Job Code 0-7577-20-0000

Owner's Doc.
No.
Contractor's
SONATRACH HASSI R'MEL S-3009-1223-061
Doc. No.
BOOSTING PHASE III PROJECT Sheet 1 OF 38

SONATRACH
Activité E&P
Pôle Exploitation & Production
Division Production
Direction Régionale Hassi-R’mel

REALISATION DES INSTALLATIONS DE SEPARATION ET DE


COMPRESSION ENTREE BOOSTING PHASE III
Contract N° : E/05/SH/E-P/DP/HR/2016

CAUSE AND EFFECT CHART


OF
SBC

PREP'D CHK'D APP'D


REV. DATE PAGE RESON FOR ISSUE
BY BY BY
A 29-May-17 ALL FOR INFORMATION N.Iwasaki T.Hotta T.Noda
B 10-Oct-17 ALL FOR INFORMATION N.Iwasaki T.Hotta T.Noda
C 5-Dec-17 ALL FOR INFORMATION N.Iwasaki T.Hotta T.Noda
0 19-Feb-18 ALL FOR CONSTRUCTION N.Iwasaki T.Noda T.Noda
1 24-Apr-18 2-4, 11-16, 22-27, 36-38 FOR CONSTRUCTION N.Iwasaki T.Noda T.Noda
2 22-Jun-18 1-31,36,38 FOR CONSTRUCTION N.Iwasaki T.Noda T.Noda
3 20-Jan-20 6 - 16 AS BUILT S.Koga N.Oshima M.Nakamura

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN 1 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

4
1. Deleted.

3009-231

3009-231

3009-800

3009-604

3009-604
Number
ESD LEVEL 0-1 (Station Shutdown)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE: NOTE 3
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and

Ejector and PWT package fuel gas line ESDV


SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.

Process shutdown (Block 1 inlet facility)

Process shutdown (Block 2 inlet facility)

Depressuring of all ZONEs (STATION)


SD - SHUTDOWN

Process shutdown (common facility)


B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START

Depressuring of ZONE 3
X - ACTIVATED

Boosting unit shutdown

Recovered oil pump A

Recovered oil pump B


D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

Z-961-P002A

Z-961-P002B
TAG Number
M - Manual Reset / A - Auto Reset

ESDV-9092
ESD-2-1-2

ESD-2-2-2

UZ-9000

UZ-9000
ESD-2-3
ESD-1
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number 1. Deleted.

Manual push button for pressurized station shutdown HRS-


HZS-9000 UZ-9000 3009-231 1 X X X X PS PS C SP SP 1
(P-ESD) 9000

HZDS-9000A
Manual push button for depressurized station shutdown (D-
UZ-9000 3009-231
HRS-
2 X X X X X X C SP SP 2
2. Sequential depressuring is achieved ZONE by ZONE by opening BDVs and
ESD) 9000 HVs with depressuring function in predeterminded order. Refer to Flare
3 3 System Design Report (S-3000-1223-004).
PT- HRS-
IA header pressure low low LL UZ-9000 3009-456 2oo3 4 X X X X PS PS C 4
9455A/B/C 9000
HZS: Hand Switch (Depressurized)
5 5 3.
HDS: Hand Switch (Pressurized)
6 6 Refer to Project Numbering Procedure (S-3000-1141-001).

7 7

PDT-9091 Low differential pressure across ESDV-9092 3009-800 MO 8 PO 8


4. 3009-XV-9662 close automatically when 3009-Z-961-P002A/B stop.

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 2 OF 38
2 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES
1. Deleted.

3009-800
Number
ESD LEVEL 0-2 (Station Shutdown without ZONE 3)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and

Ejector and PWT Package fuel gas line ESDV


SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.

Process shutdown (Block 1 inlet facility)

Process shutdown (Block 2 inlet facility)


SD - SHUTDOWN

Process shutdown (common facility)


B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED

Boosting unit shutdown


D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

TAG Number
M - Manual Reset / A - Auto Reset

ESDV-9092
ESD-2-1-2

ESD-2-2-2

ESD-2-3
ESD-1
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number 1. ZONE 3 is isolated automatically after 6 hours from cause initiation.

Manual push button for pressurized station shutdown without HRS-


HZS-9001 UZ-9001 3009-231 1 X X X X C 1
ZONE 3 (P-ESD) 9001

2 2

HRS-
XS-9000 Total power failure (TPF) UZ-9001 1 3 X X X X C 3
9001

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 3 OF 38
3 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-800
Number

902G/H

273G/H
902C/D

273C/D
902A/B

273A/B
902E/F

273E/F
902I/J

273I/J
3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-
3009-

3009-

3009-
ESD LEVEL 1 (Boosting Unit Shutdown)

P&ID

902K
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and

Process shutdown (Block 1 compressor train)

Process shutdown (Block 2 compressor train)


SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START

Depressuring of ZONE 1 (MP) (FZ-C21)

Depressuring of ZONE 1 (MP) (FZ-C20)

Depressuring of ZONE 1 (MP) (FZ-C19)

Depressuring of ZONE 1 (MP) (FZ-C18)

Depressuring of ZONE 1 (MP) (FZ-C17)


Depressuring of ZONE 1 (LP) (FZ-C59)

Depressuring of ZONE 1 (LP) (FZ-C60)

Depressuring of ZONE 1 (LP) (FZ-C61)

Depressuring of ZONE 1 (LP) (FZ-C62)

Depressuring of ZONE 1 (LP) (FZ-C63)

Depressuring of ZONE 1 (LP) (FZ-C52)


or timer expired.
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual

Depressuring of ZONE 1 (total)


PO - PERMISSIVE TO OPEN

GT fuel gas supply line ESDV


for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START

Depressuring of ZONE 4
X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

TAG Number
M - Manual Reset / A - Auto Reset

UZ-9301G/H

UZ-9101G/H
UZ-9301C/D

UZ-9101C/D
UZ-9301A/B

UZ-9101A/B
UZ-9301E/F

UZ-9101E/F
ESDV-9091

UZ-9301I/J

UZ-9101I/J
ESD-2-1-1

ESD-2-2-1

UZ-9301K

UZ-9010

UZ-9010
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Delted.
HRS-
ESD-0-1 Station shutdown UZ-9000 3009-231
9000
1 X X C PS PS PS PS PS PS PS PS PS PS PS PS PS 1 2. To be developed in Step 2 detail engineering stage.

ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231 HRS-9001 2 X X C PS PS PS PS PS PS PS PS PS PS PS PS PS 2

Manual push button with pressurized boosting unit shutdown HRS-


HZS-9010 UZ-9010 3009-271 3 X X C PS PS PS PS PS PS PS PS PS PS PS PS PS 3
(P-ESD) 9010

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

PDT-9093 Low differential pressure across ESDV-9091 3009-800 MO 28 PO 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 4 OF 38
4 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

Number
ESD LEVEL 1 (Boosting Unit Shutdown)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and

Emergency shutdown (trip) to MARK VI (MP)

Emergency shutdown (trip) to MARK VI (MP)

Emergency shutdown (trip) to MARK VI (MP)

Emergency shutdown (trip) to MARK VI (MP)

Emergency shutdown (trip) to MARK VI (MP)


Emergency shutdown (trip) to MARK VI (LP)

Emergency shutdown (trip) to MARK VI (LP)

Emergency shutdown (trip) to MARK VI (LP)

Emergency shutdown (trip) to MARK VI (LP)

Emergency shutdown (trip) to MARK VI (LP)

Emergency shutdown (trip) to MARK VI (LP)


SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

XS-9251GA/HA
XS-9251CA/DA
XS-9251AA/BA

XS-9251EA/FA

XS-9251IA/JA
TAG Number
M - Manual Reset / A - Auto Reset

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number 1. To be developed in Step 2 detail engineering stage.

ESD-0-1 Station shutdown UZ-9000 3009-231


HRS-
1 X X X X X X X X X X X 1
2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).
9000

ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231 HRS-9001 2 X X X X X X X X X X X 2 3. Deleted.


Manual push button with pressurized boosting unit shutdown HRS-
HZS-9010 UZ-9010 3009-271 3 X X X X X X X X X X X 3
(P-ESD) 9010

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 5 OF 38
5 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

901A

901A

901A

902A

902A

902A
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 1)


Depressuring of LP compressor A
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301A

ESDV-9303A

ESDV-9304A

ESDV-9302A
TAG Number

UZ-9301A
FV-9301A

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9859A Confirmed fire detection in ZONE 1 (LP) (FZ-C59) 2, 5 3 C C C C O X X X 3

XY-9859B Confirmed gas detection in ZONE 1 (LP) (FZ-C59) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).

Manual push button for pressurized compressor shutdown HRS-


HZS-9301A
(P-ESD)
UZ-9301A 3009-902A
9301A
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.

Manual push button for depressurized compressor shutdown HRS-


HZDS-9301AA UZ-9301A 3009-902A 2 7 C C C C O X X 7
in field (D-ESD) 9301A
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301AC
(D-ESD)
UZ-9301A 3009-902A
9301A
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304AA/AB/AC
LP Compressor discharge high high pressure HH UZ-9301A 3009-902A 2oo3
9301A
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301A 3009-902A 2oo3 OO 2 11 C C C C O X 11
9302AA/AB/AC 9301A
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301A 3009-902A 2oo3 2 12 C C C C O X 12
9304AA/AB/AC 9301A
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301A 3009-902A 2oo3 2 13 C C C C O X 13
9309AA/AB/AC 9301A
HRS-
LT-9303A LP Compressor inlet drum high high level HH UZ-9301A 3009-901A MO 2 14 C C C C O X 14
9301A
HRS-
LT-9303A LP Compressor inlet drum low low level LL UZ-9302A 3009-901A MO 2 15 C 15
9302A

PDT-9301A Low differential pressure across ESDV9301A/ 9303A 3009-901A MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 6 OF 38
6 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

901B

901B

901B

902B

902B

902B
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 1)


Depressuring of LP compressor B
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301B

ESDV-9303B

ESDV-9304B

ESDV-9302B
TAG Number

UZ-9301B
FV-9301B

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9859A Confirmed fire detection in ZONE 1 (LP) (FZ-C59) 2, 5 3 C C C C O X X X 3

XY-9859B Confirmed gas detection in ZONE 1 (LP) (FZ-C59) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301B
(P-ESD)
UZ-9301B 3009-902B
9301B
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301BA UZ-9301B 3009-902B 2 7 C C C C O X X 7
in field (D-ESD) 9301B
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301BC
(D-ESD)
UZ-9301B 3009-902B
9301B
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304BA/BB/BC
LP Compressor discharge high high pressure HH UZ-9301B 3009-902B 2oo3
9301B
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301B 3009-902B 2oo3 OO 2 11 C C C C O X 11
9302BA/BB/BC 9301B
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301B 3009-902B 2oo3 2 12 C C C C O X 12
9304BA/BB/BC 9301B
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301B 3009-902B 2oo3 2 13 C C C C O X 13
9309BA/BB/BC 9301B
HRS-
LT-9303B LP Compressor inlet drum high high level HH UZ-9301B 3009-901B MO 2 14 C C C C O X 14
9301B
HRS-
LT-9303B LP Compressor inlet drum low low level LL UZ-9302B 3009-901B MO 2 15 C 15
9302B

PDT-9301B Low differential pressure across ESDV9301B/ 9303B 3009-901B MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 7 OF 38
7 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

901C

901C

901C

902C

902C

902C
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 1)


Depressuring of LP compressor C
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301C

ESDV-9303C

ESDV-9304C

ESDV-9302C
TAG Number

UZ-9301C
FV-9301C

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9860A Confirmed fire detection in ZONE 1 (LP) (FZ-C60) 2, 5 3 C C C C O X X X 3

XY-9860B Confirmed gas detection in ZONE 1 (LP) (FZ-C60) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301C
(P-ESD)
UZ-9301C 3009-902C
9301C
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301CA UZ-9301C 3009-902C 2 7 C C C C O X X 7
in field (D-ESD) 9301C
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301CC
(D-ESD)
UZ-9301C 3009-902C
9301C
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304CA/CB/CC
LP Compressor discharge high high pressure HH UZ-9301C 3009-902C 2oo3
9301C
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301C 3009-902C 2oo3 OO 2 11 C C C C O X 11
9302CA/CB/CC 9301C
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301C 3009-902C 2oo3 2 12 C C C C O X 12
9304CA/CB/CC 9301C
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301C 3009-902C 2oo3 2 13 C C C C O X 13
9309CA/CB/CC 9301C
HRS-
LT-9303C LP Compressor inlet drum high high level HH UZ-9301C 3009-901C MO 2 14 C C C C O X 14
9301C
HRS-
LT-9303C LP Compressor inlet drum low low level LL UZ-9302C 3009-901C MO 2 15 C 15
9302C

PDT-9301C Low differential pressure across ESDV9301C/ 9303C 3009-901C MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 8 OF 38
8 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

901D

901D

901D

902D

902D

902D
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 1)


Depressuring of LP compressor D
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301D

ESDV-9303D

ESDV-9304D

ESDV-9302D
TAG Number

UZ-9301D
FV-9301D

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9860A Confirmed fire detection in ZONE 1 (LP) (FZ-C60) 2, 5 3 C C C C O X X X 3

XY-9860B Confirmed gas detection in ZONE 1 (LP) (FZ-C60) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301D
(P-ESD)
UZ-9301D 3009-902D
9301D
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301DA UZ-9301D 3009-902D 2 7 C C C C O X X 7
in field (D-ESD) 9301D
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301DC
(D-ESD)
UZ-9301D 3009-902D
9301D
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304DA/DB/DC
LP Compressor discharge high high pressure HH UZ-9301D 3009-902D 2oo3
9301D
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301D 3009-902D 2oo3 OO 2 11 C C C C O X 11
9302DA/DB/DC 9301D
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301D 3009-902D 2oo3 2 12 C C C C O X 12
9304DA/DB/DC 9301D
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301D 3009-902D 2oo3 2 13 C C C C O X 13
9309DA/DB/DC 9301D
HRS-
LT-9303D LP Compressor inlet drum high high level HH UZ-9301D 3009-901D MO 2 14 C C C C O X 14
9301D
HRS-
LT-9303D LP Compressor inlet drum low low level LL UZ-9302D 3009-901D MO 2 15 C 15
9302D

PDT-9301D Low differential pressure across ESDV9301D/ 9303D 3009-901D MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 9 OF 38
9 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

901E

901E

901E

902E

902E

902E
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 1)


Depressuring of LP compressor E
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301E

ESDV-9303E

ESDV-9304E

ESDV-9302E
TAG Number

UZ-9301E
FV-9301E

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9861A Confirmed fire detection in ZONE 1 (LP) (FZ-C61) 2, 5 3 C C C C O X X X 3

