Air Handling Units

BWQ Series
Chilled/Hot water
BWQ03 thru BWQ25
3 TR thru 30 TR
10 kW thru 100 kW
Company Business
Zamil Air Conditioners was founded in 1974, and is the first major business venture in manufacturing sector for the
Al Zamil group of Companies. It is also the first manufacturing unit for air conditioners to be established in Saudi Arabia.

Zamil Air conditioners manufactures both consumer and central range of air conditioners and has sales operations in
over 55 countries in the Middle East, Europe, America, Africa, Australia and the Far East.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting six in - house product and
service brands as well as a number of international brands under the OEM sales.

The six in-house brands are Classic, Cooline, CoolCare, Clima Tech, Geoclima and Kessler Clima Tech.

The four SBUs are:


1. Consumer Business unit supporting Classic, Cooline, GE and OEM brands for consumer range of air conditioners.
2. Unitary & Applied Business unit supporting Classic, Cooline, GE and OEM brands for commercial range of air
conditioners.
3. Zamil CoolCare - service and maintenance provider.
4. Geoclima srl - independent business and supporting other SBUs for their requirement of Chillers & Double skin
AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and Zamil CoolCare direct their business opera-
tions from the corporate headquarters at Dammam, Saudi Arabia.

The production facilities at Dammam are shared by Consumer Products and Unitary & Applied Products. Geoclima has
its own production and functional departments located at Monfalcone, Italy.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work at
its best and achieve the corporate goals of increased productivity and efficiently.

Factories and Productions


Zamil Air Conditioners has its prime manufacturing base at Dammam, Saudi Arabia and has one speciality production
facility in Italy operated by Geoclima.
The company can produce up to 440,000 room air conditioners, 60,000 mini-split systems and 36,500 central air-condi-
tioning systems per year.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)
certificate for room air conditioners. Its products and services are also certified with:

1. CE (Council of European Community)


2. UL (Underwriters Laboratory)
3. AHAM certificate (Association of Home Appliance Manufacturers)
4. Eurovent
5. DEMKO
6. ETL

Other awards include the prestigious Engineering Excellence Award of General Electric, and the inaugural Prince
Mohammed bin Fahd Al Saud Award for Factory Safety.

Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners
manufacturers a host of residential and commercial air conditioners. This board range extends from the concealed units
up to 5 ton, the ducted splits up to 30 tons, the packaged units up to 70 tons. The single and double skin air handling units
up to 130,000 CFM and the water chillers up to 487 ton cooling capacity.
INDEX
Contents Page

Outstanding features ................................................................................................................................ 2

Model decoding ........................................................................................................................................ 3

Blower drive options ................................................................................................................................. 4

Standard specifications ............................................................................................................................ 4

Options and accessories .......................................................................................................................... 5

Physical data ............................................................................................................................................ 6

Hot water capacities ................................................................................................................................. 6

Cooling capacities ................................................................................................................................. 7-8

Fan performance data ......................................................................................................................... 9-10

Electrical data ......................................................................................................................................... 11

Dimensions ........................................................................................................................................ 12-15

Dimensions, heater box .......................................................................................................................... 16

Typical schematic wiring diagram ........................................................................................................... 17

Controls and sequence of operation ....................................................................................................... 18

Installation instructions ........................................................................................................................... 19

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
OUTSTANDING FEATURES
* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS

* LOW CEILING HEIGHT REQUIREMENTS

* CHILLED & HOT WATER COILS

* ONE SIDE TOTAL SERVICE ACCESSIBILITY

* SINGLE POINT POWER ENTRY

* UV FLOW™ LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)

* NUMBER CODED WIRES

* INSULATED DRAIN PAN

* FACTORY INSTALLED OPTIONS UPON REQUEST

* SMALL FOOTPRINT

* LIGHT WEIGHT

* PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION

* LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION

* STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION

* ALUMINUM OR SYNTHETIC FILTERS

* UL LISTED MAJOR COMPONENTS

2
MODEL DECODING
MODELS: BWQ03 - BWQ05
1, 2 & 3 4&5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL COIL APPLICATION BLOWER DRIVE HEATER COIL FINS FILTER UNIT OTHER
(SQ. FT.) SUPPLY MOTOR OPTIONS OPTIONS
OPTIONS ACCESSORIES
(V-Ph-Hz) (kW/STAGE)

BWQ 03 H : HORIZONTAL B : 220/240-1-50 A : STD. 3 ROW CHILLED U : 0.5 HP ODP N : DIRECT N : NO HEATER A : ALUMINUM N : NO FILTER N : STD. UNIT. N : STD. UNIT
COOLINE WATER COIL DRIVE FIN NO ACCESORIES
V : VERTICAL L : 380/415-3-50 W : 0.75 HP ODP A : 5/1 E : 1/2" ALUMINUM
AIR HANDLING
V : VOLT FREE
UNIT (4 WIRE) B : 2 ROW CHILLED B : COATED
F : 1/2" SYNTHETIC CONTACTS*
(CHILLED WATER) 05 WATER + 1 ROW W : 0.75 HP ODP B : 6/1 ALUMINUM
HEATING SPLIT COIL FIN
Y :1 HP ODP C : 7.5 /1** A : 1" ALUMINUM
C : COPPER FIN
C : 1" SYNTHETIC

NOTES: * – Blower motor ON/OFF and trip indication.


** – Heater capacity will be 7kW for single phase power supply.

3
MODELS: BWQ07 - BWQ25
1, 2 & 3 4&5 6 7 8 9 10 11 12 13 14 15
BASIC FACE AREA ARRANGEMENT ELECTRICAL COIL APPLICATION BLOWER DRIVE HEATER COIL FINS FILTER UNIT OTHER
(SQ. FT.) SUPPLY MOTOR OPTIONS OPTIONS
OPTIONS ACCESSORIES
(V-Ph-Hz) (kW/STAGE)

BWQ 07 H : HORIZONTAL L : 380/415-3-50 A : STD. 3 ROW CHILLED FOR BWQ07 N : NO HEATER A : ALUMINUM FOR BWQ07 N : STD. UNIT. N : STD. UNIT
J : ALT. I
COOLINE (4 WIRE) WATER COIL D : 2 HP ODP A : 5/1 FIN N : NO FILTER NO ACCESORIES
V : VERTICAL B : 2 ROW CHILLED K : ALT. II B : 6/1 E : 1/2" ALUMINUM
AIR HANDLING E : 3 HP ODP
WATER + 1 ROW C : 7.5 /1 F : 1/2" SYNTHETIC V : VOLT FREE
UNIT B : COATED
D : 10 /2 CONTACTS*
(CHILLED WATER) HEATING SPLIT COIL ALUMINUM A : 1" ALUMINUM
E : 12/2
FIN C : 1" SYNTHETIC
10 C : STD. 4 ROW CHILLED FOR BWQ10 F : 15 /2
D : 2 HP ODP G : 20 /2 FOR BWQ10, 14 & 18
WATER COIL
E : 3 HP ODP H : 25/2 C : COPPER FIN
N : NO FILTER
J : 30/2
D : 3 ROW CHILLED A : 1" ALUMINUM
14 WATER + 1 ROW FOR BWQ14/18 FOR BWQ18/25
B : 2" ALUMINUM
HEATING SPLIT COIL G : 5 HP ODP N : NO HEATER
C : 1" SYNTHETIC
18 J : 7.5 HP ODP E : 12/2
F : 15 /2 D : 2"SYNTHETIC
G : 20 /2
H : 25/2
25 FOR BWQ25 J : 30/2 FOR BWQ25
J : 7.5 HP ODP K : 35/2
L : 10 HP ODP N : NO FILTER
L : 40/2
B : 2" ALUMINUM
D : 2"SYNTHETIC

NOTES: * – Blower motor ON/OFF and trip indication.


