Professional Documents
Culture Documents
Aux Boiler Final DWG Kangrim PA0501P32
Aux Boiler Final DWG Kangrim PA0501P32
Aux Boiler Final DWG Kangrim PA0501P32
,Ltd SPECIFICATION
Hull No : 2660
2656~58 Type No. - PA0501P32 x 1 set/ship
Classification : ABS Capacity - 3,000 kg/hr
2660
Work order No. : PAW13HD2656~58 Working pressure - 6kg/㎠.G
Burner type - RP-250M x 1 set/ship
Auxiliary Boiler
40,WOUNGNAM-DONG,CHANGWON CITY,KOREA
TEL : 055) 269 ~ 7700(REP) / 760(DIR)
FAX : 055) 269 ~ 7795~9
E-MAIL: tech1@kangrim.com
CONTENTS
1. DESIGN DATA
2. DRAWINGS
3. ACCESSORIES
4. BURNER SPECIFICATION
6 CONTROL PANEL
6.
8. INSTRUCTION MANUAL
*NOTE
If we may be of further assistance, please do not hesitate to contact Mr. Dae-Young, Byun at 82-55-269-7774.
PLAN HISTORY
1. DESIGN DATA
1 - Technical data 0
3 MB-INT-001 Installation 0
4 MB-MN-01 Preservation 0
TECHNICAL DATA
General description
The PA type boiler is a pin tube type vertical cylindrical boiler. The steam generating section
consists of straight tubes with pin that provide a high heat transfer. On the water side the heat is
transferred by evaporation of the saturated water adjacent to the furnace shell or pin tube wall
where steam bubbles are formed. The boiler is insulated and preassembled with boiler mountings
for easy installation and operation. The boiler is side - fired and equipped with a burner. (Refer to
Fig.1)
1. Design data
Number of boiler / ship 1 Set
Steam production 3,000 kg/hr
Working pressure / Design pressure 6/8 kg/㎠.G
Feed water temperature 60 ℃
3. Dimension
Diameter excl. of insulation 1,950 mm
Height excl. of smoke uptake 4,550 mm
Water volume at normal water level 6.39 m³
Weight of boiler including of burner and fittings (dry) 10.5 Ton
4. Classification
Hull No. 2656~58 ABS
5. Paint color
Body Heat resistance paint silver
Contol panel RAL 7032
17 High salinity in feed water PPM 0~200 W03 (80) - - ● F.W. Pipe
Thermostat
19 ℃ 20~150 F13 (55) - - ● F.O. Pipe
for high M.G.O temp.
Control
20 Emergency stop - - - - ● ●
panel
Control
21 PLC fail - - - - ● ●
panel
Control
22 Power failure - - - - ● ●
panel
(20 mA)
+400 mmH₂O
+250 mmH₂O
(
Normal Water Level (10.7 mA))
0 mmH₂O
(4 mA)
400 mmH₂O
☞ 6.5
6 5 Burner stop
Design Specification
Boiler Type : PA0501P32
Boiler steam production (Oil fired / exh gas) : 3,000 kg/hr
Boiler working / design pressure :6/8
Steam temperature at W.P / D.P : 164.2 / 174.7
Ambient temperature Max. : 45 ℃
unit : mm
Point Design length Expansion at W.P Expansion at D.P
H1 4,250 6.3 7.0
H2 4,550 6.7 7.5
H3 5,385 7.9 8.9
L1 1,187 1.8 2.0
2. DRAWINGS
LIST OF DRAWINGS
3 PA-GA-01 Arrangement 0
3. ACCESSORIES
A01 MB-DP-01 Safety valve with drip pan JIS B8210, 20K-50/80A 2 0
A12 MB-JF-7303 Low water level switch valve JIS F7303, 16K
16K-25A
25A 2 0
8 Cable gland - PG 16
BURNER SPECIFICATION
4. BURNER SPECIFICATION
3. Burner specification
Number of burner / ship :1 Set
Burner type (Pressure jet) : RP-250M (OILON)
Burner control type : Modulating
Burner range : 58~282 kg/h
Turn down : apprix. 1:3
Burner motor : 8.6 kW
Pre-heater : 14.4 kW
Weight of burner with motor : 195 kg
4. Electric data
Power source : AC440, 60Hz, 3ph
Control source : AC220, 60Hz, 3ph
Motor insulation : Class F
Enclosure type : IP 55
5. F.O Pump
Number of pump / ship :2 sets / ship
Type : DS3-1100
Pump capa(at H.F.O used) : 1446 l/hr
Pump capa(at M.G.O used) : 1020 l/hr
Discharge pressure :6 bar
Normal pressure :5 bar
Operating pressure :4 bar
Pump motor : 0.66 kW
Motor insulation : Class F/B
Enclosure type : IP 55
Weight : 99.5 kg
6. Paint color
Burner body : Maker standard
F.O Pump : Maker standard
OPTION SELECTION
E NO.
25/0
26/0 31
33 18 RE RE
EL.TR
35/0 EV1112 EV1111
28
D
15
14
34 5 7
21 EL.TR
11
PI PI PS 13
4 8 10 TZA
EV1101 EV1102 30 29
TI
C
EL.TR
23 6 EL.TR PT TT TE
OIL TO 3 2 9
BURNER TE
35 25 26
EL.TR EL.TR OPTION OPTION OPTION
24
ZA
12
B OIL TO EL.TR
1 22
TANK
Osa/no Osan tai jaoksen nimitys Piir. ja osan no Laatu Muoto, mitat, malli, koodi Massa Kpl
Part/No Part or Group Drw. and Part No Material Shape, Dimensions, Code Weight Pcs
(netto)
Osan aines työvaroineen
Material incl.working allowance
Yleistoleranssit Massa Tilaaja Suhde Suunn. MPE 2012-05-24
General toler. Weight Client Scale Design
Työno Piirt.
Project Drawn
Merkki Hyv.
kg Ref. Appr. HN 2012-05-24
Valmiste ATK
Product RP-250 M ABS
A Versio Piir.no Drw. No
Rev.
Nimitys 0
Title PI-DIAGRAM B-569T
Korvaa n:on Korvattu n:olla
LAHTI FINLAND HP-PUMP Supersedes Drw. Superseded by Drw.
Versio Muutos Muuttaja Hyv. Pvm Koord. Lkm Merkki Micro
Rev. Description Drawn Appr. Date Coord. Pcs Mark film O
557
7.20 11.1.9 7.21 11.1.15 11.1.12 7.29 11.1.11 7.30 6.2 6.9 15.1 3.1001 3.1002 3.1003 3.1004 3.1 3.5
J
244 490
A
CONNECTION POINT TO
ELECTRICAL CABLE (CUSTOMER) 1.1
1.20 1.19
356
427
95
9.1001
99 6.2.14
364
850
6.1001 422 78
221
13.1
365
18
A OIL TO BURNER D22
B OIL TO TANK R1/2"
PARTIAL SECTION
A-A
15.14
15.2
SCAVENGING AIR
PIPE D12
B
TRACE HEATING OF OIL LINE
13.1002
LAHTI FINLAND
Document
MARINE PARTLIST RP250M050_157938_1 0
Marine partlist RP250M050_157938_1 Latest view of documentation 29.5.2012 15:52:03
3.1006 35455047 PRECISION STEEL PIPE Mannesmann EN 10025, DIN 2391 0,12
NBK 0355027 m
8mm 1,5mm ST37.4 Zinc coated
3.1007 35455054 PRECISION STEEL PIPE EN 10025, DIN 2391 0,11
DIN2391 ZN 12.0*3.0 MARINE m
12mm 3mm ST37.4 Zinc coated
3.1008 35455054 PRECISION STEEL PIPE EN 10025, DIN 2391 0,11
DIN2391 ZN 12.0*3.0 MARINE m
12mm 3mm ST37.4 Zinc coated
3.1009 37068010 HEATING CARTRIDGE 1
40W230V STP10*50 L1500 pcs
230VAC 40W 1500mm
5.2 V36961274 ELECTRIC MOTOR 1
pcs
5.3 34367049 FAN WHEEL Punker DIN 1304, DIN24163 1
PUHALLINPYÖRÄ TLR 280*102 pcs
280mm 102mm 38mm
6.2 -B309Y20 OIL REGULATOR Oilon 1
REGULATING SHAFT 20 pcs
6.2.14 34247223 NON-RETURN VALVE Bell DIN 2353 1
RHV 12-PLR-ED R3/8 VITON pcs
R 3/8" PN 300 12mm
6.9 36962058 SERVOMOTOR Siemens DIN 40050 1
SQM10.16502 pcs
10Nm 3.1°/s
6.17 34035106 GAUGE VALVE Tognella 1
FT 290-1/4 VITON pcs
G 1/4" PN 400 Thread
6.19 V34021225 PRESSURE GAUGE Wika EN 837-1 1
233.50.63.XX pcs
-20...150°C 0...6000kPa G 1/4" (Item is virtual / alternative)
LAHTI FINLAND
Document
MARINE PARTLIST RP250M050_157938_1 0
Marine partlist RP250M050_157938_1 Latest view of documentation 29.5.2012 15:52:03
LAHTI FINLAND
Document
MARINE PARTLIST RP250M050_157938_1 0
Marine partlist RP250M050_157938_1 Latest view of documentation 29.5.2012 15:52:03
LAHTI FINLAND
Document
MARINE PARTLIST RP250M050_157938_1 0
Marine partlist RP250M050_157938_1 Latest view of documentation 29.5.2012 15:52:03
LAHTI FINLAND
Document
MARINE PARTLIST RP250M050_157938_1 0
Marine partlist RP250M050_157938_1 Latest view of documentation 29.5.2012 15:52:03
LAHTI FINLAND
Document
MARINE PARTLIST RP250M050_157938_1 0
- 2096 -
L2000
L2000
OILON Burner L.O chart
1. Recommended L.O chart 2012-12-12
Application
No. Sets Q'ty/set Initial filling Q'ty/Burner Oil changining interval Remark
Point
Adjusting lever
1 2 10 g by maker 2 1 time / year
bearing
MOBILGREASE
2 MOBIL
XHP220
Energrease
4 BP
MP-MG 2
5 TOTAL CERAN WR 2
F07 BNR-PS-01 Press. switch for F.O p/p stand-by 1 0 904 type
F08 BNR-PS-01 Press. switch for F.O low press. 1 0 904 type
F22 BNR-QV-01
BNR QV 01 Quick closing valve 1 0 PN16 - DN25
6. CONTROL PANEL
8. INSTRUCTION MANUAL
1. Boiler
2. Safety valve
5. Dosing Unit
6 Salinity Indicator
6.
7. Oil detector
8. Flow meter
10. Burner
1. General -----------------------------------------------------------------3
5. Cleaning ----------------------------------------------------------------7
2
Auxiliary Boiler
1. General
1.1 It rests with the boiler attendant to see to service and supervision of the
boiler plant. He is to see to it that all parts of the plant are properly
maintained, if the task has not been assigned to other persons. On sea-
going vessels the tasks and responsibility of the boiler attendant rest with
the ship's officer from the machine section on duty.
1.2 The boiler attendant is to follow the below working and operation
instructions. If there are interruptions of service and damages and other
irregularities this must be reported to the nearest superior after, of course,
the operational measures, which are necessary in order to obviate a
situation of danger, have been carried out.
2.2 Before heating is begun it must be checked if the gas openings are open
(danger of explosion), that all safety devices are OK, accurately adjusted
and ready for service, and that the water in the boiler is between the lowest
and normal water level.
2.3 Valves and shut-off devices ought to be served slowly, connection pipes
must, if necessary, be emptied of water and ventilated.
( water chock, coolings, at sudden differences in temperature ).
2.4 Before the boiler is used for the first time it must be boiled out in order to
remove all protecting materials and dirt in pipes and drums.
See paragraph about boiling out.
2.5 During the first filling with boiler water the water level indicators to be
controlled by opening the blow–off valve and upper and lower water level
valve to open by turns. a weak air flow should then be heard.
3
Auxiliary Boiler
The mode of operation of A) and B) will required constant water level of the
boiler. Because of danger of burning down in operation. Constant water
level is not required at C). However, this is recommended, as the most
favorable water circulation and most be stable operating conditions will be
obtained. As to the construction and the strength it is fully proper at C) to
lover the water level of the exhaust tube section and even empty the boiler
from water, while the whole gas volume flows through the tube section. The
boiler will in such case, gradually, get the same temperature as that of the
exhaust gas.
The boiler should be cooled before refilling it with feed water. where this
could not be done the feed water is to be preheated, and the feeding should
commence very carefully ( slowly ).
3.2 When the boiler has been ignited the lighting-up rate must not be speeded
up too much in order not unnecessarily to overstrain the boiler material by
quick, uneven temperature rises.
The lighting–up time ought to be about. 1 1/2 hours.
3.3 The air escape valve at the boiler is to be kept open until a heavy steam
jet is flowing out, this occurs at a steam pressure of abt.1, 5 bar.
3.4 The pressure gauge and its connecting pipe line are regularly to be tested
carefully as regards free passage. By this must be stated if the indicator can
reach the O-point without obstructions at slow relief of the pressure gauge,
and if it can reach its former position at slow load.
Further, it must be stated if the pressure gauge shows the indicated
allowable working pressure. At and after every blow-through of the
connecting pipe line the pressure gauge may not be connected until
sufficient steam is condensed in the pipe loop.
4
Auxiliary Boiler
3.5 During service the water level may not fall below the mark for lowest water
level. If the water level cannot with certainty be said to be sufficient the
firing must be stopped at once ( see also paragraph 4.1 ) and the nearest
superior informed immediately.
If the water level goes beyond the top visible water level without perceptible
reason the firing must be stopped at once if you cannot with other
measures again reduce the water level.
3.6 All the water level indication instruments are currently used and have,
therefore, to be kept clean.
The same thing applies for water level regulator and limiter.
Cocks and valves are to be opened slowly and to be closed in the same
way.
Lacks, especially obstructions, are to be removed at once.
3.7 Before the boiler is connected it is necessary that the safety valves are
adjusted so that they can begin to function at the prescribed pressure.
Alteration of the adjustment is to be carried out only by an expert from the
local classification society.
If the steam pressure rises above the allowable working pressure, which is
marked by a red line
line, the firing I reduced and the feeding intensified
intensified.
If the safety valves do not blow, they are to be checked at once.
If the cause is not stated the firing must be stopped and the superior
informed.
3.8 Once a day mud is blown from the boiler through the bottom blow-off valve
until clear water is coming.
3.9 If priming takes place as a consequence of pollution of oil or the like in the
boiler water ( is normally seen as a brown layer in the water gauge glasses),
the impurities are blown out through the scum valve ( see paragraph about
boiling out ).
3.10 Should the firing fail, for some reason, during a heavy steam demand
period, then the steam outlet valve is to be closed immediately, and the
feed pump is to kept in service until a normal water level is reached.
3.11 If priming takes place because of a sudden pressure drop in the pipe, the
firing to be reduced, the feeding increased and if necessary the steam
outlet to be reduce, too.
5
Auxiliary Boiler
4.3 If part of the heating surface has been glowing or the boiler shows
recognizable deformations the supervising authorities must be informed,
and the boiler is not to be used until approval from these authorities is
available.
4.4 When stopping the service, so much feed water to be filled on that a
suitable water level is present at next firing ( between lower and normal
water level ).
6
Auxiliary Boiler
5.3 Once a day mud is blown from the boiler through the bottom blow–off valve
until clear water is coming.
5.4 If the oil burner is functioning correctly and the combustion is complete the
soot deposit on the tubes will be minimal, but in practice it can hardly be
avoided that soot will deposit in the course of time, I. e. due to the starting
periods of the oil burner. Attached soot deposits can be removed by water
washing with a 10 percent soda solution through the inlet door in the
uptake, drain pipe at the bottom of the fire box is available.
5.5 Cleaning of exhaust gas fired section outside the tubes are to be cleaned
by boiling out, possible by using scraper and brush.
5.6 Inside the tubes can be cleaned for attached soot deposits by washing
with water with a 10 percent soda solution through the inlet door of the
uptake, drain pipe at the bottom of the boiler is available.
The cleaning can possibly be mode by brushes mounted in chains.
7
Auxiliary Boiler
8
Auxiliary Boiler
6. Boiling out
6.2 The boiler is slowly brought on working pressure and kept on this pressure
in abt. 6-8 hours with closed main stop valve, after which fat and other
impurities should be boiled out of the interior surfaces of the boiler.
6.3 Then to be skimmed of ( through the scum valve ), However, it must be
seen that before the water level is 20-30 mm above the scum funnel. If the
boiler is equipped with automatic water level control it may be necessary to
close for this unit during the skimming.
6.4 After the boiling out the burner is switched off, and after abt.1 quarter
the bottom blow-off valve and the air valve at the boiler top is to be opened,
and all the water is to be blown out of the boiler.
Then the boiler is washed and brushed inside, and the bottom blow-off
valve is examined in such a way that possible oxide scales and welding
pearls, which have been collected there, can be removed ( if necessary the
bottom blow-off valve is to be dismounted ).
The hand-holes in the bottom of the boiler is to be opened and the boiler
cleaned.
6.5 Treated, softened water to be added to a little below normal water level
when the bottom valve and hand-holes have been closed.
6.6 If the boiler shows a tendency to priming it is recommended to carry out an
boiling out. Besides, it is recommended to carry out another boiling out after
a time of operation of 2 to 3 months with a subsequent inside cleaning and
inspection.
9
Auxiliary Boiler
NOTICE!
Estimate the pH value from alkalinity tends to give pH readings
varying with silica, Ca, Mg, and other salt contents of boiler
water and dhhence iis not necessarily
il ddeemed d appropriate
i : resort
to this method only as a means to obtain a rough guide
(alkalinity serves merely as an auxiliary means in determining
the pH level). Also, be sure to control pH to the target value
while, on the other hand, Keeping alkalinity at the minimum
necessary level. Limiting the P alkalinity to within a certain
range would make it possible to inhibit the alkali corrosion even
if boiler water concentration should take place on the heating
surface, etc.
10
Auxiliary Boiler
** Note **
A) A new pin tube element should be replaced as soon as possible.
B) The boiler should not be operated with more than one plugging tube.
C) If flue gas temperature exceeds 450℃ the burner must be stopped or
at low load.
11
Auxiliary Boiler
The work procedures for these preservation are described in the following:
12
Auxiliary Boiler
** The boiler shall be completely drained and refilled with boiler feed water
before re-operation.
13
SAFETY VALVE
INSTALLATION OPERATION
AND MAINTENANCE INSTRUCTION
SAFETY VALVE
TABLE OF CONTENTS
PAGE
1. Design/Construction -------------------------- 3
3. Installation -------------------------- 8
5. Adjustment -------------------------- 11
8. Reassembly -------------------------- 15
2
SAFETY VALVE
1. DESIGN / CONSTRUCTION
Full Bore Type is provided that Seat Opening Diameter (SOD) is not less
than 1.15 times the throat Opening Diameter(TOD), and that the steam
passage area of the seat when opened is not less than 1.05 times of the
throat opening area, and that the area of the valve inlet and the connection
nozzle are not less than 1.7 times of the throat opening area.
For easy access to resume normal seating face. if need due to failure of its
trueness, the most important characteristic of Flat Seat Nozzle Valve is the
ease with which seating surface can be reconditioned the slight deviation
from the specific angles can lead leakage and faulty operation.
All important part are thermally balanced and precisely machined, thus
assuring accurate alignment regardless of temperature variation.
For reinforcement of seating faces both on disc and nozzle seat to insure
their trueness from violent and rapid shout down force during operating,
3
SAFETY VALVE
2) Nozzle seat
As the nozzle seat is fully and tightly screwed up into the main body
keeping seating face same contour parallel, it will not come out of the
position and any deviation from disc contacting center.
Also, with a view to avoid any malfunction, leaks, or other problems which
may be caused by stress from the outlet piping or by thermal strains, the
seat surface is designed to occupy a position at the center of the body
cylinder and separated as far as possible from the contact position with
body.
Since the fluid channel from the throat to the valve seat is the most
important part determining the performance of the valve, a logical Shape is
provided so that there will be no interruption in the fluid expansion.
4
SAFETY VALVE
The area expansion due to a small amount of fluid leakage just before the
blow-off produces pressure enough to lift the disc. this force causes a quick
popping action of the valve. The ring adjusts the simmer of the fluid.
1.3 Body
The body maintains tightness with its precise finishing and its stout
construction ensures safety against thermal stress due to the rapid variation
in the temperature of the fluid to be blown off as well as securing it against
the reaction strength resulting from a large amount of fluid blown off.
1.4 Bonnet
Standard construction of bonnet includes closed one to protect the internal
spring and support the adjusting screw.
On model SSRF open and yoke bonnet can be provided to ensure safety
against
i thermal
h l stress d
due to rapid
id variation
i i iin the
h temperature off the
h
discharging flow during blowing off.
5
SAFETY VALVE
2. OPERATING CYCLE
All of safety-relief valves are of the direct spring loaded construction. The
operating mechanism of each type is as follows:
Should the pressure upstream of the valve rise abnormally and reach near
to the set pressure, it cause the balanced spring to push upward and the
valve disc be slightly lifted up to make an initial opening. Steam or gas
gushing out of this initial opening will be guided by the properly adjusted
lower ring to exert dynamic pressures on the valve disc and the valve disc
will be lifted quickly, the valve will start to discharge.
I case off the
In th Full
F ll Bore
B Type
T Valve.
V l operating
ti characteristic
h t i ti off which
hi h iis
controlled by the ring, fluid discharged by the initial blowing-out will be
deflected in a downward direction through upper ring and this deflection as
well as pressure generated between two ring are exerted on the face of the
valve disc to lift it to a higher position.
As the Low-Lift Type Valve is not provided with an upper ring, the fluid is
deflected through a chamber formed by the lower face of the valve disc and
the lower ring. The valve disc is lifted by static and dynamic pressure.
