Professional Documents
Culture Documents
BWQ Series - PDF - Zamil Air Conditioners
BWQ Series - PDF - Zamil Air Conditioners
BWQ Series - PDF - Zamil Air Conditioners
BWQ Series
Chilled/Hot water
BWQ03 thru BWQ25
3 TR thru 30 TR
10 kW thru 100 kW
Company Business
Zamil Air Conditioners was founded in 1974, and is the first major business venture in manufacturing sector for the
Al Zamil group of Companies. It is also the first manufacturing unit for air conditioners to be established in Saudi Arabia.
Zamil Air conditioners manufactures both consumer and central range of air conditioners and has sales operations in
over 55 countries in the Middle East, Europe, America, Africa, Australia and the Far East.
The company’s operations are structured into four Strategic Business Units (SBUs) supporting six in - house product and
service brands as well as a number of international brands under the OEM sales.
The six in-house brands are Classic, Cooline, CoolCare, Clima Tech, Geoclima and Kessler Clima Tech.
The first three SBUs - Consumer Products, Unitary & Applied Products and Zamil CoolCare direct their business opera-
tions from the corporate headquarters at Dammam, Saudi Arabia.
The production facilities at Dammam are shared by Consumer Products and Unitary & Applied Products. Geoclima has
its own production and functional departments located at Monfalcone, Italy.
All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work at
its best and achieve the corporate goals of increased productivity and efficiently.
Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)
certificate for room air conditioners. Its products and services are also certified with:
Other awards include the prestigious Engineering Excellence Award of General Electric, and the inaugural Prince
Mohammed bin Fahd Al Saud Award for Factory Safety.
Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners
manufacturers a host of residential and commercial air conditioners. This board range extends from the concealed units
up to 5 ton, the ducted splits up to 30 tons, the packaged units up to 70 tons. The single and double skin air handling units
up to 130,000 CFM and the water chillers up to 487 ton cooling capacity.
INDEX
Contents Page
1
OUTSTANDING FEATURES
* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS
* SMALL FOOTPRINT
* LIGHT WEIGHT
2
MODEL DECODING
MODELS: BWQ03 - BWQ05
1, 2 & 3 4&5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL COIL APPLICATION BLOWER DRIVE HEATER COIL FINS FILTER UNIT OTHER
(SQ. FT.) SUPPLY MOTOR OPTIONS OPTIONS
OPTIONS ACCESSORIES
(V-Ph-Hz) (kW/STAGE)
BWQ 03 H : HORIZONTAL B : 220/240-1-50 A : STD. 3 ROW CHILLED U : 0.5 HP ODP N : DIRECT N : NO HEATER A : ALUMINUM N : NO FILTER N : STD. UNIT. N : STD. UNIT
COOLINE WATER COIL DRIVE FIN NO ACCESORIES
V : VERTICAL L : 380/415-3-50 W : 0.75 HP ODP A : 5/1 E : 1/2" ALUMINUM
AIR HANDLING
V : VOLT FREE
UNIT (4 WIRE) B : 2 ROW CHILLED B : COATED
F : 1/2" SYNTHETIC CONTACTS*
(CHILLED WATER) 05 WATER + 1 ROW W : 0.75 HP ODP B : 6/1 ALUMINUM
HEATING SPLIT COIL FIN
Y :1 HP ODP C : 7.5 /1** A : 1" ALUMINUM
C : COPPER FIN
C : 1" SYNTHETIC
3
MODELS: BWQ07 - BWQ25
1, 2 & 3 4&5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL COIL APPLICATION BLOWER DRIVE HEATER COIL FINS FILTER UNIT OTHER
(SQ. FT.) SUPPLY MOTOR OPTIONS OPTIONS
OPTIONS ACCESSORIES
(V-Ph-Hz) (kW/STAGE)
BWQ 07 H : HORIZONTAL L : 380/415-3-50 A : STD. 3 ROW CHILLED FOR BWQ07 N : NO HEATER A : ALUMINUM FOR BWQ07 N : STD. UNIT. N : STD. UNIT
J : ALT. I
COOLINE (4 WIRE) WATER COIL D : 2 HP ODP A : 5/1 FIN N : NO FILTER NO ACCESORIES
V : VERTICAL B : 2 ROW CHILLED K : ALT. II B : 6/1 E : 1/2" ALUMINUM
AIR HANDLING E : 3 HP ODP
WATER + 1 ROW C : 7.5 /1 F : 1/2" SYNTHETIC V : VOLT FREE
UNIT B : COATED
D : 10 /2 CONTACTS*
(CHILLED WATER) HEATING SPLIT COIL ALUMINUM A : 1" ALUMINUM
E : 12/2
FIN C : 1" SYNTHETIC
10 C : STD. 4 ROW CHILLED FOR BWQ10 F : 15 /2
D : 2 HP ODP G : 20 /2 FOR BWQ10, 14 & 18
WATER COIL
E : 3 HP ODP H : 25/2 C : COPPER FIN
N : NO FILTER
J : 30/2
D : 3 ROW CHILLED A : 1" ALUMINUM
14 WATER + 1 ROW FOR BWQ14/18 FOR BWQ18/25
B : 2" ALUMINUM
HEATING SPLIT COIL G : 5 HP ODP N : NO HEATER
C : 1" SYNTHETIC
18 J : 7.5 HP ODP E : 12/2
F : 15 /2 D : 2"SYNTHETIC
G : 20 /2
H : 25/2
25 FOR BWQ25 J : 30/2 FOR BWQ25
J : 7.5 HP ODP K : 35/2
L : 10 HP ODP N : NO FILTER