BLOWER DRIVE OPTIONS
MOTOR BLOWER APPROX. SPEED
MODEL CHANGE PER
OPTION PULLEY SPEED RANGE (RPM) PULLEY PULLEY
NUMBER PITCH DIA. PITCH DIA.
HP RPM TURN (RPM)
(INCH) MINIMUM MAXIMUM (INCH)
ALT. I 2 1450 2.7 - 3.7 850 1166 4.6 63
BWQ07
ALT. II 3 1450 3.1 - 4.1 977 1292 4.6 63
BWQ10 ALT. I 2 1450 3.1 - 4.1 725 958 6.2 38
ALT. II 3 1450 3.1 - 4.1 864 1143 5.2 46
ALT. I 5 1450 3.7 - 4.7 812 1032 6.6 37
BWQ14
ALT. II 7.5 1450 4.3 - 5.5 944 1208 6.6 44
ALT. I 5 1450 3.7 - 4.7 812 1032 6.6 37
BWQ18
ALT. II 7.5 1450 4.3 - 5.5 890 1140 7.0 41
ALT. I 7.5 1450 4.8 - 6.0 810 1012 8.6 34
BWQ25
ALT. II 10 1450 4.8 - 6.0 810 1012 8.6 34

STANDARD SPECIFICATIONS
A. General
Cooline Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with blower
motor, chilled/hot water coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applica-
tions. The unit is ready to operate when connected to piping, power/controls and air ducts or plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application require-
ments.

B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick TUFF-SKIN fiberglass insulation to prevent conden-
sation from forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deteriora-
tion and errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality
conforming to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. Coils
Coils are of the enhanced louvered fin-and-tube type, constructed of seamless copper tubes, mechanically bonded to
aluminum fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided.
The standard chilled water coil is 3 row for BWQ03, BWQ05 & BWQ07 and 4 row for BWQ10 & above. For heating
application, the coils are split as 2 row chilled water + 1 row hot water for BWQ03, BWQ05 & BWQ07 and 3 row chilled
water + 1 row hot water for BWQ10 & above. End plates and tube support sheets are 18 gauge galvanized steel, formed
to provide structural strength.
Each coil is pressure tested in the factory at not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain Pans
Drain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection and the outer surface is thermally insulated. Drain outlets of 3/4" NPT is provided for field connec-
tion.

E. Evaporator Fan
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor
(except for BWQ03 & BWQ05, which have direct drive motors) is mounted on an adjustable base and secured by a
locking device. Fan drive is through adjustable motor pitch pulley and belt-driven. Fan shafts are designed to operate at
less than 2/3rds of the first critical speed when the unit comes up to rated revolutions per minute (RPM). Units have
sealed, permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing
during final assembly. Fan motors are of the open drip-proof type (totally enclosed types are optional, for belt driven
only) and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-the-line type.

4
OPTIONS AND ACCESSORIES
A. Zone Control
Total comfort zone control systems are available up to 19 zones and can provide a comfortable temperature to each
zone/room (field supplied).
B. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switches
are provided to shut-off power to heaters in case of airflow failure.
C. Filters
Filters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum type, one or two inch
thick (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units (BWQ07 - BWQ25).
D. Discharge Air Plenum & Return Air Grille
As an accessory, discharge air plenum with return air grilles can be provided on vertical units.
E. UV Flow™ Light Emitters
The damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The UV
flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth of these
microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow™.
To order the UV flow™ use the kit numbers in the table below.

MODEL NUMBER BWQ03 BWQ05 BWQ07 BWQ10 BWQ14 BWQ18 BWQ25

KIT PART NUMBER 700-391-16 700-391-17 700-391-18 700-391-19 700-391-20 700-391-21 700-391-22

F. Electronic Thermostats
General Informations: Single stage or two stage thermostats provide low voltage control of one or two stage heating and/or
cooling applications. The thermostat normally displays room temperature, mode of operation and which system is currently on.
You may select different heating and cooling setpoints for the systems to maintain (example 700F in heating and 750F in
cooling). Raising or lowering the setpoints in heating or cooling is as simple as pushing a button.
The thermostat also allows you to select continuous fan operation, (useful when using an electronic air cleaner), or have
the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should not
be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers /diffusers.

TYPICAL THERMOSTAT
Heating Cooling Selector Switch Positions
Part No.
Stages Stages Mode Switch Fan Switch
800-646-91 1 1 OFF-AUTO - HEAT/COOL ON - AUTO
800-646-92* 2 2 OFF-AUTO - HEAT/COOL ON - AUTO
800-646-26 2 2 OFF-AUTO - HEAT/COOL ON - AUTO
* with built-in compressor fault & clogged filter indication led lights.

TYPICAL THERMOSTAT

5
PHYSICAL DATA
MODEL NUMBER BWQ03 BWQ05 BWQ07 BWQ10 BWQ14 BWQ18 BWQ25

EVAPORATOR BLOWER Type Centrifugal

Nominal airflow, CFM (L/S) 1200 (566) 2000 (944) 3000 (1416) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)

Motor HP (Std/Alt) 0.5/0.75 0.75/1 2/3 3/2 5/7.5 5/7.5 7.5/10

Drive type Direct Direct Belt Belt Belt Belt Belt

Blower size 10x10 10x10 12x12 15x15 15x15 15x12 18x18

Quantity 1 1 1 1 1 2 2

EVAPORATOR COIL Type Corrugated Fin & Tube, 3/8" dia tube, 14 FPI

Rows, std. chilled water 3 3 3 4 4 4 4

Rows, split (chilled + hot water) 2+1 2+1 2+1 3+1 3+1 3+1 3+1

Face area, Sq. ft. (Sq. m.) 3.2 (0.3) 4.5 (0.42) 7 (0.65) 10 (0.93) 14 (1.3) 17.5 (1.62) 25 (2.32)

Water in/out size, MPT (inch) Chilled water 3/4 1 1-1/4 1-1/2 1-1/2 1-1/2 1-1/2

Water in/out size, MPT (inch) Hot water 3/4 1 1 1-1/4 1-1/4 1-1/4 1-1/4

Condensate drain connection (inch) 3/4 3/4 3/4 3/4 3/4 3/4 3/4

RETURN AIR FILTER Size (inch) 24 x 20 x 1/2 16 x 20 x 1/2 20 x 20 x 1/2 18 x 24 x 1 20 x 24 x 1 20 x 24 x 1 20 x 24 x 2

Quantity 1 2 2 3 3 4 4

SHIPPING WEIGHT kg. (approx.) 80 120 165 225 300 340 420

HOT WATER CAPACITIES


EWT - 1500F (650C) EWT - 1800F (820C)
MODEL
NUMBER CAPACITIES CAPACITIES
GPM (LPS) GPM (LPS)
MBH (kW) MBH (kW)

BWQ03 2.5 (0.16) 24.7 (7.23) 4 (0.25) 38.5 (11.3)

BWQ05 3.8 (0.24) 36.5 (10.7) 6 (0.38) 57.7 (16.9)

BWQ07 5.7 (0.36) 56.2 (16.5) 9 (0.57) 89.2 (26.1)

BWQ10 8.1 (0.51) 80.4 (23.5) 13 (0.81) 128.3 (37.6)

BWQ14 11.6 (0.73) 113.4 (33.2) 18 (1.13) 177 (51.8)

BWQ18 14 (0.90) 138 (40.4) 22 (1.40) 218 (63.8)

BWQ25 20 (1.26) 194.3 (56.9) 31 (1.95) 304 (89)


NOTE: Capacities @ 70 F (21 C) Entering Air Temperature & 20 F (11 C) Water Temperature Drop.
0 0 0 0

LEGEND: EWT - Entering Water Temperature; MBH - 1000 BTUH; GPM - Gallons Per Minute; LPS - Liters Per Second

6
E CHILLED WATER COOLING CAPACITIES
STANDARD COIL
N
ENTERING AIR TEMP. = 760F DB/650F WB ENTERING AIR TEMP. = 800F DB/670F WB
G WTR UNIT
0
40 F EWT
0
45 F EWT
0
50 F EWT WTR UNIT
0
40 F EWT
0
45 F EWT
0
50 F EWT

L 0
F SIZE TC SC GPM TC SC GPM TC SC GPM
0
F SIZE TC SC GPM TC SC GPM TC SC GPM

BWQ03 37.87 23.64 9.46 30.59 20.55 7.65 24.37 18.54 6.09 BWQ03 47.30 29.43 11.82 39.53 26.17 9.88 31.96 23.53 7.99
I BWQ05
BWQ07
61.29
97.68
38.37
60.84
15.32
24.42
49.28
77.28
33.26 12.32 38.95 29.87 9.74
51.86 19.32 60.71 46.22 15.18
BWQ05
BWQ07
77.63
124.79
48.35
77.23
19.41
31.20
64.16
102.39
42.63
67.52
16.04
25.60
51.58
81.08
38.15
59.52
12.89
20.27

