Journal of Electrical and Electronics Engineering 111
_________________________________________________________________________________________________________________

A Comparative Study of Impact Series FACTS Devices on Distance


Relay Setting in 400 kV Transmission Line
ZELLAGUI Mohamed1, CHAGHI Abdelaziz2
1
University of Batna, Algeria
LSP-IE Research Laboratory, Department of Electrical Engineering, Faculty of Technology,
Campus of CUB, Street Med El Hadi Boukhlouf, 05000, Batna, Algeria, E-mail: m.zellagui@ymail.com
2
University of Batna, Algeria
LSP-IE Research Laboratory, Department of Electrical Engineering, Faculty of Technology,
Campus of CUB, Street Med El Hadi Boukhlouf, 05000, Batna, Algeria, E-mail: az_chaghi@univ-batna.dz

Abstract – This research paper presents a comparative stability using FACTS controllers has been extensively
study of the performance of distance protection for investigated. There are two generations for realization of
transmission line 400 kV in Algerian transmission power electronics based FACTS controllers: the first
networks at Group Sonelgaz (Algerian Company of generation employs conventional thyristor-switched
Electricity and Gas) compensated by two different series capacitors and reactors, and quadrature tap-changing
Flexible Alternative Current Transmission System transformers, the second generation employs gate turn-off
(FACTS) i.e. GTO Controlled Series Capacitor (GCSC) (GTO) thyristor-switched converters as voltage source
and Thyristor Controlled Series Capacitor (TCSC) converters (VSCs). The first generation has resulted in the
connected at midpoint of an electrical transmission line. Static Var Compensator (SVC), the Thyristor-Controlled
The facts are used for controlling transmission voltage, Series Capacitor (TCSC), and the Thyristor-Controlled
power flow and reactive power in high power transfer Phase Shifter (TCPS) [2, 3]. The second generation has
levels. This paper studies the effects of angle variation Ȗ produced the Static Synchronous Compensator
and Į controlled GCSC and TCSC insertion on the total (STATCOM), the Static Synchronous Series Compensator
impedance of a transmission line protected by MHO (SSSC), the Unified Power Flow Controller (UPFC), and
distance relay. The modified setting zone protection the Interline Power Flow Controller (IPFC) [4-7]. The two
(resistance and reactance) in capacitive and inductive groups of FACTS controllers have distinctly different
boost mode for three forward zones and one reverse operating and performance characteristics.
zone are investigated in order to improve the The voltage source converter (VSC) type FACTS
performances of distance protection. The simulation controller group employs self-commutated DC to AC
results are performed in MATLAB software. converters, using GTO thyristors, which can internally
generate capacitive and inductive reactive power for
Keywords: FACTS; GCSC; TCSC; Apparent reactance; transmission line compensation, without the use of capacitor
Transmission line; Distance relay; Zones Setting. or reactor banks. The converter with energy storage device
can also exchange real power with the system, in addition to
I. INTRODUCTION the independently controllable reactive power. The VSC can
be used uniformly to control transmission line voltage,
In recent years, power demand has increased impedance, and angle by providing reactive shunt
substantially while the expansion of power generation and compensation, series compensation, and phase shifting, or to
transmission has been severely limited due to limited control directly the real and reactive power flow in the
resources and environmental restrictions. As a consequence, transmission line [5, 6, and 7].
some transmission lines are heavily loaded and the system Many researchers have focused on GCSC’s different
stability becomes a power transfer-limiting factor. FACTS aspect into the power systems. In [8] the GCSC with a
controllers have been mainly used for solving various power simple controller, can damp both SSR and low frequency
system steady state control problems [1]. oscillations. However their concentration is on mitigating
However, recent studies reveal that FACTS controllers the SSR rather those LFOs damping and the controller
could be employed to enhance power system stability in parameters are designed by trial and error. In [9], in addition
addition to their main function of power flow control. to introducing the structure of the GCSC, a comparative
The literature shows an increasing interest in this subject work, shows some advantages of the GCSC with respect to
for the last two decades, where the enhancement of system
112 Volume 5, Number 2, October 2012
_________________________________________________________________________________________________________________