L : 40/2
B : 2" ALUMINUM
D : 2"SYNTHETIC
STANDARD SPECIFICATIONS
A. General
Cooline Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with blower
motor, chilled/hot water coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applica-
tions. The unit is ready to operate when connected to piping, power/controls and air ducts or plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-
ments.
B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick TUFF-SKIN fiberglass insulation to prevent conden-
sation from forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deteriora-
tion and errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality
conforming to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.
C. Coils
Coils are of the enhanced louvered fin-and-tube type, constructed of seamless copper tubes, mechanically bonded to
aluminum fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided.
The standard chilled water coil is 3 row for BWQ03, BWQ05 & BWQ07 and 4 row for BWQ10 & above. For heating
application, the coils are split as 2 row chilled water + 1 row hot water for BWQ03, BWQ05 & BWQ07 and 3 row chilled
water + 1 row hot water for BWQ10 & above. End plates and tube support sheets are 18 gauge galvanized steel, formed
to provide structural strength.
Each coil is pressure tested in the factory at not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.
D. Drain Pans
Drain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection and the outer surface is thermally insulated. Drain outlets of 3/4" NPT is provided for field connec-
tion.
E. Evaporator Fan
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor
(except for BWQ03 & BWQ05, which have direct drive motors) is mounted on an adjustable base and secured by a
locking device. Fan drive is through adjustable motor pitch pulley and belt-driven. Fan shafts are designed to operate at
less than 2/3rds of the first critical speed when the unit comes up to rated revolutions per minute (RPM). Units have
sealed, permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing
during final assembly. Fan motors are of the open drip-proof type (totally enclosed types are optional, for belt driven
only) and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-line type.
4
OPTIONS AND ACCESSORIES
A. Zone Control
Total comfort zone control systems are available up to 19 zones and can provide a comfortable temperature to each
zone/room (field supplied).
B. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switches
are provided to shut-off power to heaters in case of airflow failure.
C. Filters
Filters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum type, one or two inch
thick (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units (BWQ07 - BWQ25).
D. Discharge Air Plenum & Return Air Grille
As an accessory, discharge air plenum with return air grilles can be provided on vertical units.
E. UV Flow™ Light Emitters
The damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The UV
flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth of these
microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow™.
To order the UV flow™ use the kit numbers in the table below.
KIT PART NUMBER 700-391-16 700-391-17 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22
F. Electronic Thermostats
General Informations: Single stage or two stage thermostats provide low voltage control of one or two stage heating and/or
cooling applications. The thermostat normally displays room temperature, mode of operation and which system is currently on.
You may select different heating and cooling setpoints for the systems to maintain (example 700F in heating and 750F in
cooling). Raising or lowering the setpoints in heating or cooling is as simple as pushing a button.
The thermostat also allows you to select continuous fan operation, (useful when using an electronic air cleaner), or have
the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should not
be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers /diffusers.
TYPICAL THERMOSTAT
Heating Cooling Selector Switch Positions
Part No.
Stages Stages Mode Switch Fan Switch
800-646-91 1 1 OFF-AUTO - HEAT/COOL ON - AUTO
800-646-92* 2 2 OFF-AUTO - HEAT/COOL ON - AUTO
800-646-26 2 2 OFF-AUTO - HEAT/COOL ON - AUTO
* with built-in compressor fault & clogged filter indication led lights.