S 8 BWQ10
BWQ14
BWQ18
165.61
212.95
282.70
102.19
130.60
172.69
41.40
53.24
70.67
131.67
169.61
223.23
87.23 32.92 103.05 77.16 25.76
111.30 42.40 131.18 97.03 32.79
145.85 55.81 170.46 125.64 42.61
8 BWQ10
BWQ14
BWQ18
208.72
268.25
360.07
128.14
163.51
218.37
52.18
67.06
90.02
173.15
222.61
296.09
112.65
143.44
189.60
43.29
55.65
74.02
138.95
178.89
235.88
99.94
126.99
166.38
34.74
44.72
58.97
H BWQ25 390.34 236.86 97.58 307.49 199.09 76.87 231.68 169.10 57.92 BWQ25 491.2 298.1 121.0 409.10 259.51 102.27 325.04 226.37 81.26
BWQ03 35.99 22.58 7.20 29.80 20.09 5.96 23.71 18.14 4.74 BWQ03 44.35 27.76 8.87 37.35 24.92 7.47 31.14 23.01 6.23
BWQ05 57.86 35.78 11.57 47.59 32.26 9.52 37.61 28.98 7.52 BWQ05 71.52 43.85 14.30 60.13 40.27 12.03 49.80 37.06 9.96
BWQ07 90.57 56.78 18.11 74.15 50.03 14.83 58.33 44.74 11.66 BWQ07 113.74 71.02 22.75 94.23 62.78 18.84 77.67 57.42 15.53

U 10 BWQ10
BWQ14
BWQ18
152.98
196.88
258.49
95.08
121.53
159.22
30.60
39.37
51.70
125.95
160.32
208.21
83.93 25.19 99.70 75.06 19.94
106.04 32.06 126.92 94.46 25.38
137.29 41.64 163.94 121.66 32.79
10 BWQ10
BWQ14
BWQ18
193.61
249.05
329.72
119.71
152.92
201.68
38.72
49.81
65.94
159.91
206.06
270.95
105.18
134.16
175.67
31.98
41.21
54.19
131.76
167.72
218.07
95.73
120.43
155.99
26.35
33.54
43.61
N BWQ25
BWQ03
355.94
35.23
217.76
22.14
71.19
5.87
282.91
29.14
185.25 56.58 222.31 163.45 44.46
19.70 4.86 23.12 17.76 3.85
BWQ25
BWQ03
454.86
42.76
276.33
26.28
90.97
7.13
373.16
36.57
239.74
24.46
74.63
6.09
296.47
30.46
209.98
22.59
59.29
5.07
I BWQ05
BWQ07
56.24
87.60
35.47
54.92
9.37
14.60
46.25
71.77
31.44 7.71 36.47 28.24 6.08
48.62 11.96 56.39 43.46 9.40
BWQ05
BWQ07
68.72
107.54
43.30
66.16
11.45
17.92
58.45
91.10
39.28
60.97
9.74
15.18
48.41
75.17
36.20
55.86
8.07
12.53
BWQ10 148.85 92.77 24.81 122.60 81.96 20.43 96.94 73.32 16.16 BWQ10 181.69 113.03 30.28 154.64 102.14 25.77 128.25 93.60 21.37
T
12 12
BWQ14 189.47 117.38 31.58 156.06 103.49 26.01 123.47 92.41 20.58 BWQ14 233.36 144.14 38.89 196.85 128.98 32.81 163.25 117.90 27.21
BWQ18 245.97 152.16 40.99 201.69 133.55 33.61 158.86 118.69 26.48 BWQ18 306.28 188.70 51.05 255.80 167.16 42.63 211.18 151.94 35.20
S BWQ25 334.17 205.75 55.69 273.54 179.83 45.59 215.17 159.08 35.86 BWQ25 421.72 258.06 70.29 347.67 225.48 57.94 286.51 204.19 47.75

ENTERING AIR TEMP. = 840F DB/690F WB


0 0 0
40 F EWT 45 F EWT 50 F EWT
WTR UNIT NOTE:
0
F SIZE TC SC GPM TC SC GPM TC SC GPM 1. Capacities are based on nominal airflow.
BWQ03 56.99 35.17 14.25 49.01 31.89 12.25 41.21 29.24 10.30 2. For any other conditions, please use selection software for fan coil units.
BWQ05 94.75 58.49 23.69 80.62 52.54 20.15 67.04 47.76 16.76 Apart from capacities, this software provides;
BWQ07 153.80 94.25 38.45 129.82 83.87 32.45 107.16 75.48 26.79
8 BWQ10 254.16 154.60 63.54 216.65 138.36 54.16 180.76 125.13 45.19 a) Sensible heat ratio
BWQ14 326.78 197.38 81.69 278.45 176.04 69.61 232.35 158.78 58.09
BWQ18 437.20 263.60 109.10 374.52 235.07 93.63 309.66 209.78 77.41 b) Leaving air temperature (DB/WB) - 0F
BWQ25 605.20 360.60 149.00 510.00 321.50 126.00 428.14 286.00 107.03 c) Leaving water temperature - 0F
BWQ03 53.71 33.34 10.74 46.01 30.20 9.20 38.72 27.76 7.74
d) Water pressure drop (feet of water)
BWQ05 87.60 54.49 17.52 74.35 48.97 14.87 62.41 45.01 12.48
BWQ07 140.25 86.72 28.05 118.38 77.39 23.68 97.91 70.05 19.58
10 BWQ10 235.97 144.60 47.19 201.06 129.71 40.21 167.16 117.40 33.43
BWQ14 303.30 184.55 60.66 258.57 165.16 51.71 215.30 149.14 43.06
BWQ18 405.03 245.25 81.01 342.85 217.76 68.57 283.51 195.21 56.70
BWQ25 560.45 336.96 112.09 473.19 297.69 94.64 390.57 265.58 78.11 LEGEND:
BWQ03 50.85 31.73 8.47 44.12 29.10 7.35 37.91 27.28 6.32 TC - Total Capacity (MBH)
BWQ05 81.77 51.21 13.63 70.98 47.04 11.83 60.66 43.97 10.11
BWQ07 129.88 79.83 21.64 111.18 73.25 18.53 94.63 68.12 15.77 SC - Sensible Heat Capacity (MBH)
12 BWQ10 221.71 136.62 36.95 188.16 122.43 31.36 160.46 113.46 26.74 WTR - Water Temperature Rise (0F)
BWQ14 285.29 174.59 47.55 242.53 156.25 40.42 204.27 142.92 34.04
BWQ18 377.02 229.86 62.84 318.70 204.48 53.11 265.70 185.04 44.28 EWT - Entering Water Temperature (0F)
BWQ25 519.84 314.87 86.64 438.88 278.96 73.15 361.03 249.00 60.17
GPM - Water flow (Gallons Per Minute)

SPLIT COIL*
ENTERING AIR TEMP. = 800F DB/670F WB
0 0 0
40 F EWT 45 F EWT 50 F EWT
WTR UNIT
0
F SIZE TC SC GPM TC SC GPM TC SC GPM

BWQ03 35.0 22.5 8.8 29.7 20.6 7.5 23.5 18.4 6.0
BWQ05 53.8 34.6 13.5 44.7 31.0 11.2 34.8 27.4 8.7
BWQ07 85.4 54.7 21.4 71.7 49.3 18.0 56.1 43.7 14.2
8 BWQ10 172.5 107.8 43.0 143.2 95.5 36.0 115.3 85.6 29.0
BWQ14 230.1 142.5 57.5 191.0 126.0 48.0 153.0 112.0 38.5
BWQ18 296.3 183.0 74.0 245.0 161.0 62.0 194.4 142.0 49.0
BWQ25 386.1 238.8 81.5 335.0 219.0 81.0 268.8 194.7 67.0
BWQ03 32.9 21.2 6.6 26.4 18.5 5.3 20.0 16.0 4.1
BWQ05 49.2 31.9 9.8 39.4 27.7 7.9 28.8 23.1 5.8
BWQ07 79.3 51.0 16.0 62.3 43.5 12.5 45.4 36.4 9.1
10 BWQ10 159.6 100.4 32.0 132.4 89.1 26.7 103.8 78.5 21.0
BWQ14 213.0 133.0 42.8 178.1 118.5 35.8 139.6 103.8 28.0
BWQ18 272.4 169.6 55.0 223.0 148.3 45.0 174.2 129.6 35.0
BWQ25 377.4 233.8 75.5 308.1 203.6 61.5 245.2 180.5 49.0
BWQ03 29.7 19.4 5.0 23.2 16.5 4.0 19.5 15.6 3.9
BWQ05 43.8 28.6 7.3 32.4 23.1 5.4 21.8 18.1 4.0
BWQ07 69.4 45.1 11.6 52.1 37.0 8.7 25.6 21.7 4.8
12 BWQ10 149.2 94.5 25.0 120.0 81.8 20.0 89.9 69.5 15.0
BWQ14 200.1 122.7 33.5 162.2 109.1 27.0 124.4 94.3 20.8
BWQ18 251.0 154.4 42.0 203.0 136.5 34.0 154.6 117.3 26.0
BWQ25 353.4 220.3 59.0 286.1 190.9 47.8 217.8 163.5 36.5

* 2 row cooling coil for BWQ03, BWQ05 & BWQ07. 3 row cooling coil for BWQ10 & above. (with 1 row heating coil).