2.1 when inner pressure is lower than set pressure, the valve disc keeps the
condition of full close due to differential power between the fluid pressure
and the condition of full close due to differential power between the fluid
pressure and the counter-pressure by the adjusted spring
6
SAFETY VALVE
2.4 Re-seating
Re-seating will be duly obtained at the adjusted ring mechanism after
enhancement of blow-off.
7
SAFETY VALVE
3. INSTALLATION
3.1 Storage and Conveyance
Safety-relief valve are often off hand at the job site several months before
they are actually installed. Unless they are properly stored and protected
their performance may be affected deadly. Roughness in handling may
damage valve appearance sharp, worst to crack, or cause misalignment of
the valve part. Furthermore carrying by pulling up the lever may cause
change of the spring set pressure and alignment of the stem.
It is essential that the boiler, pressure vessel, valve inlet, and all
connections should be cleaned thoroughly before the valve is mounted.
8
SAFETY VALVE
2) Discharge piping should be so designed that the weight of the piping will at
no time be taken up by the valve body.
A sufficient flexibility to the discharge piping is also essential to avoid strain
on the valve caused by thermal pipe expansion.
9
SAFETY VALVE
4.1 Cautions
The test gag can not be mounted on the ordinary type caps. Therefore, the
caps should be replaced with those made for the purpose.
In case of pressure test for pressure vessels without using test gag, test
them without the safety valves for safety of it.
Removed valve should be covered at the flange parts against intrusion of
dusts, etc.
Replace with a plug and gasket in case of closed top (or take off when
open top) after the test, otherwise the valve will not operate thereby creating
a dangerous situation.
10
SAFETY VALVE
5. ADJUSTMENT
Consideration of service pressure characteristic(differential between
operating and set pressure)
In order to avoid unsatisfactory operation of safety relief valves in normal
processing service. the operating pressure of the system should not exceed
90% of the set pressure. in the pump and compressor delivery line,
however, the difference between the set pressure and the operating
pressure should be made large on account of the pulsation attributable to
the pump delivery pressure is a better method.
Before re-adjustment, remove a Pb seal to cap and set screws which is
sealed to prevent arbitrary adjustment by an incompetent and visual check
of any external changes of set pressure or blowdown pressure.
11
SAFETY VALVE
Take off cap, loosen lock nut and turn down the adjusting screw to the
right(clockwise viewing from above) to raise set pressure and turn up the
left (anti-clockwise viewing from above) to lower the set pressure.
At the readjustment, be sure to lower the pressure of the system at below
90% of the set pressure.
After completion of re-adjustment, screw up the adjusting screw with lock
nut.
12
SAFETY VALVE
2) Chattering
This is a rapid reciprocating variations in valve lift during which the disc
repeatedly contacts the seat. It is because popping power is weak. In this
case, bring up the lower ring (closer to the bottom face of the disc but never
contact each other)
3) Hunting
This is the states where the disc repeats violent vertical motion during
operation as if it beat the seat violently. This is often caused when there is
much flow restriction in the piping connected with inlet and discharge side
of the safety valve or when blowdown is excessively too short, in this case,
open the gland cock or needle valve or bring down the upper ring to
increase blowdown.
If hunting is not ceased despite the above adjustment, rechecking of the
piping is necessary.
KANGRIM HEAVY INDUSTRIES CO., LTD.
13
SAFETY VALVE
7.3 Washing
Carefully wash the valve seat and valve disc with cleaning oil or liquid after
lapping to make them completely free from lapping compound.
7.4 Inspection of lapped surfaces
Inspection of lapped surface is extremely difficult. Try the following method:
Lighten the lapped surface. If the brightness is even all over the surface,
the lapping is complete. If any shady portion is present, the lapping is
incomplete.
14
SAFETY VALVE
8. REASSEMBLY
Reassembly will be made following the reverse order of disassembly.
Especially the following attention should be paid:
1) Care should be taken not to damage or soil the lapped surfaces of valve
disc and valve seat.
2) Properly center the tip end of the valve spindle on the valve disc.
3) Evenly and alternately lock up nuts to tighten the bonnet or yoke bolts.
15
Operating Instructions
Deltabar S FMD76/77/78, PMD70/75
Differential pressure measurement
BA00270P/00/EN/15.13
71204581
valid from Software version:
02.11.zz
Overview documentation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
Overview documentation
Deltabar S Technical Information TI00382P Technical data The documentation is available on the Internet.
4...20 mA HART → See: www.endress.com → Download
Operating Instructions BA00274P – Examples of configuration for – The documentation can be found on the
pressure, level and flow supplied documentation CD.
measurement – The documentation is also available via the
– Description of parameters Internet. → See: www.endress.com
– Trouble-shooting
– Appendix: Illustration of menu
Brief Operating Instructions KA01018P – Installation – The documentation is supplied with the
– Wiring device.
– Operation on-site – The documentation can be found on the
– Commissioning supplied documentation CD.
– Description of Quick Setup menus – The documentation is also available via the
Internet. → See: www.endress.com
2 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Table of contents
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 4 8.2 Response of outputs to errors . . . . . . . . . . . . . . . . . 72
8.3 Confirming messages . . . . . . . . . . . . . . . . . . . . . . . 74
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
8.4 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
1.2 Installation, commissioning and operation . . . . . . . . 4
8.5 Repair of Ex-certified devices . . . . . . . . . . . . . . . . . 75
1.3 Operational safety and process safety . . . . . . . . . . . . 4
8.6 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
1.4 Notes on safety conventions and icons . . . . . . . . . . . 5
8.7 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
8.8 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
2 Identification . . . . . . . . . . . . . . . . . . . . 6 8.9 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 9 Technical data . . . . . . . . . . . . . . . . . . . 80
2.3 CE mark, declaration of conformity . . . . . . . . . . . . . 9
2.4 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 9
10 Appendix . . . . . . . . . . . . . . . . . . . . . . . 80
3 Installation . . . . . . . . . . . . . . . . . . . . . 10 10.1 Operating menu for on-site display, FieldCare and HART
handheld terminal . . . . . . . . . . . . . . . . . . . . . . . . . 80
3.1 Incoming acceptance and storage . . . . . . . . . . . . . . 10
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 10
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
3.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . 10
3.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 22
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 23
4.1 Connecting the device . . . . . . . . . . . . . . . . . . . . . . 23
4.2 Connecting the measuring unit . . . . . . . . . . . . . . . 25
4.3 Potential matching . . . . . . . . . . . . . . . . . . . . . . . . 27
4.4 Overvoltage protection (optional) . . . . . . . . . . . . . . 27
4.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 27
5 Operation . . . . . . . . . . . . . . . . . . . . . . 28
5.1 On-site display (optional) . . . . . . . . . . . . . . . . . . . . 28
5.2 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3 On-site operation –
on-site display not connected . . . . . . . . . . . . . . . . . 33
5.4 On-site operation –
on-site display connected . . . . . . . . . . . . . . . . . . . . 37
5.5 HistoROM®/M-DAT (optional) . . . . . . . . . . . . . . 39
5.6 Operation via SFX100 . . . . . . . . . . . . . . . . . . . . . . 43
5.7 FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.8 Locking/unlocking operation . . . . . . . . . . . . . . . . . 44
5.9 Factory setting (reset) . . . . . . . . . . . . . . . . . . . . . . 45
6 Commissioning. . . . . . . . . . . . . . . . . . 47
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.2 Selecting language and measuring mode . . . . . . . . 47
6.3 Position adjustment . . . . . . . . . . . . . . . . . . . . . . . . 48
6.4 Flow measurement . . . . . . . . . . . . . . . . . . . . . . . . 49
6.5 Level measurement . . . . . . . . . . . . . . . . . . . . . . . . 52
6.6 Differential pressure measurement . . . . . . . . . . . . . 59
7 Maintenance. . . . . . . . . . . . . . . . . . . . 62
7.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8 Trouble-shooting . . . . . . . . . . . . . . . . 63
8.1 Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Endress+Hauser 3
Safety instructions Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
1 Safety instructions
4 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Safety instructions
Safety conventions
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal
injury, a safety hazard or destruction of the instrument.
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal
injury or incorrect functioning of the instrument.
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect
operation or may lead to an instrument response which is not planned.
0
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its nameplate, it can be installed in an explosion
hazardous area or a non-explosion hazardous area, according to the approval.
Explosion hazardous area
% Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied.
&
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied
or supplied.
)
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of
an earth grounding system.
*
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the
equipment.
+
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or
equipotential line according to national or company practice.
Safety instruction
For safety instructions refer to the manual for the appropriate instrument version.
Endress+Hauser 5
Identification Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
2 Identification
2.1.1 Nameplate
! Note!
• The MWP (maximum working pressure) is specified on the nameplate. This value refers to a
reference temperature of 20°C (68°F) or 100°F for ANSI flanges.
• The pressure values permitted at higher temperatures can be found in the following standards:
– EN 1092-1: 2001 Tab. 18 1)
– ASME B 16.5a – 1998 Tab. 2-2.2 F316
– ASME B 16.5a – 1998 Tab. 2.3.8 N10276
– JIS B 2220
• For PMD70 and PMD75, the MWP applies for the temperature ranges specified in the Technical
Information TI00382P in the "Ambient temperature range" and "Process temperature limits"
sections.
• The test pressure corresponds to the over pressure limit (OPL) of the device = MWP x 1.5.
• The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The
abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring
device.
1) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO
in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
R1 55
1
Order Code: 2
4
Ser.-No.: 3 6
23,5
MWP 5 Span 7
8 15
14
2,5
9 U= 11
Mat. 10
12 13
2,1 -0,1
26
P01-XMX7Xxxx-18-xx-xx-xx-000
Fig. 1: Nameplate
1 Device name
2 Order code
See the specifications on the order confirmation for the meanings of the individual letters and digits.
3 Serial number
4 Degree of protection
5 MWP (Maximum working pressure)
6 Symbol: Note: pay particular attention to the data in the "Technical Information"!
7 Minimum/maximum span
8 Nominal measuring range
9 Electronic version (output signal)
10 Wetted materials
11 Supply voltage
12 GL-symbol for GL marine certificate (optional)
13 SIL-symbol for devices with SIL3/IEC 61508 Declaration of conformity (optional)
14 Approval ID and ID numbers
15 Address of manufacturer
6 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Identification
Devices for use in hazardous areas are fitted with an additional nameplate.
1
2
4 5 Dat.: 6
P01-xMD7xxxx-18-xx-xx-xx-002
Devices suitable for oxygen applications are fitted with an additional nameplate.
Bei Sauerstoffeinsatz/
for oxygen service
Pmax 1 3
Tmax 2
P01-xxxxxxxx-18-xx-xx-xx-000
Endress+Hauser 7
Identification Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
13
1 19
2 20
Order Code: 3 21
Ser.-No.: 4
MWP 5 22
6
Span 7
8 23
9 U= 10
Mat.
24 - 25
11
12 Dat.: 26
P01-XMX7Xxxx-18-xx-xx-xx-001
Fig. 4: Nameplate
1 Device name
2 Address of manufacturer
3 Order code
See the specifications on the order confirmation for the meanings of the individual letters and digits.
4 Serial number
5 MWP (Maximum working pressure)
6 Symbol: Note: pay particular attention to the data in the "Technical Information"!
7 Minimum/Maximum span
8 Nominal measuring range
9 Electronic version (output signal)
10 Supply voltage
11 Wetted materials
12 Degree of protection
Optional:
13 Approval ID and ID numbers
14 3A-symbol
15 CSA-symbol
16 FM-symbol
17 SIL-symbol for devices with SIL3/IEC 61508 Declaration of conformity
18 GL-symbol for GL marine certificate
19 EC type examination certificate
20 Type of protection
21 Approval number for WHG overspill protection
22 Temperature operating range for devices for use in hazardous areas
23 Electrical data for devices for use in hazardous areas
24 Safety Instructions number
25 Safety Instructions index
26 Device manufacture data
27 Maximum temperature for devices suitable for oxygen applications
28 Maximum pressure for devices suitable for oxygen applications
8 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Identification
Endress+Hauser 9
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
3 Installation
3.1.2 Transport
" Caution!
Follow the safety instructions and transport conditions for devices of more than 18 kg (39.69 lbs).
Transport the measuring device to the measuring point in its original packaging or at the process
connection.
3.1.3 Storage
The device must be stored in a dry, clean area and protected against damage from impact
(EN 837-2).
Storage temperature range:
• –40 to +90°C (–40 to +194°F)
• On-site display: –40 to +85°C (–40 to +185°F)
• Separate housing: –40 to +60°C (–40 to +140°F)
3.2.1 Dimensions
→ For dimensions, please refer to the Technical Information for Deltabar S TI00382P, "Mechanical
construction" section. → ä 2 "Overview documentation.
10 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Installation
! Note!
For more information about flow measurement with the Deltabar S differential pressure transmitter
• Deltabar S with orifice plate (TI00422P, Deltatop DO6x)
• Deltabar S with Pitot tube (TI00425P, Deltatop DP6x)
➁
➂
+ – ➃
P01-PMD75xxx-11-xx-xx-xx-000
• Mount the Deltabar S above the measuring point so that the condensate can run off into the
process piping.
➁
➂ ➂
➃
+ –
➄ ➄
➅ ➅
➆
P01-PMD75xxx-11-xx-xx-xx-001
Endress+Hauser 11
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
➁ ➁
+ ➂ –
➃ ➃
➄ ➄
➅
P01-PMD75xxx-11-xx-xx-xx-002
• Mount the Deltabar S below the measuring point so that the impulse piping is always filled with
liquid and gas bubbles can run back into the process piping.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
patm
min. + patm ➀
➃ ➁
➄
➂
P01-PMD75xxx-11-xx-xx-xx-003
Fig. 8: Measuring layout for level measurement in open containers with PMD75
1 The negative side is open to atmospheric pressure
2 Deltabar S, here PMD75
3 Shut-off valve
4 Separator
5 Drain valve
• Mount the Deltabar S below the lower measuring connection so that the impulse piping is always
filled with liquid.
• The negative side is open to atmospheric pressure.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
12 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Installation
patm
min.
+ ➀
–
patm
➁
P01-FMD76xxx-11-xx-xx-xx-003
Fig. 9: Measuring layout for level measurement in open containers with FMD76
1 Deltabar S, here FMD76
2 The negative side is open to atmospheric pressure
• Mount the Deltabar S direct on the container. → ä 19, Section 3.3.5 "Seal for flange mounting".
• The negative side is open to atmospheric pressure.
–➀
max.
min. ➀
+
➁
➂ ➂
➃ ➃
➄
P01-PMD75xxx-11-xx-xx-xx-004
Fig. 10: Measuring layout for level measurement in a closed container with PMD75
1 Shut-off valves
2 Deltabar S, PMD75
3 Separator
4 Drain valves
5 Three-valve manifold
• Mount the Deltabar S below the lower measuring connection so that the impulse piping is always
filled with liquid.
• Always connect the impulse piping of negative side above the maximum level.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
Endress+Hauser 13
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
➀
–
max.
min.
➁
+ ➂
➃
P01-FMD76xxx-11-xx-xx-xx-004
Fig. 11: Measuring layout for level measurement in a closed container with FMD76
1 Shut-off valve
2 Separator
3 Drain valve
4 Deltabar S, here FMD76
• Mount the Deltabar S direct on the container. → ä 19, Section 3.3.5 "Seal for flange mounting".
• Always connect the impulse piping of negative side above the maximum level.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
–
max.
➀
+
min.
P01-FMD78xxx-11-xx-xx-xx-000
Fig. 12: Measuring layout for level measurement in a closed container with FMD78
1 Deltabar S, here FMD78
• Mount the Deltabar S below the lower diaphragm seal. → ä 17, Section 3.3.4 "Installation
instructions for devices with diaphragm seals (FMD78)".
• The ambient temperature should be the same for both capillaries.
! Note!
Level measurement is only ensured between the upper edge of the lower diaphragm seal and the
lower edge of the upper diaphragm seal.
14 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Installation
Level measurement in a closed container with superimposed steam with PMD 70/
PMD75
– ➀
max.
➁
min. ➁
+
➂
➃ ➃
➄ ➄
➅
P01-PMD75xxx-11-xx-xx-xx-005
Fig. 13: Measuring layout for level measurement in a container with superimposed steam with PMD75
1 Condensate trap
2 Shut-off valves
3 Deltabar S, here PMD75
4 Separator
5 Drain valves
6 Three-valve manifold
• Mount the Deltabar S below the lower measuring connection so that the impulse piping is always
filled with liquid.
• Always connect the impulse piping of negative side above the maximum level.
• A condensate trap ensures constant pressure on the negative side.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
Level measurement in a closed container with superimposed steam with FMD 76/
FMD77
– ➀
max.
➁
min.
➂
+ ➃
➄
P01-FMD76xxx-11-xx-xx-xx-005
Fig. 14: Measuring layout for level measurement in a container with superimposed steam with FMD76
1 Condensate trap
2 Shut-off valve
3 Separator
4 Drain valve
5 Deltabar S, here FMD76
Endress+Hauser 15
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
• Mount the Deltabar S direct on the container. → ä 19, Section 3.3.5 "Seal for flange mounting".
• Always connect the impulse piping of negative side above the maximum level.
• A condensate trap ensures constant pressure on the negative side.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
➁
+
➂ ➂
➃
P01-PMD75xxx-11-xx-xx-xx-006
Fig. 15: Measuring layout for differential pressure measurement in gases and steam with PMD75
1 Deltabar S, here PMD75
2 Three-valve manifold
3 Shut-off valves
4 e.g. filter
• Mount the Deltabar S above the measuring point so that the condensate can run off into the
process piping.
➀
➁ ➁
+ –
➂
➃ ➃
➄ ➄
➅
P01-PMD75xxx-11-xx-xx-xx-007
Fig. 16: Measuring layout for differential pressure measurement in liquids with PMD75
1 e.g. filter
2 Shut-off valves
3 Deltabar S, here PMD75
4 Separator
5 Drain valves
6 Three-valve manifold
• Mount the Deltabar S below the measuring point so that the impulse piping is always filled with
liquid and gas bubbles can run back into the process piping.
• When measuring in media with solid parts, such as dirty liquids, installing separators and drain
valves is useful for capturing and removing sediment.
16 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Installation
➀
➁ ➁
+ –
➂
➃
P01-FMD78xxx-11-xx-xx-xx-000
Fig. 17: Measuring layout for differential pressure measurement in gases, steam and liquids with FMD78
1 Diaphragm seal
2 Capillary
3 e.g. filter
4 Deltabar S, here FMD78
• Mount the diaphragm seal with capillaries at the top or on the side on the piping.
• For vacuum applications: mount the Deltabar S below the measuring point. → ä 17,
Section 3.3.4 "Installation instructions for devices with diaphragm seals (FMD78)", "Vacuum
application" part.
• The ambient temperature should be the same for both capillaries.
! Note!
• The diaphragm seal, together with the pressure transmitter, forms a closed, calibrated system,
which is filled through openings in the diaphragm seal and in the measurement system of the
pressure transmitter. This openings are sealed and must not be opened.
• Do not clean or touch diaphragm seals with hard or pointed objects.
• Do not remove the protection of the process isolating diaphragm until shortly before installation.
• When using a mounting bracket, sufficient strain relief must be ensured for the capillaries in order
to prevent the capillary bending down (bending radius ≥ 100 mm (3.94 in)).
• Please note that the hydrostatic pressure of the liquid columns in the capillaries can cause zero
point shift. The zero point shift can be corrected. → ä 48, Section 6.3 "Position adjustment".
• Please note the application limits of the diaphragm seal filling oil as detailed in the Technical
Information for Deltabar S TI00382P, Section "Planning instructions for diaphragm seal systems".
→ → ä 2 "Overview documentation".
In order to obtain more precise measurement results and to avoid a defect in the device, mount the
capillaries as follows:
• vibration-free (in order to avoid additional pressure fluctuations)
• not in the vicinity of heating or cooling lines
• insulate if the ambient temperature is below ore above the reference temperature
• with a bending radius of ≥100 mm (3.94 in).
• The ambient temperature and length of both capillaries should be the same when using two-sided
diaphragm seal systems.
• Two diaphragm seals which are the same (e.g. with regard to diameter, material, etc.) should
always be used for the negative and positive side (standard delivery).
Endress+Hauser 17
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
–
≥ 100 mm
+ –
P01-FMD78xxx-11-xx-xx-xx-005
Fig. 18: Mounting Deltabar S, FMD78 with diaphragm seals and capillary, recommended mounting for vacuum
applications: mount pressure transmitter below the lowest diaphragm seal!
12.0
Low temperature oil
10.0
Height difference H1 [m]
Vegetable oil
8.0
– Silicone oil
6.0
High temperature
– + oil
4.0
+ –
H1 Inert oil
2.0
+
0.0
50 100 200 300 400 500 600 700 800 900 1000
Pressure, diaphragm seal positive side [mbarabs]
P01-FMD7xxxx-11-xx-xx-xx-001 P01-FMD7xxxx-05-xx-xx-xx-002
Fig. 19: Installation above the lower Fig. 20: Diagram of maximum installation height above the lower
diaphragm seal diaphragm seal for vacuum applications dependent on
the pressure at the diaphragm seal on the positive side
18 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Installation
➀ ➁
P01-FMD7xxxx-11-xx-xx-xx-002
# Warning!
The seal is not allowed to press on the process isolating diaphragm as this could affect the
measurement result.
TA λ ≤ 0.04 W
m•K
TP
P01-FMD77xxxx-11-xx-xx-xx-000
FMD77
Endress+Hauser 19
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
When using a valve block, the block's dimensions must be taken into account.
