Professional Documents
Culture Documents
(5) التــأريــــــــض د.الشرقاوى
(5) التــأريــــــــض د.الشرقاوى
Grounding Fundamentals
1. Definitions
The words "earthing" and "grounding" have the same meaning. The term "earthing"
is used in U.K. and "grounding" in U.S.A. Both of them electrically mean connection to
ground or earth. The word "grounding" is commonly used in electric power system to
cover both "system grounding" and "equipment grounding".
These terms are defined by the National Electrical Code (NEC) as follows:
System Ground: A system ground is the connection to ground from one of the current
carrying conductors of a distribution system or of an interior wiring system.
System Neutral Ground: A system neutral ground is a connection to ground from the
neutral point or points of a circuit, transformer, rotating machine, or system. The neutral
point of a system is that point which has the same potential as the point of junction of a
group of equal non-reactive resistances if connected at their free ends to the appropriate
main terminals or lines of the system.
____________________________________________ 1
Grounding Fundamentals
2. Neutral Grounding
The advantages of operating an industrial power system grounded compared with
operating it ungrounded may be one or more of the following:
1. Reduced operating and maintenance expense.
a- Reduction in magnitude of transient overvoltages;
b- Improved lightning protection;
c- Simplification of ground fault location;
d- Improved system and equipment fault protection;
2. Improved service reliability.
3. Greater safety for personnel and equipment.
____________________________________________ 2
Grounding Fundamentals
____________________________________________ 3
Grounding Fundamentals
____________________________________________ 4
Grounding Fundamentals
- Perception;
- Muscular contraction;
- Unconsciousness;
- Fibrillation of the heart;
- Respiratory nerve blockage; and
- Burning.
The stages of physiological effects of electric current are diagrammatically illustrated
in Fig.1
Occupation Percentage of
injuries
Electrical Personnel, including: 42.2
- Electricians and radio technicians 31
- Electric arc welders 2.3
- Crane operators. 1.3
- Personnel servicing electric and radio equipment 2.4
- Operators of electrically–driven vessels and vehicles 0.7
- Electrical and radio engineers 2.5
Non-electrical personnel, including: 58.8
- Workers attending to cold metal – working machinery
workers engaged in assembly of machines and metallic
structures (filters, erectors, turners, etc ) 11.2
- Construction workers (diggers, plasterers, carpenters,
building erectors and filters , etc ) 15.4
- Miscellaneous workers (drolleries, diggers, agricultural
workers, motormen stokers, ash handlers, workers engaged
in the food stuff and consumer–goods industry, agronomists,
collective farmers, etc .) 20.2
- Loaders and labourers 5.6
- Engineering personnel ,junior maintenance personnel and
office employees 6.4
Total 100.0
____________________________________________ 5
Grounding Fundamentals
____________________________________________ 6
Grounding Fundamentals
Figure 1
i- Fibrillation current
Grounding systems must be carefully designed to keep shock currents below the
fibrillation threshold to reduce the probability of injury or death due to the shock.
Fibrillation current is actually a function of individual body weight and shock duration.
Based on the results of Dalzeil's studies, it is assumed that 99.5% of all persons can
safely withstand, without ventricular fibrillation, the passing of a 50 60 Hz current in the
magnitude and duration determined by the formula:
IB = 0.116 / √ ts A for 50 kg body weight (1)
= 0.157 / √ ts A for 70 kg body weight (2)
where ts is the duration of current exposure in seconds. This formula is valid on for
values of t in the range of
0.3 < ts < 3 sec.
____________________________________________ 7
Grounding Fundamentals
For body weights other than 50 and 70 kg weights the fibrillation current can be found
from Fig.2.
____________________________________________ 8
Grounding Fundamentals
____________________________________________ 9
Grounding Fundamentals
dF = 1m
RA = RB + 2 RF – 2RMF
IA = U/RA
RB = 1000 Ohm where
IA = the current of accidental circuit
RA = the total resistance of accidental circuit
RA + RB + ½ (RF + RMF)
where
RB is the human body resistance;
R2fs is the resistance of two feet in series;
R2fp is the resistance of two feet in parallel;
IB is the permissible current.