7
CHILLED WATER COOLING CAPACITIES M
STANDARD COIL
E
ENTERING AIR TEMP. = 250C DB/18.30C WB ENTERING AIR TEMP. = 270C DB/19.50C WB
WTR UNIT
0
4 C EWT
0
7 C EWT
0
10 C EWT WTR UNIT
0
4 C EWT
0
7 C EWT
0
10 C EWT T
0
C SIZE TC SC LPS TC SC LPS TC SC LPS
0
C SIZE TC SC LPS TC SC LPS TC SC LPS
R
BWQ03 10.96 7.09 0.52 8.92 6.25 0.43 6.97 5.63 0.33 BWQ03 13.91 8.72 0.66 11.48 7.69 0.55 9.35 7.00 0.45
BWQ05
BWQ07
17.61
27.95
11.42
18.03
0.84
1.34
14.31
22.36
10.06
15.65
0.68
1.07
11.10
17.25
9.02
13.94
0.53
0.82
BWQ05 22.67
BWQ07 36.27
14.24
22.64
1.08
1.73
18.50
29.41
12.44
19.64
0.88
1.40
15.02
23.50
11.31
17.58
0.72
1.12
I
5 BWQ10
BWQ14
BWQ18
47.78
61.49
81.20
30.51
39.01
51.31
2.28
2.94
3.88
37.83
48.16
62.95
26.15
33.02
42.98
1.81
2.30
3.01
29.39
37.41
48.44
23.31
29.30
37.82
1.40
1.79
2.31
5 BWQ10 61.08
BWQ14 78.52
BWQ18 104.76
37.81
48.28
64.14
2.92
3.75
5.01
50.11
64.47
85.29
33.01
42.04
55.32
2.39
3.08
4.08
39.71
50.94
66.85
29.19
36.94
48.21
1.90
2.43
3.19
C
BWQ25 111.94 70.27 5.35 86.67 58.63 4.14 65.75 50.82 3.14 BWQ25 144.91 88.11 6.92 117.63 75.61 5.62 92.04 65.55 4.40
BWQ03 10.68 6.92 0.43 8.73 6.12 0.35 6.81 5.52 0.27 BWQ03 13.16 8.29 0.52 11.10 7.47 0.44 9.15 6.87 0.36
BWQ05 17.12
BWQ07 26.76
11.13
17.33
0.68
1.07
13.91
21.63
9.81
15.19
0.55
0.86
10.78
16.69
8.80
13.57
0.43
0.66
BWQ05 21.15
BWQ07 33.57
13.37
21.11
0.84
1.34
17.83
27.90
12.05
18.75
0.71
1.11
14.60
22.73
11.05
17.09
0.58
0.91
U
6 BWQ10 45.28
BWQ14 57.65
BWQ18 75.30
29.06
36.79
47.93
1.80
2.30
3.00
36.82
46.87
60.75
25.53
32.23
41.68
1.47
1.87
2.42
28.60
36.42
46.95
22.79
28.70
36.87
1.14
1.45
1.87
6 BWQ10 57.37
BWQ14 73.84
BWQ18 97.51
35.73
45.67
60.09
2.28
2.94
3.88
47.16
60.37
79.19
31.31
39.74
51.89
1.88
2.40
3.15
38.64
49.18
63.82
28.53
35.90
46.41
1.54
1.96
2.54
N
BWQ25 103.67
BWQ03 10.48
65.55
6.80
4.13
0.36
82.48
8.56
56.18
6.02
3.28
0.29
63.62
6.66
49.48
5.42
2.53
0.23
BWQ25 134.42
BWQ03 12.86
82.31
8.12
5.35
0.44
109.04
10.90
70.79
7.35
4.34
0.37
86.69
8.98
62.42
6.76
3.45
0.31
I
BWQ05
BWQ07
16.72
26.02
10.89
16.89
0.57
0.89
13.57
21.04
9.61
14.83
0.46
0.72
10.49
16.21
8.61
13.23
0.36
0.55
BWQ05 20.65
BWQ07 32.30
13.08
20.37
0.70
1.10
17.41
27.12
11.81
18.30
0.59
0.93
14.25
22.11
10.83
16.71
0.49
0.75 T
BWQ10 44.26 28.47 1.51 35.99 25.03 1.23 27.91 22.33 0.95 BWQ10 54.60 34.15 1.86 46.08 30.68 1.57 37.77 28.00 1.29
S
7 7
BWQ14 56.33 36.03 1.92 45.81 31.61 1.56 35.56 28.14 1.21 BWQ14 69.80 43.39 2.38 58.65 38.74 2.00 48.08 35.26 1.64
BWQ18 73.07 46.64 2.49 59.15 40.73 2.02 45.70 36.11 1.56 BWQ18 91.54 56.73 3.12 76.16 50.17 2.60 62.13 45.43 2.12
BWQ25 99.23 63.02 3.39 80.20 54.84 2.74 61.88 48.37 2.11 BWQ25 126.03 77.64 4.30 103.47 67.69 3.53 84.27 60.99 2.88

ENTERING AIR TEMP. = 290C DB/20.50C WB


0 0 0
4 C EWT 7 C EWT 10 C EWT
WTR UNIT
0 NOTE:
C SIZE TC SC LPS TC SC LPS TC SC LPS
BWQ03 16.42 10.22 0.78 13.95 9.19 0.67 11.52 8.35 0.55
1. Capacities are based on nominal airflow.
BWQ05 27.05 16.84 1.29 22.73 15.01 1.09 18.56 13.54 0.89 2. For any other conditions, please use selection software for fan coil units.
BWQ07 43.59 26.96 2.08 36.37 23.82 1.74 29.50 21.31 1.41 Apart from capacities, this software provides;
5 BWQ10 72.66 44.59 3.47 61.24 39.62 2.93 50.27 35.59 2.40
BWQ14 93.39 56.94 4.46 78.72 50.43 3.76 64.67 45.19 3.09 a) Sensible heat ratio
BWQ18 125.73 76.24 6.01 105.05 66.87 5.02 85.56 59.37 4.09
BWQ25 172.00 103.80 9.00 145.31 89.97 6.94 118.01 80.79 5.64 b) Leaving air temperature (DB/WB) - 0C
BWQ03 15.62 9.76 0.62 13.20 8.76 0.53 11.13 8.12 0.44 c) Leaving water temperature - 0C
BWQ05 25.34 15.87 1.01 21.20 14.14 0.84 17.88 13.13 0.71
d) Water pressure drop (feet of water)
BWQ07 40.44 25.18 1.61 33.67 22.27 1.34 27.97 20.38 1.11
6 BWQ10 68.39 42.21 2.72 57.53 37.53 2.29 47.28 33.86 1.88
BWQ14 87.92 53.90 3.50 74.03 47.83 2.95 60.57 42.82 2.41
BWQ18 116.94 71.39 4.66 97.78 62.85 3.89 79.45 55.87 3.16
BWQ25 161.56 97.97 6.43 134.80 85.84 5.37 109.39 75.98 4.36 LEGEND:
BWQ03 14.88 9.34 0.51 12.89 8.58 0.44 10.93 8.00 0.37 TC - Total Capacity (kW)
BWQ05 24.02 15.12 0.82 20.70 13.83 0.71 17.46 12.87 0.60
BWQ07 37.84 23.71 1.29 32.37 21.53 1.10 27.20 19.92 0.93 SC - Sensible Heat Capacity (kW)
7 BWQ10 64.80 40.20 2.21 54.73 35.94 1.87 46.20 33.22 1.58
BWQ14 83.42 51.39 2.85 70.00 45.55 2.39 58.81 41.83 2.01
WTR - Water Temperature Rise (0C)
BWQ18 110.04 67.55 3.76 91.80 59.51 3.13 76.36 54.08 2.61 EWT - Entering Water Temperature (0C)
BWQ25 151.65 92.51 5.18 126.39 81.16 4.31 103.75 72.75 3.54
LPS - Water flow (Liters Per Second)