the TCSC, such as smaller size of GCSC’s capacitor and


lower current rating in the GCSC’s switches.
They mentioned that although the GCSC has a better
performance with respect to the TCSC, especially in power
oscillation damping purposes, TCSC is more practical
because of its simpler protection scheme and being an
already established technology. In [10] introduced principle
of operation and some prospective applications of the GCSC
proved by simulation that in most situations, GCSC can be
more attractive than TCSC. References [11-12], present a
new, simple and robust control strategy for the GCSC
controlling the active power transmitted by very long lines. (a)
The GCSC was proved to be very effective, in controlling
the power-flow of the transmission lines that are little longer
than half the wavelength of the system frequency
comparative to the HVDC systems [13]. Reference [14]
study the distance relay measured impedance for faults on a
double circuit transmission line in the presence of TCSC in (b)
the case of phase to phase and three phases, faults. The
effect of TCSC on a double circuit transmission line, on the Fig. 1. Transmission line in presence of GCSC system.
measured impedance at the relaying point is carried out in a). Principle, b). Apparent reactance.
[15]. In the presence of TCSC, the measured impedance at
the relaying point is affected not only in its compensation This compensator injected in the transmission line a
degree, but also in its installation point. In reference [16], variable capacitive reactance (XGCSC).From figure 1.b.this
the influence of TCSC to EHV transmission line protection, capacitive reactance is defined by the following equation
especially to the high-frequency directional protection and [6,7,8,10]:
presents a novel transient protection scheme based on
Wavelet Transform (WT) is analyzed. Paper [17] study ª 2 1 º
X GCSC (γ ) = X C «1 − γ − sin(2π ) » (1)
analytically by using simple models the general impact of ¬ π π ¼
TCSS on transmission line protection.
In this paper, the setting protection zones for a distance
Where, X C = 1 (2)
relay on a 400 kV single transmission line is considered for C .ω
the GCSC and TCSC series FACTS devices, in capacitive
and inductive modes for different values of firing angle for III. THYRISTOR CONTROLLED SERIES CAPACITOR
series compensation on transmission line using controlled (TCSC)
GTO and thyristors.
The compensator TCSC mounted on figure 2.a is a type
II. GTO CONTROLLED SERIES CAPACITOR (GCSC) of series FACTS compensators. It consists of a capacitance
(C) connected in parallel with an inductance (L) controlled
The compensator GCSC mounted on figure 1.a is the by a valve mounted in anti-parallel thyristors conventional
first that appears in the family series compensators. It (T1 and T2) and controlled by an angle of extinction (Į) is
consists of a capacitance (C) connected in series with the varied between 90° and 180°.
transmission line and controlled by a valve-type GTO
thyristors mounted in anti-parallel and controlled by an
angle of extinction (Ȗ) is varied between 0° and 180°.
If the GTOs are kept turned-on all the time, the capacitor
C is bypassed and it does not realize any compensation
effect. On the other hand, if the positive-GTO (GTO1) and
the negative-GTO (GTO2) turn off once per cycle, at a given
angle Ȗ counted from the zero-crossings of the line current,
the main capacitor C charges and discharges with alternate
polarity. Hence, a voltage VC appears in series with the
transmission line, which has a controllable fundamental
component that is orthogonal (lagging) to the line current.
(a)
Journal of Electrical and Electronics Engineering 113
_________________________________________________________________________________________________________________

The setting zones for protected transmission line AB


without series FACTS is [19, 20]:

Z1 = R1 + jX1 = 80%Z AB = 0,8.( RAB + jX AB ) (6)


(b)
Z 2 = R2 + jX 2 = RAB + jX AB + 0, 2.( RBC + jX BC ) (7)
Fig. 2. Transmission line on presence TCSC system.
a). Principle, b). Apparent reactance. Z3 = R3 + jX 3 = RAB + jX AB + 0, 4.( RBC + jX BC ) (8)

This compensator injected in the transmission line a Z4 = R4 + jX 4 = 60%Z AB = 0,6.( RAB + jX AB ) (9)
variable reactance (XTCSC) indicated by figure 2.b.The
apparent reactance XTCSC is defined by the following The impedance total of transmission line AB and BC
equation [6, 15-16]. The expression of XTCSC is directly measured by distance relay is:
related to the angle Į, which was varied, following the
above equation: KVT
Z AB = KZ .ZL− AB = Z L− AB (10)
KCT
ª π º
X L (α ) = X L max « » (3)
Z BC = KZ .Z L−BC =
KVT
Z L−BC (11)
¬ π − 2α − sin(2α ) ¼ KCT