37.5
➀
12
135
74
12 74
4 6
10
P01-xMD7xxxx-11-xx-xx-xx-008
20 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Installation
5
7
4
1 r ³ 120 mm
P01-xMD7xxxx-11-xx-xx-xx-011
Endress+Hauser 21
Installation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
max. 380°
P01-xMD7xxxx-11-xx-xx-xx-001
! Note!
When closing the housing cover, please ensure that the thread of the cover and housing are free
from dirt, e.g. sand.If you feel any resistance when closing the cover, check the thread on both again
to ensure that they are free from dirt.
+–
P01-PMD75xxx-17-xx-xx-xx-000
The covers for the terminal and electronics compartment are hooked into the casing and closed with
a screw. These screws should be finger-tightened (2 Nm (1.48 lbf ft)) to the stop to ensure that the
covers sit tightly.
22 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Wiring
4 Wiring
# Warning!
Risk of electric shock and/or explosion in hazardous areas! In a wet environment, do not open the
cover if voltage is present.
! Note!
• When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
• Devices with integrated overvoltage protection must be earthed.
• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
• The supply voltage must match the supply voltage on the nameplate. (→ ä 6, Section 2.1.1
"Nameplate".)
• Switch off the supply voltage before connecting the device.
• Remove housing cover of the terminal compartment.
• Guide cable through the gland. Preferably use twisted, screened two-wire cable.
• Connect device in accordance with the following diagram.
• Screw down housing cover.
• Switch on supply voltage.
➀ ➅ 10.5 V DC
➆ 11.5 V DC
4…20 mA
Test
Test
➂ ➄
➇
4... 20mA Test
➃
P01-xMx7xxxx-04-xx-xx-xx-001
Endress+Hauser 23
Wiring Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
+ – 7
– 8 6
1
2 5
Han7D 3 4
+ –
P01-xxx7xxxx-04-xx-xx-xx-001
Fig. 28: Left: electrical connection for devices with Harting plug Han7D
Right: view of the plug connector at the device
PIN Meaning
1 Signal +
4 3 –
2 Not assigned
3 Signal –
1 + 2 nc
4 Earth
A0011175
24 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Wiring
! Note!
• All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all devices approved for use in
explosion hazardous areas.
• When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
Electronic version Jumper for 4...20 mA test signal in Jumper for 4...20 mA test signal in
"Test" position (Delivery status) "Non-Test" position
Endress+Hauser 25
Wiring Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
4.2.3 Load
➀ RLmax ➁ RLmax
[Ω] [Ω]
Test 1500 Test
1456
1282 1239
847 804
➃ ➃
413
➂ 369
➂
10.5 20 30 40 45 U 11.5 20 30 40 45 U
[V] [V]
U – 10.5 V U – 11.5 V
RLmax ≤ RLmax ≤
23 mA 23 mA
P01-xMD7xxxx-05-xx-xx-xx-005
Fig. 29: Load diagram, observe the position of the jumper and the explosion protection (→ ä 25, Section 4.2.1
"Taking 4...20 mA test signal".)
1 Jumper for 4...20 mA test signal inserted in "Non-Test" position
2 Jumper for 4...20 mA test signal inserted in "Test" position
3 Supply voltage 10.5 (11.5)...30 V DC for 1/2 G, 1GD, 1/2 GD, FM IS, CSA IS, IECEx ia, NEPSI Ex ia
4 Supply voltage 10.5 (11.5)...45 V DC for device for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d,
3 G Ex nA, FM XP, FM DIP, FM NI, CSA XP, CSA Dust Ex, NEPSI Ex d
RLmaxMaximum load resistance
U Supply voltage
! Note!
When operating via a handheld terminal or via PC with an operating program, a minimum
communication resistance of 250 Ω must exist within the loop.
26 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Wiring
! Note!
For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional
accessory:
• Cerabar S PMC71, PMP7x
• Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70
# Warning!
Devices with integrated overvoltage protection must be earthed.
Endress+Hauser 27
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
5 Operation
Feature 20 "Output; operation" in the order code provides you with information on the operating
options available to you.
A 4...20 mA HART; external operation, LCD Via on-site display and 3 keys on the exterior of the device
B 4...20 mA HART; internal operation, LCD Via on-site display and 3 keys on the inside of the device
C 4...20 mA; internal operation Without on-site display, 3 keys on the inside of the device
Header line
Main line
Unit
Information
line
– + E Symbol
Bargraph
Editing modes
Operating keys
Selection
options
Value that
can be edited
28 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
The following table illustrates the symbols that can appear on the on-site display. Four symbols can
occur at one time.
Symbol Meaning
Alarm symbol
– Symbol flashing: warning, device continues measuring.
– Symbol permanently lit: error, device does not continue measuring.
Note: The alarm symbol may overlie the tendency symbol.
Lock symbol
The operation of the device is locked. Unlock device, → Section 5.8.
Communication symbol
Data transfer via communication
Note: The alarm symbol may overlie the communication symbol.
Endress+Hauser 29
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
➃➄
t ➅
on
➀
➀ ➁
off
➂
1 2
PC
P01-xxxxxxxx-19-xx-xx-xx-056 P01-xxxxxxxx-19-xx-xx-xx-104
Fig. 30: Operating keys, external Fig. 31: Operating keys, internal
1 Operating keys on the exterior of the device under 1 Operating keys
the protective flap 2 Slot for optional display
3 Slot for optional HistoROM®/M-DAT
4 DIP-switch for locking/unlocking measured-value-
relevant parameters
5 DIP-switch for damping on/off
6 Green LED to indicate value being accepted
30 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
Position adjustment
Reset all parameters. The reset via operating keys corresponds to the software reset code
and and 7864.
Copy the configuration data from the optional HistoROM®/M-DAT module to the device.
and
Copy the configuration data from the device to the optional HistoROM®/M-DAT module.
and
Endress+Hauser 31
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
F – Confirm entry
– Jump to the next item
Contrast setting of on-site display: darker
O and F
Contrast setting of on-site display: brighter
S and F
ESC functions:
– Exit edit mode without saving the changed value.
– You are in a menu within a function group. The first time you press the keys
simultaneously, you go back a parameter within the function group. Each time you press
O and S the keys simultaneously after that, you go up a level in the menu.
– You are in a menu at a selection level. Each time you press the keys simultaneously, you
go up a level in the menu.
Note: The terms function group, level and selection level are explained in section 5.4.1,
page 37.
32 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
! Note!
• The operation must be unlocked. → ä 44, Section 5.8 "Locking/unlocking operation".
• The device is configured for the Pressure measuring mode as standard. You can switch measuring
modes by means of the MEASURING MODE parameter. → ä 47, Section 6.2 "Selecting
language and measuring mode".
• The pressure applied must be within the nominal pressure limits of the sensor. See information
on the nameplate.
Carry out position adjustment.1) Setting lower range value. Setting upper range value.
Pressure is present at device. Desired pressure for lower range Desired pressure for upper range
value is present at device. value is present at device.
↓ ↓ ↓
↓ ↓ ↓
Does the LED on the electronic insert Does the LED on the electronic insert Does the LED on the electronic insert
light up briefly? light up briefly? light up briefly?
↓ ↓ ↓ ↓ ↓ ↓
Applied pressure Applied pressure Applied pressure Applied pressure Applied pressure Applied pressure
for for position for for for for
position adjustment has lower range value lower range value upper range value upper range value
adjustment has not been has been has not been has been has not been
been accepted. accepted. accepted. accepted. accepted. accepted.
Observe the input Observe the input Observe the input
limits. limits. limits.
Endress+Hauser 33
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• The "-" and "+"- keys only have a function in the following cases:
– LEVEL SELECTION "Level Easy Pressure", CALIBRATION MODE "Wet"
– LEVEL SELECTION "Level Standard", LEVEL MODE "Linear",
CALIBRATION MODE "Wet"
The keys have no function in other settings.
• The device is configured for the Pressure measuring mode as standard. You can switch measuring
modes by means of the MEASURING MODE parameter. → ä 47, Section 6.2 "Selecting
language and measuring mode".
The following parameters are set to the following values in the factory:
– LEVEL SELECTION: Level Easy Pressure
– CALIBRATION MODE: Wet
– OUTPUT UNIT or LIN. MEASURAND: %
– EMPTY CALIB.: 0.0
– FULL CALIB.: 100.0.
– SET LRV: 0.0 (corresponds to 4 mA value)
– SET URV: 100.0 (corresponds to 20 mA value)
These parameters can only be modified by means of the on-site display or remote operation such
as the FieldCare.
• The operation must be unlocked. → ä 44, Section 5.8 "Locking/unlocking operation".
• The pressure applied must be within the nominal pressure limits of the sensor. See information
on the nameplate.
• → ä 52, Section 6.5 "Level measurement". For parameter description see Operating Instructions
BA00274P.
• LEVEL SELECTION, CALIBRATION MODE, LEVEL MODE, EMPTY CALIB., FULL CALIB, SET
LRV and SET URV are parameter names used for on-site display or remote operation such as
FieldCare for instance.
34 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
Carry out position adjustment.1) Setting lower pressure value. Setting upper pressure value.
Pressure is present at device. Desired pressure for lower pressure Desired pressure for upper pressure
value (EMPTY PRESSURE2)) is value (FULL PRESSURE1) is present
present at device. at device.
↓ ↓ ↓
Press "E"-key for 3 s. Press "–"-key for 3 s. Press "+"-key for 3 s.
↓ ↓ ↓
Does the LED on the electronic insert Does the LED on the electronic insert Does the LED on the electronic insert
light up briefly? light up briefly? light up briefly?
↓ ↓ ↓ ↓ ↓ ↓
Applied pressure Applied pressure The pressure The pressure The pressure The pressure
for for position present was saved present was not present was saved present was not
position adjustment has as the lower saved as the as the upper saved as the
adjustment has not been pressure value lower pressure pressure value upper pressure
been accepted. accepted. (EMPTY value. Observe (FULL value. Observe
Observe the input PRESSURE1) and the input limits. PRESSURE1) and the input limits.
limits. assigned to the assigned to the
lower level value upper level value
(EMPTY (FULL CALIB.1).
CALIB.1).
Endress+Hauser 35
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• The operation must be unlocked. → ä 44, Section 5.8 "Locking/unlocking operation".
• The device is configured for the Pressure measuring mode as standard. You can switch measuring
modes by means of the MEASURING MODE parameter. → ä 47, Section 6.2 "Selecting
language and measuring mode".
• The "-"- key does not have any function.
• The pressure applied must be within the nominal pressure limits of the sensor. See information
on the nameplate.
• → ä 51, Section 6.4.3 "Quick Setup menu for the Flow measuring mode" and Operating
Instructions BA00274P, parameter descriptions MAX. PRESS. FLOW, MAX. FLOW, SET LRV –
Flow and LINEAR/SQROOT.
↓ ↓
↓ ↓
Does the LED on the electronic insert Does the LED on the electronic insert
light up briefly? light up briefly?
Yes No Yes No
↓ ↓ ↓ ↓
36 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
Measured value
GROUP SELECTION
➁
➀ SETTINGS DISPLAY
➂
➃ POS. INPUT VALUE
CALIB. OFFSET
P01-xxxxxxxx-19-xx-xx-xx-097
! Note!
The LANGUAGE and MEASURING MODE parameters are only displayed via the on-site display on
the 1st selection level. In the digital communication, the LANGUAGE parameter is displayed in the
DISPLAY group and the MEASURING MODE parameter is displayed in the QUICK SETUP menus
or in the BASIC SETUP function group. → See also Section 10.1 "Operating menu for on-site
display, FieldCare and HART handheld terminal".
Endress+Hauser 37
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
P01-xxxxxxxx-19-xx-xx-xx-017
P01-xxxxxxxx-19-xx-xx-xx-033
P01-xxxxxxxx-19-xx-xx-xx-034
P01-xxxxxxxx-19-xx-xx-xx-023
P01-xxxxxxxx-19-xx-xx-xx-027
P01-xxxxxxxx-19-xx-xx-xx-028
P01-xxxxxxxx-19-xx-xx-xx-029
P01-xxxxxxxx-19-xx-xx-xx-030
38 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
Use "E" to save the new value and exit the editing mode.
→ See next graphic.
P01-xxxxxxxx-19-xx-xx-xx-031
P01-xxxxxxxx-19-xx-xx-xx-032
P01-xxxxxxxx-19-xx-xx-xx-035
P01-xxxxxxxx-19-xx-xx-xx-036
Use "E" to assign the value (400 mbar) to the GET URV
parameter. The device confirms the calibration and jumps
back to the parameter, here GET URV (see next graphic).
P01-xxxxxxxx-19-xx-xx-xx-037
P01-xxxxxxxx-19-xx-xx-xx-035
# Warning!
Detach HistoROM®/M-DAT from the electronic insert or attach it to the insert in a deenergised
state only.
Endress+Hauser 39
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• The HistoROM®/M-DAT module may be retrofitted at any time (Order No.: 52027785).
• The HistoROM data and the data in the device are analysed once a HistoROM®/M-DAT is
attached to the electronic insert and power is reestablished to the device. During the analysis, the
messages "W702, HistoROM data not consistent" and "W706, Configuration in HistoROM and
device not identical" can occur. For measures, → ä 63, Section 8.1 "Messages."
➁
on
t
off
➀
1 2
PC
R
HART
250002271-–
FIELD COMMUNICATION PROTOCOL
HW-Version: 1
SW-Version: 2
P01-xxxxxxxx-19-xx-xx-xx-098
! Note!
The operation must be unlocked.
1. Disconnect device from supply voltage.
2. Attach the HistoROM®/M-DAT module to the electronic insert.
3. Reestablish supply voltage to the device.
4. Press "E" and "-"-keys (for at least 3 seconds) until the LED on the electronic insert lights up.
5. Wait approx. 20 seconds. Configuration data are loaded from the device to the HistoROM®/
M-DAT. The device is not restarted.
6. Disconnect device from the supply voltage again.
7. Detach memory module.
8. Reestablish supply voltage to the device.
40 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
! Note!
The operation must be unlocked.
1. Disconnect device from supply voltage.
2. Attach the HistoROM®/M-DAT module to the electronic insert. Configuration data from
another device are stored in the HistoROM®/M-DAT.
3. Reestablish supply voltage to the device.
4. Press "E" und "+"-keys (for at least 3 seconds) until the LED on the electronic insert lights up.
5. Wait approx. 20 seconds. All parameters except DEVICE SERIAL No, DEVICE DESIGN.,
CUST. TAG NUMBER, LONG TAG NUMBER, DESCRIPTION, BUS ADDRESS and the
parameters in the POSITION ADJUSTMENT and PROCESS CONNECTION group are loaded
into the device by HistoROM®/M-DAT. The device is restarted.
6. Before removing the HistoROM®/M-DAT again from the electronic insert, disconnect the
device from supply voltage.
! Note!
The operation must be unlocked.
1. Disconnect device from supply voltage.
2. Attach the HistoROM®/M-DAT module to the electronic insert.
3. Reestablish supply voltage to the device.
4. The DOWNLOAD SELECT. parameter setting has no influence on an upload from the device
into HistoROM.
(Menu path: (GROUP SELECTION →) OPERATING MENU → OPERATION)
5. Using the HistoROM CONTROL parameter select the option "Device → HistoROM" as the
data transfer direction.
(Menu path: GROUPSELECTION → OPERATING MENU → OPERATION)
6. Wait approx. 20 seconds. Configuration data are loaded from the device to the HistoROM®/
M-DAT. The device is not restarted.
7. Disconnect device from the supply voltage again.
8. Detach memory module.
9. Reestablish supply voltage to the device.
Endress+Hauser 41
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
The operation must be unlocked.
1. Disconnect device from supply voltage.
2. Attach the HistoROM®/M-DAT module to the electronic insert. Configuration data from
another device are stored in the HistoROM®/M-DAT.
3. Reestablish supply voltage to the device.
4. Use the DOWNLOAD SELECT parameter to select which parameters are to be overwritten
(Menu path: (GROUPS SELECTION →) OPERATING MENU → OPERATION).
42 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
5.7 FieldCare
FieldCare is an FDT-based system asset management tool from Endress+Hauser. With FieldCare,
you can configure all Endress+Hauser devices as well as devices from other manufacturers that
support the FDT standard. Hardware and software requirements you can find on the internet:
www.endress.com → select your country → Search: FieldCare → FieldCare → Technical Data.
FieldCare supports the following functions:
• Configuration of transmitters in online operation
• Loading and saving device data (upload/download)
• HistoROM®/M-DAT analysis
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA195 and the USB interface of a computer
• HART via Fieldgate FXA520
! Note!
• → ä 26, Section 4.2.6 "Connecting Commubox FXA195".
• Further information on the FieldCare can be found on the Internet (http://www.endress.com,
Download → Search for: FieldCare).
Endress+Hauser 43
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• If operation is locked by means of the DIP-switch, you can only unlock operation again by means
of the DIP-switch. If operation is locked by means of the on-site display or remote operation e.g.
FieldCare, you can only unlock operation again by means of the on-site display or remote
operation.
1) Parameters which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST can still be altered.
Damping [t]
➀
➁ ➂
on on
1 2
PC
1 2 1 2
off off
R
HART
250002271-–
HW-Version: 1
SW-Version: 2
– + E
P01-xxxxxxxx-19-xx-xx-xx-133
44 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Operation
Description
! Note!
Any customer-specific configuration carried out by the factory is not affected by a reset (customer-
specific configuration remains). If, after a reset, you wish the parameters to be reset to the factory
settings, please contact Endress+Hauser Service.
Endress+Hauser 45
Operation Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
46 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
6 Commissioning
# Warning!
• If a pressure smaller than the minimum permitted pressure is present at the device, the messages
"E120 Sensor low pressure" and "E727 Sensor pressure error - overrange" are output in
succession.
• If a pressure greater than the maximum permitted pressure is present at the device, the messages
"E115 Sensor overpressure" and "E727 Sensor pressure error - overrange" are output in
succession.
• Messages E727, E115 and E120 are "Error"-type messages and can be configured as a "Warning"
or an "Alarm". These messages are configured as "Warning" messages at the factory. This setting
prevents the current output from assuming the set alarm current value for applications (e.g.
cascade measurement) where the user is consciously aware of the fact that the sensor range can
be exceeded
• We recommend setting messages E727, E115 and E120 to "Alarm" in the following instances:
– The sensor range does not have to be exceeded for the measuring application.
– Position adjustment has to be carried out that has to correct a large measured error as a result
of the orientation of the device (e.g. devices with a diaphragm seal).
! Note!
The device is configured for the Pressure measuring mode as standard. The measuring range and
the unit in which the measured value is transmitted correspond to the specifications on the
nameplate.
Endress+Hauser 47
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
POS. ZERO ADJUST (685) Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure need not be known.
Example:
– MEASURED VALUE = 2.2 mbar (0,032 psi)
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
– The current value is also corrected.
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Factory setting:
0.0
POS. INPUT VALUE (563) Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure need not be known. To correct the pressure difference, you need a reference
measurement value (e. g. from a reference device).
Example:
– MEASURED VALUE = 0.5 mbar (0,0073 psi)
– For the POS. INPUT VALUE parameter, specify the desired set point for the
MEASURED VALUE, e.g. 2.0 mbar (0,029 psi).
(MEASURED VALUEnew = POS. INPUT VALUE)
– MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar (0,029 psi)
– The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
CALIB. OFFSET = MEASURED VALUEold – POS. INPUT VALUE,
here: CALIB. OFFSET = 0.5 mbar (0,0073 psi) – 2.0 mbar (0,029 psi) = – 1.5 mbar
(0,022 psi))
– The current value is also corrected.
Factory setting:
0.0
CALIB. OFFSET (319) Position adjustment – the pressure difference between zero (set point) and the measured
Entry pressure is known.
Example:
– MEASURED VALUE = 2.2 mbar (0,032 psi)
– Via the CALIB. OFFSET parameter, enter the value by which the MEASURED VALUE
should be corrected. To correct the MEASURED VALUE to 0.0 mbar, you must enter
the value 2.2 here.
(MEASURED VALUE new = MEASURED VALUEold – CALIB. OFFSET)
– MEASURED VALUE (after entry for calib. offset) = 0.0 mbar
– The current value is also corrected.
Factory setting:
0.0
48 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
! Note!
• The Deltabar S PMD70 or PMD75 is usually used for flow measurement.
• Before calibrating the Deltabar S, the impulse piping must be cleaned and filled with fluid. → See
the following table.
1 Close 3.
4 Vent device.
6 Set measuring point in operation. Fig. 35: Above: preferred installation for gases
Below: preferred installation for liquids
Close 3. Shut off positive side from
negative side. I Deltabar S, PMD70 or PMD75
II Three-valve manifold
Open 4. Connect negative side. Separator
1, 5 Drain valves
Now
2, 4 Inlet valves
– 11, 3, 51, 6 and 7 are closed.
3 Equalising valve
– 2 and 4 are open.
6, 7 Vent valves on Deltabar S
– A and B open (if present).
A, B Shut-off valves
7 Carry out pos. zero adjustment if the flow can be blocked off.
In this case, step 5 is not applicable.
→ ä 51, Section 6.4.3 and → ä 48, Section 6.3
Endress+Hauser 49
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• There is a Quick Setup menu for each of the measuring modes Pressure, Level and Flow which
guides you through the most important basic functions. With the setting in the MEASURING
MODE parameter, you specify which Quick Setup menu should be displayed. → See also
→ ä 47, Section 6.2 "Selecting language and measuring mode".
• For a detailed description of the parameters see the Operating Instructions BA00274P "Cerabar
S/Deltabar S/Deltapilot S, Description of device functions"
– Table 6, POSITION ADJUSTMENT
– Table 12, BASIC SETUP
– Table 17, EXTENDED SETUP
– Table 20, TOTALIZER SETUP.
→ See also → ä 2, section "Overview documentation".
• For flow measurement, select the "Flow" option by means of the MEASURING MODE parameter.