SPLIT COIL*
ENTERING AIR TEMP. = 270C DB/19.50C WB
0 0 0
4 C EWT 7 C EWT 10 C EWT
WTR UNIT
0
C SIZE TC SC LPS TC SC LPS TC SC LPS

BWQ03 10.25 6.59 0.55 8.70 6.03 0.47 6.88 5.39 0.38
BWQ05 15.75 10.13 0.85 13.09 9.08 0.71 10.19 8.02 0.55
BWQ07 25.01 16.02 1.35 21.0 14.44 1.13 16.43 12.80 0.89
5 BWQ10 50.51 31.57 2.71 41.93 27.96 2.27 33.76 25.07 1.83
BWQ14 67.38 41.73 3.62 55.93 36.90 3.02 44.80 32.80 2.43
BWQ18 86.76 53.59 4.66 71.74 47.14 3.91 56.93 41.58 3.09
BWQ25 113.06 69.93 5.13 98.10 64.13 5.10 78.71 57.01 4.22
BWQ03 9.63 6.21 0.42 7.73 5.42 0.33 5.86 4.69 0.26
BWQ05 14.41 9.34 0.62 11.54 8.11 0.50 8.43 6.76 0.37
BWQ07 23.22 14.93 1.01 18.24 12.74 0.79 13.29 10.66 0.57
6 BWQ10 46.73 29.40 2.02 38.77 26.09 1.68 30.40 22.99 1.32
BWQ14 62.37 38.95 2.70 52.15 34.70 2.26 40.88 30.40 1.76
BWQ18 79.77 49.66 3.47 65.30 43.43 2.84 51.01 37.95 2.21
BWQ25 110.51 68.46 4.76 90.22 59.62 3.87 71.80 52.86 3.09
BWQ03 8.70 5.67 0.32 6.79 4.83 0.25 5.71 4.57 0.25
BWQ05 12.83 8.37 0.46 9.49 6.76 0.34 6.38 5.30 0.25
BWQ07 20.32 13.21 0.73 15.26 10.83 0.55 7.50 6.35 0.30
7 BWQ10 43.69 27.67 1.58 35.14 23.95 1.26 26.33 20.35 0.95
BWQ14 58.59 35.93 2.11 47.50 31.95 1.70 36.43 27.61 1.31
BWQ18 73.50 45.21 2.65 59.44 39.97 2.14 45.27 34.35 1.64
BWQ25 103.48 64.51 3.72 83.78 55.90 3.01 63.78 47.88 2.30

* 2 row cooling coil for BWQ03, BWQ05 & BWQ07. 3 row cooling coil for BWQ10 & above. (with 1 row heating coil).

8
FAN PERFORMANCE DATA
DIRECT DRIVE MOTORS
MODEL No.: BWQ03
BLOWER MOTOR HP BLOWER MOTOR CFM @ External Static Pressure (inch wg.)
SPEED 0.1 0.2 0.3 0.4 0.5 0.6
HIGH 1350 1290 1220 1160 1070 990
0.5 MEDIUM 1260 1200 1125 1060 1000 900
LOW 1070 1020 960 900 830 740
HIGH 1660 1480 1300 1230 1140 1060
0.75 MEDIUM 1570 1375 1180 1120 1060 960
LOW 1500 1320 1130 940 870 780

MODEL No.: BWQ05


BLOWER MOTOR HP BLOWER MOTOR CFM @ External Static Pressure (inch wg.)
SPEED 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
HIGH 2010 1920 1820 1730 1620 1490 1350 1230
0.75 MEDIUM 1830 1740 1660 1570 1470 1360 1240 1100
LOW 1710 1650 1570 1490 1390 1300 1170 975
HIGH 2252 2215 2180 2140 2105 2065 2020 1950
1.0 MEDIUM 2021 1990 1950 1920 1880 1840 1795 1700
LOW 1820 1805 1790 1735 1700 1665 1630 1530
NOTE: Values include losses for dry coil, 1" thick filters & unit casing.

BELT DRIVEN MOTORS


MODEL No.: BWQ07
External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 (849)
2000 (944)
820*
824*
0.62*
0.7*
900
905
I 0.71
0.79
965
970
0.82
0.91
1020
1026
0.88
1.0
1102
1107
1.03
1.12
1145
1152
1.14
1.25
1220
1225
1.26
1.35
2200 (1038) 853 0.81 927 0.91 986 1.02 1041 1.13 1111 1.25 1160 1.36 1237 1.48
2400 (1133) 950 0.94 1004 1.05 1059 1.21 1132 1.27 1155 1.38 1244 1.5 1297 1.65
2600 (1227) 968 1.1 1032 1.22 1086 1.33 1150 1.45 1194 1.57 1250 1.69 1305* 1.82*
2800 (1321) 1054 1.4 1106 1.5 1160 1.61 1216 1.76 1261 1.88 1323* 2.02* 1380* 2.2*
3000 (1416) 1066 1.55 1133 1.7 1180 1.82 1234 1.94 1276 2.09 1334* 2.23* 1400* 2.3*
3200 (1510)
3400 (1605)
1091
1116
1.75
1.96
1157
1171
1.91
2.1
1202
1228
2.02
2.3
1255
1276
2.2
2.45
1307*
1329*
2.33*
2.6*
1359*
1368*
2.47*
2.73* II
MODEL No.: BWQ10
External Static Pressure (inch wg.)
Airflow, 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2800 (1321)
3000 (1416)
610*
625*
0.62*
0.69*
710*
720*
0.75*
0.80*
745
760 I 0.87
0.95
760
810
0.95
1.12
850
865
1.2
1.25
905
915
1.32
1.4
965
970
1.5
1.6
1000
1013
1.6
1.75
1054
1065
1.8
2.0
1100
1115
2.0
2.15
3200 (1510) 636* 0.77* 734 0.92 780 1.06 820 1.26 870 1.38 925 1.51 978 1.73 1023 1.86 1073 2.1 1122 2.28
3400 (1605) 660* 0.88* 746 1.01 805 1.18 833 1.34 881 1.5 939 1.67 983 1.84 1033 2.02 1083 2.25 1128 2.44
3600 (1699) 675* 1.0* 760 1.16 820 1.32 848 1.48 900 1.66 950 1.82 995 1.98 1043 2.21 1090 2.41 1131 2.6
3800 (1793) 700* 1.13* 778 1.3 840 1.43 868 1.63 913 1.8 966 2.0 1006 2.18 1056 2.39 1100 2.58 1143 2.78
4000 (1888) 727 1.28 790 1.45 865 1.62 882 1.8 926 1.96 980 2.18 1023 2.4 1066 2.6 1108 2.77
4200 (1982)
4400 (2076)
772
791
1.41
1.58
843
864
1.62
1.79
880
887
1.78
1.94
921
934
1.96
2.14
968
979
2.16
2.34
1011
1024
2.36
2.54
1054
1067
2.56
2.77
1096 2.76
II
4600 (2170) 840 1.79 890 1.96 931 2.2 975 2.38 1017 2.59 1058 2.77
4800 (2265) 857 1.95 906 2.17 947 2.4 988 2.57 1035 2.76
5000 (2360) 876 2.15 920 2.38 961 2.6 1005 2.76
NOTES (For BWQ07/BWQ10): 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.

