1 DATA SHEET FOR DC UNINTERRUPTIBLE POWER SUPPLY UNIT

2 CLIENT: SHEET NO.;


3 GNPOC 1 OF 2
4 PROJECT: GREATER JOB NO.:
5 DIFFRA FPF AND FLOWLINES 4002-A94
6 EQUIPMENT NO.: LOCATION:
7 Greater Nile Petroleum Operating OGP Technical Services Sdn Bhd DIF-DCUPS-01 DIFFRA, SUDAN
Company
8 SERVICE NAME:
9

10 DATA SUPPLIED BY PURCHASER DATA SUPPLIED BY BIDDER/VENDOR


11 Applicable Specification, Codes and Standards General and Basic Data
12 1. Electrical Design Basis Manufacturers and Country of Manufacturers
13 2. Specification for UPS, 6610A Battery :
14 3. IEC 60146, 60439, 60478, 60529, 60896, 60947, ISO 3746 and BS 6290 Charger :
15 Power Supply / Rating Distribution Panel :
16 Supply Voltage : 230 V +/- 10% Technical Requirements
17 Supply Phases : 1 phase UPS Rating : KVA
18 Supply Frequency : 50 Hz +/- 3% Output Voltage No Load to Full Load :
19 System Neutral : Insulated [ ] Earthed [ X ] Battery Type :
20 Installation Atmospheric Conditions Guaranteed Battery Standby Time : hours
21 Altitude (Meters above sea level) : 403m Number of Cells Per Battery :
22 Location : Indoor in Airconditioning Ripple Content : %
23 Substation Construction
24 Outdoor Climate : Humid IP Classification of Equipment :
25 Design Ambient Temperature : 50 deg. Celcius Maximum Sound Power Level at 1m :
26 Minimum Ambient Temperature : 10 deg Celcius Type of Cooling :
27 Design Relative Humidity : 20% - 80% Weight of battery :
28 Technical Requirements Weight of battery rack :
29 Charger Duty : 2 x 100 % Weight of charger and cabinets :
30 DC Output Voltage No Load to Full Load : 24V +1% to -1% Battery dimensions :
31 DC Output Phases : 1 phase 2 wire Charger dimensions :
32 Battery Standby Time : 8 hours Power and Control Cable
33 Design Load : 1 kW (BIDDER to Confirm) Supply Cable Type./Size :
34 Ripple Content : <2% Control Cable Type/Size :
35 Battery Duty : 2x100%[X] 2x50%[ ]1x100%[ ] Output Cable Type/Size :
36 Battery Earth : Unearthed[X] Positive Pole[ ] DC Cable Type/Size :
37 Midpoint[ ]
38 Battery Type : Maintenance Free Lead Acid
39 Battery Location : Enclosure [ X ] Stands [ ]
40 Drip Tray : Required [ ] Not Required [ X ]
41 Battery Monitoring : Required [ X ] Not Required [ ]
42 Cable Entry to Cubicle : Top [ ] Bottom [ X ]
43 Earth Bar : 70 mm²
44 Earth Bar Position : Bottom of cabinet
45 Construction
46 IP Classification of Equipment : IP31
47 Label Language : ENGLISH
48 Paint Finish : Munsell N-7 light grey
49 Supplier Standard For
50 Specified Climate
51 Maximum Sound Power Level at 1m : 75dB(A)
52 Cooling : Natural without fan
53
54
55
56
57
58
59
60
61
62
63 REQUISITION NUMBER
64
65 0 APPROVED FOR ITB RA MSS MSS
66 B 8-Nov-02 ISSUED FOR COMMENTS RA MSS MSS DATA SHEET NUMBER
67 A 6-Nov-02 ISSUED FOR IDC RA MSS MSS
DIF-0015-ELC-ED-0009
19902:\grp06\petronas\excel\datashts\710003739.xls
68 REV DATE DESCRIPTION BY CHK'D APP'D
DIF-0015-ELC-ED-0009
69

19902:\grp06\petronas\excel\datashts\710003739.xls
1 DATA SHEET FOR DC UNINTERRUPTIBLE POWER SUPPLY UNIT
2 CLIENT: SHEET NO.;
3 GNPOC 2 OF 2
4 PROJECT: GREATER JOB NO.:
5 DIFFRA FPF AND FLOWLINES 4002-A94
6 EQUIPMENT NO.: LOCATION:
7 Greater Nile Petroleum Operating OGP Technical Services Sdn Bhd DIF-DCUPS-01 DIFFRA, SUDAN
Company
8 SERVICE NAME:
9

10 DATA SUPPLIED BY PURCHASER


11 Accessories Accessories (cont'd)
12 1. The following status indication shall be provided on the front panel 4. The following control facilities shall be provided
13 (refer remark no. 4) a. Rectifier Input Circuit Breaker
14 a. AC input supply available b. Rectifier On/Off Control Switch
15 b. Rectifier on & fault c. Auto/Off/Manual Selector Switch for Equalise and Float
16 c. Boost Charge on Charge Operation
17 d. Battery on d. Manual/Off Selector Switch for Boost Charge Operation
18 e. Battery MCCB tripped e. Boost Charge Duration Timer
19 f. Rectifier mains failure f. DC Output Voltage adjustment
20 g. Synchronisation failure g. DC Current Limit adjustment
21 h. DC earth fault h. Battery Isolation Circuit Breaker
22 i. Cubicle Over Temperature
23 Remarks
24 2. The following measurement shall be provided 1. Distribution Panel shall be supplied as part of UPS cabinet
25 a. AC Voltmeter measuring Charger input 2. Immunity from portable radio hand set to be provided
26 b. AC ammeter measuring Charger input 3. Separate cubicles required for Charger, Battery
27 c. DC voltmeter measuring DC circuit voltage and Distribution Panel
28 d. DC ammeter measuring Battery Charge and Discharge Current 4. All normal conditions to be indicated in green and
29 e. DC ammeter measuring charger output current abnormal conditions in red
30 5. Remote monitoring status of UPS to DCS shall be provided
31 3. The following alarm and protection functions shall be provided as common alarm
32 (refer remark no. 5 and 6) 6. Alarms associated with trip functions shall be hand reset
33 a. AC input phase undervoltage : alarm and trip rectifier 7. A buzzer shall be provided on the UPS/rectifier front panel to give
34 b. Rectifier failure : alarm and trip rectifier audible alarm. The buzzer shall be fitted with an alarm
35 c. DC overvoltage : alarm accept/reset feature
36 DC undervoltage : alarm 8. Anti-condensation heater shall be provided
37 d. Charger failure/battery discharging : alarm only
38 e. Battery disconnected : alarm only
39 f. DC earth fault : alarm only
40 g. Cubicle/inverter stack overtemperature : alarm and trip rectifier
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63 REQUISITION NUMBER
64
65 0 APPROVED FOR ITB RA MSS MSS
66 B 8-Nov-02 ISSUED FOR COMMENTS RA MSS MSS DATA SHEET NUMBER
67 A 6-Nov-02 ISSUED FOR IDC RA MSS MSS
DIF-0015-ELC-ED-0009
19902:\grp06\petronas\excel\datashts\710003739.xls
68 REV DATE DESCRIPTION BY CHK'D APP'D
DIF-0015-ELC-ED-0009
69

19902:\grp06\petronas\excel\datashts\710003739.xls