GENERAL ENGINEERING WORKS

C 35-36 UPSIDC Industrial Area Naini, Prayagraj, Uttar Pradesh-211010


MADE IN INDIA

Copper Wound Converter duty Transformer

KVA 2000 Standard IS 2026


HV 11000 Impedance Volts 6.25%

DATE: 29.11.2023
Volts at no load
LV 433 Vector Symbol Dyn11

APPD. BY : MS
DRN. BY : DK

CHD. BY : MS
Amperes HV 104.98 Type of cooling ONAN
LV 2666.82 Temp. rise Oil/Wdg. 40/45ºC
Phases 3 Weight of oil (kg) 2025
Serial number Total weight (kg) 8700
Taps for HV variation in +9.375 % to Untanking Mass(kg) 4300

CUSTOMER & PO. No.POLYVION CABLES PRIVATE LIMITED, SONIPAT


1.5625 % steps -15.625 % Oil volume (Litres) 2440
Frequency, Hz 50 Year / manufacture 2023

Drawing no. TRFD0XXX/GCD/RP


Basic Insulation level KVp KVrms
HV terminals 75 28

MATL : ANODISED ALUMINIUM


LV terminals ---- 3

No load Losses, W 2050 Load Losses, W 13450

SPEC : M.S - 100


Customer : POLYVION CABLES PRIVATE LIMITED, SONIPAT
P.O. No. : POLY/PO/27/23-24

DATE
REASONS
REV.
3

1
2) PLATE SIZE 250x150 WITH 4 HOLES 4.0 Ø AT 10MM FROM

3) IMPEDENCE = 5.00% SUBJECTED TO IS TOLERENCE AND WILL


1) ART WORK TO BE DONE BY SUPPLIER

BE PUNCHED AFTER TESTING OF TRANSFORMER

CT DETAILS:
WTI CT: 2667/2 A, 7.5 VA, ACC. Class 5
NCT-1: 3200/1 A, Class-PS, Vk>150V,Imag at Vk/2 30 mA Max Rct 7.0 ohms
NCT-2: 100/5 A, 10VA, Class-5P20
NOTE :-

EDGES

This document is the exclusive property of GENERAL ENGINEERING WORKS and shall not be used, copied or communicated to third parties without its prior authorisation. /
Local language

PLATE12/2/2023
On Load Tap Changer (OLTC) suitable for off circuit application. Fitted with changeover selector enabling
utilisation in coarse-fine or reversing winding configuration of transformer. Fully bidirectional. Compact, flange
mounted, comprising driving mechanism and high speed selector switch. Local manual and electrical control,
with provision for remote electrical operation. Optional equipment includes Remote Tapchange Control
Cubical (RTCC) with or without line drop compensation, etc. Fitted with protective devices to prevent
malfunctioning. Should be connected to transformer conservator. Fitted with pressure relief switch (PRS) set
to specified pressure for additional safety.

Rated voltage : 33 kV Max. Rated through current : 300 A


Max. system voltage : 37 kV Time per tap change. : 4-6 secs.
Max. voltage per step at rated : Weight with oil without conservator : 720 kg
through current of 100 A : 1200 V Oil for first filling without conservator : 38 0 ltrs.
200 A : 1000 V Mechanical operations : 500,000
300 A : 850 V operations
Max. no. of steps : 16 Short circuit withstand : 4.0 kAmps
Max. no. of positions : 17 for 3 secs.

Power Freq. (kV) Impulse (kVpeak)


Between phases : 70 170
To earth : 70 170
Between a djacent contacts : 25 70
Between first and last contact : 30 95
Over changeover selector contacts : 30 95

JAN 2014
Rights reserved to amend design data without prior notification