9
FAN PERFORMANCE DATA (BELT DRIVEN MOTORS)
MODEL No.: BWQ14
External Static Pressure (inch wg.)
Airflow, 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 (1888)
4200 (1982)
4400 (2076)
694*
705*
719*
1.21*
1.33*
1.43*
743*
761*
774
1.3*
1.45*
1.6
797
811
823
I 1.52
1.67
1.8
845
857
869
1.66
1.81
1.97
890
903
918
1.83
2.0
2.17
937
951
963
2.03
2.19
2.33
975
992
1006
2.25
2.43
2.58
992
1002
1010
2.4
2.6
2.78
1075
1080
1093
2.64
2.82
2.97
II1102
1110
1133
2.85
3.05
3.2
4600 (2170) 735* 1.57* 787 1.75 835 1.95 885 2.17 929 2.34 971 2.55 1013 2.75 1053 2.93 1100 3.17 1138 3.41
4800 (2265) 748* 1.72* 800 1.92 846 2.09 897 2.35 935 2.52 979 2.72 1023 2.91 1065 3.14 1107 3.4 1144 3.62
5000 (2360) 761* 1.87* 812 2.09 862 2.30 904 2.52 948 2.70 989 2.91 1032 3.11 1068 3.37 1113 3.6 1150 3.86
5200 (2454) 778 2.06 823 2.27 873 2.48 917 2.70 959 2.91 1001 3.11 1038 3.34 1070 3.59 1119 3.85 1159 4.08
5400 (2548) 800 2.31 846 2.5 894 2.72 934 2.94 979 3.15 1019 3.38 1056 3.64 1098 3.88 1133 4.10 1171 4.36
5600 (2643) 808 2.46 858 2.7 903 2.90 945 3.12 987 3.38 1028 3.65 1063 3.83 1106 4.14 1139 4.35 1176 4.57
5800 (2737) 826 2.68 869 2.9 917 3.12 955 3.4 1000 3.65 1041 3.9 1078 4.13 1114 4.37 1150 4.6 1186 4.78
6000 (2832) 837 2.90 885 3.12 927 3.37 965 3.64 1009 3.9 1047 4.13 1088 4.35 1123 4.59 1157 4.85 1194 5.05
6200 (2926) 850 3.12 900 3.41 940 3.65 980 3.92 1021 4.17 1061 4.38 1100 4.66 1133 4.85 1167 5.1 1205 5.4
6400 (3020) 879 3.41 920 3.70 962 3.96 1000 4.2 1040 4.45 1078 4.69 1114 4.92 1150 5.2 1183 5.45 1218 5.76
6600 (3115) 894 3.76 933 4.0 973 4.24 1013 4.44 1050 4.68 1091 4.92 1125 5.2 1161 5.51 1194 5.8 1229 6.08

MODEL No.: BWQ18


External Static Pressure (inch wg.)
Airflow,
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5000 (2360)
5200 (2454)
715*
718*
1.33*
1.42*
731*
737*
1.56*
1.68*
787*
793* I 1.82*
1.96*
850
856
2.07
2.26
902
905
2.4
2.53
955
961
2.66
2.83
1005
1010
2.96
3.15
1057
1060
3.3
II
3.46
1104
1107
3.6
3.76
1153*
1155*
3.88*
4.04*
5400 (2548) 721* 1.53* 750* 1.81* 802* 2.07* 860 2.35 911 2.66 966 2.96 1012 3.23 1062 3.57 1109 3.88 1157* 4.27*
5600 (2643) 725* 1.68* 756* 1.92* 807 2.21 866 2.5 916 2.79 968 3.07 1015 3.38 1065 3.73 1110 4.07 1158* 4.4*
5800 (2737) 729* 1.81* 762* 2.03* 816 2.35 872 2.64 921 2.9 970 3.23 1020 3.53 1066 3.84 1113 4.18 1159* 4.59*
6000 (2832) 733* 1.9* 775* 2.14* 833 2.42 877 2.78 930 3.02 980 3.4 1025 3.69 1070 4.0 1118 4.4 1162* 4.72*
6200 (2926) 738* 2.03* 788* 2.35* 839 2.57 888 2.92 935 3.24 985 3.56 1030 3.84 1080 4.27 1120 4.63 1163* 4.95*
6400 (3020) 745* 2.15* 795* 2.5* 850 2.71 900 3.08 940 3.41 990 3.72 1036 4.04 1082 4.45 1126 4.82 1165* 5.09*
6600 (3115) 753* 2.38* 800* 2.64* 855 2.92 905 3.25 950 3.58 1000 3.88 1045 4.23 1083 4.6 1127 5 1170* 5.3*
6800 (3209) 761* 2.5* 810 2.78 863 3.08 910 3.41 960 3.75 1004 4.14 1050 4.47 1090 4.83 1134 5.16 1175* 5.51*
7000 (3303) 772* 2.69* 820 2.92 875 3.33 918 3.58 967 3.95 1012 4.28 1054 4.66 1095 5.04 1135 5.39 1179* 5.72*
7200 (3398) 777* 2.84* 830 3.08 880 3.41 927 3.75 976 4.14 1017 4.47 1059 4.85 1100 5.19 1141* 5.58* 1183* 5.95*
7400 (3492) 794* 2.96* 845 3.3 890 3.62 936 3.95 985 4.4 1021 4.68 1065 5.09 1108 5.47 1150* 5.8* 1185* 6.12*
7600 (3587) 805 3.18 850 3.5 900 3.83 941 4.2 990 4.57 1026 4.85 1069 5.23 1112 5.66 1154* 6* 1193* 6.42*
7800 (3681) 820 3.36 870 3.69 909 4.1 954 4.5 1002 4.9 1041 5.14 1083 5.47 1125 5.9 1158* 6.36* 1200* 6.78*
8000 (3775) 830 3.59 880 3.86 922 4.25 963 4.65 1008 5.05 1046 5.33 1087 5.75 1128 6.12 1164* 6.6*
8200 (3870) 867 3.77 890 4.1 936 4.5 972 4.9 1016 5.25 1054 5.56 1100 6 1132 6.36 1172* 6.84*
8400 (3964) 890 4.05 904 4.42 945 4.75 986 5.1 1025 5.45 1066 5.85 1107 6.24 1140 6.72
NOTES (For BWQ14/BWQ18): 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.
MODEL No.: BWQ25
External Static Pressure (inch wg.)
Airflow, 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
CFM (L/S)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6000 (2832)
6400 (3020)
700*
706*
2.6*
2.8*
762*
764*
3.12*
3.3* I 812
813
3.6
3.78
857
858
4.0
4.22
900
901
4.5
4.73
944
945
5.0
5.23
980
981
5.46
5.71
1000
1002
6.0
6.3II 1059*
1059*
6.6*
6.92*
6800 (3209) 716* 3.05* 766* 3.5* 814 4.0 859 4.42 902 4.96 946 5.45 982 5.97 1003 6.6 1059* 7.22*
7200 (3398) 722* 3.24* 768* 3.7* 815 4.19 860 4.64 903 5.2 946 5.68 983 6.23 1005 6.95 1060* 7.51*
7600 (3587) 732* 3.4* 770* 3.82* 816 4.35 861 4.88 904 5.45 947 5.9 985 6.5 1007 7.25 1060* 7.78*
8000 (3775) 740* 3.6* 772* 4.0* 818 4.56 861 5.18 904 5.65 947 6.12 986 6.8 1009 7.5 1061* 8.05*
8400 (3964) 751* 3.9* 778* 4.35* 819 4.85 865 5.5 906 5.97 949 6.48 988 7.2 1010 7.8 1062* 8.35*
8800 (4152) 790 4.2 800 4.65 821 5.16 869 5.81 908 6.3 951 6.8 990 7.6 1011 8.1 1062* 8.65*
9200 (4341) 800 4.5 810 5.0 823 5.5 873 6.14 911 6.75 953 7.15 992 8.0 1014 8.45 1064* 9.0*
9600 (4530) 805 4.9 820 5.35 825 5.84 877 6.45 915 7.1 955 7.6 994 8.35 1017* 8.75* 1065* 9.45*
10000 (4719) 815 5.2 825 5.67 826 6.15 882 6.7 920 7.4 957 8.06 996 8.71 1020* 9.25* 1067* 9.8*
10400 (4907) 825 5.55 830 6.1 838 6.6 890 7.1 928 7.85 965 8.4 1003 9.1 1023* 9.7* - -
10800 (5096) 835 5.9 840 6.5 870 7.0 898 7.5 936 8.3 973 8.8 1009 9.5 - - - -
11200 (5286) 840 6.4 856 6.9 876 7.4 906 7.95 944 8.7 981 9.25 1014 9.9 - - - -
11600 (5474) 852 6.8 872 7.3 885 7.9 914 8.45 952 9.15 989 9.6 - - - - - -
12000 (5663) 870 7.2 885 7.8 892 8.5 925 9.0 961 9.6 996 10.1 - - - - - -
Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 10 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest COOLINE representative for proper selection of drives. Drives shall be field supplied & installed.