TYPICAL THERMOSTAT
5
PHYSICAL DATA
MODEL NUMBER BWQ03 BWQ05 BWQ07 BWQ10 BWQ14 BWQ18 BWQ25
Nominal airflow, CFM (L/S) 1200 (566) 2000 (944) 3000 (1416) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)
Quantity 1 1 1 1 1 2 2
EVAPORATOR COIL Type Corrugated Fin & Tube, 3/8" dia tube, 14 FPI
Rows, split (chilled + hot water) 2+1 2+1 2+1 3+1 3+1 3+1 3+1
Face area, Sq. ft. (Sq. m.) 3.2 (0.3) 4.5 (0.42) 7 (0.65) 10 (0.93) 14 (1.3) 17.5 (1.62) 25 (2.32)
Water in/out size, MPT (inch) Chilled water 3/4 1 1-1/4 1-1/2 1-1/2 1-1/2 1-1/2
Water in/out size, MPT (inch) Hot water 3/4 1 1 1-1/4 1-1/4 1-1/4 1-1/4
Condensate drain connection (inch) 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Quantity 1 2 2 3 3 4 4
SHIPPING WEIGHT kg. (approx.) 80 120 165 225 300 340 420
LEGEND: EWT - Entering Water Temperature; MBH - 1000 BTUH; GPM - Gallons Per Minute; LPS - Liters Per Second
6
E CHILLED WATER COOLING CAPACITIES
STANDARD COIL
N
ENTERING AIR TEMP. = 760F DB/650F WB ENTERING AIR TEMP. = 800F DB/670F WB
G WTR UNIT
0
40 F EWT
0
45 F EWT
0
50 F EWT WTR UNIT
0
40 F EWT
0
45 F EWT
0
50 F EWT
L 0
F SIZE TC SC GPM TC SC GPM TC SC GPM
0
F SIZE TC SC GPM TC SC GPM TC SC GPM
BWQ03 37.87 23.64 9.46 30.59 20.55 7.65 24.37 18.54 6.09 BWQ03 47.30 29.43 11.82 39.53 26.17 9.88 31.96 23.53 7.99
I BWQ05
BWQ07
61.29
97.68
38.37
60.84
15.32
24.42
49.28
77.28
33.26 12.32 38.95 29.87 9.74
51.86 19.32 60.71 46.22 15.18
BWQ05
BWQ07
77.63
124.79
48.35
77.23
19.41
31.20
64.16
102.39
42.63
67.52
16.04
25.60
51.58
81.08
38.15
59.52
12.89
20.27
S 8 BWQ10
BWQ14
BWQ18
165.61
212.95
282.70
102.19
130.60
172.69
41.40
53.24
70.67
131.67
169.61
223.23
87.23 32.92 103.05 77.16 25.76
111.30 42.40 131.18 97.03 32.79
145.85 55.81 170.46 125.64 42.61
8 BWQ10
BWQ14
BWQ18
208.72
268.25
360.07
128.14
163.51
218.37
52.18
67.06
90.02
173.15
222.61
296.09
112.65
143.44
189.60
43.29
55.65
74.02
138.95
178.89
235.88
99.94
126.99
166.38
34.74
44.72
58.97
H BWQ25 390.34 236.86 97.58 307.49 199.09 76.87 231.68 169.10 57.92 BWQ25 491.2 298.1 121.0 409.10 259.51 102.27 325.04 226.37 81.26
BWQ03 35.99 22.58 7.20 29.80 20.09 5.96 23.71 18.14 4.74 BWQ03 44.35 27.76 8.87 37.35 24.92 7.47 31.14 23.01 6.23
BWQ05 57.86 35.78 11.57 47.59 32.26 9.52 37.61 28.98 7.52 BWQ05 71.52 43.85 14.30 60.13 40.27 12.03 49.80 37.06 9.96
BWQ07 90.57 56.78 18.11 74.15 50.03 14.83 58.33 44.74 11.66 BWQ07 113.74 71.02 22.75 94.23 62.78 18.84 77.67 57.42 15.53
U 10 BWQ10
BWQ14
BWQ18
152.98
196.88
258.49
95.08
121.53
159.22
30.60
39.37
51.70
125.95
160.32
208.21
83.93 25.19 99.70 75.06 19.94
106.04 32.06 126.92 94.46 25.38