The operating menu is structured appropriately. → Section 10.1.
50 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
Measured value
1)
GROUP SELECTION
1) 1)
LANGUAGE MEASURING MODE QUICK SETUP OPERATING MENU
2)
MEASURING MODE
MAX FLOW
P01-xxxxxxxx-19-xx-xx-xx-067
Fig. 36: Quick Setup menu for the Flow measuring mode
MEASURING MODE
Select "Flow" option.
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in Due to orientation of the device, there may be a shift in
the measured value. You correct the MEASURED the measured value. You correct the MEASURED
VALUE via the POS. ZERO ADJUST parameter with the VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option, i. e. you assign the value 0.0 to the "Confirm" option, i. e. you assign the value 0.0 to the
pressure present. pressure present.
! Note!
For on-site operation, → ä 32, Section 5.2.3 "Function of the operating elements – on-site display
connected" and → ä 37, Section 5.4 "On-site operation – on-site display connected".
Endress+Hauser 51
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
Open container
! Note!
• The Deltabar S PMD70, PMD75, FMD76 and FMD77 are suitable for level measurement in an
open container.
• FMD76 and FMD77: the device is ready for calibration immediately after opening a shut-off valve
(may or may not be present).
• PMD70 and PMD75: before calibrating the device, the impulse piping must be cleaned and filled
with fluid. → See the following table.
3 Vent device. +
Open 6 briefly, then close it Fill device completely with 6
again. fluid and remove air. II I
52 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
Closed container
! Note!
• All Deltabar S versions are suitable for level measurement in closed containers.
• FMD76 and FMD77: the device is ready for calibration immediately after opening the shut-off
valves (may or may not be present).
• FMD78: the device is ready for calibration immediately.
• PMD70 and PMD75: before calibrating the device, the impulse piping must be cleaned and filled
with fluid. → See the following table.
Now 2 4
– 3, 6 and 7 are closed.
1 5
– 2, 4, A and B are open.
Endress+Hauser 53
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• All Deltabar S versions are suitable for level measurement in containers with superimposed steam.
• FMD76 and FMD77: the device is ready for calibration immediately after opening the shut-off
valves (may or may not be present).
• FMD78: the device is ready for calibration immediately.
• PMD70 and PMD75: before calibrating the device, the impulse piping must be cleaned and filled
with fluid. → See the following table.
B
Fill the negative impulse piping to the level of the condensate
trap. + A
3 Vent device.
54 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
! Note!
• The Flow, Level and Pressure operating modes each have a quick setup menu which guides you
through the most important basic functions. → ä 57 for the "Level" quick setup menu.
• Furthermore, the three level modes "Level Easy Pressure", "Level Easy Height" and "Level
Standard" are available to you for level measurement. You can select from the "Linear", "Pressure
linearized" and "Height linearized" level types for the "Level Standard" level mode. The table in
the "Overview of level measurement" section below provides an overview of the various
measuring tasks.
– In the "Level Easy Pressure" and "Level Easy Height" level modes, the values entered are not
tested as extensively as in the "Level Standard" level mode. The values entered for EMPTY
CALIB./FULL CALIB., EMPTY PRESSURE/FULL PRESSURE, EMPTY HEIGHT/FULL
HEIGHT and SET LRV/SET URV must have a minimum interval of 1% for the "Level Easy
Pressure" and "Level Easy Height" level modes. The value will be rejected with a warning
message if the values are too close together. Further limit values are not checked; i.e. the values
entered must be appropriate for the sensor and the measuring task so that the measuring device
can measure correctly.
– The "Level Easy Pressure" and "Level Easy Height" level modes encompass fewer parameters
than the "Level Standard" mode and are used for quick and easy configuration of a level
application.
– Customer-specific units of fill level, volume and mass or a linearization table may only be
entered in the "Level Standard" level mode.
– Where the device is intended for use as a subsystem in a safety function (SIL), a "Device
configuration with enhanced parameter security" (SAFETY CONFIRM.) is only possible for the
"Level" operating mode in the "Level Easy Pressure" level mode. All parameters previously
entered are checked after a password is entered. Once the "Level Easy Height" or "Level
Standard" has been selected, the configuration will first have to be reset to the ex-works setting
using the RESET parameter (menu path: (GROUP SELECTION →) OPERATING MENU →
OPERATION) using the reset code "7864". → For further information see the Deltabar S
(SD00189P) Functional Safety Manual.
• See the Operating Instructions BA00274P "Cerabar S/Deltabar S/Deltapilot S, Description of
device functions". See also → ä 2, "Overview documentation" section.
Endress+Hauser 55
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
The measured variable is LEVEL SELECTION: Via OUTPUT UNIT – Calibration with reference – Incorrect entries are The measured value
in direct proportion to the Level Easy Pressure parameter: %, level, pressure – wet calibration, possible display and the LEVEL
measured pressure. volume or mass see Operating Instructions – SIL mode possible BEFORE LIN parameter
Calibration is performed units. BA00274P. – Customised units are show the measured value.
by entering two pressure- – Calibration without not possible
level value pairs. reference pressure – dry
calibration, see Operating
Instructions BA00274P.
The measured variable is LEVEL SELECTION: Via OUTPUT UNIT – Calibration with reference – Incorrect entries are The measured value
in direct proportion to the Level Easy Height parameter: %, level, pressure – wet calibration, possible display and the LEVEL
measured pressure. volume or mass see Operating Instructions – SIL mode not possible BEFORE LIN parameter
Calibration is performed units. BA00274P. – Customised units are show the measured value.
by entering the density – Calibration without not possible
and two height-level value reference pressure – dry
pairs. calibration, see Operating
Instructions BA00274P.
The measured variable is LEVEL SELECTION: Via LIN. – Calibration with reference – Incorrect entries are The measured value
in direct proportion to the Level standard/ MEASURAND pressure – wet calibration, rejected by the device display and the LEVEL
measured pressure. LEVEL MODE: parameter: see Operating Instructions – SIL mode not possible BEFORE LIN parameter
Linear – % (level) BA00274P. – Customised level, show the measured value.
– Level – Calibration without volume and mass units
– Volume reference pressure – dry are possible
– Mass calibration, see Operating
Instructions BA00274P.
The measured variable is LEVEL SELECTION: Via LINd. – Calibration with reference – Incorrect entries are The measured value
not in direct proportion to Level standard/ MEASURAND pressure: semiautomatic rejected by the device display and the
the measured pressure as, LEVEL MODE: parameter: entry of linearisation table, – SIL mode not possible TANK CONTENT
for example, with Pressure linearized – Pressure + % see Operating Instructions – Customised level, parameter show the
containers with a conical – Pressure + volume BA00274P. volume and mass units measured value.
outlet. A linearisation table – Pressure + mass – Calibration without are possible
must be entered for the reference pressure: manual
calibration. entry of linearisation table,
see Operating Instructions
BA00274P.
– Two measured variables LEVEL SELECTION: Via COMB. – Calibration with reference – Incorrect entries are The measured value
are required or Level standard/ MEASURAND pressure: wet calibration rejected by the device display and the
– The container shape is LEVEL MODE: parameter: and semiautomatic entry of – SIL mode not possible TANK CONTENT
given by value pairs, Height linearized – Height + volume linearisation table, see – Customised level, parameter show the 2nd
such as height and – Height + mass Operating Instructions volume and mass units measured value (volume,
volume. – Height + % BA00274P. are possible mass or %).
The 1st measured variable – %-Height + – Calibration without
%-height or height must be volume reference pressure: dry The LEVEL BEFORE LIN
in direct proportion to the – %-Height + mass calibration and manual parameter displays the 1st
measured pressure. The – %-Height + % entry of linearisation table, measured value (%-height
2nd measured variable see Operating Instructions or height).
volume, mass or % need BA00274P.
not to be in direct
proportion to the
measured pressure. A
linearisation table must be
entered for the 2nd
measured variable. The
2nd measured variable is
assigned to the 1st
measured variable by
means of this table.
56 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
! Note!
• Some parameters are only displayed if other parameters are appropriately configured. For
example, the EMPTY CALIB. parameter is only displayed in the following cases:
– LEVEL SELECTION "Level Easy Pressure" and CALIBRATION MODE "Wet"
– LEVEL SELECTION "Level Standard", LEVEL MODE "Linear" and
CALIBRATION MODE "WET"
You can find the LEVEL MODE parameter in the BASIC SETTINGS function group (menu path:
(GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETTINGS).
• The following parameters are set to the following values in the factory:
– LEVEL SELETION: Level Easy Pressure
– CALIBRATION MODE: Wet
– OUTPUT UNIT or LIN. MEASURAND: %
– EMPTY CALIB.: 0.0
– FULL CALIB.: 100.0
– SET LRV (BASIC SETTINGS group): 0.0 (corresponds to 4 mA value)
– SET URV (BASIC SETTINGS group): 100.0 (corresponds to 20 mA value).
• The quick setup is suitable for simple and quick commissioning. If you wish to make more
complex settings, e.g. change the unit from "%" to "m", you will have to calibrate using the BASIC
SETTINGS group. → See Operating Instructions BA00274P or → ä 2, "Overview
documentation" section.
Measured value
1)
GROUP SELECTION
1) 1)
LANGUAGE MEASURING MODE QUICK SETUP OPERATING MENU
2)
LEVEL SELECTION
MEASURING MODE
LEVEL SELECTION
Fig. 40: Quick Setup menu for the Level measuring mode
MEASURING MODE
Select "Level" option.
LEVEL SELECTION LEVEL SELECTION
Select level mode. For an overview → ä 56. Select level mode. For an overview → ä 56.
GROUP SELECTION
Select QUICK SETUP menu.
Endress+Hauser 57
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
For on-site operation, → ä 32, Section 5.2.3 "Function of the operating elements – on-site display
connected" and → ä 37, Section 5.4 "On-site operation – on-site display connected".
58 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
! Note!
• The Deltabar S PMD70, PMD75 and FMD78 are usually used for differential pressure
measurement.
• FMD78: the device is ready for calibration immediately.
• PMD70 and PMD75: before calibrating the device, the impulse piping must be cleaned and filled
with fluid. → See the following table.
1 Close 3.
4 Vent device.
– A and B open (if present). Fig. 41: Above: preferred installation for gases
Below: preferred installation for liquids
6 Carry out calibration if necessary. → ä 60, Section 6.6.2.
I Deltabar S, PMD70 or PMD75
II Three-valve manifold
III Separator
1, 5 Drain valves
2, 4 Inlet valves
3 Equalising valve
6, 7 Vent valves on Deltabar S
A, B Shut-off valve
Endress+Hauser 59
Commissioning Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
! Note!
• There is a Quick Setup menu for each of the measuring modes Pressure, Level and Flow which
guides you through the most important basic functions. With the setting in the MEASURING
MODE parameter, you specify which Quick Setup menu should be displayed. → ä 47,
Section 6.2 "Selecting language and measuring mode".
• For a detailed description of the parameters see the Operating Instructions BA00274P "Cerabar
S/Deltabar S/Deltapilot S, Description of device functions"
– Table 6, POSITION ADJUSTMENT
– Table 7, BASIC SETUP
– Table 15, EXTENDED SETUP
→ See also → ä 2, section "Overview documentation".
• For differential pressure measurement, select the "Pressure" option by means of the MEASURING
MODE parameter. The operating menu is structured appropriately. → See also Section 10.1.
Measured value
1)
GROUP SELECTION
1) 1)
LANGUAGE MEASURING MODE QUICK SETUP OPERATING MENU
2)
MEASURING MODE
SET LRV
P01-xxxxxxxx-19-xx-xx-xx-066
MEASURING MODE
Select "Pressure" option.
GROUP SELECTION
Select QUICK SETUP menu.
60 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Commissioning
! Note!
For on-site operation, → ä 32, Section 5.2.3 "Function of the operating elements – on-site display
connected" and → ä 37, Section 5.4 "On-site operation – on-site display connected".
Endress+Hauser 61
Maintenance Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
7 Maintenance
Deltabar S requires no maintenance.
62 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
8 Trouble-shooting
8.1 Messages
The following table lists all the possible messages that can occur.
The device differentiates between the error types "Alarm", "Warning" and "Error". You may specify
whether the instrument should react as if for an "Alarm" or "Warning" for "Error" messages.
→ See "Error type/NA 64" column and Section 8.2 "Response of outputs to errors".
In addition, the "Error type/NA 64" column classifies the messages in accordance with NAMUR
Recommendation NA 64:
• Break down: indicated with "B"
• Maintenance need: indicated with "C" (check request)
• Function check: indicated with "I" (in service)
Error message display on the on-site display:
• The measured value display shows the message with the highest priority. → See "Priority"
column.
• The ALARM STATUS parameter shows all the messages present in descending order of priority.
You can scroll through all the messages present with the S-key or O-key.
Message display via digial communication:
• The ALARM STATUS parameter shows the message with the highest priority. → See "Priority"
column.
! Note!
• If the device detects a defect in the on-site display during initialization, special error messages are
generated. → For the error messages, → ä 71, Section 8.1.1 "On-site display error messages".
• For support and further information, please contact Endress+Hauser Service.
• → See also Section 8.4 ff.
101 (A101) Alarm Failure (F) B>Sensor electronic EEPROM – Electromagnetic effects are greater – Wait a few minutes. 17
B error than specifications in the – Restart the device. Perform reset
technical data. (→ See Section 9.) (Code 62).
This message normally only – Block off electromagnetic effects
appears briefly. or eliminate source of
disturbance.
– Sensor defect. – Replace sensor.
102 (W102) Warning Maintenance C>Checksum error in – Main electronics defect. Correct – Replace main electronics. 53
C request (M) EEPROM: peakhold segment measurement can continue as
long as you do not need the peak
hold indicator function.
106 (W106) Warning Funktion C>Downloading - please wait – Downloading. – Wait for download to complete. 52
C check (C)
110 (A110) Alarm Failure (F) B>Checksum error in – The supply voltage is – Reestablish supply voltage. 6
B EEPROM: configuration disconnected when writing. Perform reset (Code 7864) if
segment necessary. Carry out calibration
again.
113 (A113) Alarm Failure (F) B>ROM failure in transmitter – Main electronics defect. – Replace main electronics. 1
B electronic
Endress+Hauser 63
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
116 (W116) Warning Maintenance C>Download error, repeat – The file is defect. – Use another file. 36
C request (M) download
– During the download, the data are – Check cable connection PC –
not correctly transmitted to the transmitter.
processor, e.g. because of open – Block off electromagnetic effects
cable connections, spikes (ripple) or eliminate sources of
on the supply voltage or disturbance.
electromagnetic effects. – Perform reset (Code 7864) and
carry out calibration again.
– Repeat download.
120 (E120) Error Out of B>Sensor low pressure – Pressure too low. – Increase pressure until message 30
B specification disappears.
factory (S)
– Sensor defect. – Replace sensor.
setting:
Warning C
121 (A121) Alarm Failure (F) B>Checksum error in factory – Main electronics defect. – Replace main electronics. 5
B segment of EEPROM
122 (A122) Alarm Failure (F) B>Sensor not connected – Cable connection sensor –main – Check cable connection and 13
B electronics disconnected. repair if necessary.
– Electromagnetic effects are greater – Block off electromagnetic effects
than specifications in the or eliminate source of
technical data. disturbance.
(→ See Section 9.)
131 (A131) Alarm Failure (F) B>Checksum error in – Main electronics defect. – Replace main electronics. 9
B EEPROM: min/max segment
132 (A132) Alarm Failure (F) B>Checksum error in – Main electronics defect. – Replace main electronics. 7
B totalizer EEPROM
133 (A133) Alarm Failure (F) B>Checksum error in History – An error occurred when writing. – Perform reset (Code 7864) and 8
B EEPROM carry out calibration again.
602 (W602) Warning Funktion C>Linearisation curve not – The linearisation table is not – Add to linearisation table or 57
C check (C) monotone monotonic increasing or perform linearisation again.
decreasing.
64 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
613 (W613) Warning Funktion I>Simulation is active – Simulation is switched on, i.e. the – Switch off simulation. 60
I check (C) device is not measuring at
present.
620 (E620) Error Out of C>Current output out of The current is outside the permitted – Check pressure applied, 49
C specification range range 3.8 to 20.5 mA. reconfigure measuring range if
Factory (S) – The pressure applied is outside necessary (→ See also Operating
setting: Instructions BA00274P or these
the set measuring range (but
Warning C Operating Instructions → ä 2.)
within the sensor range).
– Perform reset (Code 7864) and
carry out calibration again.
700 (W700) Warning Maintenance C>Last configuration not – An error occurred when writing – Perform reset (Code 7864) and 54
C request (M) stored or reading configuration data or carry out calibration again.
the power supply was
disconnected.
702 (W702) Warning Maintenance C>HistoROM data not – Data were not written correctly to – Repeat upload. 55
C request (M) consistent. the HistoROM, e.g. if the – Perform reset (Code 7864) and
HistoROM was detached during carry out calibration again.
the writing process.
Endress+Hauser 65
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
705 (A705) Alarm Failure (F) B>Measurement error – Fault in the main electronics. – Briefly disconnect device from the 21
B power supply.
706 (W706) Warning Maintenance C>Configuration in – Configuration (parameters) in the – Copy data from the device to the 59
C request (M) HistoROM and device not HistoROM and in the device is HistoROM. (→ See also
identical not identical. → ä 40, Section 5.5.1 "Copying
configuration data".)
– Copy data from the HistoROM to
the device. (→ See also → ä 40,
Section 5.5.1 "Copying
configuration data".) The message
remains if the HistoROM and the
device have different software
versions. The message goes out if
you copy the data from the device
to the HistoROM.
– Device reset codes such as 7864
do not have any effect on the
HistoROM. That means that if you
do a reset, the configurations in
the HistoROM and in the device
may not be the same.
707 (A707) Alarm Funktion B>X-VAL. of lin. table out of – At least one X-VALUE in the – Carry out calibration again. (→ 38
B check (C) edit limits. linearisation table is either below See also Operating Instructions
the value for HYDR. PRESS MIN. BA00274P or these Operating
or MIN. LEVEL or above the Instructions → ä 2.)
value for HYDR. PRESS. MAX. or
LEVEL MAX.
710 (W710) Warning Funktion B>Set span too small. Not – Values for calibration (e.g. lower – Adjust calibration to suit sensor. 51
C check (C) allowed. range value and upper range (→ See also Operating
value) are too close together. Instructions BA00274P,
parameter description MINIMUM
SPAN or these Operating
Instructions → ä 2.)
– The sensor was replaced and the – Adjust calibration to suit sensor.
customer-specific configuration – Replace sensor with a suitable
does not suit the sensor. sensor.
711 (A711) Alarm Funktion B>LRV or URV out of edit – Lower range value and/or upper – Reconfigure lower range value 37
B check (C) limits range value undershoot or and/or upper range value to suit
overshoot the sensor range limits. the sensor. Pay attention to
position factor.
– The sensor was replaced and the – Reconfigure lower range value
customer-specific configuration and/or upper range value to suit
does not suit the sensor. the sensor. Pay attention to
position factor.
– Replace sensor with a suitable
sensor.
713 (A713) Alarm Funktion B>100% POINT level out of – The sensor was replaced. – Carry out calibration again. 39
B check (C) edit limits
66 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
715 (E715) Error Out of C>Sensor over temperature – The temperature measured in the – Reduce process temperature/ 32
C specification sensor is greater than the upper ambient temperature.
Factory (S) nominal temperature of the
setting: sensor. (→ See also Operating
Warning C Instructions BA00274P,
parameter description Tmax
SENSOR or these Operating
Instructions → ä 2.)
716 (E716) Error Failure (F) B>process isolating – Sensor defect. – Replace sensor. 24
B diaphragm broken – PMD70, FMD76: Overpressure is – Reduce pressure.
Factory present at minus or plus side of
setting: the device (on-sided overpressure)
Alarm B
717 (E717) Error Out of C>Transmitter over – The temperature measured in the – Reduce ambient temperature. 34
C specification temperature electronics is greater than the
Factory (S) upper nominal temperature of the
setting: electronics (+88 °C (+190 °F)).
Warning
– Unsuitable download carried out. – Check configuration and perform
download again.
718 (E718) Error Out of C>Transmitter under – The temperature measured in the – Increase ambient temperature. 35
C specification temperature electronics is smaller than the Insulate device if necessary.
Factory (S) lower nominal temperature of the
setting: electronics (–43 °C (-45 °F)).
Warning C
– Unsuitable download carried out. – Check configuration and perform
download again.
719 (A719) Alarm Funktion B>Y-VAL of lin. table out of – At least on Y-VALUE in the – Carry out calibration again. (→ 40
B check (C) edit limits linearisation table is below the See also Operating Instructions
MIN. TANK CONTANT or above BA00274P or these Operating
the MAX. TANK CONTENT. Instruction → ä 2.)
720 (E720) Error Out of C>Sensor under temperature – The temperature measured in the – Increase process temperature/ 33
C specification sensor is smaller than the lower ambient temperature.
Factory (S) nominal temperature of the
setting: sensor. (→ See also Operating
Warning C Instructions BA00274P,
parameter description Tmin
SENSOR or Operating
Instructions → ä 2.)
721 (A721) Alarm Funktion B>ZERO POSITION level out – LEVEL MIN or LEVEL MAX has – Perform reset (Code 2710) and 41
B check (C) of edit limits been changed. carry out calibration again.
722 (A722) Alarm Funktion B>EMPTY CALIB. or FULL – LEVEL MIN or LEVEL MAX has – Perform reset (Code 2710) and 42
B check (C) CALIB. out of edit limits been changed. carry out calibration again.
723 (A723) Alarm Funktion B>MAX. FLOW out of edit – FLOW-MEAS. TYPE has been – Carry out calibration again. 43
B check (C) limits changed.