Where, X L max = L.ω and X C = 1 (4) Where, ZL-AB and ZL-BC is real total impedance of line AB
C .ω and BC respectively. KVT and KCT is ratio of voltage to
current.
A part of the equation (4), final the equation (3) becomes: The presence of series FACTS systems in a reactor (XFACTS)
is a direct influence on the total impedance of the line
ª π º protected (ZAB), especially against the reactance XAB and no
X C .X L « » influence on the resistance RAB. The setting zones for
X TCSC (α ) = ¬ π − 2α − sin(2α ) ¼ (5) protected transmission line with series FACTS connected at
ª π º midline are:
XC + XL « »
¬ π − 2α − sin(2α ) ¼
Z1 = 80%Z AB = 0,8.RAB + 0,8. j( X AB + X FACTS ) (12)
IV. SETTING ZONES FOR DISTANCE RELAYS IN
PRESENCE OF SERIES FACTS DEVICES Z 2 = RAB + j ( X AB + X FACTS ) + 0, 2.( RBC + jX BC ) (13)

Distance protection is so called because it is based on an Z3 = RAB + j ( X AB + X FACTS ) + 0, 4.( RBC + jX BC ) (14)
electrical measure of distance along a transmission line to a
fault. The distance along the transmission line is directly Z4 = 60%Z AB = 0,6.( RAB + jX AB ) (15)
proportional to the series electrical impedance of the
transmission line. Impedance is defined as the ratio of For the case of on integration of GCSC, the reactance
voltage to current. Therefore, distance protection measures XFACTS is equal XGCSC and on integration of TCSC, the
distance to a fault by means of a measured voltage to reactance XFACTS is equal XTCSC.
measured current ratio computation [18, 19]. The
philosophy of setting relay at Sonelgaz Group is three zones V. CASE STUDY AND SIMULATION RESULTS
forward (Z1, Z2 and Z3) and one zone reverse (Z4) for
protection the transmission line HV and EHV between Figure 4 is represented the power system studied in this
busbar A and B with ZAB is showed in figure 3. paper is the Algerian electrical transmission networks at
group Sonelgaz [21, 22, 23]. The MHO distance relay is
located in the bus bar at Oued El Athmania substation in
Mila to protect electrical transmission line 400 kV between
busbar A and busbar B at Ain El Beida substation in Oum El
Bouaghi, the bus bar C at Bir El D’heb substation in
Tébessa.
The parameters of transmission line are summarized in
the appendix.

Fig. 3. Setting zones for distance relay.


114 Volume 5, Number 2, October 2012
_________________________________________________________________________________________________________________

(b). Capacitive mode.

Ȗ (°) 100 120 140 160 180


XGCSC (ȍ) -0,476 -12,237 -51,371 -121,63 -212,20
XAB (ȍ) 222,40 210,64 171,51 101,25 10,673
RAB (ȍ) 23,051 23,051 23,051 23,051 23,051

The impact of the angle Ȗ variation on the value of


reactance setting zones is represented in following figure.

Fig. 4. Algerian electrical transmission network study.

A. Impact of GCSC

The figure 5 shows the characteristic curve XGCSC (Ȗ) of


the compensator used GCSC in this case study.

Fig. 6. Characteristic curve X = f (Ȗ).

The impact of the angle Ȗ variation on the value of


resistance setting zones is represented in figure 7.

Fig. 5. Characteristic curve XGCSC = f (Ȗ) installed.

The impact of the angle variation Ȗ on reactance XGCSC


and the total impedance for transmission line protected (XAB
and RAB) is summarized in table 1.

TABLE 1. The variation of XGCSC, XAB and RAB in function of Ȗ.

(a). Inductive mode.

Fig. 7. Characteristic curve R = f (Ȗ).


Ȗ (°) 0 20 40 60 80
XGCSC (ȍ) 212,20 121,63 51,371 12,237 0,475 As can be seen from figure 5, which represents the curve
XAB (ȍ) 435,09 344,51 274,25 235,12 223,36 characteristics XGCSC (Ȗ) for installed GCSC, the value of the
reactance XGCSC varies with the angle Ȗ. In this case there is
RAB (ȍ) 23,051 23,051 23,051 23,051 23,051 a reduction of XGCSC between Xmax which is equal to 212, 20
ȍ and Xmin equal to -212, 20 ȍ.

From figures 6 and 7 it can be seen that, the total line


reactance XAB and the forward reactance zone (X1, X2 and
Journal of Electrical and Electronics Engineering 115
_________________________________________________________________________________________________________________

X3) are decreases but X4 increased with the same form of


angle Ȗ variation.
However the total resistance of the line RAB and the
different zones resistance (R1, R2, R3 and R4) are constant
regardless changes in XGCSC and Ȗ.