137.29 41.64 163.94 121.66 32.79
10 BWQ10
BWQ14
BWQ18
193.61
249.05
329.72
119.71
152.92
201.68
38.72
49.81
65.94
159.91
206.06
270.95
105.18
134.16
175.67
31.98
41.21
54.19
131.76
167.72
218.07
95.73
120.43
155.99
26.35
33.54
43.61
N BWQ25
BWQ03
355.94
35.23
217.76
22.14
71.19
5.87
282.91
29.14
185.25 56.58 222.31 163.45 44.46
19.70 4.86 23.12 17.76 3.85
BWQ25
BWQ03
454.86
42.76
276.33
26.28
90.97
7.13
373.16
36.57
239.74
24.46
74.63
6.09
296.47
30.46
209.98
22.59
59.29
5.07
I BWQ05
BWQ07
56.24
87.60
35.47
54.92
9.37
14.60
46.25
71.77
31.44 7.71 36.47 28.24 6.08
48.62 11.96 56.39 43.46 9.40
BWQ05
BWQ07
68.72
107.54
43.30
66.16
11.45
17.92
58.45
91.10
39.28
60.97
9.74
15.18
48.41
75.17
36.20
55.86
8.07
12.53
BWQ10 148.85 92.77 24.81 122.60 81.96 20.43 96.94 73.32 16.16 BWQ10 181.69 113.03 30.28 154.64 102.14 25.77 128.25 93.60 21.37
T
12 12
BWQ14 189.47 117.38 31.58 156.06 103.49 26.01 123.47 92.41 20.58 BWQ14 233.36 144.14 38.89 196.85 128.98 32.81 163.25 117.90 27.21
BWQ18 245.97 152.16 40.99 201.69 133.55 33.61 158.86 118.69 26.48 BWQ18 306.28 188.70 51.05 255.80 167.16 42.63 211.18 151.94 35.20
S BWQ25 334.17 205.75 55.69 273.54 179.83 45.59 215.17 159.08 35.86 BWQ25 421.72 258.06 70.29 347.67 225.48 57.94 286.51 204.19 47.75
SPLIT COIL*
ENTERING AIR TEMP. = 800F DB/670F WB
0 0 0
40 F EWT 45 F EWT 50 F EWT
WTR UNIT
0
F SIZE TC SC GPM TC SC GPM TC SC GPM
BWQ03 35.0 22.5 8.8 29.7 20.6 7.5 23.5 18.4 6.0
BWQ05 53.8 34.6 13.5 44.7 31.0 11.2 34.8 27.4 8.7
BWQ07 85.4 54.7 21.4 71.7 49.3 18.0 56.1 43.7 14.2
8 BWQ10 172.5 107.8 43.0 143.2 95.5 36.0 115.3 85.6 29.0
BWQ14 230.1 142.5 57.5 191.0 126.0 48.0 153.0 112.0 38.5
BWQ18 296.3 183.0 74.0 245.0 161.0 62.0 194.4 142.0 49.0
BWQ25 386.1 238.8 81.5 335.0 219.0 81.0 268.8 194.7 67.0
BWQ03 32.9 21.2 6.6 26.4 18.5 5.3 20.0 16.0 4.1
BWQ05 49.2 31.9 9.8 39.4 27.7 7.9 28.8 23.1 5.8
BWQ07 79.3 51.0 16.0 62.3 43.5 12.5 45.4 36.4 9.1
10 BWQ10 159.6 100.4 32.0 132.4 89.1 26.7 103.8 78.5 21.0
BWQ14 213.0 133.0 42.8 178.1 118.5 35.8 139.6 103.8 28.0
BWQ18 272.4 169.6 55.0 223.0 148.3 45.0 174.2 129.6 35.0
BWQ25 377.4 233.8 75.5 308.1 203.6 61.5 245.2 180.5 49.0
BWQ03 29.7 19.4 5.0 23.2 16.5 4.0 19.5 15.6 3.9
BWQ05 43.8 28.6 7.3 32.4 23.1 5.4 21.8 18.1 4.0
BWQ07 69.4 45.1 11.6 52.1 37.0 8.7 25.6 21.7 4.8
12 BWQ10 149.2 94.5 25.0 120.0 81.8 20.0 89.9 69.5 15.0
BWQ14 200.1 122.7 33.5 162.2 109.1 27.0 124.4 94.3 20.8
BWQ18 251.0 154.4 42.0 203.0 136.5 34.0 154.6 117.3 26.0
BWQ25 353.4 220.3 59.0 286.1 190.9 47.8 217.8 163.5 36.5
* 2 row cooling coil for BWQ03, BWQ05 & BWQ07. 3 row cooling coil for BWQ10 & above. (with 1 row heating coil).