XY-9861B Confirmed gas detection in ZONE 1 (LP) (FZ-C61) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301E
(P-ESD)
UZ-9301E 3009-902E
9301E
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301EA UZ-9301E 3009-902E 2 7 C C C C O X X 7
in field (D-ESD) 9301E
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301EC
(D-ESD)
UZ-9301E 3009-902E
9301E
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304EA/EB/EC
LP Compressor discharge high high pressure HH UZ-9301E 3009-902E 2oo3
9301E
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301E 3009-902E 2oo3 OO 2 11 C C C C O X 11
9302EA/EB/EC 9301E
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301E 3009-902E 2oo3 2 12 C C C C O X 12
9304EA/EB/EC 9301E
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301E 3009-902E 2oo3 2 13 C C C C O X 13
9309EA/EB/EC 9301E
HRS-
LT-9303E LP Compressor inlet drum high high level HH UZ-9301E 3009-901E MO 2 14 C C C C O X 14
9301E
HRS-
LT-9303E LP Compressor inlet drum low low level LL UZ-9302E 3009-901E MO 2 15 C 15
9302E

PDT-9301E Low differential pressure across ESDV9301E/ 9303E 3009-901E MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 10 OF 38
10 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-901F

3009-901F

3009-901F

3009-902F

3009-902F

3009-902F

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of LP compressor F
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9301F

ESDV-9303F

ESDV-9304F

ESDV-9302F

UZ-9301F
FV-9301F

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9861A Confirmed fire detection in ZONE 1 (LP) (FZ-C61) 2, 5 3 C C C C O X X X 3

XY-9861B Confirmed gas detection in ZONE 1 (LP) (FZ-C61) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301F
(P-ESD)
UZ-9301F 3009-902F
9301F
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301FA UZ-9301F 3009-902F 2 7 C C C C O X X 7
in field (D-ESD) 9301F
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301FC
(D-ESD)
UZ-9301F 3009-902F
9301F
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304FA/FB/FC
LP Compressor discharge high high pressure HH UZ-9301F 3009-902F 2oo3
9301F
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301F 3009-902F 2oo3 OO 2 11 C C C C O X 11
9302FA/FB/FC 9301F
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301F 3009-902F 2oo3 2 12 C C C C O X 12
9304FA/FB/FC 9301F
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301F 3009-902F 2oo3 2 13 C C C C O X 13
9309FA/FB/FC 9301F
HRS-
LT-9303F LP Compressor inlet drum high high level HH UZ-9301F 3009-901F MO 2 14 C C C C O X 14
9301F
HRS-
LT-9303F LP Compressor inlet drum low low level LL UZ-9302F 3009-901F MO 2 15 C 15
9302F

PDT-9301F Low differential pressure across ESDV9301F/ 9303F 3009-901F MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 11 OF 38
11 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-232
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID

901G

901G

901G

902G

902G

902G
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of LP compressor G
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301G

ESDV-9303G

ESDV-9304G

ESDV-9302G
TAG Number

UZ-9301G
FV-9301G

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9862A Confirmed fire detection in ZONE 1 (LP) (FZ-C62) 2, 5 3 C C C C O X X X 3

XY-9862B Confirmed gas detection in ZONE 1 (LP) (FZ-C62) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301G
(P-ESD)
UZ-9301G 3009-902G
9301G
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301GA UZ-9301G 3009-902G 2 7 C C C C O X X 7
in field (D-ESD) 9301G
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301GC
(D-ESD)
UZ-9301G 3009-902G
9301G
2 8 C C C C O X X 8 5.
061)
9 9
PT-
HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304GA/GB/G LP Compressor discharge high high pressure HH UZ-9301G 3009-902G 2oo3
9301G
2 10 C C C C O X 10 6.
C automatically.
PT-
HRS-
9302GA/GB/G LP Compressor suction low low pressure LL UZ-9301G 3009-902G 2oo3 OO 2 11 C C C C O X 11
9301G
C
TT-
HRS-
9304GA/GB/G LP Compressor discharge high high temperature HH UZ-9301G 3009-902G 2oo3 2 12 C C C C O X 12
9301G
C
TT-
HRS-
9309GA/GB/G LP Compressor aftercooler discharge high high temperature HH UZ-9301G 3009-902G 2oo3 2 13 C C C C O X 13
9301G
C
HRS-
LT-9303G LP Compressor inlet drum high high level HH UZ-9301G 3009-901G MO 2 14 C C C C O X 14
9301G
HRS-
LT-9303G LP Compressor inlet drum low low level LL UZ-9302G 3009-901G MO 2 15 C 15
9302G

PDT-9301G Low differential pressure across ESDV9301G/ 9303G 3009-901G MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 12 OF 38
12 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-232
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID

901H

901H

901H

902H

902H

902H
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of LP compressor H
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301H

ESDV-9303H

ESDV-9304H

ESDV-9302H
TAG Number

UZ-9301H
FV-9301H

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9862A Confirmed fire detection in ZONE 1 (LP) (FZ-C62) 2, 5 3 C C C C O X X X 3

XY-9862B Confirmed gas detection in ZONE 1 (LP) (FZ-C62) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301H
(P-ESD)
UZ-9301H 3009-902H
9301H
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301HA UZ-9301H 3009-902H 2 7 C C C C O X X 7
in field (D-ESD) 9301H
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301HC
(D-ESD)
UZ-9301H 3009-902H
9301H
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304HA/HB/HC
LP Compressor discharge high high pressure HH UZ-9301H 3009-902H 2oo3
9301H
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301H 3009-902H 2oo3 OO 2 11 C C C C O X 11
9302HA/HB/HC 9301H
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301H 3009-902H 2oo3 2 12 C C C C O X 12
9304HA/HB/HC 9301H
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301H 3009-902H 2oo3 2 13 C C C C O X 13
9309HA/HB/HC 9301H
HRS-
LT-9303H LP Compressor inlet drum high high level HH UZ-9301H 3009-901H MO 2 14 C C C C O X 14
9301H
HRS-
LT-9303H LP Compressor inlet drum low low level LL UZ-9302H 3009-901H MO 2 15 C 15
9302H

PDT-9301H Low differential pressure across ESDV9301H/ 9303H 3009-901H MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 13 OF 38
13 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-901I

3009-901I

3009-901I

3009-902I

3009-902I

3009-902I

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of LP compressor I
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9301I

ESDV-9303I

ESDV-9304I

ESDV-9302I

UZ-9301I
FV-9301I

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9863A Confirmed fire detection in ZONE 1 (LP) (FZ-C63) 2, 5 3 C C C C O X X X 3

XY-9863B Confirmed gas detection in ZONE 1 (LP) (FZ-C63) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).

Manual push button for pressurized compressor shutdown HRS-


HZS-9301I
(P-ESD)
UZ-9301I 3009-902I
9301I
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.

Manual push button for depressurized compressor shutdown HRS-


HZDS-9301IA UZ-9301I 3009-902I 2 7 C C C C O X X 7
in field (D-ESD) 9301I
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301IC
(D-ESD)
UZ-9301I 3009-902I
9301I
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304IA/IB/IC
LP Compressor discharge high high pressure HH UZ-9301I 3009-902I 2oo3
9301I
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301I 3009-902I 2oo3 OO 2 11 C C C C O X 11
9302IA/IB/IC 9301I
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301I 3009-902I 2oo3 2 12 C C C C O X 12
9304IA/IB/IC 9301I
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301I 3009-902I 2oo3 2 13 C C C C O X 13
9309IA/IB/IC 9301I
HRS-
LT-9303I LP Compressor inlet drum high high level HH UZ-9301I 3009-901I MO 2 14 C C C C O X 14
9301I
HRS-
LT-9303I LP Compressor inlet drum low low level LL UZ-9302I 3009-901I MO 2 15 C 15
9302I

PDT-9301I Low differential pressure across ESDV9301I/ 9303I 3009-901I MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 14 OF 38
14 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-901J

3009-901J

3009-901J

3009-902J

3009-902J

3009-902J

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation or

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual for
PO - PERMISSIVE TO OPEN associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of LP compressor J
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9301J

ESDV-9303J

ESDV-9304J

ESDV-9302J

UZ-9301J
FV-9301J

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2 station
shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9863A Confirmed fire detection in ZONE 1 (LP) (FZ-C63) 2, 5 3 C C C C O X X X 3

XY-9863B Confirmed gas detection in ZONE 1 (LP) (FZ-C63) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301J
(P-ESD)
UZ-9301J 3009-902J
9301J
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301JA UZ-9301J 3009-902J 2 7 C C C C O X X 7
in field (D-ESD) 9301J
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301JC
(D-ESD)
UZ-9301J 3009-902J
9301J
2 8 C C C C O X X 8 5. Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-061)

9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304JA/JB/JC
LP Compressor discharge high high pressure HH UZ-9301J 3009-902J 2oo3
9301J
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301J 3009-902J 2oo3 OO 2 11 C C C C O X 11
9302JA/JB/JC 9301J
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301J 3009-902J 2oo3 2 12 C C C C O X 12
9304JA/JB/JC 9301J
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301J 3009-902J 2oo3 2 13 C C C C O X 13
9309JA/JB/JC 9301J
HRS-
LT-9303J LP Compressor inlet drum high high level HH UZ-9301J 3009-901J MO 2 14 C C C C O X 14
9301J
HRS-
LT-9303J LP Compressor inlet drum low low level LL UZ-9302J 3009-901J MO 2 15 C 15
9302J

PDT-9301J Low differential pressure across ESDV9301J/ 9303J 3009-901J MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 15 OF 38
15 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2, 6

2, 6

2
1. Deleted.

3009-232
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID

901K

901K

901K

902K

902K

902K
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (LP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

LP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

LP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START

LP booster compressor suction isolation ESDV

LP booster compressor suction isolation ESDV


or timer expired.

Emergency shutdown (trip) to MARK VI (LP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of LP compressor K
PS - PERMISSIVE TO START

Start valve sequence by DCS


X - ACTIVATED

LP booster compressor ASV


D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9301K

ESDV-9303K

ESDV-9304K

ESDV-9302K
TAG Number

UZ-9301K
FV-9301K

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. To be developed in Step 2 detail engineering stage.

XY-9852A Confirmed fire detection in ZONE 1 (LP) (FZ-C52) 2, 5 3 C C C C O X X X 3

XY-9852B Confirmed gas detection in ZONE 1 (LP) (FZ-C52) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9301K
(P-ESD)
UZ-9301K 3009-902K
9301K
2 6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9301KA UZ-9301K 3009-902K 2 7 C C C C O X X 7
in field (D-ESD) 9301K
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9301KC
(D-ESD)
UZ-9301K 3009-902K
9301K
2 8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9304KA/KB/KC
LP Compressor discharge high high pressure HH UZ-9301K 3009-902K 2oo3
9301K
2 10 C C C C O X 10 6.
automatically.
PT- HRS-
LP Compressor suction low low pressure LL UZ-9301K 3009-902K 2oo3 OO 2 11 C C C C O X 11
9302KA/KB/KC 9301K
TT- HRS-
LP Compressor discharge high high temperature HH UZ-9301K 3009-902K 2oo3 2 12 C C C C O X 12
9304KA/KB/KC 9301K
TT- HRS-
LP Compressor aftercooler discharge high high temperature HH UZ-9301K 3009-902K 2oo3 2 13 C C C C O X 13
9309KA/KB/KC 9301K
HRS-
LT-9303K LP Compressor inlet drum high high level HH UZ-9301K 3009-901K MO 2 14 C C C C O X 14
9301K
HRS-
LT-9303K LP Compressor inlet drum low low level LL UZ-9302K 3009-901K MO 2 15 C 15
9302K

PDT-9301K Low differential pressure across ESDV9301K/ 9303K 3009-901K MO 2 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

- GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

- GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

- ASV solenoid valve open from MARK VI 2 26 O 26

- Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 2, 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 16 OF 38
16 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

272A

272A

272A

273A

273A

273A
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of MP compressor A

Depressuring of ZONE 1 (Block 1)


PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101A

ESDV-9103A

ESDV-9104A

ESDV-9102A
TAG Number

XS-9251AA

XS-9251AB

XS-9219AB
UZ-9101A

XS-9260A
FV-9101A

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9821A Confirmed fire detection in ZONE 1 (MP) (FZ-C21) 2, 5 3 C C C C O X X X 3

XY-9821B Confirmed gas detection in ZONE 1 (MP) (FZ-C21) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101A
(P-ESD)
UZ-9101A 3009-273A
9101A
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101AA UZ-9101A 3009-273A 7 C C C C O X X 7
in field (D-ESD) 9101A
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101AC
(D-ESD)
UZ-9101A 3009-273A
9101A
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104AA/AB/AC
MP Compressor discharge high high pressure HH UZ-9101A 3009-273A 2oo3
9101A
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101A 3009-273A 2oo3 OO 7 11 C C C C O X 11
9102AA/AB/AC 9101A
TT-
MP Compressor discharge high high temperature HH UZ-9101A 3009-273A 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102AA/AB/AC detects
9104AA/AB/AC 9101A LL pressure. OO shall deactivate when 2oo3 of PT-9102AA/AB/AC reach
TT- HRS- above LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101A 3009-273A 2oo3 13 C C C C O X 13
9109AA/AB/AC 9101A
HRS-
LT-9103A MP Compressor inlet drum high high level HH UZ-9101A 3009-272A MO 14 C C C C O X 14
9101A
HRS-
LT-9103A MP Compressor inlet drum low low level LL UZ-9102A 3009-272A MO 15 C 15
9102A

PDT-9101A Low differential pressure across ESDV9101A/ 9103A 3009-272A MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250AA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250AB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101A ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224A Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 17 OF 38
17 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

272B

272B

272B

273B

273B

273B
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of MP compressor B

Depressuring of ZONE 1 (Block 1)


PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101B

ESDV-9103B

ESDV-9104B

ESDV-9102B
TAG Number

XS-9251BA

XS-9251BB

XS-9219BB
UZ-9101B

XS-9260B
FV-9101B

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9821A Confirmed fire detection in ZONE 1 (MP) (FZ-C21) 2, 5 3 C C C C O X X X 3

XY-9821B Confirmed gas detection in ZONE 1 (MP) (FZ-C21) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101B
(P-ESD)
UZ-9101B 3009-273B
9101B
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101BA UZ-9101B 3009-273B 7 C C C C O X X 7
in field (D-ESD) 9101B
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101BC
(D-ESD)
UZ-9101B 3009-273B
9101B
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104BA/BB/BC
MP Compressor discharge high high pressure HH UZ-9101B 3009-273B 2oo3
9101B
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101B 3009-273B 2oo3 OO 7 11 C C C C O X 11
9102BA/BB/BC 9101B
TT-
MP Compressor discharge high high temperature HH UZ-9101B 3009-273B 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102BA/BB/BC detects
9104BA/BB/BC 9101B LL pressure. OO shall deactivate when 2oo3 of PT-9102BA/BB/BC reach
TT- HRS- above LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101B 3009-273B 2oo3 13 C C C C O X 13
9109BA/BB/BC 9101B
HRS-
LT-9103B MP Compressor inlet drum high high level HH UZ-9101B 3009-272B MO 14 C C C C O X 14
9101B
HRS-
LT-9103B MP Compressor inlet drum low low level LL UZ-9102B 3009-272B MO 15 C 15
9102B

PDT-9101B Low differential pressure across ESDV9101B/ 9103B 3009-272B MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250BA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250BB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101B ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224B Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 18 OF 38
18 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

272C

272C

272C

273C

273C

273C
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of MP compressor C

Depressuring of ZONE 1 (Block 1)


PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101C

ESDV-9103C

ESDV-9104C

ESDV-9102C
TAG Number

XS-9251CA

XS-9251CB

XS-9219CB
UZ-9101C

XS-9260C
FV-9101C

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9820A Confirmed fire detection in ZONE 1 (MP) (FZ-C20) 2, 5 3 C C C C O X X X 3

XY-9820B Confirmed gas detection in ZONE 1 (MP) (FZ-C20) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101C
(P-ESD)
UZ-9101C 3009-273C
9101C
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101CA UZ-9101C 3009-273C 7 C C C C O X X 7
in field (D-ESD) 9101C
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101CC
(D-ESD)
UZ-9101C 3009-273C
9101C
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104CA/CB/CC
MP Compressor discharge high high pressure HH UZ-9101C 3009-273C 2oo3
9101C
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101C 3009-273C 2oo3 OO 7 11 C C C C O X 11
9102CA/CB/CC 9101C
TT-
MP Compressor discharge high high temperature HH UZ-9101C 3009-273C 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102CA/CB/CC detects
9104CA/CB/CC 9101C LL pressure. OO shall deactivate when 2oo3 of PT-9102CA/CB/CC reach
TT- HRS- above LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101C 3009-273C 2oo3 13 C C C C O X 13
9109CA/CB/CC 9101C
HRS-
LT-9103C MP Compressor inlet drum high high level HH UZ-9101C 3009-272C MO 14 C C C C O X 14
9101C
HRS-
LT-9103C MP Compressor inlet drum low low level LL UZ-9102C 3009-272C MO 15 C 15
9102C

PDT-9101C Low differential pressure across ESDV9101C/ 9103C 3009-272C MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250CA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250CB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101C ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224C Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 19 OF 38
19 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-272D

3009-272D

3009-272D

3009-273D

3009-273D

3009-273D

3009-231
Number
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


function in isolated ZONE by completion of isolation or timer expired.
O - OPEN

MP booster compressor inlet drum bottom isolation ESDV


C - CLOSE
4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP
automatically depressurize the isolated ZONE after completion of isolation or

MP booster compressor discharge isolation ESDV


ST - START

SERVICE DESCRIPTION

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


timer expired.