10
ELECTRICAL DATA
MODEL No.: BWQ03 MODEL No.: BWQ05
VOLTAGE BLOWER VOLTAGE BLOWER
POWER POWER
ELECTRIC HEATER ELECTRIC HEATER
SUPPLY RANGE MOTOR ** MCA MOCP
SUPPLY RANGE MOTOR ** MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 2.4 15 – – 6.1 15
5 21.7 29.5 30 5 21.7 33.3 35
0.50 1.9 6/7 26.1/30.4 35/40.4 40/45 0.75 4.9 6/7 26.1/30.4 38.8/44.1 40/45
(STD.) 10*/12* 43.5/52.2 56.8/67.6 60/70 (STD.) 10*/12* 43.5/52.2 60.5/71.4 70/80
14* 60.9 78.5 80 14* 60.9 82.3 90
220/240-1-50 198 264 – – 6.1 15 220/240-1-50 198 264 – – 6.8 15
5 21.7 33.3 35 5 21.7 33.9 35
0.75 4.9 6/7 26.1/30.4 38.8/44.1 40/45 1.0 5.4 6/7 26.1/30.4 39.4/44.8 40/45
(ALT.) 10*/12* 43.5/52.2 60.5/71.4 70/80 (ALT.) 10*/12* 43.5/52.2 61.1/72 70/80
14* 60.9 82.3 90 14* 60.9 81.2 90
– – 2.4 15 – – 6.1 15
5 7.6 11.9 15 5 7.6 15.6 20
0.50 1.9 6/7.5 9.1/11.4 13.8/16.6 15/20 0.75 4.9 6/7.5 9.1/11.4 17.5/20.4 20/25
(STD.) 10*/12* 15.2/18.2 21.4/25.1 25/30 (STD.) 10*/12* 15.2/18.2 25.1/28.9 30/30
15* 22.8 30.9 35 15* 22.8 34.6 35
380/415-3-50 342 457 – – 6.1 15 380/415-3-50 342 457 – – 6.8 15
(4 WIRE) 5 7.6 15.6 20 (4 WIRE) 5 7.6 16.3 20
0.75 4.9 6/7.5 9.1/11.4 17.5/20.4 20/25 1.0 5.4 6/7.5 9.1/11.4 18.1/21 20/25
(ALT.) 10*/12* 15.2/18.2 25.1/28.9 30/30 (ALT.) 10*/12* 15.2/18.2 25.8/29.5 30/35
15* 22.8 34.6 40 15* 22.8 35.3 40

MODEL No.: BWQ07 MODEL No.: BWQ10


POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
RANGE MOTOR ELECTRIC HEATER RANGE MOTOR ELECTRIC HEATER
SUPPLY SUPPLY
MCA MOCP MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 4.5 15 – – 4.5 15
5 7.6 14 15 5 7.6 14 15
2 3.6 6/7.5 9.1/11.4 15.9/18.8 20/20 2 3.6 6/7.5 9.1/11.4 15.9/18.8 20/20
(STD.)
10*/12* 15.2/18.2 23.5/27.3 25/30 (ALT.)
10*/12* 15.2/18.2 23.5/27.3 25/30
15*/20* 22.8/30.4 33/42.5 35/45 15*/20* 22.8/30.4 33/42.5 35/45
25*/30* 38/45.6 52/61.5 60/70
380/415-3-50 342 457 25*/30* 38/45.6 52/61.5 60/70
(4 WIRE) – – 5.9 15
380/415-3-50 342 457 – – 5.9 15
5 7.6 15.4 20 (4 WIRE) 5 7.6 15.4 20
3 4.7 6/7.5 9.1/11.4 17.3/20.1 20/25
(ALT.) 3 4.7 6/7.5 9.1/11.4 17.3/20.1 20/25
10*/12* 15.2/18.2 24.9/28.6 25/30 (STD.)
10*/12* 15.2/18.2 24.9/28.6 25/30
15*/20* 22.8/30.4 34.4/43.9 35/45
25*/30* 38/45.6 53.4/62.9 60/70 15*/20* 22.8/30.4 34.4/43.9 35/45
25*/30* 38/45.6 53.4/62.9 60/70

MODEL No.: BWQ14 & BWQ18 MODEL No.: BWQ25


POWER VOLTAGE BLOWER POWER VOLTAGE BLOWER
RANGE MOTOR ELECTRIC HEATER RANGE MOTOR ELECTRIC HEATER
SUPPLY SUPPLY
MCA MOCP MCA MOCP
(V-Ph-Hz) (V-Ph-Hz)
MIN. MAX. HP FLA kW FLA MIN. MAX. HP FLA kW FLA
– – 11.3 20 – – 16.3 25
5 7.6 20.8 25 5 7.6 25.7 35
5 9 6/7.5 9.1/11.4 22.6/25.5 25/30 7.5 13 6/7.5 9.1/11.4 27.6/30.5 35/40
(STD.) 10*/12* 15.2/18.2 30.3/34 35/35 (STD.) 10*/12* 15.2/18.2 35.2/39 40/45
15*/20* 22.8/30.4 39.7/49.3 40/50 15*/20* 22.8/30.4 44.7/54.2 50/60
25*/30* 38/45.6 58.8/68.3 60/70 25*/30* 38/45.6 63.7/73.2 70/80
35*/40* 53.2/60.8 77.8/87.3 80/90 35*/40* 53.2/60.8 82.7/92.2 90/100
380/415-3-50 342 457 380/415-3-50 342 457
(4 WIRE) – – 16.3 25 (4 WIRE) – – 18.8 30
5 7.6 25.7 30 5 7.6 28.2 40
7.5 13 6/7.5 9.1/11.4 27.6/30.5 35/40 10 15 6/7.5 9.1/11.4 30.1/33 40/45
(ALT.) (ALT.)
10*/12* 15.2/18.2 35.2/39 40/45 10*/12* 15.2/18.2 37.7/41.5 45/50
15*/20* 22.8/30.4 44.7/54.2 50/60 15*/20* 22.8/30.4 47.2/56.7 50/60
25*/30* 38/45.6 63.7/73.2 70/80 25*/30* 38/45.6 66.2/75.7 70/80
35*/40* 53.2/60.8 82.7/92.2 90/100 35*/40* 53.2/60.8 85.2/94.7 90/100

LEGEND
FLA – Full Load Amps
HP – Horse Power
MOCP – Maximum Over Current Protection
MCA – Minimum Circuit Amps
* Combination of 2 heater modules
** Single phase motors (220/240V-1Ph-50Hz power supply).
11
DIMENSIONS
BWQ03 - BWQ14 (HORIZONTAL DISCHARGE)

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Hot water coil connection is available only if hot water coils are ordered.
DIMENSIONS
MODEL
A B C D E F G H J K L M N P Q R
BWQ03 1092(43) 648(25.5) 575(22.64) 483(19.02) 143(5.63) 406(15.98) 45(1.77) 542(21.34) 524(20.63) 297(11.69) 553(21.77) 171(6.73) 178(7.01) 140(5.51) 19(0.75) 19(0.75)
BWQ05 1092(43) 813(32) 600(23.62) 483(19.02) 224(8.82) 406(15.98) 45(1.77) 707(27.83) 550(21.65) 297(11.69) 553(21.77) 171(6.73) 178(7.01) 140(5.51) 25(1) 25(1)
BWQ07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 182(7.16) 406(15.98) 66(2.6) 995(39.17) 550(21.65) 378(14.88) 721(28.38) 164(6.46) 165(6.5) 132(5.2) 32(1.25) 25(1)
BWQ10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 332(13.1) 406(15.98) 42(1.65) 1295(51) 625(24.61) 378(14.88) 721(28.38) 112(4.41) 206(8.11) 140(5.51) 38(1.5) 32(1.25)
BWQ14 1625(64) 1600(63) 705(27.75) 1321(52) 187(7.36) 406(15.98) 55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

12
DIMENSIONS
BWQ03 - BWQ14 (VERTICAL DISCHARGE)

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Hot water coil connection is available only if hot water coils are ordered.
DIMENSIONS
MODEL
A B C D E F G H J K L M N P Q R
BWQ03 1092(43) 648(25.5) 575(22.64) 483(19.02) 134(5.28) 406(15.98) 35(1.38) 543(21.38) 502(19.76) 285(11.22) 553(21.77) 171(6.73) 178(7.01) 140(5.51) 19(0.75) 19(0.75)
BWQ05 1092(43) 813(32) 600(23.62) 483(19.02) 229(9.02) 406(15.98) 32(1.26) 712(28.03) 502(19.76) 300(11.81) 553(21.77) 171(6.73) 178(7.01) 140(5.51) 25(1) 25(1)
BWQ07 1360(53.5) 1100(43.31) 600(23.62) 813(32) 213(8.4) 406(15.98) 85(3.34) 991(39) 504(19.83) 302(11.87) 697(27.53) 164(6.46) 165(6.5) 132(5.2) 32(1.25) 25(1)
BWQ10 1490(58.7) 1400(55.12) 675(26.57) 813(32) 365(14.38) 406(15.98) 35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 101(3.98) 194(7.64) 159(6.26) 38(1.5) 32(1.25)
BWQ14 1625(64) 1600(63) 705(27.75) 1321(52) 224(8.82) 406(15.98) 49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