7
CHILLED WATER COOLING CAPACITIES M
STANDARD COIL
E
ENTERING AIR TEMP. = 250C DB/18.30C WB ENTERING AIR TEMP. = 270C DB/19.50C WB
WTR UNIT
0
4 C EWT
0
7 C EWT
0
10 C EWT WTR UNIT
0
4 C EWT
0
7 C EWT
0
10 C EWT T
0
C SIZE TC SC LPS TC SC LPS TC SC LPS
0
C SIZE TC SC LPS TC SC LPS TC SC LPS
R
BWQ03 10.96 7.09 0.52 8.92 6.25 0.43 6.97 5.63 0.33 BWQ03 13.91 8.72 0.66 11.48 7.69 0.55 9.35 7.00 0.45
BWQ05
BWQ07
17.61
27.95
11.42
18.03
0.84
1.34
14.31
22.36
10.06
15.65
0.68
1.07
11.10
17.25
9.02
13.94
0.53
0.82
BWQ05 22.67
BWQ07 36.27
14.24
22.64
1.08
1.73
18.50
29.41
12.44
19.64
0.88
1.40
15.02
23.50
11.31
17.58
0.72
1.12
I
5 BWQ10
BWQ14
BWQ18
47.78
61.49
81.20
30.51
39.01
51.31
2.28
2.94
3.88
37.83
48.16
62.95
26.15
33.02
42.98
1.81
2.30
3.01
29.39
37.41
48.44
23.31
29.30
37.82
1.40
1.79
2.31
5 BWQ10 61.08
BWQ14 78.52
BWQ18 104.76
37.81
48.28
64.14
2.92
3.75
5.01
50.11
64.47
85.29
33.01
42.04
55.32
2.39
3.08
4.08
39.71
50.94
66.85
29.19
36.94
48.21
1.90
2.43
3.19
C
BWQ25 111.94 70.27 5.35 86.67 58.63 4.14 65.75 50.82 3.14 BWQ25 144.91 88.11 6.92 117.63 75.61 5.62 92.04 65.55 4.40
BWQ03 10.68 6.92 0.43 8.73 6.12 0.35 6.81 5.52 0.27 BWQ03 13.16 8.29 0.52 11.10 7.47 0.44 9.15 6.87 0.36
BWQ05 17.12
BWQ07 26.76
11.13
17.33
0.68
1.07
13.91
21.63
9.81
15.19
0.55
0.86
10.78
16.69
8.80
13.57
0.43
0.66
BWQ05 21.15
BWQ07 33.57
13.37
21.11
0.84
1.34
17.83
27.90
12.05
18.75
0.71
1.11
14.60
22.73
11.05
17.09
0.58
0.91
U
6 BWQ10 45.28
BWQ14 57.65
BWQ18 75.30
29.06
36.79
47.93
1.80
2.30
3.00
36.82
46.87
60.75
25.53
32.23
41.68
1.47
1.87
2.42
28.60
36.42
46.95
22.79
28.70
36.87
1.14
1.45
1.87
6 BWQ10 57.37
BWQ14 73.84
BWQ18 97.51
35.73
45.67
60.09
2.28
2.94
3.88
47.16
60.37
79.19
31.31
39.74
51.89
1.88
2.40
3.15
38.64
49.18
63.82
28.53
35.90
46.41
1.54
1.96
2.54
N
BWQ25 103.67
BWQ03 10.48
65.55
6.80
4.13
0.36
82.48
8.56
56.18
6.02
3.28
0.29
63.62
6.66
49.48
5.42
2.53
0.23
BWQ25 134.42
BWQ03 12.86
82.31
8.12
5.35
0.44
109.04
10.90
70.79
7.35
4.34
0.37
86.69
8.98
62.42
6.76
3.45
0.31
I
BWQ05
BWQ07
16.72
26.02
10.89
16.89
0.57
0.89
13.57
21.04
9.61
14.83
0.46
0.72
10.49
16.21
8.61
13.23
0.36
0.55
BWQ05 20.65
BWQ07 32.30
13.08
20.37
0.70
1.10
17.41
27.12
11.81
18.30
0.59
0.93
14.25
22.11
10.83
16.71
0.49
0.75 T
BWQ10 44.26 28.47 1.51 35.99 25.03 1.23 27.91 22.33 0.95 BWQ10 54.60 34.15 1.86 46.08 30.68 1.57 37.77 28.00 1.29