EFFECT
SD - SHUTDOWN

Emergency shutdown (trip) to MARK VI (MP)


B - BYPASS
5. DCS logic design to input the 0% output and change the mode to manual for
PO - PERMISSIVE TO OPEN
associated downstream LV by UZ activation.

Depressuring of MP compressor D
PS - PERMISSIVE TO START

Depressuring of ZONE 1 (Block 1)


X - ACTIVATED

MP booster compressor ASV

Start valve sequence by DCS


D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

Fire trip to MARK VI

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101D

ESDV-9103D

ESDV-9104D

ESDV-9102D
TAG Number

XS-9251DA

XS-9251DB

XS-9219DB
UZ-9101D

XS-9260D
FV-9101D

UZ-9020

-
CAUSE

ESD Loop
NOTES
TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2 station
1.
shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
HRS-
HZS-9020 Manual push button for pressurized Block 1 shutdown (P-ESD) UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9820A Confirmed fire detection in ZONE 1 (MP) (FZ-C20) 2, 5 3 C C C C O X X X 3

Sequence for process valve positioning to be referred to Process Control


XY-9820B Confirmed gas detection in ZONE 1 (MP) (FZ-C20) 2, 5 4 C C C C O X X X 4 3.
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).

Manual push button for pressurized compressor shutdown HRS-


HZS-9101D
(P-ESD)
UZ-9101D 3009-273D
9101D
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown in HRS-
HZDS-9101DA UZ-9101D 3009-273D 7 C C C C O X X 7
field (D-ESD) 9101D
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101DC
(D-ESD)
UZ-9101D 3009-273D
9101D
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104DA/DB/DC
MP Compressor discharge high high pressure HH UZ-9101D 3009-273D 2oo3
9101D
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101D 3009-273D 2oo3 OO 7 11 C C C C O X 11
9102DA/DB/DC 9101D
TT-
MP Compressor discharge high high temperature HH UZ-9101D 3009-273D 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102DA/DB/DC detects LL
9104DA/DB/DC 9101D pressure. OO shall deactivate when 2oo3 of PT-9102DA/DB/DC reach
TT- HRS- above LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101D 3009-273D 2oo3 13 C C C C O X 13
9109DA/DB/DC 9101D
HRS-
LT-9103D MP Compressor inlet drum high high level HH UZ-9101D 3009-272D MO 14 C C C C O X 14
9101D
HRS-
LT-9103D MP Compressor inlet drum low low level LL UZ-9102D 3009-272D MO 15 C 15
9102D

PDT-9101D Low differential pressure across ESDV9101D/ 9103D 3009-272D MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250DA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250DB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101D ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224D Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

IN N-2
DR02A
0
35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
21-JABUILTPRINTED
1

SHEET 20 OF 38
AS ED WHEN 20 / 39
T ROLL
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-1 (Process Shutdown Block 1 Compressor)

P&ID

272E

272E

272E

273E

273E

273E
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of MP compressor E

Depressuring of ZONE 1 (Block 1)


PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101E

ESDV-9103E

ESDV-9104E

ESDV-9102E
TAG Number

XS-9251EA

XS-9251EB

XS-9219EB
UZ-9101E

XS-9260E
FV-9101E

UZ-9020

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 1 shutdown (P- HRS-
HZS-9020
ESD)
UZ-9020 3009-231
9020
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9819A Confirmed fire detection in ZONE 1 (MP) (FZ-C19) 2, 5 3 C C C C O X X X 3

XY-9819B Confirmed gas detection in ZONE 1 (MP) (FZ-C19) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101E
(P-ESD)
UZ-9101E 3009-273E
9101E
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101EA UZ-9101E 3009-273E 7 C C C C O X X 7
in field (D-ESD) 9101E
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101EC
(D-ESD)
UZ-9101E 3009-273E
9101E
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104EA/EB/EC
MP Compressor discharge high high pressure HH UZ-9101E 3009-273E 2oo3
9101E
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101E 3009-273E 2oo3 OO 7 11 C C C C O X 11
9102EA/EB/EC 9101E
TT-
MP Compressor discharge high high temperature HH UZ-9101E 3009-273E 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102EA/EB/EC detects
9104EA/EB/EC 9101E LL pressure. OO shall deactivate when 2oo3 of PT-9102EA/EB/EC reach
TT- HRS- above LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101E 3009-273E 2oo3 13 C C C C O X 13
9109EA/EB/EC 9101E
HRS-
LT-9103E MP Compressor inlet drum high high level HH UZ-9101E 3009-272E MO 14 C C C C O X 14
9101E
HRS-
LT-9103E MP Compressor inlet drum low low level LL UZ-9102E 3009-272E MO 15 C 15
9102E

PDT-9101E Low differential pressure across ESDV9101E/ 9103E 3009-272E MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250EA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250EB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101E ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224E Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 21 OF 38
21 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-272F

3009-272F

3009-272F

3009-273F

3009-273F

3009-273F

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of MP compressor F

Depressuring of ZONE 1 (Block 2)


PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9101F

ESDV-9103F

ESDV-9104F

ESDV-9102F

XS-9251FA

XS-9251FB

XS-9219FB
UZ-9101F

XS-9260F
FV-9101F

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9819A Confirmed fire detection in ZONE 1 (MP) (FZ-C19) 2, 5 3 C C C C O X X X 3

XY-9819B Confirmed gas detection in ZONE 1 (MP) (FZ-C19) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101F
(P-ESD)
UZ-9101F 3009-273F
9101F
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101FA UZ-9101F 3009-273F 7 C C C C O X X 7
in field (D-ESD) 9101F
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101FC
(D-ESD)
UZ-9101F 3009-273F
9101F
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104FA/FB/FC
MP Compressor discharge high high pressure HH UZ-9101F 3009-273F 2oo3
9101F
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101F 3009-273F 2oo3 OO 7 11 C C C C O X 11
9102FA/FB/FC 9101F
TT-
MP Compressor discharge high high temperature HH UZ-9101F 3009-273F 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102FA/FB/FC detects LL
9104FA/FB/FC 9101F pressure. OO shall deactivate when 2oo3 of PT-9102FA/FB/FC reach
TT- HRS- above LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101F 3009-273F 2oo3 13 C C C C O X 13
9109FA/FB/FC 9101F
HRS-
LT-9103F MP Compressor inlet drum high high level HH UZ-9101F 3009-272F MO 14 C C C C O X 14
9101F
HRS-
LT-9103F MP Compressor inlet drum low low level LL UZ-9102F 3009-272F MO 15 C 15
9102F

PDT-9101F Low differential pressure across ESDV9101F/ 9103F 3009-272F MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250FA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250FB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101F ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224F Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 22 OF 38
22 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

3009-

3009-

3009-

3009-

3009-

3009-
P&ID

272G

272G

272G

273G

273G

273G
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


function in isolated ZONE by completion of isolation or timer expired.
O - OPEN

MP booster compressor inlet drum bottom isolation ESDV


C - CLOSE
4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP
automatically depressurize the isolated ZONE after completion of isolation or

MP booster compressor discharge isolation ESDV


ST - START

SERVICE DESCRIPTION

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


timer expired.

EFFECT
SD - SHUTDOWN

Emergency shutdown (trip) to MARK VI (MP)


B - BYPASS
5. DCS logic design to input the 0% output and change the mode to manual for
PO - PERMISSIVE TO OPEN
associated downstream LV by UZ activation.

Depressuring of MP compressor G
PS - PERMISSIVE TO START

Depressuring of ZONE 1 (Block 2)


X - ACTIVATED

MP booster compressor ASV

Start valve sequence by DCS


D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

Fire trip to MARK VI

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101G

ESDV-9103G

ESDV-9104G

ESDV-9102G
TAG Number

XS-9251GA

XS-9251GB

XS-9219GB
UZ-9101G

XS-9260G
FV-9101G

UZ-9030

-
CAUSE

ESD Loop
NOTES
TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2 station
1.
shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
HRS-
HZS-9030 Manual push button for pressurized Block 2 shutdown (P-ESD) UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9818A Confirmed fire detection in ZONE 1 (MP) (FZ-C18) 2, 5 3 C C C C O X X X 3

Sequence for process valve positioning to be referred to Process Control


XY-9818B Confirmed gas detection in ZONE 1 (MP) (FZ-C18) 2, 5 4 C C C C O X X X 4 3.
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).

Manual push button for pressurized compressor shutdown HRS-


HZS-9101G
(P-ESD)
UZ-9101G 3009-273G
9101G
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown in HRS-
HZDS-9101GA UZ-9101G 3009-273G 7 C C C C O X X 7
field (D-ESD) 9101G
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101GC
(D-ESD)
UZ-9101G 3009-273G
9101G
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104GA/GB/G
MP Compressor discharge high high pressure HH UZ-9101G 3009-273G 2oo3
9101G
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101G 3009-273G 2oo3 OO 7 11 C C C C O X 11
9102GA/GB/G 9101G
TT-
9104GA/GB/G MP Compressor discharge high high temperature HH UZ-9101G 3009-273G 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102GA/GB/GC detects LL
9101G pressure. OO shall deactivate when 2oo3 of PT-9102GA/GB/GC reach
C
TT-
HRS- above LL pressure.
9109GA/GB/G MP Compressor aftercooler discharge high high temperature HH UZ-9101G 3009-273G 2oo3 13 C C C C O X 13
9101G
C
HRS-
LT-9103G MP Compressor inlet drum high high level HH UZ-9101G 3009-272G MO 14 C C C C O X 14
9101G
HRS-
LT-9103G MP Compressor inlet drum low low level LL UZ-9102G 3009-272G MO 15 C 15
9102G

PDT-9101G Low differential pressure across ESDV9101G/ 9103G 3009-272G MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250GA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250GB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101G ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224G Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

D R A 35 35

IN1-JAN- T0
2 0 2
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

2 UIL TED
AS LBLED WHEN PRIN SHEET 23 OF 38
23 / 39
T RO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-232
Number

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID

272H

272H

272H

273H

273H

273H
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of MP compressor H

Depressuring of ZONE 1 (Block 2)


PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9101H

ESDV-9103H

ESDV-9104H

ESDV-9102H
TAG Number

XS-9251HA

XS-9251HB

XS-9219HB
UZ-9101H

XS-9260H
FV-9101H

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9818A Confirmed fire detection in ZONE 1 (MP) (FZ-C18) 2, 5 3 C C C C O X X X 3

XY-9818B Confirmed gas detection in ZONE 1 (MP) (FZ-C18) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101H
(P-ESD)
UZ-9101H 3009-273H
9101H
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101HA UZ-9101H 3009-273H 7 C C C C O X X 7
in field (D-ESD) 9101H
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101HC
(D-ESD)
UZ-9101H 3009-273H
9101H
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104HA/HB/HC
MP Compressor discharge high high pressure HH UZ-9101H 3009-273H 2oo3
9101H
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101H 3009-273H 2oo3 OO 7 11 C C C C O X 11
9102HA/HB/HC 9101H
TT- HRS-
MP Compressor discharge high high temperature HH UZ-9101H 3009-273H 2oo3 12 C C C C O X 12 7. OO shall automatically activate when 2oo3 of PT-9102HA/HB/HC detects
9104HA/HB/HC 9101H
LL pressure. OO shall deactivate when 2oo3 of PT-9102HA/HB/HC reach
TT- HRS-
9109HA/HB/HC
MP Compressor aftercooler discharge high high temperature HH UZ-9101H 3009-273H 2oo3
9101H
13 C C C C O X 13 above LL pressure.
HRS-
LT-9103H MP Compressor inlet drum high high level HH UZ-9101H 3009-272H MO 14 C C C C O X 14
9101H
HRS-
LT-9103H MP Compressor inlet drum low low level LL UZ-9102H 3009-272H MO 15 C 15
9102H

PDT-9101H Low differential pressure across ESDV9101H/ 9103H 3009-272H MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250HA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250HB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101H ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224H Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 24 OF 38
24 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-272I

3009-272I

3009-272I

3009-273I

3009-273I

3009-273I

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of MP compressor I
PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9101I

ESDV-9103I

ESDV-9104I

ESDV-9102I

XS-9251IA

XS-9251IB

XS-9219IB
UZ-9101I

XS-9260I
FV-9101I

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9817A Confirmed fire detection in ZONE 1 (MP) (FZ-C17) 2, 5 3 C C C C O X X X 3

XY-9817B Confirmed gas detection in ZONE 1 (MP) (FZ-C17) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101I
(P-ESD)
UZ-9101I 3009-273I
9101I
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101IA UZ-9101I 3009-273I 7 C C C C O X X 7
in field (D-ESD) 9101I
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101IC
(D-ESD)
UZ-9101I 3009-273I
9101I
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104IA/IB/IC
MP Compressor discharge high high pressure HH UZ-9101I 3009-273I 2oo3
9101I
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101I 3009-273I 2oo3 OO 7 11 C C C C O X 11
9102IA/IB/IC 9101I
TT-
MP Compressor discharge high high temperature HH UZ-9101I 3009-273I 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102IA/IB/IC detects LL
9104IA/IB/IC 9101I pressure. OO shall deactivate when 2oo3 of PT-9102IA/IB/IC reach above
TT- HRS- LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101I 3009-273I 2oo3 13 C C C C O X 13
9109IA/IB/IC 9101I
HRS-
LT-9103I MP Compressor inlet drum high high level HH UZ-9101I 3009-272I MO 14 C C C C O X 14
9101I
HRS-
LT-9103I MP Compressor inlet drum low low level LL UZ-9102I 3009-272I MO 15 C 15
9102I

PDT-9101I Low differential pressure across ESDV9101I/ 9103I 3009-272I MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250IA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250IB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101I ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224I Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 25 OF 38
25 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES

2, 3, 4

2, 3, 4
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-272J

3009-272J

3009-272J

3009-273J

3009-273J

3009-273J

3009-232
Number
ESD LEVEL 2-2-1 (Process Shutdown Block 2 Compressor)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:

Emergency shutdown with vent (trip with vent) to MARK VI (MP)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.

