 P126 Flow monitoring engine circuit Fault - Acknowledged


13:35:28.562 P309 Flow monitoring intercooler circuit Fault - Acknowledged
13:28:15.777 P126 Flow monitoring engine circuit Fault - Appears
--> 13:35:28.579 P126 Flow monitoring engine circuit Fault - Acknowledged
13:25:03.662 P309 Flow monitoring intercooler circuit Fault -
--> 13:35:28.562 P309 Flow monitoring intercooler circuit Fault - Acknowledged
13:24:38.889 Engine running Message - Stopped
13:24:36.075 Start abortion Message - On 4 0
13:24:31.489 Engine running Message - Running
13:23:54.675 Start Message - On
13:23:15.875 Start Message - On
13:23:15.662 P309 Flow monitoring intercooler circuit Fault - Acknowledged

13:22:59.461 P309 Flow monitoring intercooler circuit Fault -


--> 13:23:15.662 P309 Flow monitoring intercooler circuit Fault - Acknowledged
13:22:53.389 Engine running Message - Stopped
13:22:51.375 Start abortion Message - On 4 0
13:22:44.690 Engine running Message - Running
13:22:16.289 Engine running Message - Stopped
13:22:14.675 Start abortion Message - On 4 0
13:22:10.791 Engine running Message - Running
13:21:33.975 Start Message - On
13:20:53.862 P309 Flow monitoring intercooler circuit Fault - Acknowledged
13:16:41.614 P309 Flow monitoring intercooler circuit Fault -
--> 13:20:53.862 P309 Flow monitoring intercooler circuit Fault - Acknowledged

12:47:09.473 Engine running Message - Stopped


12:46:37.956 Island operation mode Message - On
12:46:37.855 G106 Power switch Message - Off
12:46:37.783 Power switch enable Message - Off
07:24:05.047 Island operation mode Message - Off
07:23:25.646 Island operation mode Message - On
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

07:23:25.446 Island operation mode Message - Off


07:22:15.146 Island operation mode Message - On
07:22:14.947 Island operation mode Message - Off
07:21:25.246 Island operation mode Message - On

07:21:25.046 Island operation mode Message - Off


04:57:05.548 Island operation mode Message - On
04:36:25.348 Island operation mode Message - Off
04:32:38.149 Island operation mode Message - On
02:46:23.850 Island operation mode Message - Off
02:46:23.849 G106 Power switch Message - On
02:45:56.476 Power switch enable Message - On
02:45:39.978 Engine running Message - Running
02:45:02.263 Start Message - On
01:45:44.788 Engine running Message - Stopped

01:45:13.470 Island operation mode Message - On


01:45:13.369 G106 Power switch Message - Off
01:45:13.296 Power switch enable Message - Off

Nov 16, 2023

22:35:18.533 Island operation mode Message - Off


22:14:40.633 Island operation mode Message - On
14:50:33.940 Gas Pressure Low Alarm - Acknowledged
14:49:51.739 Gas Pressure Low Alarm -
--> 14:50:33.940 Gas Pressure Low Alarm - Acknowledged
11:18:46.321 Island operation mode Message - Off
11:18:46.320 G106 Power switch Message - On
11:18:35.349 Power switch enable Message - On
11:18:19.351 Engine running Message - Running
11:17:41.934 Start Message - On
11:15:51.041 P126 Flow monitoring engine circuit Fault - Acknowledged

11:15:51.026 Safety chain Fault - Acknowledged


11:15:51.025 E121 Generator protection Fault - Acknowledged
11:15:51.022 Generator Protection Fault - Acknowledged
11:15:51.021 P309 Flow monitoring intercooler circuit Fault - Acknowledged
11:13:32.122 Gas Pressure Low Alarm - Acknowledged
11:10:24.537 P126 Flow monitoring engine circuit Fault - Appears
--> 11:15:51.041 P126 Flow monitoring engine circuit Fault - Acknowledged
11:09:25.847 Engine running Message - Stopped
11:09:02.321 P309 Flow monitoring intercooler circuit Fault -
--> 11:15:51.021 P309 Flow monitoring intercooler circuit Fault - Acknowledged
11:08:55.721 G106 Power switch Message - Off
11:08:55.648 Power switch enable Message - Off