The resistances R2fs and R2fp are given by:
R2fs = 2.0 ( Rfoot -RMfoot ) (5)
R2fP = 0.5 ( Rfoot + RMfoot ) (6)
where Rfoot is the self-resistance of each foot to remote earth
RMfoot is the mutual resistance between the feet.
d-Foot Resistance
For the purposes of circuit analysis, the human foot is usually represented as a conducting
metallic disk and the contact resistance of shoes and shocks is neglected. The self and
mutual resistances for two metallic disks of radius b, separated by a distance df on the
surface of a homogeneous earth of resistivity ρ, are given by Sunde as:
Rfoot= ρ/4b (7)
RMfoot = ρ /2πdf (8)
b and df are considered here as the equivalent radius of foot and separation distance of the
feet ( measured in m). It is widely accepted in many references to choose a 0.08 m radius
for the disk representing one foot and to neglect the effect of the mutual resistance term,
as a result of which, the above formula giving the series and parallel resistance of two
feet can be reduced to:
R2fs = 6 ρ (9)
R2fp = 1.5 ρ (10)
Therefore, for all practical purposes, the resistance of a foot is given by:
Rf = 3 ρ (11)
In cases when more accurate analysis is required, the foot-wear (shoe) resistance can
be taken in consideration together with the foot resistance R .Approximate values of foot-
wear resistance are given in Table 5.
Table 5 Approximate Values of Foot Wear Resistance
(For preliminary calculations)
Resistance, kΩ, at Mains voltage, V
Premises Sole material
Below 65 127 220 Above 220
Moist and Leather 1.6 0.8 0.5 0.2
damp Simulated leather 2.0 1.0 0.7 0.5
Rubber 2.0 1.8 1.5 1.0
Dry Leather 200 150 100 50
Simulated leather 150 100 50 25
Rubber 500 500 500 500
____________________________________________ 11
Grounding Fundamentals
Finally, substituting IB, RB, R2fs and R2fp as given by Eqns (1) or (2), (12), (9) and (10)
into Eqns (3) and (4), we get the following expressions for the maximum allowable step
and touch voltages:
Estep 50 = 0.116( 1000 + 6 ρ ) / √ ts (13)
or
Estep 70 = 0.157( 1000 + 6 ρ ) / √ ts (13a)
and
Etouch 50 = 0.116( 1000 + 1.5 ρ ) / √ ts (14)
or
Etouch 70 = 0.157( 1000 + 1.5 ρ ) / √ ts (14a)
The actual step and touch voltages to be allowed in earthing installations should be
less than the voltages given by these equations. The maximum allowable step and touch
voltages as affected by shock duration and body weight for a soil of resistivity 100 Ω.m
are given in Table 7.
____________________________________________ 12
Grounding Fundamentals
3.5 Allowable Earth Electrode Voltage and Contact Voltage According to the VDE
a- In High Voltage Systems (Rated Voltage > 1 kV)
According to VDE 0141/2.64 the voltage of an earthing installation with respect to
reference earth during the time the earth fault current is flowing must not rise higher than
125 V. The contact voltage (part of the earth installation voltage which can be bridged by
person) must not be higher than 65 V.
b- In Low Voltage Systems (Rated Voltage < 1 kV)
According to VDE 0100/15, in multiple wire systems with operating voltages above 250
V between line conductors, and not higher than 250 V between a line conductor and
neutral, the neutral point must be earthed directly to prevent, in the event of an earth
fault, any single conductor from reaching a voltage higher than 250 V to earth.
____________________________________________ 13
Grounding Fundamentals
smaller and they are in general only accessible to qualified personnel. Preferably,
however, it should not exceed 5 ohms and should be as much as can be realized
economically.
b- According to the VDE
The resistance of the ground bus to earth must not be higher than 2 ohms in low
voltage systems. At least one earth electrode must be placed close to the source of
current. If the required earth electrode resistance of 2 ohms cannot be achieved, other
measures have to be taken to ensure that the line to earth voltage of 250 V is not
exceeded.
____________________________________________ 14
Grounding Fundamentals
The National Electrical Code (NEC), however, stated that the size of equipment
grounding conductor depends on the rating or setting of the overcurrent device provided
to the feeding circuit ahead of the ground conductor of equipment or raceway. The
minimum size of grounding conductor of equipment or racway according to the NEC is
given in Table 8.
Table 8 Minimum Size of Grounding Conductor for
Grounding Raceway or Equipment
3.183 m will be required. To get a resistance of 0.5 ohm in such a soil, the electrode
radius should be increased to 31.83 meters, which is impossible to construct.
Soil Characteristics
Electrical conduction in soil is essentially electrolytic for this reason the resistivity of
most soils rises abruptly whenever the moisture content accounts for lees than 15% of the
soil weight .The amount of water further depends upon the grain size compactness, and
variability of grain size. Soil resistivity is also dependent on its temperature and on the
amount of soluble salts, acids, or alkali present in it.