MP booster compressor inlet drum bottom isolation ESDV


O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

MP booster compressor discharge isolation ESDV


automatically depressurize the isolated ZONE after completion of isolation

MP booster compressor suction isolation ESDV

MP booster compressor suction isolation ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

Emergency shutdown (trip) to MARK VI (MP)


EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 1 (Block 2)


Depressuring of MP compressor J
PS - PERMISSIVE TO START

MP booster compressor ASV

Start valve sequence by DCS


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Fire trip to MARK VI


LL - LOW LOW

Ready to crank
OO - OPERATIONAL OVERRIDE (Start-up override etc.)
MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9101J

ESDV-9103J

ESDV-9104J

ESDV-9102J

XS-9251JA

XS-9251JB

XS-9219JB
UZ-9101J

XS-9260J
FV-9101J

UZ-9030

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-1 Boosting unit shutdown UZ-9010 3009-271 1 C C C C O PS PS X 1
9010
Manual push button for pressurized Block 2 shutdown (P- HRS-
HZS-9030
ESD)
UZ-9030 3009-232
9030
1 2 C C C C O PS PS X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

XY-9817A Confirmed fire detection in ZONE 1 (MP) (FZ-C17) 2, 5 3 C C C C O X X X 3

XY-9817B Confirmed gas detection in ZONE 1 (MP) (FZ-C17) 2, 5 4 C C C C O X X X 4 3. Sequence for process valve positioning to be referred to Process Control
Philosophy (S-3000-1222-003) and DCS Control Narrative (S-3000-1371-
5 5 301).
Manual push button for pressurized compressor shutdown HRS-
HZS-9101J
(P-ESD)
UZ-9101J 3009-273J
9101J
6 C C C C O PS X 6 4. For depressurized compressor shutdown case only.
Manual push button for depressurized compressor shutdown HRS-
HZDS-9101JA UZ-9101J 3009-273J 7 C C C C O X X 7
in field (D-ESD) 9101J
Manual push button for depressurized compressor shutdown HRS- Refer to Fire & Gas Alarm System Cause and Effect Chart (S-3009-1241-
HZDS-9101JC
(D-ESD)
UZ-9101J 3009-273J
9101J
8 C C C C O X X 8 5.
061)
9 9

PT- HRS- When the main ESDV with PDT opens, the bypass ESDV closes
9104JA/JB/JC
MP Compressor discharge high high pressure HH UZ-9101J 3009-273J 2oo3
9101J
10 C C C C O X 10 6.
automatically.
PT- HRS-
MP Compressor suction low low pressure LL UZ-9101J 3009-273J 2oo3 OO 7 11 C C C C O X 11
9102JA/JB/JC 9101J
TT-
MP Compressor discharge high high temperature HH UZ-9101J 3009-273J 2oo3
HRS-
12 C C C C O X 12 7.
OO shall automatically activate when 2oo3 of PT-9102JA/JB/JC detects LL
9104JA/JB/JC 9101J pressure. OO shall deactivate when 2oo3 of PT-9102JA/JB/JC reach above
TT- HRS- LL pressure.
MP Compressor aftercooler discharge high high temperature HH UZ-9101J 3009-273J 2oo3 13 C C C C O X 13
9109JA/JB/JC 9101J
HRS-
LT-9103J MP Compressor inlet drum high high level HH UZ-9101J 3009-272J MO 14 C C C C O X 14
9101J
HRS-
LT-9103J MP Compressor inlet drum low low level LL UZ-9102J 3009-272J MO 15 C 15
9102J

PDT-9101J Low differential pressure across ESDV9101J/ 9103J 3009-272J MO 16 PO 16

17 17

18 18

19 19

20 20

21 21

22 22

23 23

XS-9250JA GT pressurized trip nortification from MARK VI 2 24 C C C C O PS 24

XS-9250JB GT depressurized trip nortification from MARK VI 2 25 C C C C O X 25

FSOV-9101J ASV solenoid valve open from MARK VI 2 26 O 26

XS-9224J Start process valve positioning from MARK VI 2, 3, 4 27 X 27

- Completion of valve sequence 3, 4 28 X 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 26 OF 38
26 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

4
1. Deleted.

3009-231

3009-231

3009-231

3009-231

3009-281

3009-281

3009-292

3009-292

3009-242

3009-252

3009-271

3009-274

3009-274

3009-231
Number

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-1-2 (Process Shutdown Block 1 Inlet Facility)

P&ID

241C

241D

251C

251D

251C

251D
241A

241B

251A

251B

251A

251B

241A

241A
2. Deleted.

Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
3. provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN

Condensate rundown pump minimum flow line (Block 1)


C - CLOSE Depressurized emergency shutdown (D-ESD) activates ZONE isolation and

MP compressor inlet manifold banalizing line ESDV


LP compressor inlet manifold banalizing line ESDV
SP - STOP 4. automatically depressurize the isolated ZONE after completion of isolation

Condensate rundown pump suction line (Block 1)

Condensate return pump discharge line (Block 1)


Lower gas coalescer condensate isolation ESDV

Lower gas coalescer condensate isolation ESDV

Lower gas coalescer condensate isolation ESDV

Lower gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Inlet separator condensate banalizing line ESDV

Inlet separator vaporoutlet banalizing line ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

EFFECT
SD - SHUTDOWN

Inlet separator water banalizing line ESDV


B - BYPASS

MP-discharge manifold ESDV (Block 1)

MP discharge manifold ESDV (Block 1)


DCS logic design to input the 0% output and change the mode to manual

Flash gas ejector outlet line (Block 1)


PO - PERMISSIVE TO OPEN 5. for associated downstream LV by UZ activation.

Depressuring of ZONE 2 (Block 1)


PS - PERMISSIVE TO START

Produced water isolation ESDV

Produced water isolation ESDV

Produced water isolation ESDV

Produced water isolation ESDV


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Inlet isolation ESDV

Inlet isolation ESDV

Inlet isolation ESDV

Inlet isolation ESDV


LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9061C

ESDV-9061D

ESDV-9071C

ESDV-9071D

ESDV-9072C

ESDV-9072D
ESDV-9061A

ESDV-9061B

ESDV-9071A

ESDV-9071B

ESDV-9072A

ESDV-9072B

ESDV-9086A

ESDV-9084A

ESDV-9085A
TAG Number

ESDV-9051

ESDV-9052

ESDV-9053

ESDV-9054

ESDV-9062

ESDV-9063

ESDV-9082

ESDV-9064

ESDV-9305

ESDV-9105

ESDV-9111

ESDV-9115

UZ-9020
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-0-1 Station shutdown UZ-9000 3009-231 1 C C C C C C C C C C C C C C C C C C C C C C C C C C C PS 1
9000
HRS-
ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231
9001
2 C C C C C C C C C C C C C C C C C C C C C C C C C C C PS 2 2. Deleted.
Manual push button for pressurized Block 1 shutdown (P- HRS- Activation of Block 1 shutdown will eliminate level signals of LI-9063A/B/C/D in
HZS-9020 UZ-9020 3009-231 1, 3 3 C C C C C C C C C C C C C C C C C C C C C C C C C C C PS 3 3.
ESD) 9020 calculation of average PV by LY-9063.
4 4

When the main ESDV with PDT opens, the loading ESDV closes
5 5 4.
automatically.
PDT-9064 Low differential pressure across ESDV9064 3009-242 MO 6 PO 6

PDT-9306 Low differential pressure across ESDV9305 3009-252 MO 7 PO 7

PDT-9106 Low differential pressure across ESDV9105 3009-271 MO 8 PO 8

PDT-9115 Low differential pressure across ESDV-9111 3009-274 MO 9 PO 9

PDT-9062A Low differential pressure across ESDV-9063 3009-241A MO 10 PO 10

HRS-
PT-9055A/B/C Block 2 Inlet high high pressure HH UZ-9056 3009-232 2oo3 11 C C C C 11
9056
HRS-
PT-9051A/B/C Block 1 Inlet high high pressure HH UZ-9055 3009-231 2oo3 12 C C C C C C 12
9055

PDT-9051 Low differential pressure across ESDV9051/9052 3009-231 MO 13 PO PO 13

PDT-9053 Low differential pressure across ESDV9053/9054 3009-231 MO 14 PO PO 14

15 15

HRS-
LT-9062A Inlet separator water low level LL UZ-9061A 3009-241A MO 16 C 16
9061A
HRS-
LT-9062B Inlet separator water low level LL UZ-9061B 3009-241B MO 17 C 17
9061B
HRS-
LT-9062C Inlet separator water low level LL UZ-9061C 3009-241C MO 18 C 18
9061C
HRS-
LT-9062D Inlet separator water low level LL UZ-9061D 3009-241D MO 19 C 19
9061D

20 20

HRS-
LT-9074A Lower gas coalescer condensate low level LL UZ-9072A 3009-251A MO 21 C 21
9072A
HRS-
LT-9074B Lower gas coalescer condensate low level LL UZ-9072B 3009-251B MO 22 C 22
9072B
HRS-
LT-9074C Lower gas coalescer condensate low level LL UZ-9072C 3009-251C MO 23 C 23
9072C
HRS-
LT-9074D Lower gas coalescer condensate low level LL UZ-9072D 3009-251D MO 24 C 24
9072D

25 25

HRS-
LT-9075A Upper gas coalescer condensate low level LL UZ-9071A 3009-251A MO 26 C 26
9071A
HRS-
LT-9075B Upper gas coalescer condensate low level LL UZ-9071B 3009-251B MO 27 C 27
9071B
HRS-
LT-9075C Upper gas coalescer condensate low level LL UZ-9071C 3009-251C MO 28 C 28
9071C
HRS-
LT-9075D Upper gas coalescer condensate low level LL UZ-9071D 3009-251D MO 29 C 29
9071D

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 27 OF 38
27 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

4
1. Deleted.

3009-241F

3009-251F

3009-251F
3009-232

3009-232

3009-232

3009-232

3009-281

3009-281

3009-292

3009-292

3009-242

3009-252

3009-271

3009-275

3009-275

3009-232
Number

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-2-2 (Process Shutdown Block 2 Inlet Facility)

P&ID

241G

251G

251G
241H

251H

251H
241E

251E

251E

241A

241A
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN

Condensate rundown pump minimum flow line (Block 2)


C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and

MP compressor inlet manifold banalizing line ESDV


LP compressor inlet manifold banalizing line ESDV
SP - STOP automatically depressurize the isolated ZONE after completion of isolation

Condensate rundown pump suction line (Block 2)

Condensate return pump discharge line (Block 2)


Lower gas coalescer condensate isolation ESDV

Lower gas coalescer condensate isolation ESDV

Lower gas coalescer condensate isolation ESDV

Lower gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Upper gas coalescer condensate isolation ESDV

Inlet separator condensate banalizing line ESDV

Inlet separator vaporoutlet banalizing line ESDV


SERVICE DESCRIPTION
ST - START or timer expired.

EFFECT
SD - SHUTDOWN

Inlet separator water banalizing line ESDV


B - BYPASS

MP discharge manifold ESDV (Block 2)

MP discharge manifold ESDV (Block 2)


5. DCS logic design to input the 0% output and change the mode to manual

Flash gas ejector outlet line (Block 2)


PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.

Depressuring of ZONE 2 (Block 2)


PS - PERMISSIVE TO START

Produced water isolation ESDV

Produced water isolation ESDV

Produced water isolation ESDV

Produced water isolation ESDV


X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH

Inlet isolation ESDV

Inlet isolation ESDV

Inlet isolation ESDV

Inlet isolation ESDV


LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

ESDV-9061G

ESDV-9071G

ESDV-9072G
ESDV-9061H

ESDV-9071H

ESDV-9072H
ESDV-9061E

ESDV-9071E

ESDV-9072E

ESDV-9086B

ESDV-9084B

ESDV-9085B
TAG Number

ESDV-9061F

ESDV-9071F

ESDV-9072F
ESDV-9055

ESDV-9056

ESDV-9057

ESDV-9058

ESDV-9062

ESDV-9063

ESDV-9083

ESDV-9064

ESDV-9305

ESDV-9105

ESDV-9113

ESDV-9116

UZ-9030
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number
1. Activation of both Block 1 and Block 2 shutdown will activate ESD 0-2
station shutdown without ZONE 3.
HRS-
ESD-0-1 Station shutdown UZ-9000 3009-231 1 C C C C C C C C C C C C C C C C C C C C C C C C C C C PS 1
9000
HRS-
ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231
9001
2 C C C C C C C C C C C C C C C C C C C C C C C C C C C PS 2 2. Deleted.
Manual push button for pressurized Block 2 shutdown (P- HRS- Activation of Block 2 shutdown will eliminate level signals of LI-9063E/F/G/H in
HZS-9030 UZ-9030 3009-232 1, 3 3 C C C C C C C C C C C C C C C C C C C C C C C C C C C PS 3 3.
ESD) 9030 calculation of average PV by LY-9063.
4 4

When the main ESDV with PDT opens, the loading ESDV closes
5 5 4.
automatically.
PDT-9064 Low differential pressure across ESDV9064 3009-242 MO 6 PO 6

PDT-9306 Low differential pressure across ESDV9305 3009-252 MO 7 PO 7

PDT-9106 Low differential pressure across ESDV9105 3009-271 MO 8 PO 8

PDT-9116 Low differential pressure across ESDV-1113 3009-275 MO 9 PO 9

PDT-9062A Low differential pressure across ESDV-9063 3009-241A MO 10 PO 10

HRS-
PT-9051A/B/C Block 1 Inlet high high pressure HH UZ-9055 3009-231 2oo3 11 C C C C 11
9055
HRS-
PT-9055A/B/C Block 2 Inlet high high pressure HH UZ-9056 3009-232 2oo3 12 C C C C C C 12
9056

PDT-9055 Low differential pressure across ESDV9055/9056 3009-232 MO 13 PO PO 13

PDT-9057 Low differential pressure across ESDV9057/9058 3009-232 MO 14 PO PO 14

15 15

HRS-
LT-9062E Inlet separator water low level LL UZ-9061E 3009-241E MO 16 C 16
9061E
HRS-
LT-9062F Inlet separator water low level LL UZ-9061F 3009-241F MO 17 C 17
9061F
HRS-
LT-9062G Inlet separator water low level LL UZ-9061G 3009-241G MO 18 C 18
9061G
HRS-
LT-9062H Inlet separator water low level LL UZ-9061H 3009-241H MO 19 C 19
9061H

20 20

HRS-
LT-9074E Lower gas coalescer condensate low level LL UZ-9072E 3009-251E MO 21 C 21
9072E
HRS-
LT-9074F Lower gas coalescer condensate low level LL UZ-9072F 3009-251F MO 22 C 22
9072F
HRS-
LT-9074G Lower gas coalescer condensate low level LL UZ-9072G 3009-251G MO 23 C 23
9072G
HRS-
LT-9074H Lower gas coalescer condensate low level LL UZ-9072H 3009-251H MO 24 C 24
9072H

25 25

HRS-
LT-9075E Upper gas coalescer condensate low level LL UZ-9071E 3009-251E MO 26 C 26
9071E
HRS-
LT-9075F Upper gas coalescer condensate low level LL UZ-9071F 3009-251F MO 27 C 27
9071F
HRS-
LT-9075G Upper gas coalescer condensate low level LL UZ-9071G 3009-251G MO 28 C 28
9071G
HRS-
LT-9075H Upper gas coalescer condensate low level LL UZ-9071H 3009-251H MO 29 C 29
9071H

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 28 OF 38
28 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

1
1. Deleted.