11:08:55.624 Safety chain Fault -


--> 11:15:51.026 Safety chain Fault - Acknowledged
11:08:55.623 E121 Generator protection Fault -
--> 11:15:51.025 E121 Generator protection Fault - Acknowledged
11:08:55.621 Generator Protection Fault -
--> 11:15:51.022 Generator Protection Fault - Acknowledged
11:08:49.521 Gas Pressure Low Alarm -
--> 11:13:32.122 Gas Pressure Low Alarm - Acknowledged
10:21:02.024 Gas Pressure Low Alarm - Acknowledged
10:18:33.522 Gas Pressure Low Alarm -
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

--> 10:21:02.024 Gas Pressure Low Alarm - Acknowledged


10:18:32.421 Island operation mode Message - On
08:56:50.024 Gas Pressure Low Alarm - Acknowledged
08:56:32.423 Gas Pressure Low Alarm -
--> 08:56:50.024 Gas Pressure Low Alarm - Acknowledged
08:25:58.024 Gas Pressure Low Alarm - Acknowledged

08:25:27.523 Gas Pressure Low Alarm -


--> 08:25:58.024 Gas Pressure Low Alarm - Acknowledged
07:19:55.924 Island operation mode Message - Off
07:19:15.029 Island operation mode Message - On
07:19:14.830 Island operation mode Message - Off
07:18:34.641 Island operation mode Message - On
07:18:34.441 Island operation mode Message - Off
05:11:04.705 Island operation mode Message - On
04:37:59.906 Island operation mode Message - Off
04:37:59.905 G106 Power switch Message - On
04:37:11.532 Power switch enable Message - On

04:36:56.233 Engine running Message - Running


04:36:19.119 Start Message - On
04:36:14.511 Safety chain Fault - Acknowledged
04:36:14.509 E121 Generator protection Fault - Acknowledged
04:36:14.507 Generator Protection Fault - Acknowledged
04:36:14.506 P309 Flow monitoring intercooler circuit Fault - Acknowledged
04:34:17.832 Engine running Message - Stopped
04:33:51.205 P309 Flow monitoring intercooler circuit Fault -
--> 04:36:14.506 P309 Flow monitoring intercooler circuit Fault - Acknowledged
04:33:44.234 Power switch enable Message - Off
04:33:44.209 Safety chain Fault -
--> 04:36:14.511 Safety chain Fault - Acknowledged

04:33:44.208 E121 Generator protection Fault -


--> 04:36:14.509 E121 Generator protection Fault - Acknowledged
04:33:44.206 Generator Protection Fault -
--> 04:36:14.507 Generator Protection Fault - Acknowledged
04:33:44.205 G106 Power switch Message - Off
02:37:07.671 Island operation mode Message - On
02:35:23.503 Island operation mode Message - Off
02:35:23.502 G106 Power switch Message - On
02:34:43.342 Power switch enable Message - On
02:34:27.745 Engine running Message - Running
02:33:50.344 Start Message - On
01:47:57.814 Engine running Message - Stopped

01:47:26.487 Island operation mode Message - On


01:47:26.387 G106 Power switch Message - Off
01:47:26.315 Power switch enable Message - Off

Nov 15, 2023

15:28:21.774 Gas Pressure Low Alarm - Acknowledged


15:28:02.073 Gas Pressure Low Alarm -
--> 15:28:21.774 Gas Pressure Low Alarm - Acknowledged
14:41:19.274 Gas Pressure Low Alarm - Acknowledged
14:40:40.873 Gas Pressure Low Alarm -
--> 14:41:19.274 Gas Pressure Low Alarm - Acknowledged
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

09:16:21.577 Gas Pressure Low Alarm - Acknowledged


09:15:24.876 Gas Pressure Low Alarm -
--> 09:16:21.577 Gas Pressure Low Alarm - Acknowledged
08:37:31.577 Gas Pressure Low Alarm - Acknowledged
08:37:01.176 Gas Pressure Low Alarm -
--> 08:37:31.577 Gas Pressure Low Alarm - Acknowledged
07:13:07.294 Island operation mode Message - Off
02:46:29.759 Island operation mode Message - On

