Professional Documents
Culture Documents
Multianalyser (Three-In-One)
Multianalyser (Three-In-One)
Multianalyser (Three-In-One)
MultiAnalyser
3-038R-R303V2-B
MultiAnalyser SF6
(three-in-one)
Special features
■ Gas type: SF6
■ Sensors: percentage in N2
■ Sensors: moisture
■ Sensors: SO
2
■ Features: storage of measuring results
■ Features: WiFi
■ Features: gas return system
Sensor data
Sensor Vol.-% Moisture SO2 Option: HF Option: Option: CO
H2 S
Measuring Velocity of Electronic Electrochem Electrochem Electrochem Electrochem
principle sound dew point ical ical ical ical
measureme reaction reaction reaction reaction
nt
(capacitive)
Measuring 0 –100 vol.- -60 to +20 0 – 20 ppm 0 – 10 ppm 0 – 100 ppm 0 – 500 ppm
range % °C 0 – 100 ppm
0 – 500 ppm
Measuring ± 0.5 vol.-% ± 2 °C (to > ± 2 % of ± 10 % of ± 2 % of ± 2 % of
accuracy -40 °C) measuring measuring measuring measuring
range range range range
± 3 °C (to
-40 °C)
SF6
Overview MultiAnalyser
SF6-%
Device SF6/N2 SF6/CF Moistu SO2 to SO2 to SO2 to HF to H2S to CO to
4 re 20 100 500 10 100 500
ppmv ppmv ppmv ppm ppm ppm
R101 X
R102 X
R111 X X
R201 X X
R211 X X X
R301 X X X
R302 X X X
R303 X X X
R311 X X X X
R312 X X X X
R313 X X X X
R401 X X X X
R402 X X X X
R403 X X X X
R413 X X X X X
R601 X X X X X X
R602 X X X X X X
R603 X X X X X X
R612 X X X X X X X
R613 X X X X X X X
Optional accessories
Options (on request): All devices with percentage measuring system are additionally available for SF6
concentrations in SF6/CF4 gas mixtures (measuring accuracy: ±2.0 vol. -%). Thus, it is possible to switch
over between the SF6/N2 and SF6/CF4 measurement.