13
DIMENSIONS
BWQ18 - BWQ25 (HORIZONTAL DISCHARGE)

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Hot water coil connection is available only if hot water coils are ordered.
DIMENSIONS
MODEL
A B C D E F G H J K L M N P Q R
BWQ18 1625(64) 2070(81.5) 705(27.75) 1575(62) 382(15.04) 483(19.02) 35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)
BWQ25 1825(71.85) 2362(93) 840(33.1) 1575(62) 590(23.23) 483(19.02) 50(1.97) 2257(88.86) 790(31.1) 503(19.8) 913(35.94) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

14
DIMENSIONS
BWQ18 - BWQ25 (VERTICAL DISCHARGE)

NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Hot water coil connection is available only if hot water coils are ordered.
DIMENSIONS
MODEL
A B C D E F G H J K L M N P Q R
BWQ18 1625(64) 2070(81.5) 705(27.75) 1575(62) 422(16.61) 483(19.02) 46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)
BWQ25 1825(71.85) 2362(93) 840(33.1) 1575(62) 625(24.61) 483(19.02) 74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 127(5) 152(5.98) 140(5.51) 38(1.5) 32(1.25)

15
DIMENSIONS - HEATER BOX
BWQ03 - BWQ05
.3" )
(16
415

(1")
25.4 YP
T

205 (8.1")

490
(1 9.3")

HEATER CONTROLS MTG HEATER CONTROLS MTG


PLATE
COVER

BWQ07 - BWQ14
.2")
(1 6
412

P
TY
4( 1")
25.
205 (8.1")

DIMENSIONS
MODEL
A
HEATER ACCESS COVER
BWQ07 818 (32.2)
HEATER CONTROLS MTG
BWQ10 818 (32.2) COVER
BWQ14 1326(52.2) HEATER CONTROLS MTG
PLATE

4")
BWQ18 - BWQ25
.
(19
492

YP
") T
4 (1
25.
205 (8.1")

1581 (6
2.3")

HEATER ACCESS COVER


(BOTH SIDES) HEATER CONTROLS MTG
COVER
HEATER CONTROLS MTG
PLATE

NOTES: 1. All dimensions are in mm (dimensions in brackets are in inches).


2. Heater box is an optional feature.

16
TYPICAL SCHEMATIC WIRING DIAGRAM
LEGEND
AFS AIRFLOW SWITCH
ATB AUXILIARY TERMINAL BLOCK
AR AUXILIARY RELAY
BM BLOWER MOTOR
BMC BLOWER MOTOR CONTACTOR
FL FUSE LINK
HC HEATER CONTACTOR
HVTB HIGH VOLTAGE TERMINAL BLOCK
HTR HEATER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LVTB LOW VOLTAGE TERMINAL BLOCK
LUG LUG GROUND
MOHT MANUAL RESET OHT
N NEUTRAL
NTB NEUTRAL TERMINAL BLOCK
OHT OVERHEAT THERMOSTAT
OLR OVER LOAD RELAY
VFC VOLT FREE CONTACT
___ FIELD WIRING
+ DISCONNECT TAB - 1/4"

NOTES
1. POWER SUPPLY, 380/415V-3Ph-50Hz.
THERMOSTAT CONTROL VOLTAGE - 24VAC.

2. ANY WIRE REPLACEMENT SHOULD BE OF THE 90½C


OR ITS EQUIVALENT.
USE COPPER CONDUCTOR WIRES ONLY.
3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLE
PROTECTION FOR COMPRESSOR IS AVAILABLE IN
COOLINE ELECTRONIC THERMOSTAT.
4. IF HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER


TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY MANUFACTURER.
VFC OPTION FOR BM ON,OFF &TRIP INDICATION
WITH FURNAS/SIEMENS CONTACTOR AND OLR 6. HVTB IS REQUIRED ONLY FOR HEATER MODELS.

7. BMC-OLR CONNECTING WIRE NOT REQUIRED FOR


OLR. FIXED DIRECTLY BENEATH CONTACTOR.

BM ON,OFF & TRIP INDICATION OPTION

17
CONTROLS & SEQUENCE OF OPERATION
The operation of the air conditioning unit is controlled by a 24VAC electronic control board. All the contactors are oper-
ated by the 24V circuit, including the thermostat.

Mode:
Select the desired mode of operation by continuous press-
ing of the MODE button: 24 V
(C)
Controls cooling system only (the word COOL will 24 V
24VAC

display for 5 seconds). Equipment Line Voltage


R Relays 2nd stage Transformer
Controls heating system only (the word HEAT will Cooling
Y2
display for 5 seconds). 1st stage
Cooling
L Y1
HEAT/COOL - Controls both systems automati- I Fan Relay
G G
cally (the word AUTO will display for 5 seconds). H
T
1st stage
Heating
S W1
OFF - Systems will not operate. 2nd stage
Heating
W2

Cooling:
Select the temperature you want your cooling system to LED 1
Clogged Filter *
maintain by pressing and holding the COOLING button LED 2
Compressor Fault

under the or symbols until the desired temperature Thermostat


is displayed. The control setpoint temperature is displayed * Clogged filter switch not provided
Field Wiring
for 5 seconds.

Heating:
Select the temperature you want your heating system to maintain by pressing and holding the HEATING button under
the or symbols until the desired temperature is displayed. The control setpoint temperature is displayed for 5
seconds.

Fan:
The fan will be energized automatically when the systems are operating but no indication of this on the display. To select
continuous fan operation, press the FAN button and the display will show . This is recommended for electronic air
cleaners and continuous ventilation requirements.

Off
When the word OFF is displayed the heating and cooling systems will not operate. Avoid using the OFF mode during
extremely cold weather to prevent damage from freezing.

Auto:
Selecting this mode of operation will control both heating and cooling systems. The thermostat will automatically switch
from one to the other as determined by the selected temperatures in heating and cooling.
NOTE: The thermostat always maintains a minimum 20F (10C) difference or dead band between the heating and cooling
setpoints.

Celsius/Fahrenheit
Simultaneously press and to switch between Celsius and Fahrenheit temperature display.

18
INSTALLATION INSTRUCTIONS
A. GENERAL
Blower units are shipped completely wired. Only external power, control wiring and piping connections are needed to
complete the installation.

B. UNIT LOCATION & ACCESS SPACE


The placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be
kept on the service access side and return air side.
When making piping connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATION
Do not remove plugs from the pipe stub out until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required.
NOTE: When installing piping through walls or along side of any structural members, be sure the piping is isolated from
these members or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
NOTE: Use copper wires of proper rating for all field wiring.
Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than
one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram. Connect ground wire to the ground lug inside the control box.
C) Control wiring
Use 16 gauge color-coded wire for control wiring.

STEP 2: SEQUENCE OF OPERATION


With power supplied to indoor unit, the unit starts responding to the thermostat mode requirement.
Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on.
As the conditioned space approaches the thermostat cooling set point, the unit cycles off.
Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor for
electric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heaters
installed, the second heater also will be energized.
Once, the conditioned space approaches the desired temperature set point, the heating stages cycles off.
Fan mode: In this mode the indoor unit blower motor is switched on alone.

PARTS LIST
MODEL NUMBER BWQ03B BWQ03L BWQ05B BWQ05L BWQ07L BWQ10L BWQ14L BWQ18L BWQ25L
BLOWER MOTOR 800-547-71 800-547-71 800-546-94 800-546-94 800-544-16 800-544-17 800-544-72 800-544-72 800-544-73
BLOWER WHEEL 800-707-10 800-707-10 800-707-10 800-707-10 800-707-46 800-707-02 800-707-02 800-707-00 800-707-22
BLOWER MOTOR CONTACTOR 800-736-01 800-736-01 800-736-01 800-736-01 800-095-00 800-095-00 800-098-54 800-098-54 800-098-56
AIRFLOW SWITCH 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02 800-005-02

19