02:40:36.260 Island operation mode Message - Off


02:40:36.259 G106 Power switch Message - On
02:40:25.786 Power switch enable Message - On
02:40:10.385 Engine running Message - Running
02:39:33.272 Start Message - On
01:44:26.487 Engine running Message - Stopped
01:43:55.359 Island operation mode Message - On
01:43:55.259 G106 Power switch Message - Off
01:43:55.186 Power switch enable Message - Off

Nov 14, 2023

21:01:46.411 Lube oil filling Message - Off


21:00:59.125 Lube oil filling Message - On
20:50:59.205 Lube oil filling Message - Off
20:49:59.124 Lube oil filling Message - On
20:39:59.205 Lube oil filling Message - Off
20:38:59.022 Lube oil filling Message - On
20:28:59.001 Lube oil filling Message - Off
20:27:58.918 Lube oil filling Message - On
20:17:58.970 Lube oil filling Message - Off
20:16:58.869 Lube oil filling Message - On

20:06:58.669 Lube oil filling Message - Off


20:05:58.568 Lube oil filling Message - On
19:55:58.370 Lube oil filling Message - Off
19:54:58.270 Lube oil filling Message - On
19:44:58.169 Lube oil filling Message - Off
19:43:58.069 Lube oil filling Message - On
19:33:57.970 Lube oil filling Message - Off
19:32:57.770 Lube oil filling Message - On
19:22:57.670 Lube oil filling Message - Off
19:21:57.571 Lube oil filling Message - On

19:11:57.608 Lube oil filling Message - Off


19:10:57.428 Lube oil filling Message - On
19:00:57.507 Lube oil filling Message - Off
18:59:57.425 Lube oil filling Message - On
18:49:57.405 Lube oil filling Message - Off
18:48:57.223 Lube oil filling Message - On
18:38:57.304 Lube oil filling Message - Off
18:37:57.224 Lube oil filling Message - On
18:27:57.201 Lube oil filling Message - Off
18:26:57.119 Lube oil filling Message - On
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

18:16:57.151 Lube oil filling Message - Off


18:15:56.951 Lube oil filling Message - On
18:05:56.849 Lube oil filling Message - Off
18:04:56.757 Lube oil filling Message - On
17:54:56.649 Lube oil filling Message - Off
17:53:56.450 Lube oil filling Message - On
17:43:56.250 Lube oil filling Message - Off
17:42:56.150 Lube oil filling Message - On
17:32:55.951 Lube oil filling Message - Off
17:31:55.851 Lube oil filling Message - On

17:21:55.749 Lube oil filling Message - Off


17:20:55.550 Lube oil filling Message - On
17:10:55.351 Lube oil filling Message - Off
17:09:55.251 Lube oil filling Message - On
16:59:55.152 Lube oil filling Message - Off
16:58:55.059 Lube oil filling Message - On
16:48:54.951 Lube oil filling Message - Off
16:47:54.851 Lube oil filling Message - On
16:37:54.750 Lube oil filling Message - Off
16:36:54.550 Lube oil filling Message - On

16:26:54.450 Lube oil filling Message - Off


16:25:54.351 Lube oil filling Message - On
16:15:54.249 Lube oil filling Message - Off
16:14:54.051 Lube oil filling Message - On
16:04:53.950 Lube oil filling Message - Off
16:03:53.850 Lube oil filling Message - On
15:53:53.651 Lube oil filling Message - Off
15:52:53.551 Lube oil filling Message - On
15:42:53.451 Lube oil filling Message - Off
15:41:53.351 Lube oil filling Message - On

15:31:53.251 Lube oil filling Message - Off


15:31:42.923 Island operation mode Message - Off
15:30:53.050 Lube oil filling Message - On
15:20:52.852 Lube oil filling Message - Off
15:19:52.652 Lube oil filling Message - On
15:09:52.451 Lube oil filling Message - Off
15:08:52.451 Lube oil filling Message - On
15:04:35.123 G106 Power switch Message - On
15:03:02.151 Power switch enable Message - On
15:02:48.449 Engine running Message - Running