3009-201

3009-201

3009-202

3009-202

3009-203

3009-203

3009-204

3009-204

3009-205

3009-205

3009-206

3009-206

3009-207

3009-207

3009-208

3009-208

3009-209

3009-209

3009-210

3009-210

3009-274
Number
ESD LEVEL 2-3 (Process Shutdown Common)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START or timer expired.

EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN

Existing MPP IV line isolation ESDV


for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV


HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9001

ESDV-9002

ESDV-9003

ESDV-9004

ESDV-9005

ESDV-9006

ESDV-9007

ESDV-9008

ESDV-9009

ESDV-9010

ESDV-9011

ESDV-9012

ESDV-9013

ESDV-9014

ESDV-9015

ESDV-9016

ESDV-9017

ESDV-9018

ESDV-9019

ESDV-9020

ESDV-9112
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number When the main ESDV with PDT opens, the loading ESDV closes
1.
automatically.
HRS-
ESD-0-1 Station shutdown UZ-9000 3009-231 1 C C C C C C C C C C C C C C C C C C C C C 1
9000
HRS-
ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231 2 2
9001

3 3

4 4

5 5

HRS-
HZS-9031 Manual push button for trunk line isolation-1 UZ-9031 3009-201 6 C C 6
9031

PDT-9001 Low differential pressure across ESDV9001/9002 3009-201 MO 7 PO 7

HRS-
HZS-9032 Manual push button for trunk line isolation-2 UZ-9032 3009-202 8 C C 8
9032

PDT-9003 Low differential pressure across ESDV9003/9004 3009-202 MO 9 PO 9

HRS-
HZS-9033 Manual push button for trunk line isolation-3 UZ-9033 3009-203 10 C C 10
9033

PDT-9005 Low differential pressure across ESDV9005/9006 3009-203 MO 11 PO 11

HRS-
HZS-9034 Manual push button for trunk line isolation-4 UZ-9034 3009-204 12 C C 12
9034

PDT-9007 Low differential pressure across ESDV9007/9008 3009-204 MO 13 PO 13

HRS-
HZS-9035 Manual push button for trunk line isolation-5 UZ-9035 3009-205 14 C C 14
9035

PDT-9009 Low differential pressure across ESDV9009/9010 3009-205 MO 15 PO 15

HRS-
HZS-9036 Manual push button for trunk line isolation-6 UZ-9036 3009-206 16 C C 16
9036

PDT-9011 Low differential pressure across ESDV9011/9012 3009-206 MO 17 PO 17

HRS-
HZS-9037 Manual push button for trunk line isolation-7 UZ-9037 3009-207 18 C C 18
9037

PDT-9013 Low differential pressure across ESDV9013/9014 3009-207 MO 19 PO 19

HRS-
HZS-9038 Manual push button for trunk line isolation-8 UZ-9038 3009-208 20 C C 20
9038

PDT-9015 Low differential pressure across ESDV9015/9016 3009-208 MO 21 PO 21

HRS-
HZS-9039 Manual push button for trunk line isolation-9 UZ-9039 3009-209 22 C C 22
9039

PDT-9017 Low differential pressure across ESDV9017/9018 3009-209 MO 23 PO 23

HRS-
HZS-9040 Manual push button for trunk line isolation-10 UZ-9040 3009-210 24 C C 24
9040

PDT-9019 Low differential pressure across ESDV9019/9020 3009-210 MO 25 PO 25

HRS-
HZS-9051 Manual push button for MPP IV isolation UZ-9051 3009-274 26 C 26
9051

PDT-9112 Low differential pressure across ESDV9112 3009-274 MO 27 PO 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 29 OF 38
29 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

1
1. Deleted.

3009-211

3009-211

3009-212

3009-212

3009-213

3009-213

3009-214

3009-214

3009-215

3009-215

3009-216

3009-216

3009-217

3009-217

3009-218

3009-218

3009-219

3009-219

3009-220

3009-220

3009-275
Number
ESD LEVEL 2-3 (Process Shutdown Common)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP automatically depressurize the isolated ZONE after completion of isolation

SERVICE DESCRIPTION
ST - START or timer expired.

EFFECT
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual

Existing MPP O/I line isolation ESDV


PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV

Trunk line isolation ESDV


HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

TAG Number

ESDV-9021

ESDV-9022

ESDV-9023

ESDV-9024

ESDV-9025

ESDV-9026

ESDV-9027

ESDV-9028

ESDV-9029

ESDV-9030

ESDV-9031

ESDV-9032

ESDV-9033

ESDV-9034

ESDV-9035

ESDV-9036

ESDV-9037

ESDV-9038

ESDV-9039

ESDV-9040

ESDV-9114
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number When the main ESDV with PDT opens, the loading ESDV closes
1.
automatically.
HRS-
ESD-0-1 Station shutdown UZ-9000 3009-231 1 C C C C C C C C C C C C C C C C C C C C C 1
9000
HRS-
ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231 2 2
9001

3 3

4 4

5 5

HRS-
HZS-9041 Manual push button for trunk line isolation-11 UZ-9041 3009-211 6 C C 6
9041

PDT-9021 Low differential pressure across ESDV9021/9022 3009-211 MO 7 PO 7

HRS-
HZS-9042 Manual push button for trunk line isolation-12 UZ-9042 3009-212 8 C C 8
9042

PDT-9023 Low differential pressure across ESDV9023/9024 3009-212 MO 9 PO 9

HRS-
HZS-9043 Manual push button for trunk line isolation-13 UZ-9043 3009-213 10 C C 10
9043

PDT-9025 Low differential pressure across ESDV9025/9026 3009-213 MO 11 PO 11

HRS-
HZS-9044 Manual push button for trunk line isolation-14 UZ-9044 3009-214 12 C C 12
9044

PDT-9027 Low differential pressure across ESDV9027/9028 3009-214 MO 13 PO 13

HRS-
HZS-9045 Manual push button for trunk line isolation-15 UZ-9045 3009-215 14 C C 14
9045

PDT-9029 Low differential pressure across ESDV9029/9030 3009-215 MO 15 PO 15

HRS-
HZS-9046 Manual push button for trunk line isolation-16 UZ-9046 3009-216 16 C C 16
9046

PDT-9031 Low differential pressure across ESDV9031/9032 3009-216 MO 17 PO 17

HRS-
HZS-9047 Manual push button for trunk line isolation-17 UZ-9047 3009-217 18 C C 18
9047

PDT-9033 Low differential pressure across ESDV9033/9034 3009-217 MO 19 PO 19

HRS-
HZS-9048 Manual push button for trunk line isolation-18 UZ-9048 3009-218 20 C C 20
9048

PDT-9035 Low differential pressure across ESDV9035/9036 3009-218 MO 21 PO 21

HRS-
HZS-9049 Manual push button for trunk line isolation-19 UZ-9049 3009-219 22 C C 22
9049

PDT-9037 Low differential pressure across ESDV9037/9038 3009-219 MO 23 PO 23

HRS-
HZS-9050 Manual push button for trunk line isolation-20 UZ-9050 3009-220 24 C C 24
9050

PDT-9039 Low differential pressure across ESDV9039/9040 3009-220 MO 25 PO 25

HRS-
HZS-9052 Manual push button for MPP O/I isolation UZ-9052 3009-275 26 C 26
9052

PDT-9114 Differential pressure across ESDV9114 3009-275 MO 27 PO 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 30 OF 38
30 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES
1. Deleted.

3009-241F
3009-281

3009-281

3009-274

3009-274

3009-281

3009-281

3009-281

3009-292

3009-610

3009-281

3009-281

3009-281

3009-457

3009-458
Number

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 2-3 (Process Shutdown Common)

P&ID

241G
241C

241D

241H
282A

282B

241A

241B

241E

282A

282B
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

Condensate rundown pump suction line (Block-1)

Condensate rundown pump suction line (Block-2)


automatically depressurize the isolated ZONE after completion of isolation

Diesel-driven instrument/plant air compressor A

Diesel-driven instrument/plant air compressor B


SERVICE DESCRIPTION
ST - START or timer expired.

Offline pigging degassing line isolation ESDV


EFFECT
SD - SHUTDOWN

Condensate rundown line isolation ESDV

Condensate rundown line isolation ESDV

Inlet separator water low level protection

Inlet separator water low level protection

Inlet separator water low level protection

Inlet separator water low level protection

Inlet separator water low level protection

Inlet separator water low level protection

Inlet separator water low level protection

Inlet separator water low level protection


B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual

Condensate rundown pump protection

Condensate rundown pump protection

Condensate rundown pump protection


Liquid coalescer water isolation ESDV

Liquid coalescer water isolation ESDV


PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START

Liquid coalescer water low level

Liquid coalescer water low level


X - ACTIVATED

Condensate rundown pump

Condensate rundown pump

Condensate rundown pump


D - DISCONNECT

Condensate return pump


HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

M - Manual Reset / A - Auto Reset

3009-P-902A/B
3009-P-901C

ESDV-9087A

ESDV-9087B
TAG Number

3009-P-901A

3009-P-901B

3009-K-946A

3009-K-946B
ESDV-9082

ESDV-9083

ESDV-9121

ESDV-9122

ESDV-9617
UZ-9061G
UZ-9061C

UZ-9061D

UZ-9061H

UZ-9084C
UZ-9061A

UZ-9061B

UZ-9061E

UZ-9084A

UZ-9084B

UZ-9082A

UZ-9082B
UZ-9061F
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number When both 3009-ESDV-9082 and 9083 are closed, the effects are
1.
activated.
HRS-
ESD-0-1 Station shutdown UZ-9000 3009-231 1 C C C C SP SP SP C C SP C 1
9000
HRS-
ESD-0-2 Station shutdown without ZONE 3 UZ-9001 3009-231 2 C C C C SP SP SP C C SP 2
9001

3 3

4 4

5 5

HRS-
LT-9064A Inlet separator condensate low level LL UZ-9081 3009-241A MO 6 C C C C X X X 6
9081
HRS-
LT-9064B Inlet separator condensate low level LL UZ-9081 3009-241B MO 7 C C C C X X X 7
9081
HRS-
LT-9064C Inlet separator condensate low level LL UZ-9081 3009-241C MO 8 C C C C X X X 8
9081
HRS-
LT-9064D Inlet separator condensate low level LL UZ-9081 3009-241D MO 9 C C C C X X X 9
9081
HRS-
LT-9064E Inlet separator condensate low level LL UZ-9081 3009-241E MO 10 C C C C X X X 10
9081
HRS-
LT-9064F Inlet separator condensate low level LL UZ-9081 3009-241F MO 11 C C C C X X X 11
9081
HRS-
LT-9064G Inlet separator condensate low level LL UZ-9081 3009-241G MO 12 C C C C X X X 12
9081
HRS-
LT-9064H Inlet separator condensate low level LL UZ-9081 3009-241H MO 13 C C C C X X X 13
9081

14 14

HRS-
LT-9082A Liquid coalescer water low level LL UZ-9082A 3009-282A MO 15 C 15
9082A
HRS-
LT-9082B Liquid coalescer water low level LL UZ-9082B 3009-282B MO 16 C 16
9082B

17 17

HRS-
LT-9084 Condensate drain drum condensate low level LL UZ-9083 3009-292 MO 18 SP 18
9083

LT-9639A IGF unit high level HH UZ-9601 3009-603 MO 19 X X X X X X X X X X 19

LT-9639B IGF unit high level HH UZ-9601 3009-603 MO 20 X X X X X X X X X X 20

LT-9634A Recovered oil drum level high HH UZ-9601 3009-604 MO 21 X X X X X X X X X X 21

LT-9634B Recovered oil drum level high HH UZ-9601 3009-604 MO 22 X X X X X X X X X X 22

HRS-
LT-9617 Offline pigging degassing drum high level HH UZ-9602 3009-610 MO 23 C 23
9602
HRS-
FT-9082A Condensate rundown pump discharge flow low LL UZ-9084A 3009-281 MO / OO 24 SP 24
9084A
HRS-
FT-9082B Condensate rundown pump discharge flow low LL UZ-9084B 3009-281 MO / OO 25 SP 25
9084B
HRS-
FT-9082C Condensate rundown pump discharge flow low LL UZ-9084C 3009-281 MO / OO 26 SP 26
9084C

27 27

09-ZSX-901A 09-XV-901A Not Open 3009-101 28 C 28

09-ZSX-901B 09-XV-901B Not Open 3009-101 29 C 29

EZSO-9111 ESDV-9111 Not Open 3009-274 30 C 30

EZSO-9113 ESDV-9113 Not Open 3009-275 31 C 31

EZSO-9082 ESDV-9082 Not Open 3009-281 1 32 C C X X X 32

EZSO-9083 ESDV-9083 Not Open 3009-281 1 33 C C X X X 33

HRS-
XS-9000 Total power failure (TPF) UZ-9401 34 ST ST 34
9401
HRS-
PT-9455A/B/C IA header low pressure L UZ-9401 3009-456 2oo3 35 ST ST 35
9401
23

24

10

11

12

13

14

15

16

17

18

19

20

21

22

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 31 OF 38
31 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

6
1. Deleted.