Endress+Hauser 67
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
725 (A725) Alarm Failure (F) B>Sensor connection error, – Electromagnetic effects are greater – Block off electromagnetic effects 25
B cycle disturbance than specifications in the or eliminate source of
technical data. (→ See Section 9.) disturbance.
– Setscrew loose.
– Retighten setscrew with 1 Nm
(0,74 lbf ft) (see Chap. 3.3.9).
726 (E726) Error Out of C>Sensor temperature error - – Electromagnetic effects are greater – Block off electromagnetic effects 31
C specification overrange than specifications in the or eliminate source of
Factory (S) technical data. disturbance.
setting: (→ See Section 9.)
Warning C
– Process temperature is outside – Check temperature present,
permitted range. reduce or increase if necessary.
727 (E727) Error Out of C>Sensor pressure error - – Electromagnetic effects are greater – Block off electromagnetic effects 28
C specification overrange than specifications in the or eliminate source of
Factory (S) technical data. disturbance.
setting: (→ See Section 9.)
Warning C
– Pressure is outside permitted – Check pressure present, reduce or
range. increase if necessary.
728 (A728) Alarm Failure (F) B>RAM error – Fault in the main electronics. – Briefly disconnect device from the 2
B power supply.
729 (A729) Alarm Failure (F) B>RAM error – Fault in the main electronics. – Briefly disconnect device from the 3
B power supply.
730 (E730) Error Out of C>LRV user limits exceeded – Pressure measured value has – Check system/pressure measured 46
C specification undershot the value specified for value.
Factory (S) the Pmin ALARM WINDOW – Change value for Pmin ALARM
setting: parameter. WINDOW if necessary. (→ See
Warning C also Operating Instructions
BA00274P, parameter description
Pmin ALARM WINDOW or these
Operating Instruction → ä 2.)
731 (E731) Error Out of C>URV user limits exceeded – Pressure measured value has – Check system/pressure measured 45
C specification overshot the value specified for value.
Factory (S) the Pmax ALARM WINDOW – Change value for Pmax ALARM
setting: parameter. WINDOW if necessary. (→ See
Warning C also Operating Instructions
BA00274P, parameter description
Pmax ALARM WINDOW or these
Operating Instructions → ä 2.)
68 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
732 (E732) Error Out of C>LRV Temp. User limits – Temperature measured value has – Check system/temperature 48
C specification exceeded undershot the value specified for measured value.
Factory (S) the Tmin ALARM WINDOW – Change value for Tmin ALARM
setting: parameter. WINDOW if necessary. (→ See
Warning C also Operating Instructions
BA00274P, parameter description
Tmin ALARM WINDOW or these
Operating Instructions → ä 2.)
733 (E733) Error Out of C>URV Temp. User limits – Temperature measured value has – Check system/temperature 47
C specification exceeded overshot the value specified for measured value.
Factory (S) the Tmax ALARM WINDOW – Change value for Tmax ALARM
setting: parameter. WINDOW if necessary. (→ See
Warning C also Operating Instructions
BA00274P, parameter description
Tmax ALARM WINDOW or these
Operating Instructions → ä 2.)
736 (A736) Alarm Failure (F) B>RAM error – Fault in the main electronics. – Briefly disconnect device from the 4
B power supply.
737 (A737) Alarm Failure (F) B>Measurement error – Fault in the main electronics. – Briefly disconnect device from the 20
B power supply.
738 (A738) Alarm Failure (F) B>Measurement error – Fault in the main electronics. – Briefly disconnect device from the 19
B power supply.
739 (A739) Alarm Failure (F) B>Measurement error – Fault in the main electronics. – Briefly disconnect device from the 23
B power supply.
740 (E740) Error Maintenance C>Calculation overflow, bad – Level measuring mode: the – Check configuration and carry out 27
C request (M) configuration measured pressure has undershot calibration again if necessary.
Factory the value for HYDR. PRESS. MIN. – Select a device with a suitable
setting: or overshot the value for HYDR. measuring range.
Warning C PRESS MAX.
741 (A741) Alarm Funktion B>TANK HEIGHT out of edit – LEVEL MIN or LEVEL MAX has – Perform reset (Code 2710) and 44
B check (C) limits been changed. carry out calibration again.
742 (A742) Alarm Failure (F) B>Sensor connection error – Electromagnetic effects are greater – Wait a few minutes. 18
B (upload) than specifications in the – Perform reset (Code 7864) and
technical data. (→ See Section 9.) carry out calibration again.
This message normally only
appears briefly.
Endress+Hauser 69
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
743 (E743) Alarm Failure (F) B>Electronic PCB error – This message normally only – Wait a few minutes. 14
B during initialisation appears briefly. – Restart the device. Perform reset
(Code 62).
747 (A747) Alarm Failure (F) B>Sensor software not – Sensor does not suit the device – Replace sensor with a suitable 16
B compatible to electronics (electronic sensor nameplate). sensor.
748 (A748) Alarm Failure (F) B>Memory failure in signal – Electromagnetic effects are greater – Block off electromagnetic effects 15
B processor than specifications in the or eliminate source of
technical data. disturbance.
(→See Section 9.)
70 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
Message Measure
Endress+Hauser 71
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
Current output Assumes the value specified via the Device continues measuring. For this error, you can enter whether the
OUTPUT FAIL MODE1), ALT. CURR. device should react as in the event of an
OUTPUT1 and SET MAX. ALARM1 alarm or as in the event of a warning. See
parameter. → See also the following section corresponding "Alarm" or "Warning"
"Configuring current output for an alarm". column. (→ See also Operating Instructions
BA00274P, parameter description SELECT
ALARM TYPE or these Operating
Instructions → ä 2.)
Bargraph The bargraph adopts the value defined by The bargraph adopts the value which → See this table, "Alarm" or "Warning"
(on-site display) the OUTPUT FAIL MODE 1 parameter. corresponds to the current value. column, depending on selection.
On-site display – The measured value and message are – The measured value and message are – The measured value and message are
displayed alternately displayed alternately displayed alternately
– Measured value display: -symbol is – Measured value display: -symbol – Measured value display: see
permanently displayed. flashes. corresponding "Alarm" or "Warning"
column
Remote operation In the case of an alarm, the In the case of a warning, the ALARM In the case of an error, the
(digital communication) ALARM STATUS2) parameter displays a 3- STATUS2 parameter displays a 3-digit ALARM STATUS2 parameter displays a 3-
digit number such as 122 for "Sensor not number such as 613 for "Simulation is digit number such as 731 for "URV user
connected". active". limits exceeded".
72 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
I
max.
➀ 21...23 mA
min.
➂ 3.6 mA
t
P01-xxxxxxxx-05
Factory setting:
• OUTPUT FAIL MODE: Max. Alarm (110%)
• SET MAX. ALARM: 22 mA
Use the ALT. CURR. OUTPUT parameter to set the current output value for the error messages E
120 "Sensor low pressure" and E 115 "Sensor overpressure". You have the following options:
– Normal: the current output assumes the value set via the OUTPUT FAIL MODE and SET MAX.
ALARM parameters.
– NAMUR
– Lower sensor limit undershot (E 120 "Sensor low pressure"): 3.6 mA
– Upper sensor limit overshot (E 115 "Sensor overpressure") overshot: current output assumes
the value set via the SET MAX ALARM parameter.
Factory setting:
• ALT. CURR. OUTPUT: normal
Endress+Hauser 73
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
Settings 1) Measures
– ALARM DISPL. TIME = 0 s – Rectify cause of the message (see also Section 8.1).
– ACK. ALARM MODE = off
– ALARM DISPL. TIME > 0 s – Rectify cause of the message (see also Section 8.1).
– ACK. ALARM MODE = off – Wait for the alarm display time to elapse.
– ALARM DISPL. TIME = 0 s – Rectify cause of the message (see also Section 8.1).
– ACK. ALARM MODE = on – Confirm message using ACK. ALARM parameter.
– ALARM DISPL. TIME > 0 s – Rectify cause of the message (see also Section 8.1).
– ACK. ALARM MODE = on – Confirm message using ACK. ALARM parameter.
– Wait for the alarm display time to elapse. If a message appears and the alarm
display time elapses before the message has been acknowledged, the message
will be cleared once it has been acknowledged.
1) Menu path for ALARM DISPL. TIME and ACK. ALARM MODE: (GROUP SELECTION →) OPERATING MENU →
DIAGNOSTICS → MESSAGES
If the on-site display displays a message, you can suppress it with the F-key.
If there are several messages, the on-site display shows the message which has the highest priority
(see also Section 8.1). Once you have suppressed this message using the F-key, the message with
the next highest priority is displayed. You can use the F-key to suppress each message, one after
the other.
The ALARM STATUS parameter continues to display all the messages present.
74 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
8.4 Repair
The Endress+Hauser repairs concept provides for measuring devices to have a modular design and
also the customer may carry out repairs (→ ä 76, Section 8.6 "Spare Parts").
! Note!
• For certified devices, please consult Chapter "Repair of Ex-certified devices".
• For more information on service and spare parts contact the Endress+Hauser Service. ( → See
www.endress.com/worldwide)
Endress+Hauser 75
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
6. Select the required spare parts (You may also use the overview drawing on the right side of the
screen.)
When ordering spare parts, always quote the serial number indicated on the nameplate. As far as
necessary, the spare parts also include replacement instructions.
76 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
8.7 Return
The measuring device must be returned if repairs or a factory calibration are required, or if the
wrong measuring device has been ordered or delivered. According to legal regulations,
Endress+Hauser, as a ISO-certified company, is required to follow certain procedures when
handling returned products that are in contact with process fluids.
To ensure swift, safe and professional device returns, please read the return procedures and
conditions on the Endress+Hauser website at www.services.endress.com/return-material.
8.8 Disposal
When disposing, separate and recycle the device components based on the materials.
Endress+Hauser 77
Trouble-shooting Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
06.2004 02.00.zz – Number of parameters in the Quick Setup menus has been BA270P/00/EN/05.04 BA274P/00/EN/05.04
reduced. 52022793 52021469
– On-site operation: LANGUAGE and MEASURING MODE
parameters have been moved to the top level.
– New SAFETY CONFIRM. group implemented for SIL.
→ See also SD00189P Safety Manual Deltabar S.
– MEASURING MODE "Level", LEVEL MODE "Linear": AREA
UNIT and TANK SECTION parameters have been replaced
with the TANK VOLUME and TANK HEIGHT parameters.
– Function of the UNIT FLOW parameter has been split across
four parameters.
– Function of the SIMULATED VALUE parameter has been
split across six parameters.
– SENSOR TRIM and CURRENT TRIM groups have been
removed.
– Sensor adapt reset, code 1209 and sensor calibration reset,
code 2509 have been removed.
– Quick Setup menus are available via ToF Tool.
Compatible with:
– ToF Tool Field Tool Package version 2.00.00 or higher
– Commuwin II version 2.08.-1, Update > G
– HART Communicator DXR375 with Device Rev.: 20, DD
Rev.: 1
06.2005 02.01.zz – Operating keys also integrated on the optional on-site display. BA270P/00/EN/06.05 BA274P/00/EN/05.04
– Chinese and Japanese are available as the menu language on 71000109 52021469
request.
BA270P/00/EN/11.05 BA274P/00/EN/05.04
Compatible with: 71009586 52021469
– ToF Tool Field Tool Package version 3.00.00 or higher
– FieldCare version 2.01.00, DTM Library version 2.06.00,
DTM: Deltabar S/MD7x/V02.00 V 1.4.98.74*
– HART Communicator DXR375 with Device Rev.: 20,
DD Rev.: 1*
* Menu languages Chinese and Japanese not selectable
78 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Trouble-shooting
BA270P/00/EN/05.10 BA274P/00/EN/05.10
71114104 71118244
BA00270P/00/EN/13.11 BA00274P/00/EN/13.11
71139762 71139795
BA00270P/00/EN/14.12 BA00274P/00/EN/13.11
71161876 71139795
Endress+Hauser 79
Technical data Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
9 Technical data
For technical data, please refer to the Technical Information TI00382P for Deltabar S.
→ See also → ä 2, section "Overview documentation".
10 Appendix
80 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Appendix
Measured value
1)
GROUP SELECTION
1) 1)
LANGUAGE MEASURING MODE QUICK SETUP OPERATING MENU
1)
Level measuring
LEVEL SELECTION mode only SETTINGS
POSITION ADJUSTMENT
2)
MEASURING MODE
SET LRV POS. ZERO ADJUST MAX. FLOW POS. INPUT VALUE
DAMPING VALUE
* There are parameters that are only displayed if other parameters are
appropriately configured.
For example the CUSTOMER UNIT P parameter is only displayed
if the "User unit" option was selected for the PRESS. ENG. UNIT parameter.
These parameters are indicated with a "*".
P01-xMD7xxxx-19-xx-xx-xx-003
Endress+Hauser 81
Appendix Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
BASIC SETUP
2)
MEASURING MODE
CUSTOMER UNIT P
* CUSTOMER UNIT P
*
Level Easy Pressure Level Easy Height Level Standard
CUST. UNIT FACT. P
* CUST. UNIT FACT. P
*
PRESS. ENG. UNIT PRESS. ENG. UNIT
X
SET LRV
CUSTOMER UNIT P
* CUSTOMER UNIT P
* Continuation,
see the following page
FLOW-MEAS. TYPE
SET URV
CUST. UNIT FACT. P
* CUST. UNIT FACT. P
* A
GET LRV B
OUTPUT UNIT OUTPUT UNIT
DAMPING VALUE
Dry
CUST. UNIT FACT. F
*
Wet CALIBRATION MODE
FULL CALIB. EMPTY PRESSUE DENSITY UNIT DENSITY UNIT MAX PRESS. FLOW
FULL CALIB.
SET URV
FULL HEIGHT
DAMPING VALUE
SET LRV
SET URV
DAMPING VALUE
UNIT FLOW NORM FLOW UNIT STD. FLOW UNIT MASS FLOW UNIT
B B B B
* There are parameters that are only displayed if other parameters are
appropriately configured.
For example the CUSTOMER UNIT P parameter is only displayed
if the "User unit" option was selected for the PRESS. ENG. UNIT parameter.
These parameters are indicated with a "*".
P01-xMD7xxxx-19-xx-xx-xx-004
82 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Appendix
C
Continuation
BASIC SETUP "Level",
X see also the previous page Height Volume Mass %
LEVEL MODE
Linear
Pressure Height E
Linearized Linearized
LIN. MEASURAND LINd MEASURAND COMB. MEASURAND
% Volume Mass
TANK VOLUME
* EMPTY PRESSURE ADJUST DENSITY
*
CUST. UNIT FACT. H
HEIGHT UNIT
* FULL CALIB. HEIGHT UNIT *
H H
CUSTOMER UNIT H FULL PRESSURE CUSTOMER UNIT H *
CUST. UNIT FACT. H
* ADJUSTED DENSITY * CUST. UNIT FACT. H *
TANK HEIGHT
* 100% POINT *
100% POINT
* ZERO POSITION
ZERO POSITION
DAMPING VALUE
SET LRV
SET URV
DAMPING VALUE * There are parameters that are only displayed if other parameters are
appropriately configured.
For example the CUST. UNIT FACT. H parameter is only displayed
if the "User unit" option was selected for the HEIGHT UNIT parameter.
These parameters are indicated with a "*".
P01-xxxxxxxx-19-xx-xx-xx-140
Endress+Hauser 83
Appendix Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
TEMP. ENG UNIT TEMP. ENG UNIT TEMP. ENG UNIT TANK CONTENT MIN TANK CONTENT MIN TOTALIZER 1 UNIT
DENSITIY UNIT LOW FLOW CUT-OFF TANK CONTENT MAX TANK CONTENT MAX TOT. 1 USER UNIT
*
ADJUST DENSITIY SET L. FL. CUT-OFF
* TABLE SELECTION TABLE SELECTION FACT. U. U. TOTAL.1
*
PROCESS DENSITY SET LRV Measuring Measuring NEG. FLOW TOT. 1
Editor Table Editor Table
Table Table
SET LRV
* SET URV LIN. EDIT MODE MEASURING TABLE LIN. EDIT MODE LINE-NUMB RESET TOTALIZER 1
SET URV * EDITOR TABLE MEASURING TABLE EDITOR TABLE ACTIVE LIN. TAB. X TOTALIZER 2 UNIT
EDITOR TABLE
TANK DESCRIPTION
* There are parameters that are only displayed if other parameters are
appropriately configured.
For example the TOT. 1 USER UNIT parameter is only displayed
if the "User unit" option was selected for the TOTALIZER 1 UNIT parameter.
These parameters are indicated with a "*".
P01-xMD7xxxx-19-xx-xx-xx-005
84 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Appendix
SAFETY CONFIRM.
** DISPLAY OUTPUT
2)
CURRENT OUTPUT LANGUAGE ALT. CURR. OUTPUT
3)
MEASURING MODE ASSIGN CURRENT
4)
Pressure Level Flow LINEAR/SQROOT
5)
SET LRV EMPTY PRESSURE MAX. FLOW
CONF. PASSWORD
2) Display via
HART handheld terminal only * There are parameters that are only displayed if other parameters are
appropriately configured.
3) Level measuring mode only These parameters are indicated with a "*".
4) Flow measuring mode only See Safety Manual SD189P
5) only LEVEL SELECTION = Level Easy Pressure
** for Deltabar S.
P01-xMD7xxxx-19-xx-xx-xx-006
Endress+Hauser 85
Appendix Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
HART DATA TRANSMITTER DATA PROCESS CONNECTION SENSOR DATA PROCESS VALUE PEAK HOLD INDICATOR
BUS ADDRESS DEVICE SERIAL No Pmax PROC. CONN. SENSOR SER. NO. MEASURED VALUE MEASURED VALUE MEASURED VALUE COUNTER:P > Pmax
DEVICE TYPE ELECTR. SERIAL No PROC. CONN. TYPE PRESS. SENS LOLIM PRESSURE PRESSURE PRESSURE MAX. MEAS. PRESS.
DEVICE REVISION CUST. TAG NUMBER MAT. PROC. CONN. + PRESS. SENS HILIM CORRECTED PRESS. CORRECTED PRESS. CORRECTED PRESS. COUNTER:P < Pmin
2)
BURST MODE LONG TAG NUMBER MAT. PROC. CONN. – MINIMUM SPAN SENSOR PRESSURE SENSOR PRESSURE SENSOR PRESSURE MIN. MEAS. PRESS.
2)
BURST OPTION ADDITIONAL INFO. SEAL TYPE SENSOR MEAS. TYPE SENSOR TEMP. SENSOR TEMP. SENSOR TEMP. COUNTER:T > Tmax
2)
PREAMBLE NUMBER DEVICE DESIGN. BOLTS MATERIAL Pmin SENS. DAMAGE MEAS. VAL. TREND MEAS. VAL. TREND MEAS. VAL. TREND MAX. MEAS. TEMP.
2)
MANUFACTOR ID HARDWARE REV. NUTS MATERIAL Pmax SENS. DAMAGE LEVEL BEFORE LIN
* SUPPRESSED FLOW COUNTER:T< Tmin
2)
HART MESSAGE SOFTWARE VERSION DRAIN VENT MAT. MAT. MEMBRANE TANK CONTENT
* TOTALIZER 1 MIN. MEAS. TEMP.
2)
HART DATE CONFIG RECORDER DRAIN VENT POS. FILLING FLUID TOTAL. 1 OVERFLOW PCB COUNT:T > Tmax
2) 2)
PRIMARY VALUE IS PCB TEMPERATURE THREAD Tmin SENSOR TOTALIZER 2 PCB MAX. TEMP.
2) 2)
PRIMARY VALUE ALLOWED MIN. TEMP MOUNTING THREAD Tmax SENSOR TOTAL. 2 OVERFLOW PCB COUNT: T< Tmin
2) 2)
SECONDARY VAL. IS ALLOWED MAX. TEMP REMOTE SEAL + SENSOR H/WARE REV. PCB MIN. TEMP.
2) 2)
SECONDARY VALUE DIP STATUS REMOTE SEAL – RESET PEAKHOLD
2) 2)
THIRD VALUE IS DIAPHRAGM MAT. +
2) 2)
THIRD VALUE DIAPHRAGM MAT. –
2) 2)
4TH VALUE IS NR OF REMOTE SEAL
2) 2)
4 TH VALUE FILL FLUID
There are parameters that are only displayed if other parameters are
* appropriately configured.
These parameters are indicated with a "*".
P01-xMD7xxxx-19-xx-xx-xx-007
86 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Appendix
ENTER RESET CODE SIMULATION MODE ALARM STATUS Pmin ALARM WINDOW CURR. TRIM 4mA
OPERATING HOURS LAST DIAG. CODE Pmax ALARM WINDOW CURR. TRIM 20mA
INSERT PIN NO ACK. ALARM MODE Tmin ALARM WINDOW OFFSET 4mA TRIM
HistoROM AVAIL. ACK. ALARM * Tmax ALARM WINDOW OFFSET 20mA TRIM
SELECT ALARMTYPE
ALARM DELAY
There are parameters that are only displayed if other parameters are
* appropriately configured.
These parameters are indicated with a "*".