15:02:10.436 Start Message - On


15:01:16.636 Oil change activated Message - Off
15:00:56.850 Genset operation mode Message - Auto
15:00:52.850 Genset operation mode Message - Manual
15:00:27.441 Oil filter change is due Alarm - Acknowledged
15:00:27.440 Oil change is due Alarm - Acknowledged
15:00:27.429 L234.1 Lube oil level Alarm - Acknowledged
15:00:27.424 Gas Pressure Low Alarm - Acknowledged
14:59:54.728 L234.1 Lube oil level Fault - Acknowledged
14:58:00.349 Genset operation mode Message - Auto
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

14:57:56.119 Reset bearing lubrication Command - Input


14:57:52.320 Reset change of oil filter Command - Input
14:44:45.442 P126 Flow monitoring engine circuit Fault - Acknowledged
14:44:45.424 P309 Flow monitoring intercooler circuit Fault - Acknowledged
14:41:27.023 Gas Pressure Low Alarm -
--> 15:00:27.424 Gas Pressure Low Alarm - Acknowledged
14:35:43.927 L234.1 Lube oil level Fault - Appears 120.2 % 120.0 %
--> 14:59:54.728 L234.1 Lube oil level Fault - Acknowledged
14:34:46.027 L234.1 Lube oil level Alarm - Appears 110.6 % 110.0 %
--> 15:00:27.429 L234.1 Lube oil level Alarm - Acknowledged
14:33:53.428 L234.1 Lube oil level Alarm - Auto acknowledge
13:14:06.228 L234.1 Lube oil level Alarm - Appears 34.8 % 40.0 %
--> 14:33:53.428 L234.1 Lube oil level Alarm - Auto acknowledge
13:09:33.540 P126 Flow monitoring engine circuit Fault - Appears
--> 14:44:45.442 P126 Flow monitoring engine circuit Fault - Acknowledged

13:03:48.437 Oil change activated Message - On


12:55:06.450 Genset operation mode Message - Manual
12:54:57.923 P309 Flow monitoring intercooler circuit Fault -
--> 14:44:45.424 P309 Flow monitoring intercooler circuit Fault - Acknowledged
12:40:02.151 Engine running Message - Stopped
12:39:30.924 Island operation mode Message - On
12:39:30.824 G106 Power switch Message - Off
12:39:30.752 Power switch enable Message - Off
05:46:04.306 Island operation mode Message - Off
03:02:06.507 Island operation mode Message - On
02:41:58.707 Island operation mode Message - Off

02:41:58.607 G106 Power switch Message - On


02:41:15.033 Power switch enable Message - On
02:40:59.832 Engine running Message - Running
02:40:22.021 Start Message - On
01:39:49.434 Engine running Message - Stopped
01:39:18.207 Island operation mode Message - On
01:39:18.107 G106 Power switch Message - Off
01:39:18.035 Power switch enable Message - Off

Nov 13, 2023

12:20:34.272 Gas Pressure Low Alarm - Acknowledged


12:19:44.670 Gas Pressure Low Alarm -
--> 12:20:34.272 Gas Pressure Low Alarm - Acknowledged
12:05:37.971 Gas Pressure Low Alarm - Acknowledged
12:05:22.671 Gas Pressure Low Alarm -
--> 12:05:37.971 Gas Pressure Low Alarm - Acknowledged
07:34:52.778 Island operation mode Message - Off

Nov 12, 2023

23:34:54.032 Island operation mode Message - On


17:07:21.312 Island operation mode Message - Off
17:07:21.312 G106 Power switch Message - On
17:06:51.740 Power switch enable Message - On
17:06:37.340 Engine running Message - Running
17:06:00.125 Start Message - On
17:05:40.312 E596 Circuit breaker auxiliaries Fault - Acknowledged
17:04:59.811 E596 Circuit breaker auxiliaries Fault - Appears
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