3009-902F

3009-273F
3009-902J

3009-273J
3009-902I

3009-273I
3009-231

3009-801

3009-274

3009-274

3009-274

3009-274

3009-275

3009-275

3009-275

3009-275
Number

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 3 (Emergency Depressurization)

P&ID

902G

273G
902C

902D

902H

273C

273D

273H
902A

902B

902E

902K

273A

273B

273E
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and

MP compressor G depressuring valve (Block-2) (ZONE 1-2)


MP compressor C depressuring valve (Block-1) (ZONE 1-1)

MP compressor D depressuring valve (Block-1) (ZONE 1-1)

MP compressor H depressuring valve (Block-2) (ZONE 1-2)


MP compressor A depressuring valve (Block-1) (ZONE 1-1)

MP compressor B depressuring valve (Block-1) (ZONE 1-1)

MP compressor E depressuring valve (Block-1) (ZONE 1-1)

MP compressor F depressuring valve (Block-2) (ZONE 1-2)


LP compressor G depressuring valve (Block-2) (ZONE 1-2)

MP compressor J depressuring valve (Block-2) (ZONE 1-2)


LP compressor C depressuring valve (Block-1) (ZONE 1-1)

LP compressor D depressuring valve (Block-1) (ZONE 1-1)

LP compressor H depressuring valve (Block-2) (ZONE 1-2)


LP compressor A depressuring valve (Block-1) (ZONE 1-1)

LP compressor B depressuring valve (Block-1) (ZONE 1-1)

LP compressor E depressuring valve (Block-1) (ZONE 1-1)

LP compressor K depressuring valve (Block-2) (ZONE 1-2)


LP compressor F depressuring valve (Block-1) (ZONE 1-1)

MP compressor I depressuring valve (Block-2) (ZONE 1-2)


LP compressor J depressuring valve (Block-2) (ZONE 1-2)
NOMENCLATURE:

LP compressor I depressuring valve (Block-2) (ZONE 1-2)


Trunk line and inlet manifold depressuring valve (ZONE 3)
provides permissive to open (PO) to BDVs and HVs with depressuring

Inlet separator and gascoalescer and manifold (Block-1)

Inlet separator and gascoalescer and manifold (Block-1)

Inlet separator and gascoalescer and manifold (Block-1)

Inlet separator and gascoalescer and manifold (Block-1)

Inlet separator and gascoalescer and manifold (Block-2)

Inlet separator and gascoalescer and manifold (Block-2)

Inlet separator and gascoalescer and manifold (Block-2)

Inlet separator and gascoalescer and manifold (Block-2)


function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.

Fuel gas depressuring valve (ZONE 4)


SD - SHUTDOWN

2nd depressuring valve (ZONE 2-1)

2nd depressuring valve (ZONE 2-2)


3rd depressuring valve (ZONE 2-1)

3rd depressuring valve (ZONE 2-2)


4th depressuring valve (ZONE 2-1)

4th depressuring valve (ZONE 2-2)


1st depressuring valve (ZONE 2-1)

1st depressuring valve (ZONE 2-2)


B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)


MO - MAINTENANCE OVERRIDE

TAG Number
M - Manual Reset / A - Auto Reset

BDV-9301G

BDV-9101G
BDV-9111C

BDV-9111D

BDV-9113C

BDV-9113D

BDV-9301C

BDV-9301D

BDV-9301H

BDV-9101C

BDV-9101D

BDV-9101H
BDV-9111A

BDV-9111B

BDV-9113A

BDV-9113B

BDV-9301A

BDV-9301B

BDV-9301E

BDV-9301K

BDV-9101A

BDV-9101B

BDV-9101E
BDV-9301F

BDV-9101F
BDV-9301J

BDV-9101J
BDV-9301I

BDV-9101I
BDV-9091
HV-9051
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number 1 When the zone depressuring is activated, timer will start for prescribed
minutes. Any other depressurization buttons can not be activated until timer
Depressuring of all ZONEs (STATION) by D-ESD of is expired. Refer to Flare System Design Report (S-3000-1223-004).
UZ-9000 UZ-9000 3009-231 1, 3, 8 1 O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O 1
STATION

UZ-9301A/B Depressuring of ZONE 1 (FZ-C59) by fire and gas detection UZ-9301A/B 3009-902A/B 4, 6 2 O O 2
2 Deleted.

UZ-9301C/D Depressuring of ZONE 1 (FZ-C60) by fire and gas detection UZ-9301C/D 3009-902C/D 4, 6 3 O O 3

UZ-9301E/F Depressuring of ZONE 1 (FZ-C61) by fire and gas detection UZ-9301E/F 3009-902E/F 4, 6 4 O O 4

UZ-9301G/H Depressuring of ZONE 1 (FZ-C62) by fire and gas detection UZ-9301G/H 3009-902G/H 4, 6 5 O O 5
3 Sequential depressuring is achieved ZONE by ZONE by opening BDVs and
HVs with depressuring function in predeterminded order. Refer to Flare
UZ-9301I/J Depressuring of ZONE 1 (FZ-C63) by fire and gas detection UZ-9301I/J 3009-902I/J 4, 6 6 O O 6 System Design Report (S-3000-1223-004).

UZ-9301K Depressuring of ZONE 1 (FZ-C52) by fire and gas detection UZ-9301K 3009-902K 4, 6 7 O 7

UZ-9101A/B Depressuring of ZONE 1 (FZ-C21) by fire and gas detection UZ-9101A/B 3009-273A/B 4 8 O O 8
4 In case of confirmed fire or gas by the detector around gas turbine
compressors, the compressor trains which are exposed to fire are tripped
UZ-9101C/D Depressuring of ZONE 1 (FZ-C20) by fire and gas detection UZ-9101C/D 3009-273C/D 4 9 O O 9 and depressurized automatically.

UZ-9101E/F Depressuring of ZONE 1 (FZ-C19) by fire and gas detection UZ-9101E/F 3009-273E/F 4 10 O O 10

UZ-9101G/H Depressuring of ZONE 1 (FZ-C18) by fire and gas detection UZ-9101G/H 3009-273G/H 4 11 O O 11 5. Manual push bottun can be activated after receiving Permissive for
Depressuring.
UZ-9101I/J Depressuring of ZONE 1 (FZ-C17) by fire and gas detection UZ-9101I/J 3009-273I/J 4 12 O O 12

13 13 6. To be developed in Step 2 detail engineering stage.

HDS-9000B Manual push button for all ZONEs depressuring (STATION) UZ-9000 3009-231 1, 3, 5, 8 14 O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O 14

HDS-9010A Manual push button for ZONE 1 (Block 1, 2) depressuring UZ-9010 3009-271 5 15 O O O O O O O O O O O O O O O O O O O O O 15 7. Sequence and timer are stopped. All BDVs to be closed position.

HDS-9020A Manual push button for ZONE 1, 2 (Block 1) depressuring UZ-9020 3009-231 1, 3, 5, 8 16 O O O O O O O O O O O O O O O 16

Timer between staggered BDVs is set as 3 minutes. Refer to Flare System


HDS-9020B Manual push button for ZONE 2 (Block 1) depressuring UZ-9020 3009-231 5, 8 17 O O O O 17 8.
Design Report. (S-3000-1223-004)
HDS-9030A Manual push button for ZONE 1, 2 (Block 2) depressuring UZ-9030 3009-232 1, 3, 5, 8 18 O O O O O O O O O O O O O O 18

HDS-9030B Manual push button for ZONE 2 (Block 2) depressuring UZ-9030 3009-232 5, 8 19 O O O O 19 9. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

HDS-9000C Manual push button for ZONE 3 depressuring UZ-9000 3009-231 5 20 O 20

HDS-9010B Manual push button for ZONE 4 depressuring UZ-9010 3009-271 5 21 O 21

22 22

23 23

ABT-9000 Aborting of depressuring of all ZONEs (STATION) UZ-9000 3009-231 7 24 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A 24

25 25

ABT-9020 Aborting of depressuring of ZONE 1. 2 (Block 1) UZ-9020 3009-231 7 26 A A A A A A A A A A A A A A A 26

27 27

ABT-9030 Aborting of depressuring of ZONE 1. 2 (Block 2) UZ-9030 3009-232 7 28 A A A A A A A A A A A A A A 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 32 OF 38
32 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

8
1. Deleted.

Number
ESD LEVEL 3 (Emergency Depressurization)

P&ID
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)
(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)
MO - MAINTENANCE OVERRIDE

TAG Number
M - Manual Reset / A - Auto Reset

XS-9251GB
XS-9251CB

XS-9251DB

XS-9251HB
XS-9251AB

XS-9251BB

XS-9251EB

XS-9251FB

XS-9251JB
XS-9251IB
-

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number 1 When the zone depressuring is activated, timer will start for prescribed
minutes. Any other depressurization buttons can not be activated until timer
Depressuring of all ZONEs (STATION) by D-ESD of is expired. Refer to Flare System Design Report (S-3000-1223-004).
UZ-9000 UZ-9000 3009-231 1, 3, 7 1 X X X X X X X X X X X X X X X X X X X X X 1
STATION

2 2
2 Deleted.

3 3

4 4

5 5
3 Sequential depressuring is achieved ZONE by ZONE by opening BDVs and
HVs with depressuring function in predeterminded order. Refer to Flare
6 6 System Design Report (S-3000-1223-004).

7 7

8 4. Manual push bottun can be activated after receiving Permissive for


Depressuring.
9

10

11 11 5. To be developed in Step 2 detail engineering stage.

12 12

13 13 6. Sequence and timer are stopped. All BDVs to be closed position.

HDS-9000B Manual push button for all ZONEs depressuring (STATION) UZ-9000 3009-231 1, 3, 4, 7 14 X X X X X X X X X X X X X X X X X X X X X 14

Timer between staggered BDVs is set as 3 minutes. Refer to Flare System


HDS-9010A Manual push button for ZONE 1 (Block 1, 2) depressuring UZ-9010 3009-271 5 15 X X X X X X X X X X X X X X X X X X X X X 15 7.
Design Report. (S-3000-1223-004)
HDS-9020A Manual push button for ZONE 1, 2 (Block 1) depressuring UZ-9020 3009-231 1, 4, 7 16 X X X X X X X X X X X 16

HDS-9020B Manual push button for ZONE 2 (Block 1) depressuring UZ-9020 3009-231 4, 7 17 17 8. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

HDS-9030A Manual push button for ZONE 1, 2 (Block 2) depressuring UZ-9030 3009-232 1, 4, 7 18 X X X X X X X X X X 18

19 19

20 20

21 21

22 22

23 23

ABT-9000 Aborting of depressuring of all ZONEs (STATION) UZ-9000 3009-231 6 24 A A A A A A A A A A A A A A A A A A A A A 24

25 25

ABT-9020 Aborting of depressuring of ZONE 1. 2 (Block 1) UZ-9020 3009-231 6 26 A A A A A A A A A A A 26

27 27

ABT-9030 Aborting of depressuring of ZONE 1. 2 (Block 2) UZ-9030 3009-232 6 28 A A A A A A A A A A 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 33 OF 38
33 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-902F

3009-902J
3009-902I
Number

3009-

3009-

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 3 (Emergency Depressurization)

P&ID

902G
902C

902D

902H
902A

902B

902E

902K
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and

LP compressor G depressuring valve (Block-2) (ZONE 1-2)


LP compressor C depressuring valve (Block-1) (ZONE 1-1)

LP compressor D depressuring valve (Block-1) (ZONE 1-1)

LP compressor H depressuring valve (Block-2) (ZONE 1-2)


LP compressor A depressuring valve (Block-1) (ZONE 1-1)

LP compressor B depressuring valve (Block-1) (ZONE 1-1)

LP compressor E depressuring valve (Block-1) (ZONE 1-1)

LP compressor K depressuring valve (Block-2) (ZONE 1-2)


LP compressor F depressuring valve (Block-1) (ZONE 1-1)

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI


LP compressor J depressuring valve (Block-2) (ZONE 1-2)
NOMENCLATURE:

LP compressor I depressuring valve (Block-2) (ZONE 1-2)


provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)

(LP)
MO - MAINTENANCE OVERRIDE

TAG Number
M - Manual Reset / A - Auto Reset

BDV-9301G
BDV-9301C

BDV-9301D

BDV-9301H
BDV-9301A

BDV-9301B

BDV-9301E

BDV-9301K
BDV-9301F

BDV-9301J
BDV-9301I

-
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number Manual push bottun can be activated after receiving Permissive for
1.
Depressuring.
UZ-9301A Depressuring of LP compressor A by D-ESD UZ-9301A 3009-902A 2 1 O X 1

UZ-9301B Depressuring of LP compressor B by D-ESD UZ-9301B 3009-902B 2 2 O X 2 2. To be developed in Step 2 detail engineering stage.

UZ-9301C Depressuring of LP compressor C by D-ESD UZ-9301C 3009-902C 2 3 O X 3

UZ-9301D Depressuring of LP compressor D by D-ESD UZ-9301D 3009-902D 2 4 O X 4

UZ-9301E Depressuring of LP compressor E by D-ESD UZ-9301E 3009-902E 2 5 O X 5

UZ-9301F Depressuring of LP compressor F by D-ESD UZ-9301F 3009-902F 2 6 O X 6

UZ-9301G Depressuring of LP compressor G by D-ESD UZ-9301G 3009-902G 2 7 O X 7

UZ-9301H Depressuring of LP compressor H by D-ESD UZ-9301H 3009-902H 2 8 O X 8

UZ-9301I Depressuring of LP compressor I by D-ESD UZ-9301I 3009-902I 2 9 O X 9

UZ-9301J Depressuring of LP compressor J by D-ESD UZ-9301J 3009-902J 2 10 O X 10

UZ-9301K Depressuring of LP compressor K by D-ESD UZ-9301K 3009-902K 2 11 O X 11

12 12

HDS-9301AB Manual push button for LP compressor A depressuring UZ-9301A 3009-902A 1, 2 13 O X 13

HDS-9301BB Manual push button for LP compressor B depressuring UZ-9301B 3009-902B 1, 2 14 O X 14

HDS-9301CB Manual push button for LP compressor C depressuring UZ-9301C 3009-902C 1, 2 15 O X 15

HDS-9301DB Manual push button for LP compressor D depressuring UZ-9301D 3009-902D 1, 2 16 O X 16

HDS-9301EB Manual push button for LP compressor E depressuring UZ-9301E 3009-902E 1, 2 17 O X 17

HDS-9301FB Manual push button for LP compressor F depressuring UZ-9301F 3009-902F 1, 2 18 O X 18

HDS-9301GB Manual push button for LP compressor G depressuring UZ-9301G 3009-902G 1, 2 19 O X 19

HDS-9301HB Manual push button for LP compressor H depressuring UZ-9301H 3009-902H 1, 2 20 O X 20

HDS-9301IB Manual push button for LP compressor I depressuring UZ-9301I 3009-902I 1, 2 21 O X 21

HDS-9301JB Manual push button for LP compressor J depressuring UZ-9301J 3009-902J 1, 2 22 O X 22

HDS-9301KB Manual push button for LP compressor K depressuring UZ-9301K 3009-902K 1, 2 23 O X 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 34 OF 38
34 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

NOTES
CAUSE AND EFFECT CHART - SBC GENERAL NOTES

2
1. Deleted.

3009-273F

3009-273J
3009-273I
Number

3009-

3009-

3009-

3009-

3009-

3009-

3009-
ESD LEVEL 3 (Emergency Depressurization)

P&ID

273G
273C

273D

273H
273A

273B

273E
2. Deleted.