An extremely simple tabulation of soil resistivity is shown in Table 9. Another tabulation
showing how soil resistivity for different rocky soils is affected by ground water and salt
water is given in Table 10.
Table 9: Range of Earth Resistivity
The mean values for soil resistivities according to VDE 0100,§20 are:
Type of Marshy Loam, clay Wet Wet Dry sand Stony soil
soil soil and arable sand gravel or dry (rock)
soil gravel
Resistivity
30 100 200 500 1000 3000
ρ in Ω.m
The following figure shows how soil resistivity is affected by salt and moisture content
and temperature. Curve 1 illustrates a typical effect of salt (Sodium chloride) on the
resistivity of a soil containing 30% of moisture by weight. Curve 2 shows a typical
____________________________________________ 16
Grounding Fundamentals
variation of soil resistivity by moisture content, and curve 3 shows how the resistivity of
a clay soil containing 15.2% moisture by weight is affected by temperature variation.
It is important to note that the magnitude and duration of current flowing in soil may
affect its thermal characteristic and moisture content and thus may lead to increasing its
resistivity. A conservative value of current density is not to exceed 200A/m2 for 1
second.
is given in Table 12 and graphically illustrated in Fig.7. It can be seen from this figure
and from Table 12 that the earth resistance of a 1 meter diameter hemisphere can be
obtained by a vertically driven rod of 3 m length and 2.5 cm diameter.
Table 12: Earth-electrode resistance for soil resistivity ρ1=100 Ohm.m
(according to VDE 0100, §20)
1 2 3 4 5 6 7 10 8 911
Strip or stranded Vertical plate,
Type of conductors Rod or pipe top edge 1m below
1
earth surface of soil
electrode Length: Length: Size:
10m 25m 50m 100m 1m 2m 3m 5m 0.5x1m 1x1m
Earth-
electrode
2
resistance,
Ohms 20 10 5 3 70 40 30 20 35 25
The resistance Rg of vertically driven rod of length 1 and radius a is given by:
Rg = ρ ( ln (4L/a) -1 ) / (2πL) (17)
The combined earth resistance of a group of identical vertical rods driven into ground on
one line at equal spacings depends on the earth resistance of a single rod and on the
spacing between adjacent rods. The combined resistance of combinations of up to 100
vertical rods can be found in the way described on Fig. 8.
Figure 8
Earth Resistance of a
Horizontally Buried
Rod Rod diameter 2.5 cm,
Burial Depth = 60cm, Soil
Resistivity = 100 Ohm.m
____________________________________________ 18
Grounding Fundamentals
R= + ⎢1 + ⎜ ⎟ + ⎜ ⎟ ⎥ (19)
8a 8πd ⎢⎣ 24 ⎝ 2d ⎠ 320 ⎝ 2d ⎠ ⎥⎦
The earth resistance of a rectangular plate having different dimensions buried in soil
with its top edge 1 meter below ground surface is given in Table 12. Table 13 provides
the dimensions of a vertically driven and horizontally buried electrodes giving specific
values of earth resistances in different soils.
Table 13 Mean values of earth-electrode resistances which can be obtained with earth
electrodes in different types of soil:
Earth-electrode resistance
2Ω 5Ω 10Ω 15Ω 2Ω 5Ω 10Ω 15Ω
Type of Soil Electrode length that achieves this resistance, m
Horizontally burieda strips Vertically driven rods
Marshy Soil 30 12 6 4 15 6 3 2
Loam, clay or
arable land 100 40 20 13 50 20 10 7
Wet sand 200 80 40 27 --- 40 20 14
Wet gravel 500 200 100 67 --- --- 50 34
Dry sand or dry
gravel --- 400 200 133 --- --- --- ---
Stony soil (rock) --- 1500 600 400 --- --- --- ---
a burial depth = 0.5 – 1.0 m
--- Not usual
6.5 Grid Electrode
The earth resistance of a group of grid electrodes constructed in different soils are given
in Table 14.
Table 14: Typical Grid Resistances
Parameter SS 1 SS 2 SS 3 SS 4 SS 5
Soil Texture Sand & Sandy Sand & Sand & Soil &
Gravel Loam Clay Gravel Clay
Resistivity (Ω.m) 2000 800 200 1300 28
Grid area (ft2) 15159 60939 18849 15759 61479
Buried length 3120 9500 1775 3820 3000
Rg (calculated Ω) 25.7 4.97 2.55 16.15 0.19
Rg (measured Ω) 39.0 4.10 3.65 18.2 0.21
____________________________________________ 20