B. Impact of TCSC

Figure 8 shows the characteristic curve XTCSC (Į) of the


TCSC compensator used in this case study.

Fig. 9. Characteristic curve X = f (Į).

The impact of the angle Į variation on the value of


resistance setting zones is represented in following figure
10.

Fig. 8. Characteristic curve XTCSC = f (Į) installed.

The impact of the angle Į variation on reactance XTCSC


and on the total impedance for protected transmission line
(XAB and RAB) is summered in table 2.

TABLE 2. The variation of XTCSC, XAB and RAB with respect to Į.

(a). Inductive mode.

Į (°) 90 95 100 105 115 Fig. 10. Characteristic curve R = f (Į).


XGCSC (ȍ) 20,944 21,063 21,938 24,690 66,620
From figure 8, which represents the curve characteristics
XAB (ȍ) 243,82 243,94 244,82 247,57 289,50
XTCSC (Į) for the installed TCSC, the value of the reactance
RAB (ȍ) 23,051 23,051 23,051 23,051 23,051 XTCSC varies depending on the angle Į. For inductive the
value of reactance is increased between 12,70 ȍ and XL.max
(b). capacitive mode. which is equal to 454, 2 ȍ and in the capacitive mode
decreases from XC.max which is equal to -372, 9 ȍ to zero.
Į (°) 120 125 130 150 180 From figures 9 and 10, the total line reactance XAB and
XGCSC (ȍ) -126,91 -25,741 -12,72 -3,035 -1,090 the different zones reactance (X1, X2, X3 and X4) have the
XAB (ȍ) 95,968 197,14 210,15 219,84 221,79 same form with respect to the angle Į variation for the two
operation modes. The total resistance of the line RAB and the
RAB (ȍ) 23,051 23,051 23,051 23,051 23,051
different zones resistance (R1, R2, R3 and R4) are constant
regardless changes in XTCSC and angle Į for the two
The impact of the angle Į variation on the value of operation modes.
reactance setting zones is represented in following figure 9.
VI. CONCLUSION

The results are presented in relation to a typical 400 kV


transmission system employing GCSC and TCSC series
FACTS devices. The effects of the extinction angle Ȗ for
116 Volume 5, Number 2, October 2012
_________________________________________________________________________________________________________________