3. Pressurized emergency shutdown (P-ESD) activates ZONE isolation and

MP compressor G depressuring valve (Block-2) (ZONE 1-2)


MP compressor C depressuring valve (Block-1) (ZONE 1-1)

MP compressor D depressuring valve (Block-1) (ZONE 1-1)

MP compressor H depressuring valve (Block-2) (ZONE 1-2)


MP compressor A depressuring valve (Block-1) (ZONE 1-1)

MP compressor B depressuring valve (Block-1) (ZONE 1-1)

MP compressor E depressuring valve (Block-1) (ZONE 1-1)

MP compressor F depressuring valve (Block-2) (ZONE 1-2)

MP compressor J depressuring valve (Block-2) (ZONE 1-2)


MP compressor I depressuring valve (Block-2) (ZONE 1-2)

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI

Emergency shutdown with vent (trip with vent) to MARK VI


NOMENCLATURE:
provides permissive to open (PO) to BDVs and HVs with depressuring
function in isolated ZONE by completion of isolation or timer expired.
O - OPEN
C - CLOSE 4. Depressurized emergency shutdown (D-ESD) activates ZONE isolation and
SP - STOP

SERVICE DESCRIPTION
automatically depressurize the isolated ZONE after completion of isolation

EFFECT
ST - START or timer expired.
SD - SHUTDOWN
B - BYPASS 5. DCS logic design to input the 0% output and change the mode to manual
PO - PERMISSIVE TO OPEN for associated downstream LV by UZ activation.
PS - PERMISSIVE TO START
X - ACTIVATED
D - DISCONNECT
HH - HIGH HIGH
LL - LOW LOW

OO - OPERATIONAL OVERRIDE (Start-up override etc.)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)

(MP)
MO - MAINTENANCE OVERRIDE

TAG Number
M - Manual Reset / A - Auto Reset

BDV-9101G

XS-9251GB
BDV-9101C

BDV-9101D

BDV-9101H
BDV-9101A

BDV-9101B

BDV-9101E

XS-9251CB

XS-9251DB

XS-9251HB
XS-9251AB

XS-9251BB

XS-9251EB
BDV-9101F

XS-9251FB
BDV-9101J

XS-9251JB
BDV-9101I

XS-9251IB
CAUSE

ESD Loop NOTES


TAG Number SERVICE DESCRIPTION Trip Type P&ID Number VOTING Override Reset NOTES

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

9
Number Manual push bottun can be activated after receiving Permissive for
1.
Depressuring.
UZ-9101A Depressuring of MP compressor A by D-ESD UZ-9101A 3009-902A 1 O X 1

UZ-9101B Depressuring of MP compressor B by D-ESD UZ-9101B 3009-902B 2 O X 2 2. Refer to CAUSE/EFFECT CHART (V-2158-201-A-024).

UZ-9101C Depressuring of MP compressor C by D-ESD UZ-9101C 3009-902C 3 O X 3

UZ-9101D Depressuring of MP compressor D by D-ESD UZ-9101D 3009-902D 4 O X 4

UZ-9101E Depressuring of MP compressor E by D-ESD UZ-9101E 3009-902E 5 O X 5

UZ-9101F Depressuring of MP compressor F by D-ESD UZ-9101F 3009-902F 6 O X 6

UZ-9101G Depressuring of MP compressor G by D-ESD UZ-9101G 3009-902G 7 O X 7

UZ-9101H Depressuring of MP compressor H by D-ESD UZ-9101H 3009-902H 8 O X 8

UZ-9101I Depressuring of MP compressor I by D-ESD UZ-9101I 3009-902I 9 O X 9

UZ-9101J Depressuring of MP compressor J by D-ESD UZ-9101J 3009-902J 10 O X 10

11 11

12 12

HDS-9101AB Manual push button for MP compressor A depressuring UZ-9101A 3009-902A 1 13 O X 13

HDS-9101BB Manual push button for MP compressor B depressuring UZ-9101B 3009-902B 1 14 O X 14

HDS-9101CB Manual push button for MP compressor C depressuring UZ-9101C 3009-902C 1 15 O X 15

HDS-9101DB Manual push button for MP compressor D depressuring UZ-9101D 3009-902D 1 16 O X 16

HDS-9101EB Manual push button for MP compressor E depressuring UZ-9101E 3009-902E 1 17 O X 17

HDS-9101FB Manual push button for MP compressor F depressuring UZ-9101F 3009-902F 1 18 O X 18

HDS-9101GB Manual push button for MP compressor G depressuring UZ-9101G 3009-902G 1 19 O X 19

HDS-9101HB Manual push button for MP compressor H depressuring UZ-9101H 3009-902H 1 20 O X 20

HDS-9101IB Manual push button for MP compressor I depressuring UZ-9101I 3009-902I 1 21 O X 21

HDS-9101JB Manual push button for MP compressor J depressuring UZ-9101J 3009-902J 1 22 O X 22

23 23

24 24

25 25

26 26

27 27

28 28

29 29

30 30

31 31

32 32

33 33

34 34

35 35
10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35
1

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 35 OF 38
35 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

Overall ESD Hierarchy for SBC


Permissive ESD 3 (Emergency Depressurization)

P-ESD D-ESD
IA header
pressure low low HZS HZDS HDS HDS
9000 9000A 9000B 9000C
ESD 0-1
(Station shutdown)
P-ESD Station Depressuring Zone 3 Depressuring
Total power
ESD 0-1 failure (All Zones)
HZS
9001 NOTE 6

ESD 0-2
(Station shutdown ESD 0-2
without Zone 3)

P-ESD
HZS HDS HDS

9010 9010A 9010B

ESD 1 Zone 1 Depressuring Zone 4 Depressuring


(Boosting unit shutdown) ESD 1 Permissive (Total)

P-ESD P-ESD
HZS Permissive HZS Permissive HDS HDS HDS HDS
ESD 2-1-1 9020 9030 9020A 9020B 9030A 9030B
(Process shutdown Block 1 E SD2-1
compressor) E SD2-2

ESD ESD Zone 1 Zone 2 Zone 1 Zone 2


ESD Confirmed fire & ESD
2-1-2 2-2-1 Depressuring Depressuring Depressuring Depressuring
2-1-1 gas detection in 2-2-2
To each compressor train depressuring (Block 1) (Block 1) (Block 2) (Block 2)
Zone NOTE 6 NOTE 6
(NOTE 1)

ESD 2-2-1 D-ESD from From confirmed fire & gas detection (NOTE 1)
Permissive
(Process shutdown Block 2 MARK VI
compressor) D-ESD P-ESD from Confirmed fire &
D-ESD P-ESD D-ESD from
in field MARK VI gas detection in
Zone MARK VI Permissive
HZDS HZDS HZS D-ESD
ぅ ぅ ぅ D-ESD P-ESD HDS HDS
9101AC 9101AA 9101A in field NOTE 6
P-ESD from 9101AB 9101FB
NOTE 2 MARK VI ぅ ぅ ぅ ぅ ぅ ぅ
HZDS HZDS HZS
9101FC 9101FA 9101F
ぅ ぅ ぅ
NOTE 2 NOTE 4
ESD 2-1-2 Train A shutdown
(Process shutdown Block 1 (MP, Block 1) To each compressor train depressuring NOTE 4 Train A depressuring Train F depressuring
(NOTE 1) (MP, Block 1) (MP, Block 2)
Inlet Facility)
Train F shutdown
(MP, Block 2)
Confirmed fire &
gas detection in
Zone From confirmed fire & gas detection (NOTE 1)
D-ESD from
Permissive
MARK VI
D-ESD
D-ESD P-ESD P-ESD from D-ESD from
in field Confirmed fire &
MARK VI MARK VI Permissive
gas detection in
HZDS HZDS HZS Zone D-ESD
9301AC 9301AA 9301A ぅ ぅ ぅ D-ESD P-ESD HDS HDS
ESD 2-2-2 in field P-ESD from
9301AB 9301GB
(Process shutdown Block 2 NOTE 3 HZDS HZDS HZS
MARK VI ぅ ぅ ぅ ぅ ぅ ぅ
Inlet Facility) 9301GC 9301GA 9301G
NOTE 3 NOTE 5
Train A shutdown ぅ ぅ ぅ
(LP, Block 1)
NOTE 5

Train G shutdown
(LP, Block 2) Train A depressuring Train G depressuring
(LP, Block 1) (LP, Block 2)

NOTES
UZ-9055 UZ-9061A~D UZ-9071A~D UZ-9072A~D UZ-9056 UZ-9061E~H UZ-9071E~H UZ-9072E~H
1. Fire Zone (FZ) where fire or gas is detected will be depressurized automatically.
Inlet separator Upper gas coalescer Lower gas coalescer Inlet separator Upper gas coalescer Lower gas coalescer 2. Same configuration from Train A to Train E.
B lock 1 Inlet HH Block 2 Inlet HH
pressure shutdown
water low level vapor breakthrough vapor breakthrough
pressure shutdown
water low level vapor breakthrough vapor breakthrough 3. Same configuration from Train A to Train F.
protection protection protection protection protection protection
4. Same configuration from Train F to Train J.
5. Same configuration from Train G to Train K.
ESD 2-3 ESD 2-3 6. Sequential depressuring
ESD 2-3 7. Manual push buttons for compressor:
(Process shutdown common) HZDS-9X01YA : Isolation and depressuring automatically (D-ESD in field)
ESD 2-3 UZ-9081 UZ-9082A/B UZ-9083 UZ-9601 UZ-9602 UZ-9051 UZ-9401 HDS-9X01YB : Depressuring
Condensate
Liquid coales cer Condensate return P WT HH level
Degassing drum
Diesel driven I A HZDS-9X01YC : Isolation and depressuring automatically (D-ESD)
rundown pump high liquid level MPP I V is olation
protection
water low level pump protection protection
protection
compressor start HZS-9X01Y : Isolation (P-ESD)
X: LP(3) MP(1) Y: Train No.
UZ-9031~9050 UZ-9052
UZ-9084A~C
Trunk line isolation MPP O /I isolation
Condensate
rundown pump
protection A~C

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN SHEET 36 OF 38
36 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

Permissive for Depressuring (ESDV Isolation)


Tag Number Fluid Name P&ID Rev. ESD 2-1-2 ESD 2-2-2 ESD 2-1-1 ESD 2-1-1 ESD 2-1-1 ESD 2-1-1 ESD 2-1-1 ESD 2-2-1 ESD 2-2-1 ESD 2-2-1 ESD 2-2-1 ESD 2-2-1
ESD 0-1 ESD 0-2 ESD 1
(Block 1) (Block 2) (Train A) (Train B) (Train C) (Train D) (Train E) (Train F) (Train G) (Train H) (Train I) (Train J)
3009-ESDV-9001 HC Gas D-3009-1225-201 PS
3009-ESDV-9002 HC Gas D-3009-1225-201 PS
3009-ESDV-9003 HC Gas D-3009-1225-202 PS
3009-ESDV-9004 HC Gas D-3009-1225-202 PS
3009-ESDV-9005 HC Gas D-3009-1225-203 PS
3009-ESDV-9006 HC Gas D-3009-1225-203 PS
3009-ESDV-9007 HC Gas D-3009-1225-204 PS
3009-ESDV-9008 HC Gas D-3009-1225-204 PS
3009-ESDV-9009 HC Gas D-3009-1225-205 PS
3009-ESDV-9010 HC Gas D-3009-1225-205 PS
3009-ESDV-9011 HC Gas D-3009-1225-206 PS
3009-ESDV-9012 HC Gas D-3009-1225-206 PS
3009-ESDV-9013 HC Gas D-3009-1225-207 PS
3009-ESDV-9014 HC Gas D-3009-1225-207 PS
3009-ESDV-9015 HC Gas D-3009-1225-208 PS
3009-ESDV-9016 HC Gas D-3009-1225-208 PS
3009-ESDV-9017 HC Gas D-3009-1225-209 PS
3009-ESDV-9018 HC Gas D-3009-1225-209 PS
3009-ESDV-9019 HC Gas D-3009-1225-210 PS
3009-ESDV-9020 HC Gas D-3009-1225-210 PS
3009-ESDV-9021 HC Gas D-3009-1225-211 PS
3009-ESDV-9022 HC Gas D-3009-1225-211 PS
3009-ESDV-9023 HC Gas D-3009-1225-212 PS
3009-ESDV-9024 HC Gas D-3009-1225-212 PS
3009-ESDV-9025 HC Gas D-3009-1225-213 PS
3009-ESDV-9026 HC Gas D-3009-1225-213 PS
3009-ESDV-9027 HC Gas D-3009-1225-214 PS
3009-ESDV-9028 HC Gas D-3009-1225-214 PS
3009-ESDV-9029 HC Gas D-3009-1225-215 PS
3009-ESDV-9030 HC Gas D-3009-1225-215 PS
3009-ESDV-9031 HC Gas D-3009-1225-216 PS
3009-ESDV-9032 HC Gas D-3009-1225-216 PS
3009-ESDV-9033 HC Gas D-3009-1225-217 PS
3009-ESDV-9034 HC Gas D-3009-1225-217 PS
3009-ESDV-9035 HC Gas D-3009-1225-218 PS
3009-ESDV-9036 HC Gas D-3009-1225-218 PS
3009-ESDV-9037 HC Gas D-3009-1225-219 PS
3009-ESDV-9038 HC Gas D-3009-1225-219 PS
3009-ESDV-9039 HC Gas D-3009-1225-220 PS
3009-ESDV-9040 HC Gas D-3009-1225-220 PS
3009-ESDV-9051 HC Gas D-3009-1225-231 PS PS PS
3009-ESDV-9052 HC Gas D-3009-1225-231 PS PS PS
3009-ESDV-9053 HC Gas D-3009-1225-231 PS PS PS
3009-ESDV-9054 HC Gas D-3009-1225-231 PS PS PS
3009-ESDV-9055 HC Gas D-3009-1225-232 PS PS PS
3009-ESDV-9056 HC Gas D-3009-1225-232 PS PS PS
3009-ESDV-9057 HC Gas D-3009-1225-232 PS PS PS
3009-ESDV-9058 HC Gas D-3009-1225-232 PS PS PS
3009-ESDV-9061A Produced Water D-3009-1225-241A PS PS PS
3009-ESDV-9061B Produced Water D-3009-1225-241B PS PS PS
3009-ESDV-9061C Produced Water D-3009-1225-241C PS PS PS
3009-ESDV-9061D Produced Water D-3009-1225-241D PS PS PS
3009-ESDV-9061E Produced Water D-3009-1225-241E PS PS PS
3009-ESDV-9061F Produced Water D-3009-1225-241F PS PS PS
3009-ESDV-9061G Produced Water D-3009-1225-241G PS PS PS
3009-ESDV-9061H Produced Water D-3009-1225-241H PS PS PS
3009-ESDV-9071A Condensate D-3009-1225-251A PS PS PS
3009-ESDV-9071B Condensate D-3009-1225-251B PS PS PS
3009-ESDV-9071C Condensate D-3009-1225-251C PS PS PS
3009-ESDV-9071D Condensate D-3009-1225-251D PS PS PS
3009-ESDV-9071E Condensate D-3009-1225-251E PS PS PS
3009-ESDV-9071F Condensate D-3009-1225-251F PS PS PS
3009-ESDV-9071G Condensate D-3009-1225-251G PS PS PS
3009-ESDV-9071H Condensate D-3009-1225-251H PS PS PS
3009-ESDV-9101A HC Gas D-3009-1225-272A PS PS PS PS
3009-ESDV-9103A HC Gas D-3009-1225-272A PS PS PS PS
3009-ESDV-9102A HC Gas D-3009-1225-273A PS PS PS PS
3009-ESDV-9101B HC Gas D-3009-1225-272B PS PS PS PS
3009-ESDV-9103B HC Gas D-3009-1225-272B PS PS PS PS
3009-ESDV-9102B HC Gas D-3009-1225-273B PS PS PS PS
3009-ESDV-9101C HC Gas D-3009-1225-272C PS PS PS PS
3009-ESDV-9103C HC Gas D-3009-1225-272C PS PS PS PS
3009-ESDV-9102C HC Gas D-3009-1225-273C PS PS PS PS
3009-ESDV-9101D HC Gas D-3009-1225-272D PS PS PS PS
3009-ESDV-9103D HC Gas D-3009-1225-272D PS PS PS PS
3009-ESDV-9102D HC Gas D-3009-1225-273D PS PS PS PS
3009-ESDV-9101E HC Gas D-3009-1225-272E PS PS PS PS
3009-ESDV-9103E HC Gas D-3009-1225-272E PS PS PS PS
3009-ESDV-9102E HC Gas D-3009-1225-273E PS PS PS PS
3009-ESDV-9101F HC Gas D-3009-1225-272F PS PS PS PS
3009-ESDV-9103F HC Gas D-3009-1225-272F PS PS PS PS
3009-ESDV-9102F HC Gas D-3009-1225-273F PS PS PS PS
3009-ESDV-9101G HC Gas D-3009-1225-272G PS PS PS PS
3009-ESDV-9103G HC Gas D-3009-1225-272G PS PS PS PS
3009-ESDV-9102G HC Gas D-3009-1225-273G PS PS PS PS
3009-ESDV-9101H HC Gas D-3009-1225-272H PS PS PS PS
3009-ESDV-9103H HC Gas D-3009-1225-272H PS PS PS PS
3009-ESDV-9102H HC Gas D-3009-1225-273H PS PS PS PS
3009-ESDV-9101I HC Gas D-3009-1225-272I PS PS PS PS
3009-ESDV-9103I HC Gas D-3009-1225-272I PS PS PS PS
3009-ESDV-9102I HC Gas D-3009-1225-273I PS PS PS PS
3009-ESDV-9101J HC Gas D-3009-1225-272J PS PS PS PS
3009-ESDV-9103J HC Gas D-3009-1225-272J PS PS PS PS
3009-ESDV-9102J HC Gas D-3009-1225-273J PS PS PS PS
3009-ESDV-9111 HC Gas D-3009-1225-274 PS PS PS
3009-ESDV-9113 HC Gas D-3009-1225-275 PS PS PS
3009-ESDV-9121 Condensate D-3009-1225-274 PS PS
3009-ESDV-9091 HC Gas D-3009-1225-800 PS PS
3009-ESDV-9062 Produced Water D-3009-1225-241A PS PS PS PS
3009-ESDV-9063 Condensate D-3009-1225-241A PS PS PS PS
3009-ESDV-9082 Condensate D-3009-1225-281 PS PS PS
3009-ESDV-9083 Condensate D-3009-1225-281 PS PS PS
3009-ESDV-9072A Condensate D-3009-1225-251A PS PS PS
3009-ESDV-9072B Condensate D-3009-1225-251B PS PS PS
3009-ESDV-9072C Condensate D-3009-1225-251C PS PS PS
3009-ESDV-9072D Condensate D-3009-1225-251D PS PS PS
3009-ESDV-9072E Condensate D-3009-1225-251E PS PS PS
3009-ESDV-9072F Condensate D-3009-1225-251F PS PS PS
3009-ESDV-9072G Condensate D-3009-1225-251G PS PS PS
3009-ESDV-9072H Condensate D-3009-1225-251H PS PS PS
3009-ESDV-9112 HC Gas D-3009-1225-274 PS
3009-ESDV-9087A Produced Water D-3009-1225-282A PS PS
3009-ESDV-9087B Produced Water D-3009-1225-282B PS PS
3009-ESDV-9064 HC Gas D-3009-1225-242 PS PS PS PS
3009-ESDV-9105 HC Gas D-3009-1225-271 PS PS PS PS
3009-ESDV-9104A HC Liquid D-3009-1225-272A PS PS PS PS
3009-ESDV-9104B HC Liquid D-3009-1225-272B PS PS PS PS
3009-ESDV-9104C HC Liquid D-3009-1225-272C PS PS PS PS
3009-ESDV-9104D HC Liquid D-3009-1225-272D PS PS PS PS
3009-ESDV-9104E HC Liquid D-3009-1225-272E PS PS PS PS
3009-ESDV-9104F HC Liquid D-3009-1225-272F PS PS PS PS
3009-ESDV-9104G HC Liquid D-3009-1225-272G PS PS PS PS
3009-ESDV-9104H HC Liquid D-3009-1225-272H PS PS PS PS
3009-ESDV-9104I HC Liquid D-3009-1225-272I PS PS PS PS
3009-ESDV-9104J HC Liquid D-3009-1225-272J PS PS PS PS
3009-ESDV-9122 Condensate D-3009-1225-274 PS PS
3009-ESDV-9114 HC Gas D-3009-1225-275 PS
3009-ESDV-9086A Condensate D-3009-1225-281 PS PS PS
3009-ESDV-9086B Condensate D-3009-1225-281 PS PS PS
3009-ESDV-9084A HC Gas D-3009-1225-292 PS PS PS
3009-ESDV-9084B HC Gas D-3009-1225-292 PS PS PS
3009-ESDV-9085A HC Liquid D-3009-1225-292 PS PS PS
3009-ESDV-9085B HC Liquid D-3009-1225-292 PS PS PS
3009-ESDV-9092 Fuel Gas D-3009-1225-800 PS PS