P01-xxxxxxxx-19-xx-xx-xx-143
Endress+Hauser 87
Appendix Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART
88 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Appendix
Endress+Hauser 89
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Index
Index
Numerics N
4...20 mA test signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
A O
Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 On-site display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operating elements, function . . . . . . . . . . . . . . . . . . . 31–32
C Operating elements, position. . . . . . . . . . . . . . . . . . . . . . . 30
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Operating keys, on-site, Flow measuring mode . . . . . . . . . 36
Commubox FXA195 anschließen . . . . . . . . . . . . . . . . . . . 26 Operating keys, on-site, function. . . . . . . . . . . . . . . . . 31–32
Connecting Commubox FXA291 . . . . . . . . . . . . . . . . . . . 27 Operating keys, on-site, Level measuring mode . . . . . . . . . 34
Connecting ToF Adapter FXA291 . . . . . . . . . . . . . . . . . . . 27 Operating keys, on-site, Pressure measuring mode. . . . . . . 33
Operating keys, position . . . . . . . . . . . . . . . . . . . . . . . . . . 30
D Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37, 80
Diaphragm seals, installation instructions . . . . . . . . . . . . . 17 Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Diaphragm seals, vacuum application . . . . . . . . . . . . . . . . 18
Differential pressure measurement . . . . . . . . . . . . . . . . . . 59 P
Differential pressure measurement, information . . . . . . . . 60 Pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Differential pressure measurement, installation . . . . . . . . . 16 Position adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Differential pressure measurement, preparatory steps . . . . 59 Potential matching . . . . . . . . . . . . . . . . . . . . . . . . . . . 26–27
Differential pressure measurement, Quick Setup menu . . . 60 Pressure measurement, Quick Setup menu . . . . . . . . . . . . 60
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Q
E Quick Setup menu flow . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Quick Setup menu level . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Quick Setup menu pressure . . . . . . . . . . . . . . . . . . . . . . . 60
F R
Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Repair of Ex-certified devices . . . . . . . . . . . . . . . . . . . . . . 75
Flow measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Flow measurement, installation . . . . . . . . . . . . . . . . . . . . 11 Returning devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Flow measurement, Ouick Setup menu . . . . . . . . . . . . . . 51 Rotating the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Flow measurement, preparatory steps . . . . . . . . . . . . . . . . 49
S
H Scope of delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Screening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Heat insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Separate housing, assemble and mount . . . . . . . . . . . . . . . 21
HistoROM/M-Dat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Service Interface FXA291 . . . . . . . . . . . . . . . . . . . . . . . . . 27
SIL3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
I Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
L Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Language, selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . 55–56 T
Level measurement, installation . . . . . . . . . . . . . . . . . . . . 12 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Level measurement, preparatory steps. . . . . . . . . . . . . . . . 52
Level measurement, Quick Setup menu . . . . . . . . . . . . . . 57 U
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Unlocking operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Locking operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
W
M Wand mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Measuring layout for flow measurement . . . . . . . . . . . . . . 11 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Measuring layout for level measurement . . . . . . . . . . . . . . 12
Measuring layout for pressure measurement . . . . . . . . . . . 16
Measuring mode, selection . . . . . . . . . . . . . . . . . . . . . . . . 47
90 Endress+Hauser
Deltabar S FMD76/77/78, PMD70/75 with 4...20 mA HART Index
Endress+Hauser 91
www.endress.com/worldwide
BA00270P/00/EN/15.13
71204581
CCS/FM+SGML 9 71204581
PNEUMATIC CONTROL VALVE
INSTALLATION OPERATION
AND MAINTENANCE INSTRUCTION
( K2C(3C)-DP )
TABLE OF CONTENTS
PAGE
1. TYPE --------------------------- 3
2. MATERIALS --------------------------- 4
3. CONSTRUCTION --------------------------- 5
METHOD OF INSTALLING
7. --------------------------- 9
CONTROL VALVE
8. MAINTENANCE --------------------------- 10
2
PNEUMATIC CONTROL VALVE
1. TYPE
The indication of type of cage type control valve is as shown below :
The following sample a full designation of type.
[Example]
K2C(3C) - DP 1 ( R )
┃ ┃ ┃ ┗━━━ Diaphragm Acting Mode
┃ ┃┃ D : Direct action
┃ ┃┃ R : Reverse action
┃ ┃┃ B : Double action
┃ ┃┃
┃ ┃ ┗ Indicates body configuration. (See Table b.)
┃ ┃
┃ ┗━ ACTUATOR TYPE ( DP : Pneumatic Diaphragm)
┃
┗ 2Way(3Way) Control valve series
ANSI
(125ㆍ150) 250ㆍ300 400ㆍ600 900 1500 2500
(Class)
3
PNEUMATIC CONTROL VALVE
2. MATERIALS
2.1 BODY
Optimum materials are selected, depending on type of fluid, pressures,
temperatures and other requirements. (flushing, cavitation, corrosion, etc.)
Cast iron (FC), gunmetal (BC) , ordinary cast steel (SC) and cast stainless
steel (SUS) conform to the requirements specified in JIS and special cast
steel (WC, S5, etc.) conform to the requirements specified in ASTM.
2.2 TRIM
Table shows typical standard trim materials among types herein. The trim
materials for cage type control valves are shown on pertinent drawing.
Standard trim materials for general purpose type control valve (Mark of
materials : JIS)
Service temperature of
Lower Seat
Disc Seat Gland fluids such as water, oil,
Stem Ring
steam, air and gas (℃)
SUS 410
SCS SUS SUS SUS
or
o 220
0 AND U
UNDER
24 316 316 316
SCS 24
4
PNEUMATIC CONTROL VALVE
3. CONSTRUCTION
3.1 Body (See Attached Figs. 1~9.)
Control valves can be largely divided into single seat valve and double seat
valve. Normally single seat valve is used. How ever, for small n bore or
where pressure is relatively low and low leaking is desired single seat valve
is used.
Balance piston valve combines the advantages of both single and double
seat valves. Its leaking is similar to that of single seat valve. It can be used
up to the differential pressure 5 - 6 times that of the single seat valve.
Operation Principle of the balance piston valve is
: When working pressure is applied on diaphragm, the stem is brought
down.
This causes pilot valve to open first. Then the inlet pressure is applied on
the upper side of piston, Since the piston is almost the same in diameter
with the main valve, it balances with the back pressure of the main valve.
Thus the unbalance of the valve is reduced to a fraction.
3.2 Valve disc
a. Single seat : <FIG. 1>
b. Double seat : <FIG. 2>
See Figs. 1 and 2 for the shape of each disc.
5
PNEUMATIC CONTROL VALVE
3.3 Bonnet
Single Action
6
PNEUMATIC CONTROL VALVE
5. NAME PLATE
5.1 Name Plate for Specification
<Fig. 5>
7
PNEUMATIC CONTROL VALVE
<Fig. 6>
6. AIR PIPING CONNECTION
6.1 Direct Action Diaphragm
<Fig. 7>
KANGRIM HEAVY INDUSTRIES CO., LTD.
8
PNEUMATIC CONTROL VALVE
<Fig. 8>
7.3 Install the control valve with its flow direction conforming to the direction
shown by the arrow mark casted (or engraved) on the body.
9
PNEUMATIC CONTROL VALVE
8. MAINTENANCE
8.1 Disassembly, Assembly and Parts Replacement
10
PNEUMATIC CONTROL VALVE
Note.
1. Diaphragm stem must be screwed down completely to the step of.
2. Fasten firmly bolts after assembly at any occasion.
3. If the valve is fixed with positioner, keep the spring in positioner casing
free before disassembling, after finishing, keep it original performance.
11
PNEUMATIC CONTROL VALVE
Note.
Pay special attention in locking the nut in reassembly, taking care not to
cause uneven tightening. Move the valve stem vertically and see if it moves
smoothly by hand. While checking in this way, lock up the nut evenly.
B. Direct Valve
a) Disconnect air piping from diaphragm casing.
b) Remove bolt and disassemble into half.
c) Loosen round nut and remove it. For diaphragms larger than 410J
(nominal) yoke is bolted to upper cover. In this case, remove bolts nuts.
d) Bring up the assembly above yoke yoke.
e) Remove nut and dismount cover.
f) Draw out the valve plug from cover.
g) Reassemble approximately in the reverse order to disassembly.
First insert the valve plug into body (valve seats). Then, put back bonnet.
Note.
1. Take the same care as that in the note of page. 9.1.6.A when locking
up the Bonnet.
2. When lifting the yoke and its related parts of a large size (diaphragms
larger then 410J) it is desirable to hook a wire rope to the arm of the yoke
or the head after slightly unscrewing the two bolts and then hoist the yoke
with a chain block.
3. While lifting the yoke, care not to bend valve stem or damage the
fitted parts by lifting the yoke diagonally.
4. The same care should be paid when handling the valve plug.
12
PNEUMATIC CONTROL VALVE
13
PNEUMATIC CONTROL VALVE
9. TROUBLE SHOOTING
Problems and solutions for the cases when the lift of control valve is not
correctly changed against normal working air pressure.
Problems Solutions
Overhaul valve.
1) Sticking of valve guide, stem, etc. Remove engaged particles, scale etc,
if any and clearing
2) Defective diaphragm or leak out Replace with new one or lock
on connection face up the nut tightly
6) Disconnection of diaphragm
Correct to normal.
stem from positioner
14
PNEUMATIC CONTROL VALVE
a) Inspect valve disc and seat in the body twice a year. Overhaul and inspect
the diaphragm, diaphragm sliding parts and o-rings (in case of reverse
action type) of control section once a year.
However, when no trouble is observed, overhaul period may be
successively prolonged, and overhaul and inspection must be carried out
with proper intervals
intervals.
15
PNEUMATIC CONTROL VALVE
16
PNEUMATIC CONTROL VALVE
17
PNEUMATIC CONTROL VALVE
11.2 Fitting
11.2.1 Fit the formed ring without distorting the forming as much as practicable.
When putting the ring on the stem from the end of the stem, do not disturb
the shape of the ring. When putting the ring from the side of the stem, twist
the ring to open as shown in the diagram. In this way, deformation of the
ring, which is formed to have even density, can be minimized. It should be
avoided to loosen a ring of inappropriate size and repack it into the stuffing
box.
18
PNEUMATIC CONTROL VALVE
The density of the portions near the cut tends to become low, resulting in
leakage. Arrange the rings so that the cuts overlap once every four rings.
11.2.3 Hammer in one ring at a time with a wood hammer or a plastic hammer
and a bush-shaped jig. (The bush is made of aluminium or brass to prevent
damage to the stem or stuffing box. As for the size of the bush, it is
sufficient to have a small clearance when it is inserted in the box.) If
insertion of the first rings is not appropriate, tightening of the gland nuts will
not generate a clamping force which reaches the bottom of the stuffing box;
effective sealing can not be obtained.
It will also result in partial clamping of only one or two rings near the gland
flange. Such partial clamping has the following demerits;
19
PNEUMATIC CONTROL VALVE
11.4 Lubrication
If an oiler is provided on the side of the stuffing box, feed the specified
grease without fail.
11.5 Retightening
11.5.1 The objective of retightening is to recover the initial clamping pressure. The
procedure is the same with 3.
11.5.2 When exposed to high temperature, packing will experience thermal creep
and loss. Retightening the packing after it has been exposed to the possible
to bring the packing back to the normal temperature, it is necessary to
retighten the packing at the service temperature.
11.5.3 Should a leak be detected when the valve is in service, retighten the
packing immediately to prevent the leak from increasing.
11.5.4 If retightening to stop leakage is frequent and the clamping torque is
excessive,
degrading of the packing may be suspected. As it affects the performance
of the control valve, replace the packing with new one.
20
CHEMICAL DOSING UNIT
INSTALLATION OPERATION
AND MAINTENANCE INSTRUCTION
( CONc 1602 )
TABLE OF CONTENTS
PAGE
1. User Information --------------------------- 3
4. Installation --------------------------- 8
2
CHEMICAL DOSING UNIT
1. User Information
Thank you for having selected CONCEPT c type electromagnetic metering
pump. This instruction manual deals with the correct handling, operation
procedures and troubleshooting for the pump. Please read this manual
through completely first to ensure this equipment are operated safely and
reliably.
Please familiarize yourself with the following designations and symbols:
WARNING
There is a danger to life or a risk of serious injury if the notes on safety are
not observed!
CAUTION
There is a danger of slight injury and damage to property if the notes on
safety are not observed!
2. Safety Notes
WARNING
ㆍTurn off the power supply.
Disconnect cable from mains power supply before commencing
work on the pump, otherwise may cause an electrical shock.
ㆍArrange grounding!
This pump is supplied with a grounding conductor and grounding-
type attachment plug. To reduce the risk of electric shock, be
certain that it is connected only to a properly grounding-type
socket.
ㆍStop operating!
In emergencies the pump should be switched off immediately!
Disconnect the power cable from the power supply!
ㆍ For specified application only.
It is forbidden to use a pump for any other purpose. The pump
may be used only in compliance with the technical data and
specifications given in the operating instructions.
ㆍNo remodeling!
Do not modify the pump in any way or use parts which have not
been tested and approved by us for assembly of company
metering pumps. This can result in damage to persons and
property for which no liability will be accepted!
ㆍWear protective clothing
Always wear protective clothing (goggles and gloves, etc.) when
handling hazardous or unknown chemicals!
3
CHEMICAL DOSING UNIT
CAUTION
ㆍQualified operators only!
The pump must not be operated by untrained and unauthorized
personnel. Pump operators must have a sufficient knowledge of
the pump and its operation.
ㆍSpecified power only.
It may result in damage or fire to use the power supply which
doesn’t correspond to the details device label! Only the specified
power level is to be applied.
ㆍDo not run the pump dry.
Do not run the pump dry(without liquid inside the pump).
Otherwise heat generated by abrasion between elements inside
the pump may damage the pump.
ㆍVentilate!
Dosing toxic or odorous media may result poisonings. Ensure the
operating site with good ventilation.
ㆍFollow the instruction manual.
Replace the wear parts according to the descriptions in the
instruction manual. Do not disassemble any part which is not
regarded as wear parts
in the spare parts.
ㆍLimited operating site and storage.
Do not install or store the pump in the following places:
Places where a flammable gas or material is used or stored.
Places where the ambient temperature is extremely high(45℃ or
higher)
ㆍDisposal of used pump
For disposal of used or damaged pumps, please observe all
locally applicable directives! (Consult a licensed industrial waste
products disposing company.)
4
CHEMICAL DOSING UNIT
3. Product Description
3.1 Functions
It is a microprocessor-controlled short-stroke solenoid-operated diaphragm-
type metering pump for metering liquid, non-combustible media.
Metering is based on a pulsating action. For each pulse coming from the
electronic control, the solenoid energizes and completes a stroke. The
diaphragm, stabilized by a steel core, displaces the medium in the liquid
end, the balls on the intake side are pressed against their seat while the
balls on the delivery side open, thus releasing the medium for metering.
The solenoid is deactivated on completion of the stroke and returned to its
initial position by a spring. In so doing, the valve on the delivery end closes
while the valve on the intake side opens so as to draw medium into the
liquid end. The safety diaphragm protects the leadthrough in the housing
from dust and moisture.
The solenoid-operated, diaphragm-type metering pump covers a capacity
range from approx. 0.7 l/h to 23 l/h (liter specifications at max. stroke length
and max. stroke rate) at a max. back pressure of 1.5 bar to 16 bar. The
recommended stroke length range, which will practically guarantee
metering accuracy, is 30%-100%. The delivery capacity can be adjusted on
the basis of the stroke length by means of a rotary knob and the stroke rate
byy means of a switch. The various operating
p g statuses are indicated byy an
LED for operation and empty/fault signal.
The pump features a connection facility for a single-stage level switch.
5
CHEMICAL DOSING UNIT
* All options except for NP6 & NP7 are with bleeding valves.
** Frequency 60Hz are available for special requirements.
*** 3 or 6 or 9 is necessary for control types 1 & 2.
Viton® is a registered trademark of DuPont Dow Elastomers.
6
CHEMICAL DOSING UNIT
c) Capacity Data
d) Installation dimensions
7
CHEMICAL DOSING UNIT
4. Installation
WARNING
The metering pump can contain water residue in the liquid end as the result
of testing at the factory! If handling media, which must not come in contact
with water, all traces of water must be removed from the liquid end before
start-up! For this purpose, turn the pump through 180°and drain off the
liquid end then flush with a suitable medium from above via the intake
connection.
CAUTION
ㆍPumps must be accessible at all times to facilitate operation and
maintenance.
Access points must not be obstructed or blocked!
ㆍWhen operating the metering pump against a closed shutoff element on
the delivery side, the resulting pressure buildup can reach a multiple of the
maximum permissible backpressure! This can cause the delivery line to
burst! To avoid this, it is advisable to install a ProMinent multifunction valve
which limits the maximum pressure which can be reached!
KANGRIM HEAVY INDUSTRIES CO., LTD.
8
CHEMICAL DOSING UNIT
ㆍOnly use the clamping rings and hose sockets intended for the relevant
hose diameter as well as original hoses with the specified hose size and
wall
thickness otherwise the stability and durability of the connection will not be
guaranteed! Avoid reducing hose sizes! The next higher line cross-section
or a pulsation damper should be used for longer lines and high-viscosity
media.
4.1 Pump installation
ㆍMount metering pump on a tank or
support bracket with bolts and U-
washers (Ø5 mm).
ㆍTo ensure efficient operation, the
valves of the liquid
end must always be positioned
vertically.
ㆍShorten intake lines such that the
foot valve hangs approx.10–30mm
(approx. 50mm for heavily soiled
metering solutions) over the bottom
of the tank.
ㆍInstall
Install delivery line and metering
valve, pressure retention valve for
free outlet.
9
CHEMICAL DOSING UNIT
ㆍThe bleeder valve (10) with bypass (11) is provided on the liquid end.
ㆍFit 4mm inside Ø (max. 6mm) hose on to bypass hose socket (11),
preferably use 6 x 4mm soft PVC.
ㆍIf PE lines are used, secure with a cable tie to prevent slipping.
Insert free end of hose line in metering tank.
ㆍConnect delivery line directly to delivery connection and metering valve.
4.4 Connection of Control Cable and Level Switch
ㆍIf applicable, connect level switch to connection socket (5) on the pump.
ㆍFor control type metering pump, control cable is connected to the pump
(cable length is subject to order by Device Identification Code), please
connect the cable to your control as follows:
External Lock Function provides safer dosing mode for customer: when
External Lock is activated, the metering pump is controlled only by external
control signal,
i.e. if Frequency Selection Switch is switched to 100% or 50% positions, the
metering pump won’t stop, still respond to external control signal. If External
Lock is set inactive, a required operation mode can be selected by
Frequency Selection Switch: When switch to 100%, 50%, the pump will
operate at 100% and 50% of maximum stroke frequency respectively, and
when switch to “contact” or “analog” (External control), the metering
pump will stop.
10
CHEMICAL DOSING UNIT
CAUTION
ㆍFor control type metering pump, when priming, if External Lock is inactive
and External Lock is not reactivated after priming, then over dosing might
occurs, this would be serious to some applications (such as disinfect
d i ki water
drinking t with
ith di
disinfectant
i f t t containing
t i i chlorine).
hl i )
ㆍThe stroke length should only be set with the pump in operation when the
load on the metering stroke setting pin is relieved temporarily.
5.2 Start-
ㆍIn order to prime the metering pump, as for control type metering pump
and when External Lock is activated, if necessary, make External Lock
Inactivated, set stroke length knob (2) to 100% and stroke rate setting knob
(1) to 100%.
ㆍOpen bleeder valve by approx. 1 turn.
ㆍAllow pump to run until a little of the chemical is visible in the delivery line
or emerges at the bleeder valve.
ㆍOn metering pumps without a bleeder valve, the delivery line must be
released at the liquid end or a multifunction valve should be used.
ㆍAfter priming, close bleeder valve (10) or resecure delivery line at
metering valve.
11
CHEMICAL DOSING UNIT
CAUTION
Before carrying out any maintenance and repair work always drain off and
flush out the liquid end first if hazardous or unknown metered media are
used! Observe data sheets of metered liquids!
6.1 Maintenance
Maintenance of the CONCEPT c metering pump is restricted to checking:
ㆍthe liquid end screws (firm fit)
ㆍthe delivery lines (firm fit)
ㆍthe delivery lines (firm fit)
ㆍthe leakage hole at the end disc (moisture can indicate diaphragm failure)
12
CHEMICAL DOSING UNIT
ATTENTION
Turn diaphragm such that the 4
holes in the diaphragm and end disc
are precisely aligned! The outlet in
the end disc must face downward!
13
CHEMICAL DOSING UNIT
ㆍFit liquid end (intake connection must face downward!) with screws on to
diaphragm and end disc (once again leave approx. 5mm space between
liquidend and end disc) such that the parts can still be turnded.
ㆍNow slowly turn parts in clockwise direction until diaphragm is firmly fitted
(resistance of return spring can be felt).
ATTENTION
Do not overturn diaphragm, particularly in Type 1601!
ㆍSet stroke length to 100 % with rotary knob (2) and with metering pump
running, slowly turn thecomplete delivery unit in clockwise direction until the
intake connection faces vertically downward.
ㆍStop pump.
ㆍTighten 4 screws (15) crosswise.
ATTENTION
Observe screw tightening torques!
Check the tightening torque of the liquid end screws after 24 hours of
operation! Additionally check the tightening torques on PP pumps every 3
months!
h !
Tightening torque for screws:
M4: 2.5 to 3 Nm
M5: 4.5 to 5 Nm
ㆍSet required stroke length with pump in operation.
7. Trouble shooting
WARNING
Return the me tering pump for repair only in a clean condition with the liquid
end flushed clean. Pumps which are used for metering radioactive media
must not be shipped!
Breakdown assistance
In order to be able to repair a small breakdown at any time, we recommend
to always keep a spare parts kit in stock - consisting of diaphragm, valves,
balls andseals. See chapter 6 for order information.
14
CHEMICAL DOSING UNIT
15
CHEMICAL DOSING UNIT
8. Spare parts
In order to repair small breakdowns at any time we recommend to always
keep a spare parts kit in stock. This kit contains the following wearing or
spare parts: 1 Intake valve, complete; 1Discharge valve, complete; 1set of
seals; 1diaphragm; 1set of connection part.