S
7 7
BWQ14 56.33 36.03 1.92 45.81 31.61 1.56 35.56 28.14 1.21 BWQ14 69.80 43.39 2.38 58.65 38.74 2.00 48.08 35.26 1.64
BWQ18 73.07 46.64 2.49 59.15 40.73 2.02 45.70 36.11 1.56 BWQ18 91.54 56.73 3.12 76.16 50.17 2.60 62.13 45.43 2.12
BWQ25 99.23 63.02 3.39 80.20 54.84 2.74 61.88 48.37 2.11 BWQ25 126.03 77.64 4.30 103.47 67.69 3.53 84.27 60.99 2.88
SPLIT COIL*
ENTERING AIR TEMP. = 270C DB/19.50C WB
0 0 0
4 C EWT 7 C EWT 10 C EWT
WTR UNIT
0
C SIZE TC SC LPS TC SC LPS TC SC LPS
BWQ03 10.25 6.59 0.55 8.70 6.03 0.47 6.88 5.39 0.38
BWQ05 15.75 10.13 0.85 13.09 9.08 0.71 10.19 8.02 0.55
BWQ07 25.01 16.02 1.35 21.0 14.44 1.13 16.43 12.80 0.89
5 BWQ10 50.51 31.57 2.71 41.93 27.96 2.27 33.76 25.07 1.83
BWQ14 67.38 41.73 3.62 55.93 36.90 3.02 44.80 32.80 2.43
BWQ18 86.76 53.59 4.66 71.74 47.14 3.91 56.93 41.58 3.09
BWQ25 113.06 69.93 5.13 98.10 64.13 5.10 78.71 57.01 4.22
BWQ03 9.63 6.21 0.42 7.73 5.42 0.33 5.86 4.69 0.26
BWQ05 14.41 9.34 0.62 11.54 8.11 0.50 8.43 6.76 0.37
BWQ07 23.22 14.93 1.01 18.24 12.74 0.79 13.29 10.66 0.57
6 BWQ10 46.73 29.40 2.02 38.77 26.09 1.68 30.40 22.99 1.32
BWQ14 62.37 38.95 2.70 52.15 34.70 2.26 40.88 30.40 1.76
BWQ18 79.77 49.66 3.47 65.30 43.43 2.84 51.01 37.95 2.21
BWQ25 110.51 68.46 4.76 90.22 59.62 3.87 71.80 52.86 3.09
BWQ03 8.70 5.67 0.32 6.79 4.83 0.25 5.71 4.57 0.25
BWQ05 12.83 8.37 0.46 9.49 6.76 0.34 6.38 5.30 0.25
BWQ07 20.32 13.21 0.73 15.26 10.83 0.55 7.50 6.35 0.30
7 BWQ10 43.69 27.67 1.58 35.14 23.95 1.26 26.33 20.35 0.95
BWQ14 58.59 35.93 2.11 47.50 31.95 1.70 36.43 27.61 1.31
BWQ18 73.50 45.21 2.65 59.44 39.97 2.14 45.27 34.35 1.64
BWQ25 103.48 64.51 3.72 83.78 55.90 3.01 63.78 47.88 2.30
* 2 row cooling coil for BWQ03, BWQ05 & BWQ07. 3 row cooling coil for BWQ10 & above. (with 1 row heating coil).
8
FAN PERFORMANCE DATA
DIRECT DRIVE MOTORS
MODEL No.: BWQ03
BLOWER MOTOR HP BLOWER MOTOR CFM @ External Static Pressure (inch wg.)
SPEED 0.1 0.2 0.3 0.4 0.5 0.6
HIGH 1350 1290 1220 1160 1070 990
0.5 MEDIUM 1260 1200 1125 1060 1000 900
LOW 1070 1020 960 900 830 740
HIGH 1660 1480 1300 1230 1140 1060
0.75 MEDIUM 1570 1375 1180 1120 1060 960
LOW 1500 1320 1130 940 870 780
9
FAN PERFORMANCE DATA (BELT DRIVEN MOTORS)
MODEL No.: BWQ14
External Static Pressure (inch wg.)
