Professional Documents
Culture Documents
2000kva 11000 - 433 EO16 Drawings
2000kva 11000 - 433 EO16 Drawings
DATE: 29.11.2023
Volts at no load
LV 433 Vector Symbol Dyn11
APPD. BY : MS
DRN. BY : DK
CHD. BY : MS
Amperes HV 104.98 Type of cooling ONAN
LV 2666.82 Temp. rise Oil/Wdg. 40/45ºC
Phases 3 Weight of oil (kg) 2025
Serial number Total weight (kg) 8700
Taps for HV variation in +9.375 % to Untanking Mass(kg) 4300
DATE
REASONS
REV.
3
1
2) PLATE SIZE 250x150 WITH 4 HOLES 4.0 Ø AT 10MM FROM
CT DETAILS:
WTI CT: 2667/2 A, 7.5 VA, ACC. Class 5
NCT-1: 3200/1 A, Class-PS, Vk>150V,Imag at Vk/2 30 mA Max Rct 7.0 ohms
NCT-2: 100/5 A, 10VA, Class-5P20
NOTE :-
EDGES
This document is the exclusive property of GENERAL ENGINEERING WORKS and shall not be used, copied or communicated to third parties without its prior authorisation. /
Local language
PLATE12/2/2023
On Load Tap Changer (OLTC) suitable for off circuit application. Fitted with changeover selector enabling
utilisation in coarse-fine or reversing winding configuration of transformer. Fully bidirectional. Compact, flange
mounted, comprising driving mechanism and high speed selector switch. Local manual and electrical control,
with provision for remote electrical operation. Optional equipment includes Remote Tapchange Control
Cubical (RTCC) with or without line drop compensation, etc. Fitted with protective devices to prevent
malfunctioning. Should be connected to transformer conservator. Fitted with pressure relief switch (PRS) set
to specified pressure for additional safety.
JAN 2014
Rights reserved to amend design data without prior notification