16
CHEMICAL DOSING UNIT
Guarantee Form
17
SALINITY METER SYSTEM
INSTALLATION OPERATION
AND MAINTENANCE INSTRUCTION
SALINITY METER
( MODEL : SI - 30 )
TABLE OF CONTENTS
PAGE
1. The Generals of System
1.1 Instruction --------------------------- 3
1.2 Measuring Principle --------------------------- 3
2
SALINITY METER SYSTEM
3
SALINITY METER SYSTEM
1) The white color cable of the sensor is connected to the terminal 4 (' Sensor + ')
2) The white color cable of the sensor is connected to the terminal 5 (' Sensor - ')
3) The red color cable of the sensor is connected to the terminal 6 (' Temp +')
4) The red color cable of the sensor is connected to the terminal 7 (' TEMP.- ')
4
SALINITY METER SYSTEM
5
SALINITY METER SYSTEM
3) If you want to alter the alarm setting value, press the '▲' + key and ▼' - key
at the same time then the current setting value(PPM) will be displayed while
the ALARM lamp is turned on after that set the alarm setting value
as much as you want.
4) After adjusting, Please make sure of saving the altered value by means
pressing the 'ENTER ' key. (Very Important)
5) When occur the alarm, click the 'MENU/ACK' key once then the alarming
will be stopped but the solenoid valve will be still on working.
6) The Power Fail ,,Alarm and Sol'valve output
p function is free contact.
(NO / COM / NC).
7) To keep the salinity operating accurately all the time,
detach the electrode(cell) and clean the sensor at least once a month.
In cleaning the electrode, carefully wipe off dust and scale from
its surface with soft cloth. Do not use sandpaper or other material
whitch may hurt the surface.
6
SALINITY METER SYSTEM
4. Specificaion Sheet
SPECIFICATION SHEET
CUSMOMER :
USED FOR :
1.1 SECIFICATION
NO. DESCRIPTION VALVE ENABLE
1 MODEL SI-30
2 MEASURING RANGE 0 ~ 200 PPM
3 ACCURACY ± 2.5 %
4 TEMP. RANGE 0 ℃ ~ 100 ℃ ( ± 2.0% )
5 CELL OPERATIONG PRESSURE 5 kg / ㎠
6 ALARM POINT 80 PPM ( User can be convert)
A. CONTACT FREE CONTACT ( 250V / 5A )
B. ALARM HORN CONTACT FREE CONTACT ( 250V / 5A )
7
C. SORENOID CONTACT FREE CONTACT ( 250V / 5A )
D. S
SIGNAL
G OUTPUT
OU U 4 ~ 20
0 mA OU
OUTPUT
U
8 POWER SOURCE AC 220V, 60Hz (OPTION : AC 110V)
NOTE :
7
SALINITY METER SYSTEM
5. Drawing Inspection
8
SALINITY METER SYSTEM
9
SALINITY METER SYSTEM
6. Troubleshooting Guide
Condition Cause Solution Remark
Check the power cable or ,
Power fail No power or fuse trouble
replace the fuse.
e oso
Inferiors on tthe
e se
senser
se se
serface
ace Clean
C ea tthe
e se
sensor
so
PPM valve is higher
than normal Wire cut or error of Main-PCB Change the I/O Main-PCB
in the control box. (Contact to the manufacturer)
10
OIL DETECTOR
INSTALLATION OPERATION
AND MAINTENANCE INSTRUCTION
OIL DETECTOR
( CLS-112-2 )
TABLE OF CONTENTS
PAGE
1. INFORMATION --------------------------- 3
2. Features --------------------------- 3
4. Application --------------------------- 3
5. Specifications --------------------------- 4
8. Maintenance --------------------------- 6
9. Repair --------------------------- 6
2
OIL DETECTOR
1. INFORMATION
The Model CLS-112-2 is the versatile Capacitance Type Level switch that
can detect the level of sediments in liquid, interface between two different
liquids as well as the level of high- insulating powders / granules, conductive
liquids / viscous liquids and others. It is one of the highly efficient detectors
whitch Si-Marine Co.,Ltd. has developed to ensure a correct level detection
under such conditions requiring the high technology as varied measuring
materials, complex / harsh products and so on. Through our long-term
experiencrs and achievements, use of quality materials and strict quality
control, we have here provided you with more stable and reliable products.
2. Features
ㆍChemically highly resistant materials.
ㆍHighly sensitive and stable meter .
ㆍMaintenceance - free.
ㆍCan easily detect highly corrosive substance .
ㆍRugged construction.
ㆍInsensitive to buildup.
ㆍCan easily install and adjust .
3. Principle of Operationon
This measures the impedance variation coming out between a main
electrode and a tank-wall or between the main electrode and an earth
electrode. As the level rises, the capacitance value goes up, and it provides
a contact output when the level exceeds the set value.
4. Application
ㆍINTERFACE : Oil and Water mercury in the Water alcohol and Acid,
Sediment in the water liquid and foam.
ㆍPOWDER : Plastic power, Slaked lime, Carbon, Iron oxide, Dust, Soil and
Sand, Surgar, Flour and others.
3
OIL DETECTOR
5. Specifications
▶ Installation Method : Top Mounting , Side Mounting.
▶ Conn. Size : PF 1" Thread , JIS 10K 50A FF Flange Type.
▶ Cable Gland : PG 13.5 * 2
▶ Power Supply : AC 110 / 220 V / 60HZ
▶ Output : Relay(SPDT) Contact , 250VAC 5A
▶ Material : Housing ~ ADC12
Connector ~ SUS 304
Probe ~ SUS316L
▶ Max. Pressure : 10 Kg/Cm2
▶ Max. Temperature : -40 ~+80℃
▶ Frequency : 400KHz
▶ Power Consumption : Max. 1.5W
▶ Protection : IP66
①POWER LAMP
②INDICATOR ALARM LAMP
③TIME DELAY RANGE
④SENSITIVITY ADJUST RANGE
⑤COARSE RANGE
4
OIL DETECTOR
6. Adjustment Elements
ㆍPOWER LAMP
Diode for indication of the switching status (DC or AC power supply).
ㆍINDICATOR LAMP
Diode for indication of the switching status (when any of substances
are contacted on the probe).
ㆍTIME DELAY ADJUST RANGE
Turnning the switch to the clockwise the reponse speed of the contact
signal will be slow then it can prevent the sensing error by the rolling of the
liquid or solid.
ㆍSENSITIVITY ADJUST RANGE
At the Low position, it senses from the top of the probe, when it indicates
60, it senses from the middle of the probe. When it is 80, it senses from the
20mm place from the edge of probe and when it is the High position it
senses from the the edge.
ㆍCOARSE RANGE
The sensing position can be adjusted by turnning the coarse switch to the
colokwise.
7. Functional Table
5
OIL DETECTOR
8. Adjustment Elements
The instrument is maintenance free.
9. Repair
For safety and warranty reasons, any internal work on the instrument, apart
from installation and wiring, must be carried out only by us
6
FUEL OIL FLOWMETER
INSTALLATION OPERATION
AND MAINTENANCE INSTRUCTION
TABLE OF CONTENTS
PAGE
1. Applications --------------------------- 3
2. Features --------------------------- 3
2
FUEL OIL FLOWMETER
1. Applications
• Flow measurement of mineral oils such as heating or propellant fuels
• In burners, on board ships, land vehicles and fixed installations
• Marine and metrological type approvals (optional)
2. Features
• The complete range of products offering the best solutions for the
measurement of oil consumption.
• State-of-the-art design with electronic counter, flow indication, analogue
and digital output signals and limiting value switch.
• Mounting on the pressure or suction side of a pump, with no straight inlets
or outlets required.
• Independent of viscosity and temperature
• High vibration resistance
• Classical version with mechanical display
3. Your benefits
• The reliable solution with everything from a single supplier.
• Reliable monitoring and flexible control of the system. Simplifies burner
settings and optimising consumption.
• Highly flexible mounting with very small space requirements
• Accurate measurements
• Maximum safety in the shipbuilding and automobile industries.
• Cost-effective metering point
3
FUEL OIL FLOWMETER
VZFA
Electronic display of
• totaliser, total and resettable volume
• actual flow rate
• other flow parameters
Output signals for
• volume pulses
• actual flow rate
• limiting values (Qmin, Qmax)
Simple to operate
Interactive parameter input
External power supply
4
FUEL OIL FLOWMETER
VZOA 4 and 8
• Volume display on roller counter
VZOA 15...50
• Volume display on roller counter
5. The world’s
world s most frequently used oil consumption meter
Leading manufacturers of oil burners and operators of heating systems,
ships or diesel engines rely on CONTOIL® fuel oil meters - and with good
reasons.
5
FUEL OIL FLOWMETER
Areas of application
• to measure heating fuel consumption by oil burners (for example, in
heating boilers, industrial furnaces, tar processing plants, ships boilers)
• to measure propellant fuel consumption by motors and engines (such as
diesel locomotives, construction machinery and ships, or in emergency
power units, combined heating and power stations)
• consumption monitoring and optimisation
• flow measurement for mineral oils
• optional remote processing and integration into superior systems
• manual dosing / batching
• flow measurement for machine and motor/engine oils
• engine test benches
Fuel types
• heating fuel extra light / light, medium, heavy
• naphtha
• diesel
• petrol and other lubricating liquids
6
FUEL OIL FLOWMETER
7
FUEL OIL FLOWMETER
Display values:
• total volume, resettable volume, flow rate.
• In the information menu, hours of operation and other information can be
Obtained.
Display:
• 8-character LCD with identification of the parameter, height of numbers: 8
mm, flow rate (meter load) using bar indicator
Temperature:
• ambient temperature -25
25 … +70°
+70 C,
C
storage temperature -25 … +85° C
Safety:
• CE, vibration and shock test to DIN IEC 68
Power supply:
• 24 V DC (6...30 V DC)
Data preservation:
• by non-volatile memory (EEPROM)
Protection class:
• IP66 (IEC 60529) against water jets and dust
8
FUEL OIL FLOWMETER
6.3 Outputs
Four different output functions are available:
• Pulser for volume pulses with programmable pulse value (for external
totaliser)
• Analogue current output 4...20 mA corresponding to flow rate
• Frequency output 0...100 Hz corresponding to flow rate
• Switching function (limiting value switch) specified by programmable upper
and lower flow rates
Except for the current output function, any two of the remaining three
functions can always be used simultaneously. This results in two
types of connection:
9
FUEL OIL FLOWMETER
Volume pulses
Pulse width t: 5, 50, 250, 500 ms
Pulse value: parameterisable
Current signal
• Flow rate at 4 mA Q1 : parameterisable
• Flow rate 20 mA Q2 : parameterisable
• Attenuation: parameterisable
Frequency signal
Output frequency fmax: 100Hz
Pulse ratio: 1:1
Frequency / Flowrate f1/Q1: parameterisable
Frequency / Flowrate f2/Q2: parameterisable
10
FUEL OIL FLOWMETER
Dimensions
Ordering specifications
11
FUEL OIL FLOWMETER
12
FUEL OIL FLOWMETER
13
FUEL OIL FLOWMETER
5) RE Pulsers
6) Ordering specifications
14
FUEL OIL FLOWMETER
15
FUEL OIL FLOWMETER
1) Safety precaution
When connecting the Reed pulser to a low-voltage power source (50...250
V AC/DC), the specialist installing the equipment is responsible for ensuring
that all local regulations are observed (e.g. regulations for electrical
installations, personnel safety).
16
FUEL OIL FLOWMETER
4) RE Pulsers
6) Ordering specifications
17
FUEL OIL FLOWMETER
7.3 VZO 15 … 50
Technical data 1)
• Volume display on roller counter, in litres
• fuel oil meter with threaded or flanged ends
• for horizontal, vertical or inclined mounting
Option: Reed pulser or RV / IN pulser
Versions available on request:
• different flange drillings, such as ANSI, JIS
2)
• meters in US gallons (option)
18
FUEL OIL FLOWMETER
This type of pulser is integrated into the roller counter and thus is
especially appropriate for remote totalisation. For other applications the IN
inductive pulser is preferable.
19
FUEL OIL FLOWMETER
4) IN Pulsers
20
FUEL OIL FLOWMETER
6) Ordering specifications
DN 15 only when the plant has a dirt filter with a max. 0.1 mm mesh size.
21
FUEL OIL FLOWMETER
The meters are marked “supply” and “return” during calibration and final
testing in the factory. They must then be installed in the correct pipes.
For further information on the subject of differential measurement, see the
sections “How to obtain an optimal measurement” and "Application
examples".
22
FUEL OIL FLOWMETER
23
FUEL OIL FLOWMETER
Technical data 1)
• Versions for optimal results from differential measurement or for fiscal or
commercial transactions
• VZFA with electronic display of total volume, resettable volume and flow
rate; units of measurement: litres, US gallons 2) or m3.
• VZOA with display of total volume on roller counter; units of measurement:
litres.
Optional versions with counter in US gallons.
• VZOA option: with RV reed or IN inductive pulser
• threaded or flanged connections available
• mounting in horizontal or vertical positions possible (for calibrated meters
horizontally only).
• VZFA: User-friendly, interactive parameter input. Easy integration into
control systems. Further Versions available on request:
• different flange drillings, such as ANSI, JIS
24
FUEL OIL FLOWMETER
Note.
1) Manufacturer's specification, valid for the reference conditions as
specified under “APPENDIX: Meter data”.
2) 1 US gallon corresponds to 3.785 litres
3) For burners and engines or motors, the meter must be selected on the
basis of the permanent flow rate. For higher viscosities, or if the meter is
installed on the suction side, the pressure drop and any reduction in the
measuring range must also be taken into consideration.
4) Weight without couplings.
5) Two freely selectable outputs are available, totally independent of each
other.
1) Technical data for VZOA with PTB certification: 5.232 / 04.37 Class 1
Two items are required when ordering: the VZOA meter and EEC legal
verification, Order No. 96026.
1)
For burners and engines or motors, the meter must be selected on the
basis of the permanent flow rate. For higher viscosities, or if the meter is
installed on the suction side, the pressure drop and any reduction in the
measuring range must also be taken into consideration.
25
FUEL OIL FLOWMETER
3) Dimensions VZFA
4) Dimensions VZOA
26
FUEL OIL FLOWMETER
10) Ordering details for VZFA (meters with electronic counters and
parameterisable outputs)
27
FUEL OIL FLOWMETER
28
FUEL OIL FLOWMETER
9. Accessories
1) Ordering details for accessories
29
FUEL OIL FLOWMETER
10.2 Construction
Rotary piston, guide roller and drive are the only moving parts in contact
with the liquid. Their movement is transmitted by a magnetic coupling
through a sealing plate. The hydraulic part is completely separated from the
totalising module.
1) VZF/VZFA 15 ... 50
Connections are made radially with two cable entries
underneath the display unit which can be mounted and
rotated through 90° steps.
2) VZO/VZOA 15 … 50
With the exception of the counter with the RV Reed
pulser, the roller counter can be rotated through 360° for
optimum readability.
3) VZO/VZOA 15 … 50
The connections for the inlet and outlet are situated
vertically from below in the base plate. With the OEM
meter version the connections are situated on the side.
30
FUEL OIL FLOWMETER
31
FUEL OIL FLOWMETER
Viscosityy diagrams
g : A = 5 mPa.s C = 100 mPa.s E = 500 mPa.s
B = 50 mPa.s D = 200 mPa.s
For a pressure drop of more than 1 bar, it is recommended to use the next
larger meter size. Maximum permissible pressure drop = 3 bar
32
FUEL OIL FLOWMETER
Viscosityy diagrams
g : A = 5 mPa.s C = 50 mPa.s E = 200 mPa.s
B = 25 mPa.s D = 100 mPa.s F = 500 mPa.s
For a pressure drop of more than 1 bar, it is recommended to use the next
larger meter size. Maximum permissible pressure drop = 3 bar
33
FUEL OIL FLOWMETER
※ Example
Mineral oil, viscosity 450 mPa.s
VZO 25 mounted on pressure side of
pumps
❶ Viscosity curves DN 25
select closest curve
F = 500 mPa.s
❷Assume max. permissible pressure
drop = 1 bar
❸ The intersection of curve F with
the line corresponding
to 1bar gives a flow rate of 2000 l/h.
34
FUEL OIL FLOWMETER
S = Special versions
2) Dimensions in mm
35
FUEL OIL FLOWMETER
36
FUEL OIL FLOWMETER
37
FUEL OIL FLOWMETER
1) Only in accordance with the maximum mesh size of the dirt filter as per
technical data.
2) Determine conditions of use with supplier (other measured values!).
3)) DN 15 onlyy when the p
plant has a dirt filter with a max. 0.1 mm mesh size.
4) Two freely selectable independent outputs are always available.
※ Application note
For viscosities higher than 5mPa.s or for installations on the suction side of a
pump, pressure drop and possible limitation of flow range
must be taken into consideration.
38
FUEL OIL FLOWMETER
600 kW
= 62 l/h
11.8 kWh/kg x 0.82 kg/dm3
12.2 Engines
39
FUEL OIL FLOWMETER
Formula:
1 HP = 0.736 kW 1 kg Diesel at 0.84 kg/dm3 = 1.19 l
1 kW = 1.36 HP
Rule of thumb:
approx. 190 g/kWh correspond to 0.226 l/kWh
approx. 140 g/HP correspond to 0.167 l/HP/h
13. How to obtain an optimal measurement
13.1 Planning
Flow meters are precision measuring instruments.
They achieve optimal results if
• a few important rules are observed during plant design,
• mounting and commissioning are carried out with care,
• the meters are used for their defined purpose only.
40
FUEL OIL FLOWMETER
41
FUEL OIL FLOWMETER
13.8 Filling/Dosing
42
FUEL OIL FLOWMETER
b) for the semi conductor relay output: (volume pulses, frequency signal,
limit switch)
Limiting factors depend on the input specification of the higher system or
the totalizer. The ability of the input to detect the actual state of the switch is
specified by the system manufacturer.
For the relay switch a maximum of 100Ω at ON-state has to be considered
together with the cable’s resistance. A minimum of 10MΩ at OFF-state has
to be considered together with the cable’s capacity. The maximum
permissible length of the cable depends on the individual properties for
resistance and capacity.
43
FUEL OIL FLOWMETER
RV IN
b) Selection of the appropriate pulser
The selection of the most appropriate pulser and pulse value depends on
the application. As a rule, remote totalisation demands rather large pulse
values, whereas analogue signals, dosing control or indication of actual flow
rate tend to need small values. Battery supplied devices can only be used
together with Reed pulsers.
44
FUEL OIL FLOWMETER
e) Pulse values
Pulse values depend on type and nominal size of the meter. They are
listed in the technical information of the meter concerned.
f) Pulse period
Pulse period as well as on- and off-times can be calculated with the
following formula:
pulse value in litres 3600
Pulse period in s =
flow Q in l/h
pulse period in s x on-time in % of pulse period
On-time =
100
We recommend that this calculation be carried out for the highest and
lowest expected flow rates.
45
FUEL OIL FLOWMETER
b) Differential measurements
For differential measurements, the piping remains unchanged, with
circulation back into the tank. A flowmeter is installed in both supply and
return pipes. The consumption is determined as the difference between the
amount in the supply section and the amount in the return section. The
meter loads therefore correspond to the supply and return flow rates.
For an optimal result, special meters are therefore used for differential
measurements. These are precisely matched to the operating conditions
and are calibrated in pairs. This means that the measurement error can be
significantly reduced (for example: ±0.1% at constant flow rates on the
supply side and ±0.3% with slightly variable flow rates on the return side).
46
FUEL OIL FLOWMETER
47
FUEL OIL FLOWMETER
The magnetic valve opens as soon as the pressure drops below a defined
level.
If the flow meter is installed on the suction side of the pump, the pressure
drop at the max. allowed flow rate and highest possible viscosity must be
taken into account. Also to be considered are installed filters.
48
/0%2!4)/. !.$ -!).4%.!.#% -!.5!,
-ARINE BURNERS
41'"
1.1. Forewords................................................................................................................................. 5
1.2. Conventions in this Manual ..................................................................................................... 5
1.3. Type labelling on Oilon burners .............................................................................................. 6
1.4. General information.................................................................................................................. 7
1.5. Inspecting boiler room ............................................................................................................. 8
2. Burner operation
6. Technical data
1. General
1.1. Forewords
Thank you for using Oilon-products. We hope you are content with the product and our
service. This manual is intented to guide operation and maintenace of the product. We
pursue to improve our products and services. Therefore we readily accept feedback
about on our operation and maintenance manuals. Feedback may be sent to info@oilon.
com
KEEP THIS MANUAL ALONG WITH THE INSTALLATION RECORD AND THE
ELECTRICAL SCHEMES AVAILABLE NEAR THE BURNER!
GRP-150 M-II
1 2 3 4
Label element 1: Fuel
H Two-stage
T Three-stage
M Modulating
ME Modulating with a separate fan
P High-Low or modulating with an electronic controller
LH High-low with a preheater
On-Off
BURNER CONTROL
BURNER APPLICATIONS Most heating appliances such as hot water
boilers, steam boilers, air heaters and thermo
fluid boilers
APPLICABLE FUEL . The burners are suitable for use on
heavy fuel oil, with a viscosity of max.
380 mm²/s (cSt) at a temperature of +50
°C and on burners with electric tracing
max. 700 mm²/s (cSt) at a temperature
of +50 °C.
. Temporarily light fuel oil
MINIMUM VISCOSITY FOR IN-LET OIL 1.5 mm²/s (cSt)
IN-LET OIL TEMPERATURE The temperature of oil coming to the burner
should be from 60 to 100 degrees Celsius.
OIL FILTRATION The oil coming to the burner must be filtered
before the oil pump. Maximum filtration
degree is 125 μm.
PREHEATER Oil is preheated in the burner's preheater to
the atomizing temperature. The oil
temperature is controlled by an electronic
regulator.
HEAT CARTRIDGES Oil pump and solenoid valves are equipped
with heat cartridges.