Airflow, 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 (1888)
4200 (1982)
4400 (2076)
694*
705*
719*
1.21*
1.33*
1.43*
743*
761*
774
1.3*
1.45*
1.6
797
811
823
I 1.52
1.67
1.8
845
857
869
1.66
1.81
1.97
890
903
918
1.83
2.0
2.17
937
951
963
2.03
2.19
2.33
975
992
1006
2.25
2.43
2.58
992
1002
1010
2.4
2.6
2.78
1075
1080
1093
2.64
2.82
2.97
II1102
1110
1133
2.85
3.05
3.2
4600 (2170) 735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34 971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41
4800 (2265) 748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52 979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62
5000 (2360) 761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70 989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86
5200 (2454) 778 2.06 823 2.27 873 2.48 917 2.70 959 2.91 1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.08
5400 (2548) 800 2.31 846 2.5 894 2.72 934 2.94 979 3.15 1019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.36
5600 (2643) 808 2.46 858 2.7 903 2.90 945 3.12 987 3.38 1028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.57
5800 (2737) 826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65 1041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.78
6000 (2832) 837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9 1047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.05
6200 (2926) 850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17 1061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.4
6400 (3020) 879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45 1078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.76
6600 (3115) 894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68 1091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08
10
ELECTRICAL DATA
MODEL No.: BWQ03 MODEL No.: BWQ05
VOLTAGE BLOWER VOLTAGE BLOWER
POWER POWER
ELECTRIC HEATER ELECTRIC HEATER
SUPPLY RANGE MOTOR ** MCA MOCP
SUPPLY RANGE MOTOR ** MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 2.4 15 – – 6.1 15
5 21.7 29.5 30 5 21.7 33.3 35
0.50 1.9 6/7 26.1/30.4 35/40.4 40/45 0.75 4.9 6/7 26.1/30.4 38.8/44.1 40/45
(STD.) 10*/12* 43.5/52.2 56.8/67.6 60/70 (STD.) 10*/12* 43.5/52.2 60.5/71.4 70/80
14* 60.9 78.5 80 14* 60.9 82.3 90
220/240-1-50 198 264 – – 6.1 15 220/240-1-50 198 264 – – 6.8 15
5 21.7 33.3 35 5 21.7 33.9 35
0.75 4.9 6/7 26.1/30.4 38.8/44.1 40/45 1.0 5.4 6/7 26.1/30.4 39.4/44.8 40/45
(ALT.) 10*/12* 43.5/52.2 60.5/71.4 70/80 (ALT.) 10*/12* 43.5/52.2 61.1/72 70/80
14* 60.9 82.3 90 14* 60.9 81.2 90
– – 2.4 15 – – 6.1 15
5 7.6 11.9 15 5 7.6 15.6 20
0.50 1.9 6/7.5 9.1/11.4 13.8/16.6 15/20 0.75 4.9 6/7.5 9.1/11.4 17.5/20.4 20/25
(STD.) 10*/12* 15.2/18.2 21.4/25.1 25/30 (STD.) 10*/12* 15.2/18.2 25.1/28.9 30/30
15* 22.8 30.9 35 15* 22.8 34.6 35
380/415-3-50 342 457 – – 6.1 15 380/415-3-50 342 457 – – 6.8 15
(4 WIRE) 5 7.6 15.6 20 (4 WIRE) 5 7.6 16.3 20
0.75 4.9 6/7.5 9.1/11.4 17.5/20.4 20/25 1.0 5.4 6/7.5 9.1/11.4 18.1/21 20/25
(ALT.) 10*/12* 15.2/18.2 25.1/28.9 30/30 (ALT.) 10*/12* 15.2/18.2 25.8/29.5 30/35
15* 22.8 34.6 40 15* 22.8 35.3 40
LEGEND
FLA – Full Load Amps
HP – Horse Power
MOCP – Maximum Over Current Protection
MCA – Minimum Circuit Amps
* Combination of 2 heater modules
** Single phase motors (220/240V-1Ph-50Hz power supply).
11
DIMENSIONS
BWQ03 - BWQ14 (HORIZONTAL DISCHARGE)
12
DIMENSIONS
BWQ03 - BWQ14 (VERTICAL DISCHARGE)
13
DIMENSIONS
BWQ18 - BWQ25 (HORIZONTAL DISCHARGE)
14
DIMENSIONS
BWQ18 - BWQ25 (VERTICAL DISCHARGE)
15
DIMENSIONS - HEATER BOX
BWQ03 - BWQ05
.3" )
(16
415
(1")
25.4 YP
T
205 (8.1")
490
(1 9.3")
BWQ07 - BWQ14
.2")
(1 6
412
P
TY
4( 1")
25.
