EETC (Protection and measuring comments) on ABB Clarification For Tender no.

64/2013-
2014

ABB Clarification EETC Comment


4- Regarding the incoming panel measuring devices there is This is to inform you that the measuring devices for
a conflict between the general specs and EETC-D20 as below incoming is required as follow:
so kindly clarify/confirm which specs we follow: Measuring:
ite General Power transformers bays (low voltage side):
EETC D-20
m Specs The current for each phase.
Voltage Transformer Not Required
1 All phases and line Voltages.
mentioned
A-meter & Voltmeter Not Required
Metering:
2 Power transformers bays (low voltage side):
mentioned
Multi-Function meter Not Required MVARH.
3 MWH with maximum demand.
mentioned

5- regarding accuracy of multifunction meter there is a Please be confirmed that the accuracy class will be
conflict between the general specs and EETC-D20 as below as per EETC Specs Section (3) Item (3.6) Page (4/8).
so kindly clarify/confirm which specs we will follow: As follow:

General ite General


item EETC D-20
Specs. m Specs.
1 WH 0.2 0.5 1 WH 0.2
2 VARH 0.5 1.0 2 VARH 0.5

Sunday, June 01, 2014 Page 1