--> 17:05:40.312 E596 Circuit breaker auxiliaries Fault - Acknowledged


17:04:51.525 Start Message - On
16:59:15.112 E596 Circuit breaker auxiliaries Fault - Acknowledged

16:51:13.938 Engine running Message - Stopped


16:50:39.912 Island operation mode Message - On
16:50:39.812 G106 Power switch Message - Off
16:50:39.738 Power switch enable Message - Off
16:50:39.711 E596 Circuit breaker auxiliaries Fault - Appears
--> 16:59:15.112 E596 Circuit breaker auxiliaries Fault - Acknowledged
13:49:01.613 Island operation mode Message - Off
13:49:01.613 G106 Power switch Message - On
13:48:34.938 Power switch enable Message - On
13:48:20.340 Engine running Message - Running
13:47:42.925 Start Message - On

13:47:16.538 Engine running Message - Stopped


13:47:02.116 P196 Lube oil before filter Fault - Acknowledged
13:46:59.818 P196 Lube oil before filter Alarm - Acknowledged
13:46:49.716 P196 Lube oil before filter Fault - Appears 2.35 bar 2.80 bar
--> 13:47:02.116 P196 Lube oil before filter Fault - Acknowledged
13:46:49.716 P196 Lube oil before filter Alarm - Appears 2.35 bar 3.00 bar
--> 13:46:59.818 P196 Lube oil before filter Alarm - Acknowledged
13:46:44.839 Engine running Message - Running
13:46:07.525 Start Message - On
12:48:26.439 Engine running Message - Stopped
12:47:55.212 Island operation mode Message - On
12:47:55.111 G106 Power switch Message - Off

12:47:55.039 Power switch enable Message - Off


08:16:57.741 Island operation mode Message - Off
08:16:57.741 G106 Power switch Message - On
08:16:16.355 Power switch enable Message - On
08:16:02.053 Engine running Message - Running
08:15:24.827 Start Message - On
08:15:19.313 P309 Flow monitoring intercooler circuit Fault - Acknowledged
08:10:04.617 P309 Flow monitoring intercooler circuit Fault -
--> 08:15:19.313 P309 Flow monitoring intercooler circuit Fault - Acknowledged
08:05:39.864 Engine running Message - Stopped
08:05:08.154 Power switch enable Message - Off

08:05:07.929 Island operation mode Message - On


08:05:07.928 G106 Power switch Message - Off
07:44:36.460 Island operation mode Message - Off
07:44:36.459 G106 Power switch Message - On
07:43:28.764 Power switch enable Message - On
07:43:14.969 Engine running Message - Running
07:42:37.336 Start Message - On
07:26:52.741 E596 Circuit breaker auxiliaries Fault - Acknowledged
07:25:17.111 E596 Circuit breaker auxiliaries Fault - Appears
--> 07:26:52.741 E596 Circuit breaker auxiliaries Fault - Acknowledged
07:21:12.703 System message: 0xb0000000 System -
Name: PLC date: Number of faults: 0
LIZ Fashion Industry Ltd 22.11.2023 Number of alarms: 0
Comment: PLC release: State: Ready
Kathaltola,Shafipur,Gazipur 2.50.23 Operation mode: Island
Number: PLC operating system: Actual power: 0 kW
Com:-1711588 Date:-30.06.2022 2.53.04 Actual speed: 0.0 1/min
Engine type: Visualisation: Operation hours: 6648
TCG 2020V12K, ESN:221 6488 3.7.4 Starts: 1308
Serial number CPU-P: Serial number BRT: Serial number DZR:
400055100-11319 456910016 201006463

Date/time Ident Type - Event A B

07:21:06.572 System reset Fault - Acknowledged


07:20:43.630 Black start Message - Off
07:20:43.629 Island operation mode Message - On
07:20:06.320 Black start Message - On
07:20:06.320 Island operation mode Message - Off
07:20:06.319 E596 Circuit breaker auxiliaries Fault - Acknowledge
system
07:20:05.913 Pre-heating enable ON Command - Enabled