205 (8.1")
DIMENSIONS
MODEL
A
HEATER ACCESS COVER
BWQ07 818 (32.2)
HEATER CONTROLS MTG
BWQ10 818 (32.2) COVER
BWQ14 1326(52.2) HEATER CONTROLS MTG
PLATE
4")
BWQ18 - BWQ25
.
(19
492
YP
") T
4 (1
25.
205 (8.1")
1581 (6
2.3")
16
TYPICAL SCHEMATIC WIRING DIAGRAM
LEGEND
AFS AIRFLOW SWITCH
ATB AUXILIARY TERMINAL BLOCK
AR AUXILIARY RELAY
BM BLOWER MOTOR
BMC BLOWER MOTOR CONTACTOR
FL FUSE LINK
HC HEATER CONTACTOR
HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LVTB LOW VOLTAGE TERMINAL BLOCK
LUG LUG GROUND
MOHT MANUAL RESET OHT
N NEUTRAL
NTB NEUTRAL TERMINAL BLOCK
OHT OVERHEAT THERMOSTAT
OLR OVER LOAD RELAY
VFC VOLT FREE CONTACT
___ FIELD WIRING
+ DISCONNECT TAB - 1/4"
NOTES
1. POWER SUPPLY, 380/415V-3Ph-50Hz.
THERMOSTAT CONTROL VOLTAGE - 24VAC.
17
CONTROLS & SEQUENCE OF OPERATION
The operation of the air conditioning unit is controlled by a 24VAC electronic control board. All the contactors are oper-
ated by the 24V circuit, including the thermostat.
Mode:
Select the desired mode of operation by continuous press-
ing of the MODE button: 24 V
(C)
Controls cooling system only (the word COOL will 24 V
24VAC
Cooling:
Select the temperature you want your cooling system to LED 1
Clogged Filter *
maintain by pressing and holding the COOLING button LED 2
Compressor Fault
Heating:
Select the temperature you want your heating system to maintain by pressing and holding the HEATING button under
the or symbols until the desired temperature is displayed. The control setpoint temperature is displayed for 5
seconds.
Fan:
The fan will be energized automatically when the systems are operating but no indication of this on the display. To select
continuous fan operation, press the FAN button and the display will show . This is recommended for electronic air
cleaners and continuous ventilation requirements.
Off
When the word OFF is displayed the heating and cooling systems will not operate. Avoid using the OFF mode during
extremely cold weather to prevent damage from freezing.
Auto:
Selecting this mode of operation will control both heating and cooling systems. The thermostat will automatically switch
from one to the other as determined by the selected temperatures in heating and cooling.
NOTE: The thermostat always maintains a minimum 20F (10C) difference or dead band between the heating and cooling
setpoints.
Celsius/Fahrenheit
Simultaneously press and to switch between Celsius and Fahrenheit temperature display.
18
INSTALLATION INSTRUCTIONS
A. GENERAL
Blower units are shipped completely wired. Only external power, control wiring and piping connections are needed to
complete the installation.
C. TUBING INSTALLATION
Do not remove plugs from the pipe stub out until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required.
NOTE: When installing piping through walls or along side of any structural members, be sure the piping is isolated from
these members or walls to avoid any transmission of vibration that may occur, while unit is running.
ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
NOTE: Use copper wires of proper rating for all field wiring.
Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than
one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram. Connect ground wire to the ground lug inside the control box.
C) Control wiring
Use 16 gauge color-coded wire for control wiring.
PARTS LIST
MODEL NUMBER BWQ03B BWQ03L BWQ05B BWQ05L BWQ07L BWQ10L BWQ14L BWQ18L BWQ25L
BLOWER MOTOR 800-547-71 800-547-71 800-546-94 800-546-94 800-544-16 800-544-17 800-544-72 800-544-72 800-544-73
BLOWER WHEEL 800-707-10 800-707-10 800-707-10 800-707-10 800-707-46 800-707-02 800-707-02 800-707-00 800-707-22
BLOWER MOTOR CONTACTOR 800-736-01 800-736-01 800-736-01 800-736-01 800-095-00 800-095-00 800-098-54 800-098-54 800-098-56
AIRFLOW SWITCH 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02
19
BU-C28-07/11