controlled GTO installed on GCSC as well as extinction Design for a GCSC", IEEE Transaction on Power Delivery,
angle Į for controlled thyristors on TCSC are investigated. vol. 23, n°3, pp. 1673 – 1681, July 2008.
These devices are connected at the midpoint of a [13] M. Ardes, C. Portela, E.L.V. Emmerik, and R.F. Da Silva
transmission line protected by distance relay. Dias, "Static Series Compensators Applied to Very Long
Distance Transmission Lines", Electrical Engineering, vol. 86,
As demonstrated these angles injected variable reactance n° 2, pp. 69 – 76, February 2004.
(XGCSC or XTCSC) in the protected line which results in direct [14] S. Jamali, A. Kazemi, and H. Shateri, "Measured Impedance
impact on the total impedance of the protected line. In fact by Distance Relay for Inter Phase Faults with TCSC on a
this effect varies the settings zones by decreasing Double Circuit Line", 18th Australasian Universities Power
performance of the total system protection and lead to Engineering Conference, Australia, 14 - 17 December 2008.
unwanted tripping of circuit breaker in the presence of series [15] A. Kazemi, S. Jamali, and H. Shateri, "Comparing TCSC
FACTS compensatory. Placements on Double Circuit Line Mid-Point and Ends from
For specified systems, settings of different protections Measured Impedance Point of View", IEEE International
Conference on Industrial Technology (ICIT), Chengdu, China,
can be achieved based on the proposed setting principles.
21-24 April 2008.
Moreover following state of series FACTS devices in order [16] Q. Liu, and Z. Wang, "Research on the Influence of TCSC to
to avoid circuit breaker unwanted tripping changing the EHV Transmission Line Protection", International Conference
settings relay of overcurrent and distance protection is on Deregulation and Restructuring and Power Technologies
necessary. (DRPT), Nanjing, China, 6 - 9 April 2008.
[17] P.S. Chaudhari, P.P. Kulkarni, R.M. Holmukhe, and P.A.
REFERENCES Kulkarni, "TCSC for Protection of Transmission Line", 3rd
International Conference on Emerging Trends in Engineering
[1] N. G. Hingoran, and L. Gyugyi, "Understanding FACTS and Technology (ICETET), Goa, India, 19 - 21November
Concepts and Technology of Flexible AC transmission 2010.
Systems", Published by John Wiley & Sons Ltd, West Sussex, [18] M. Zellagui, and A. Chaghi, "Distance Protection for
United Kingdom, 2000. Electrical Transmission Line - Equipments, Settings
[2] IEEE Power Engineering Society, "FACTS Overview", Zones and Tele-Protection", Book published by LAP
Published by IEEE Special Publication 95TP108, New Jersey, Lambert Academic Publishing, Germany, June 2012.
USA, 1995. [19] G. Zigler, "Numerical Distance Protection: Principles and
[3] IEEE Power Engineering Society, "FACTS Applications", Applications", third edition, Publics Corporate Publishing,
Published by IEEE Special Publication 96TP116-0, New Germany, January 2008.
Jersey, USA, 1996. [20] L. Gérin-Lajoie, "A MHO Distance Relay Device in EMTP
[4] I.A. Erinmez, and A. M. Foss, "Static Synchronous Works", Electric Power Systems Research (EPSR), vol. 79,
Compensator (STATCOM)". Working Group 14.19, CIGRE n°. 3, pp. 484 – 449, March 2009.
Study Committee 14, Document No. 144, USA, August 1999. [21] M. Zellagui, and A. Chaghi, "MHO Distance Relay of
[5] CIGRE Task Force 14-27, "Unified Power Flow Controller", Transmission Line High Voltage using Series Compensation in
Published by CIGRE Technical Brochure, USA, 1998. Algerian Networks", ACTA Electrotehnica, vol. 52, n°. 3,
[6] R.M. Mathur, and R.S. Basati, "Thyristor-Based FACTS pp. 126 – 133, Sep. 2011.
Controllers for Electrical Transmission Systems", Published [22] M. Zellagui, and A. Chaghi, "Impact of TCSC on Measured
by IEEE Press Series in Power Engineering, USA, 2002. Impedance by MHO Distance Relay on 400 kV Algerian
[7] K.K. Sen, and M.L. Sen, "Introduction to FACTS Transmission Line in Presence of Phase to Earth Fault",
Controllers: Theory, Modeling and Applications", Published Journal of Electrical Systems, vol. 8, no.3, pp. 273 – 291,
by John Wiley & Sons, Inc., and IEEE Press, USA, 2009. 2012.
[8] F.D. De Jesus, L.F.W. De Souza, E. Wantanabe, and J.E.R. [23] Sonelgaz Group/GRTE, Topologies of Electrical
Alves, "SSR and Power Oscillation Damping using Gate- Transmission Networks High Voltage, Algerian Company of
Controlled Series Capacitors (GCSC)", IEEE Transaction on Electrical Transmission Network, February 2011, Algiers,
Power Delivery, vol. 22, n°3, pp. 1806 – 1812, Mars 2007. Algeria.
[9] L.F.W. De Souza, E.H. Wantanabe, and J.E.R. Alves,
"Thyristor and Gate-Controlled Series Capacitors: A APPENDIX
Comparison of Component Ratings", IEEE Transaction on
Power Delivery, vol. 23, n° 2, pp. 899 – 906, May 2008.
- Electrical transmission line :
[10] S. Banerjee, J.K. Chatterjee, and S.C. Triphathy, "Application
Un = 400 kV, fn = 50 Hz, ZL = 0, 03293 + j 0, 3184 ȍ/km,
of Magnetic Energy Storage Unit as Continuous VAR
Length AB = 300 km, Length BC = 170 km.
Compensator", IEEE Transaction on Energy Conversion,
vol. 5, n° 1, pp. 39 – 45, January 1990. - GCSC :
[11] E.H. Wantanabe, L.F.W. De Souza, F.D. De Jesus, and J.E.R. C = 15 mF, Semi-conductor is GTO.
Alves, "GCSC-Gate Controlled Series Capacitor: A New - TCSC :
FACTS Devices for Series Compensation of Transmission L = 3,30 mH, C = 15 mF, Semi-conductor is thyristors.
Lines", IEEE/PES Transmission and Distribution Conference
and Exposition: Latin America, 8-11 November 2004. - Current transformer :
[12] S. Ray, G.K. Venayagamoorthy, and E.H. Watanabe, "A Ipri = 1000 A, Isec = 5 A, KCT = 200.
Computational Approach to Optimal Damping Controller - Voltage transformer :
Vpri = 400000 / ¥3 V, Vsec = 100 / ¥3 V, KVT = 4000.