D R A 3009-ESDV-9115
3009-ESDV-9116
HC Gas
HC Gas
D-3009-1225-274
D-3009-1225-275
PS
PS
PS
PS
PS
PS

IN1-JAN- T0
3009-ESDV-9617 HC Gas / Liquid D-3009-1225-610 PS

2 0 2
2 UIL TED
AS LBLED WHEN PRIN SHEET 37 OF 38
37 / 39
TRO
NCON
SONATRACH HASSI R'MEL JOB CODE: 0-7577-20
BOOSTING PHASE III PROJECT DOC. No.: S-3009-1223-061 Rev.3

DEPRESSURING FUNCTION AND ACTION LIST


Definition
Abort Function To stop the depressruing and suspend the preordered depressuring sequence among depressuring zones
Reset Function To initialize the depressruing sequence and the timer

Type of Button Hard Push Button Latch Type Push Button

AUTO DEPRESSURING FUNCTION (D-ESD)


Zone Name
Function Action by BDV and Timer Action Depressuring Restart by BDV and Timer Action Finish Depressuring BDV Action Operator Action for Back to Original
(D-ESD Tag No.)
1. Turn back D-ESD Hard Button (Depressuring Reset)
Push D-ESD Button BDVs Open (Sequential) 2. BDV Close by Operator in HMI
Isolation and Depressuring Start N/A N/A Timer Expire BDVs Keep Open
(HZDS-9000A) Timer Start If the BDV still opens in case of UZ Reset,
alert goes off in HMII until closing all related BDVs.

1. Turn back D-ESD Hard Button (Depressuring Reset)


Depressuring Abort Push Abort Button BDVs Close Automatically Turn back Abort Button BDV Reopen Automatically Sequence Restart 2. BDV Close by Operator in HMI
Timer Expire BDVs Keep Open
(Sequence Suspended) (ABT-9000) Timer Stop (ABT-9000) Timer Restart If the BDV still opens in case of UZ Reset,
alert goes off in HMII until closing all related BDVs.
Station
(HZDS-9000A)
1. BDV Close by Operator in HMI
Turn Back D-ESD Button Timer Reset (Sequential)
Depressuring Reset N/A N/A N/A N/A If the BDV still opens in case of UZ Reset,
(HZDS-9000A) BDVs Keep Open
alert goes off in HMII until closing all related BDVs.

Push UZ Reset Button If the BDV still opens in case of UZ Reset,


UZ Reset BDVs Keep Open N/A N/A N/A N/A
(HRS-9000) alert goes off in HMII until closing all related BDVs.

Push D-ESD Button


(HZDS-9101XA/XC 1. Turn back D-ESD Hard Button (Depressuring Reset)
HZDS-9301XA/XC) BDVs Open 2. BDV Close by Operator in HMI
Isolation and Depressuring Start N/A N/A Timer Expire BDVs Keep Open
Timer Start If the BDV still opens in case of UZ Reset,
Fire/Gas Detection alert goes off in HMII until closing all related BDVs.
(Note 1, 2)
Compressor
(HZDS-9101XA/XC Turn Back D-ESD Button 1. BDV Close by Operator in HMI
Depressuring Reset Timer Reset
HZDS-9301XA/XC) (HZDS-9101XA/XC N/A N/A N/A N/A If the BDV still opens in case of UZ Reset,
(Note 3) BDVs Keep Open
HZDS-9301XA/XC) alert goes off in HMII until closing all related BDVs.

Push UZ Reset Button


If the BDV still opens in case of UZ Reset,
UZ Reset (HRS-9101XA/XC BDVs Keep Open N/A N/A N/A N/A
alert goes off in HMII until closing all related BDVs.
HRS-9301XA/XC)

Note1: If confirmed fire/gas is detected during the station depressuring (D-ESD Station), the station depressuring is continued because compressor zone(Zone-1) is firstly depressurized in station depressuring sequence.
Note2: Any other compressor depressurings by HZDS-9101XA/XC, HZDS-9301XA/XC can be activated during the two compressor depressuring by fire scenario.
Note3: If confirmed fire/gas is detected, related two compressors are automatically depressurized. During the depressuirng, any other depressuring in other zones cannot activated until timer is expired. Timer is set as 30 seconds for preliminary information.
Note4: BDV position is not limitation for UZ Reset. If the cause is solved, UZ can reset by operator in spite of BDV position.
Note5: Depressuring of other zone cannot be activated until timer(20 minutes) is expired or all related BDVs are closed.

MANUAL DEPRESSURING FUNCTION (SBC)


Zone Name
Function Action by BDV and Timer Action Depressuring Restart by BDV and Timer Action Finish Depressuring BDV Action Operator Action for Back to Original(Isolation)
(HDS Tag No.)
1. Turn back HDS Hard Button (HDS Reset)
Push HDS Button BDVs Open (Sequential) 2. BDV Close by Operator in HMI
Depressuring Start N/A N/A Timer Expire BDVs Keep Open
(HDS-9000B) Timer Start If the BDV still opens in case of UZ Reset,
alert goes off in HMII until closing all related BDVs.

1. Turn back HDS Hard Button (HDS Reset)


Station Depressuring Abort Push Abort Hard Button BDVs Close Automatically BDV Reopen Automatically Sequence Restart 2. BDV Close by Operator in HMI
Turn back Abort Hard Button Timer Expire BDVs Keep Open
(HDS-9000B) (Sequence Suspended) (ABT-9000) Timer Stop Timer Restart If the BDV still opens in case of UZ Reset,
alert goes off in HMII until closing all related BDVs.

1. BDV Close by Operator in HMI


Turn Back HDS Button Timer Reset (Sequential)
Depressuring Reset N/A N/A N/A N/A If the BDV still opens in case of UZ Reset,
(HDS-9000B) BDVs Keep Open
alert goes off in HMII until closing all related BDVs.

1. Turn back HDS Hard Button (HDS Reset)


Push HDS Button BDVs Open (Sequential) 2. BDV Close by Operator in HMI
Depressuring Start N/A N/A Timer Expire BDVs Keep Open
(HDS-9020A, 9030A) Timer Start If the BDV still opens in case of UZ Reset,
alert goes off in HMII until closing all related BDVs.

1. Turn back HDS Hard Button (HDS Reset)


Block (Zone1, 2)
Depressuring Abort Push Abort Hard Button BDVs Close Automatically BDV Reopen Automatically Sequence Restart 2. BDV Close by Operator in HMI
(HDS-9020A, 9030A) Turn back Abort Hard Button Timer Expire BDVs Keep Open
(Sequence Suspended) (ABT-9020, 9030) Timer Stop Timer Restart If the BDV still opens in case of HDS Reset,
alert goes off in HMII until closing all related BDVs.

1. BDV Close by Operator in HMI


Turn Back HDS Button Timer Reset (Sequential)
Depressuring Reset N/A N/A N/A N/A If the BDV still opens in case of UZ Reset,
(HDS-9020A, 9030A) BDVs Keep Open
alert goes off in HMII until closing all related BDVs.

Push HDS Button


Zone 1(total) (HDS-9010A) 1. Turn back HDS Hard Button (HDS Reset)
(HDS-9010A) (HDS-9020B, 9030B) BDVs Open 2. BDV Close by Operator in HMI
Depressuring Start N/A N/A Timer Expire BDVs Keep Open
Zone2(block) (HDS-9000C) Timer Start If the BDV still opens in case of UZ Reset,
(HDS-9020B, 9030B) (HDS-9010B) alert goes off in HMII until closing all related BDVs.
Zone3 (HDS-9101XB)
(HDS-9000C) Turn Back HDS Button
Zone 4 (HDS-9010A)
(HDS-9010B) 1. BDV Close by Operator in HMI
(HDS-9020B, 9030B) Timer Reset
Compressor Depressuring Reset N/A N/A N/A N/A If the BDV still opens in case of UZ Reset,
(HDS-9000C) BDVs Keep Open
(HDS-9101XB) alert goes off in HMII until closing all related BDVs.
(HDS-9010B)
(HDS-9101XB)
Note1: BDV position is not limitation for UZ Reset. If the cause is solved, UZ can reset by operator in spite of BDV position.
Note2: Depressuring of other zone cannot be activated until timer(20 minutes) is expired or closing all related BDVs.
General Note: The time interval between adjacent Zones is 20 minutes.

Depressuring Sequence (SBC)


Zone Name 1st 2nd 3rd 4th
Station (HZDS-9000A/HDS-9000B) Zone 1 in Block 1 and 2 Zone 2 in Block 1 Zone 2 in Block 2 Zone 3 and Zone 4

Block 1 (HDS-9020A) Zone 1 in Block 1 Zone 2 in Block 1 N/A N/A

D R A Block 2 (HDS-9030A) Zone 1 in Block 2 Zone 2 in Block 2 N/A N/A

IN1-JAN- T0
2
2 0 2
UIL TED
General Note: The time interval between adjacent Zones is 20 minutes.

AS LBLED WHEN PRIN SHEET 38 OF 38


38 / 39
TRO
NCON
Hassi R'mel Boosting Phase III Project
Comment Response Sheet (CRS)
Contractor Document Number S-3009-1223-061
Document Title CAUSE AND EFFECT CHART FOR SBC
Rev. No 2

No Comments Confirmation / Explanation by Contractor

<Page 6/7/8/9/10/11/12/13/14/15/16> The typo of "depeloped" was corrected to developed.


As for the "Note 2 : To be depeloped in Step 2
1 detail engineering stage", it is commented that the
"depeloped" should be corrected to developed.

<Page 31> This document does not describe DCS, but indicate ESD
refer to Owner'<reply regarding DCS and ESD system.
system separation>.
2 If Owner needs details of DCS system, it can be referred to
DCS Control Narrative (S-3002/3003/3009-1371-301).

D R A
IN1-JAN- T0
2
2 0 2
UIL TED
AS LBLED WHEN PRIN 39 / 39
TRO
NCON