ADDITIONAL HEATING The burner pipes are equipped with trace
heating
HEAVY FUEL OIL ATOMIZING VISCOSITY
LIGHT FUEL OIL ATOMIZING VISCOSITY 1.5 to 12 mm²/s (cSt) at a temperature of +20
°C
OIL ATOMIZING PRESSURE 25 - 30 bar for heavy fuel oil
20 - 25 bar for light fuel oil
OIL PUMP RP 130 M : TA2
RP 140 M : TA2
RP 150 M : TA2
RP 250 M : TA3
RP 280 M : TA3
NUMBER OF NOZZLES 1
NOZZLE CONTROL Nozzle valve piston opens the nozzle. The
nozzle valve is controlled with a solenoid
valve.
BURNER MAX. TURNDOWN RATIO 1:2,5 (100 - 40 %)
COMBUSTION AIR FAN The fan provides the air needed in the
combustion. It is dimensioned to provide a
sufficiently high and even air pressure for
efficient combustion in modern combustion
chamber.
REQUIRED COMBUSTION AIR QUANTITY 15 m³ of combustion air for each burnt kilo of
oil
SERVOMOTOR AND COMPOUND Controls the burner capacity and the air/fuel
REGULATOR ratio according to the capacity demand.
OPERATING TEMPERATURE 0... + 45 C°
. Make sure the burner room combustion air gap (air in-let hole) is open.
. Make sure the shut-off valves on pressure gauges are shut.
. Make sure tightness of the pipeworks, safety appliances of the boiler system,
pipeworks, and the burner are checked regularly according to rules and regulations of
public authorities.
. Check boiler and it's components.
. Making a maintenance contract is recommended.
Never use a naked flame while checking the burner or the boiler.
Never store any inflammable material in the boiler room.
Wear hearing protectors, if there is noise in the boiler room.
2. Burner operation
Burner device has been provided with a fan that is tailored to produce high and steady air
pressure, that is required to get a flawless ignition and good combustion in a modern
combustion chamber. A servomotor controls the amount of air feeded according to the
amount of fuel combusted.
During purging period solenoid valve (NC) is closed and solenoid valves (NO) and main
solenoid valves (NC) are open. During this time oil does not flow through the control
circuit, but only to the nozzle valve of the utilisation circuit.
After the end of the purging period servomotor turns to the position of ignition load and
solenoid valve (NC) opens and solenoid valve (NO) closes. The oil pressure begins to
take effect on the nozzle control circuit. Oil flows from the nozzle. Spark between the
ignition electrodes ignites oil spraying from the nozzle.
2.1.3 Atomizing
During burner operation the capacity controller drives the servomotor, which drives the oil
regulator and air dampers between partial load and full load according to the capacity
demand.
If the burner shuts down, solenoid valve (NC) and main solenoid valves close, solenoid
valve (NO) opens. Oil pressure is released from nozzle valve. Nozzle valve springback
closes the needle valve in the nozzle and closes the oil flow in the nozzle.
The oil quantity to be burnt (= burner capacity) is regulated by means of the oil regulator
by throttling the oil return flow. At partial load the oil regulator is open and at full load
closed.
To get a sufficient viscosity for the fuel atomizing the oil temperature is raised with a
preheater device. The temperature of the heated oil is controlled electronically.
Atomizing pressure is provided by the burner oil pump.
In-let oil pressure to the pump varies case-specificly; See 'Pump adjustments'.
5 23
19
*17
PS
16
20
PI
6 M
18 RE RE
21
5 7
* 11 15
14
* 12 12
4 PI PS 25
10 TZA
3 2 6
TI
9 9
* TE TIC 13
24 8
1 22 B-552E_2
1. Return to tank
2. Oil to Burner
3. Oil filter
4. Oil pump
5. Pressure gauge
6. Closing valve (normal position closed)
7. Pressure switch
8. Temperature indicator and controller
9. Main solenoid valves, NC (Normal closed)
10. Preheater
11. Limit thermostat preheater
12. Flame detector
13. Temperature indicator
*
PS
* PI
M
M
EL.TR
PS
*
RE RE
*
PI PS
* TZA EL.TR
EL.TR EL.TR
TI
TE TT
EL.TR EL.TR
B-526A_1
Shutdown period
*
PS
* PI
M
M
EL.TR
PS
*
RE RE
*
PI PS
* TZA EL.TR
EL.TR EL.TR
TI
TE TT
EL.TR EL.TR
B-526A_1
Purging period
*
PS
* PI
M
M
EL.TR
PS
*
RE RE
*
PI PS
* TZA EL.TR
EL.TR EL.TR
TI
TE TT
EL.TR EL.TR
B-526A_1
Atomizing period
M B
NO
C NC
p
5
M D
2,5s
2
F
15s
TE H
CC
PT
5s
22.5s
I * 9 10 I
PID
J V V
IV * III IV
ON/OFF
II * II
K
5s
4 7 8
M L
3
1
M
13
5s 35s 15s
1 2 3 4 5 6 7 8 9 10 11 X W 12 13 14
W W
LAL2.25 3 P 7 1 12
p_103154.1
A Control loop
B Fan
C Differential air pressure switch
D Oil pump
E Main solenoid valve, NC
F Ignition transformer
G Control circuit solenoid valves, NC and NO
H Capacity controller
J Air dampers
K Adjustable cam disc, air
L Servomotor
M Oil regulator
N Nozzle valve
O Flame signal
W Sequence switch stopped
X Sequence switch idle steps
* Required start signal to control unit terminal 8
2.4.2 Sequence point 1.1. Start-up (lockout indicator of the control unit is at symbol ◄)
2.4.5 Sequence point 4. Servomotor has run to switching point I (Air smapers are open)
. Start signal from the limit switch of switching point I to terminal 8 in control unit.
Otherwise the start-up program interrupts and the control unit remains (symbol ▲)
waiting for start signal (no failure).
. Pre-purge (22,5 s) with nominal air quantity begins.
. Differential air pressure switch has to have changed its contact over to position C/NO.
2.4.9 Sequence point 8. Servomotor has run to switching point III (ignition load)
. Required start signal from the limit switch of switching point III to terminal 8 in control
unit. Otherwise the start-up program interrupts and the control unit remains (symbol
▼) waiting for start signal (no failure).
. Contact of return oil pressure switch (max.) must have been closed (C/NC)
. in control circuit of nozzle valve solenoid valve NC opens and solenoid valve NO
closes
. Oil pressure is released to control circuit of the nozzle valve. Nozzle valve needle
moves back and opens the nozzle valve.
. Fuel atomizing from the nozzle begins with pressure set for ignition phase.
. Oil spraying through the nozzle is ignited by the electric arc
2.4.12 Sequence point 11. Lockout indicator of the control unit is at symbol | (operating)
. Burner operates thus supervised by control unit and controlled by capacity controller
according to set controller parameters and functions (see documentation of
controller)
. Burner shuts down when the load is small and the process value exceeds the burner
switch-off level set on the controller or controlled by the boiler thermostat/
pressurestat. In manual operation the burner shuts down controlled by the boiler
thermostat/ pressurestat only.
. If the oil temperature rises above the set limit on the preheater limit thermostat- the
burner shuts down. (thermostat lockup)
. stop and restart if the flame signal is lost during operation (wire link B has been cut
away from the from the plug section of the control unit)
. Stop and restart if the return oil pressure rises too high
Wire link B has been cut away at the factory.
2.4.14 Sequence point 13. Lockout indicator of the control unit is at symbol ◄
. Permissible after-burn time (15 s) ends
. Flame simulation tests initiate in control unit.
. Sequence switch stops
. Fan motor stops
Re-start possible, if the prerequisites for start-up are fulfilled (see Sequence point 1.)
XII ab
t10 t13
XIII ab
XIV ab
t8 p_101472.20
LAL2.25 P 1
a p_101472.4 b b' a
Lockout indication
. a - b = start-up sequence
. b - b' = idle steps (operation)
. b(b') - a = post-purge sequence (reset of control unit)
Numbers 4...20 are the control output contacts from the sequence switch relay
2.5.2 Switching times (in seconds) of the control program of the sequence mechanism
Switching times in seconds in the sequence of the burner start-up are valid for frequency
of 50 Hz. For 60 Hz frequency, switching times are reduced by approx. 20 %.
2.6.1 Principle
In case of any fault fuel injection is stopped immediatly. The sequence mechanism stops
along with the lockout indicator. The symbol above the reading mark of the indicator gives
the type of fault.
2.6.3 Restart
The control unit can be reset immediately after a lockout has occurred. After resetting (as
well as after correction of a fault, which resulted in a controlled shutdown, or after each
mains failure) the sequence switch always returns to its start position, whereby only
terminals 7, 9, 10 and 11 receive voltage in accordance with the control program. It is only
then that the control unit begins with a new burner start-up.
Do not keep the reset button pressed for more than 10 seconds.
1. Reset button
2. Program indicator
3. Fuses
. Control unit is a safety device. It is NOT allowed to open nor make altera-
tions or adjustments to it.
. The control unit must be completely separated from supply voltage before
carrying out any procedures to it.
. All safety functions must always be tested when using for the first time
and after changing the fuse.
. The control unit must be kept safe from water drops and sprays at all
times
2.7.1 Description
Additional heating keeps the burner ready for use. Additional heater devices ensure oil
fluency by keeping oil viscosity adequately low.
Keep heating on at all times. If the heaters are turned off they must be turned ON AT
LEAST 2 HOURS BEFORE starting the burner.
Pump Suntec
Solenoid valves
2
D3 L2
60 °
D1 D2 L2
L1
1. Gasket
2. Mounting plate
3. Ceramic wool or similar
4. Refractory
Burner Dimensions in mm
D1 D2 D3 D4 L1 L2
RP130 200 240 M16 215 200 275
RP140 240 280 M16 255 220 275
RP150 270 310 M16 285 230 275
RP250 270 310 M16 290 300 365
RP280 300 340 M16 320 312 365
The threads of the bolts must be coated with graphite-bearing grease prior to fitting
The burner has to be installed in such a way that the motor shaft lies horizontally;
however, it is not allowed to install the burner upside down.
Remove the transportation bracket after the burner is attached to the boiler
Make sure there is enough free space on the side to allow the burner to swing fully open
The burner must be installed firmly. Vibrations may damage burner or its
components.
As standard the burner can be hinged to the left. The burner can be changed to be hinged
to the right by changing the position of the hinge pins.
Switch off the electric power from your burner before burner swing-out.
ZA
C PI
PS PS TI
PI PI
A
M
B-552E_1
The oil throughput from the pumping unit must be at least 1,2 x quantity of oil to be burned
kg/h + 150 kg/h
Example
If Then
burner capacity is 200kg/h throughput must be
1,2 x 200 kg/h + 150 kg/h = 390 kg/h
Leave neutral
hose ends long
enough
B-440J
The accumulated gas must be able to vent from the deaerator. Always install the
degassing unit upright.
In case the de-aerator is installed separate from the pump, the connecting line has to be
trace heated and the pump has to be equipped with a heating cartridge.
3.6.1 Connections
The burner must be connected according to the electrical diagrams delivered together
with the burner. General and local standards and regulations as well as requirements of
electrical equipment on electrical connections must be adhered to. Burner instru-
mentation has to be configured with a switch that allows it to be disconnected from the
low-voltage supply mains.
. Check the boiler and it's components are in proper working order
. Check the pipings are installed correctly and the joints are tight and have no leaks
. Check there is sufficiently water in the heating system
. Check there is adequate air inlet to the boiler room for the burner to have sufficiently
air for combustion
. Check there is fuel in the oil tank
. Check electrical connection points (inputs/outputs) are correct
Prior to first start-up the oil pump must be vented. The pump must not operate
without oil. See chapter ”Oil Pump".
15. Use an oil flow meter to check minimum capacity. ( Minimum capacity preadjusted at
the factory )
16. increase capacity step-by-step by adjusting the screws.
17. Use a gas analyzer to adjust optimum values for the combustion.
18. Use an oil flow meter to check maximum capacity. ( Maximum capacity preadjusted
at the factory )
19. Test the safety equipments on the burner.
Never use a naked flame while checking the burner or the boiler. Never
store any inflammable material in the boiler room.
260 720
700
W1-180
680 W1-500
240 660
640
220 620
W1-160
W1-450
600
200 580
W1-140 560
180 540 W1-400
W1-125
520
160 500
W1-112
480 W1-360
460
140
W1-100 440 W1-330
420
120 W1-90
400 W1-300
W1-80 380
W1-275
100 360
W1-70
340
80 320
25 26 27 28 29 30 25 26 27 28 29 30
340 880
W2-275 860
320 840 W2-700
820
300 W2-250 800
780 W2-650
280 760
W2-225
740
720 W2-600
260
700
680
240 W2-200
660 W2-550
640
220 W2-180 620
600 W2-500
200 580
W2-160
560
180 540 W2-450
W2-145
520
160 500
W2-130
480 W2-400
460
140 W2-115
440 W2-360
420
120 W2-100
400 W2-330
W2-90 380
100 W2-80 360 W2-300
340
80 320
25 26 27 28 29 30 25 26 27 28 29 30
ATOM IZING PRESSURE bar
FOR EXAMPLE
P = boiler capacity kW
μ = boiler efficiency, 0,80-0,95
q = P/μ *Q Q =heat value, kWh/kg
q = fuel demand, kg/h (Note! all nozzles)
Heat value for light fuel oil approx. 11,86 kWh/kg and for heavy fuel oil approx. 11,22
kWh/kg. Check exact values from supplier.
Cam switches (limit switches) are set at the factory during testing as follows:
II burner shutdown
III ignition load
IV load, when changing over from ignition load to partial load
V partial load, when changing over from full load to partial load
I full load
A-492V
5
1. Flame tube
2. Adjustment ring
3. Diffuser disc
4. Combustion head extension
5. Locking of adjustment ring
4.4.3 Note!
If the position of the adjustment ring has to be altered in relation to the diffuser disc, the air
velocity and quantity in the combustion head will change. Check the combustion values by
flue gas analysis and, if necessary, adjust the combustion air quantity to be adequate.
1. Check the surplus oxygen level from the gas flue after every adjustment with a flue
gas analysator.
2. Set the combustion air levels within the operation range of the servomotor
Guideline values
A-459Z
L
P
N M
H 17 mm
K 3,5 mm
L 6 mm
M 8 mm
N 12 mm
P 4 mm
TA
6 7
1 2
4
A-212Z
8
3
Min. oil inlet pressure to burner 2.5 bar or higher depending on oil
temperature at the pump. See illustration.
In-let oil temperature range: Heavy fuel oil 60 - 100 C°
Pump operating pressure (=atomizing 25 - 30 bar
pressure) for heavy fuel oil
Pump operating pressure (=atomizing 20 - 25 bar
pressure) for light fuel oil
The diagram shows the required oil inlet pressure to the burner.
Check the inlet pressure to the burner from the the pressure gauge fitted to the filter
cover.
P max. 5
3
P min.
A B
C)
50 100 150
T min. T max.
Example A :
Example B :
Use the pressure adjustment screw. Turn the screw clockwise to increase the pressure.
Install a pressure gauge/valve -assembly if necessary.
4.8. Preheater
B-348M
1 2 3
8 7
100 C
C
75
150
50
2 1
1. Heater
2. Temperature sensor of limit thermostat
3. Controller sensor
4. Temperature controller
5. Limit thermostat
6. Limit set point - Low
7. Signal lamp, temperature low
8. Signal lamp, control
The burners have electrical preheaters which consists of one or several heating units.
The heating units have one common regulator, and individual thermostats.
The connectors in the control box are under voltage. The safety cover is
allowed to be opened only by authorized staff.
CAL 8000 C
A
B C
D E
100
150
F
G 50
90
H p_101739.10
I
Controller has three LED's, that operate in five steps and indicate the deviation of the
actual value from the set point. Each step operates for 2 % (4 °C) of full scale (0...200 ºC).
SIGNAL MEANING
more than 6 °C below set value
The limit thermostat is adjusted at the factory and sealed with paint. Set value is +180°C .
The limit thermostat has a reset button. Use the reset when the limit thermostat is not
energized.
Do not open the sealed locking screw. Breaking the seal voids warranty
The oil quantity to be burned is determined by nozzle size and oil pump pressure. The oil
regulator controlled by the servomotor regulates the return oil flow according to the
capacity demand.
At partial load the oil regulator is open so that the oil throughput in the valve is at
maximum and return flow pressure and nozzle capacity are adequate.
At full load the oil regulator is closed whereupon the oil throughput is at minimum and the
pressure at maximum. The air quantity is matched to the oil quantity to be burnt by means
of the spring band on the adjustable cam disc (see ”Adjustable Cam Disc”).
The burner is preadjusted at the factory. Accurate adjustments to be made with a flow
meter at site
5. Maintenance
Cut off electric current from the burner and close manual shut-off valves
always before any maintenance work. Cutting power is adequate when
just inspecting the device.
5.1.1 To maintain flawless operation it is recommended to do the following at least once a year:
Correct installation and adjustments and regular maintenance ensure correct operation of
the burner.
5.1.2 Note!
The burner contains electric and electronic components. Adhere to rules and regulations
from local authorities when disposing.
5.2.1 Components
. Unscrew fixing screws of the combustion head and withdraw the combustion head.
The combustion head extension is fixed with rivets to the combustion head guide.
. Reassemble in reverse order
1 2 3 4 7 5 6
B-389P
1. Burner body
2. Fixing screw for combustion head
3. Combustion head guide
4. Adjustment ring
5. Diffuser disc
6. Combustion head extension
7. Nozzle
2 3 4 5 6 7 8 9 1. Mantle
2. Cover
3. O-ring
10
4. Gasket
11 5. Hexagon head plug
1 B
6. Hexagonal screw
7. Gasket
12 8. Spring
9. Filter element
10. Washer
11. O-ring
A-525G
12. Label
13. Plug
14. Nut
A - Oil to filter
A B - Oil to burner
14
13
5.3.2 Note!!
Before cleaning of the filter make sure, that oil does not flow to the filter.
5.3.3 Cleaning
. Remove the plug by loosening the nut.
. Loosen the hexagonal screw and open the filter cover and remove the element. A
suitable solvent and a soft brush, which does not damage the screen, can be used for
cleaning of the element.
. If there is some dirt in the filter, it can be removed by for ex. vacuuming. Check the
condition of O-rings as well as the condition of the washer.
. Lock the plug with nut.
. Place the filter element into the filter and then the cover.
. Fasten the fastening screw on the cover with a torque of 25 - 30 Nm.
Switch off the electric power from the burner and ensure the motor is not
under voltage. Remove motor fuses if necessary.
5.4.1 Components
1-2 mm
A-429L
1. Motor
2. Fan wheel
3. Oil pump
4. Intermediate shaft
5. Coupling head
6. Wedge
7. Intermediate bushing
8. Fixing screw for fan wheel
9. Base bushing
10. Air dampers
11. Fixing screw for mounting flange
C R S B-384E
4 3 5 6 7 8 1 2 12 9
10
11
L1 L1
1. Body
2. Break spring
3. Rear cover
4. Hexagonal socket screw
5. O-ring for cover 18,72 x 2,62 Viton
6. O-ring for piston 12 x 2 Viton
7. O-ring for bottom plate 18,72 x 2,62 Viton
8. O-ring for spindle 6 x 2 Viton
9. Oil nozzle
10. Cylinder
11. Piston
12. Spindle
C Control circuit
R Return from nozzle
S Outlet to nozzle
L Nominal size of nozzle valve
L1 Nozzle open position (chacking the spindle movement )
If the nozzle seems to be functioning improperly, you may clean the nozzle with diesel oil.
If cleaning does not fix the problem, the properties of the nozzle have got worse and the
nozzle has to be changed. The new nozzle has to be of same type as the original.
If there is an oil leak from the hole in the rear cover , change the nozzle or install a repair
kit.
3
7
11
6
12
B-391U
Profile of the spring band sets the dampers positions at any point within the adjusting
range. The profile of the band can be shaped with the adjusting guide and the adjusting
screws.
The air dampers are connected to the adjusting cam with the adjusting lever. The
adjusting lever moves according to the profile of the spring band. Combustion values
have to be verified by doing a flue gas analysis with every adjusting cam indvidually.
The edges of the spring band are sharp. Unwary handling may cause
slashes
B-393U
2
3
4
13 9
12 8
5
15
17
18 16
B C
1. Body
2. Dosing shaft
3. Dosing nozzle
4. O-ring 9,3 x 2,4 Viton
5. Fitting
6. Compression spring
7. Thrust washer
8. Roller bearing
9. Spring cotter
10. Front flange
11. Hexagonal socket screw
12. O-ring 45 x 2 Viton
13. X-ring 10,2 x 2,62 Viton
14. Ball bearing
15. Non-return valve
16. Coupling
17. Washer
18. Retaining ring
B Oil to valve
C Oil from valve
When the in indicator for swing angel is in position 0º, the dosing shaft is in open position.
The return flow is at maximum and the return pressure at minimum. When the in indicator
for swing angel is in position approx. 160º, the dosing shaft is in closed position. The
return flow is at minimum and the return pressure at maximum.
The pressure gauge on the regulator shows the return pressure. There is a number on the
dosing shaft and on the indicator which shows the size of the groove on the shaft.
These instructions illustrate detaching the oil regulator (B309Y10...Y30) from the body of
heavy fuel oil burner for maintenance. Photographs are of a model RP 280 M-burner.
Details may vary depending on the burner model. Spare parts may be found from the
spare parts catalog.
CUT OFF ELECTRICITY from the burner main switch and CLOSE OIL
IN-LET to burner prior to dissassembly.
3. Remove the locking pin and detach the 4. Release the servomotor shaft by pressing
swivels/adjusting rod from the adjusting lever. the release switch. Turn the adjusting lever
so that your able to loosen the shaft locking
screws.
5. Unscrew the screws holding the 6. Loosen the locking screws on the oil
servomotor mounting plate. Pull out the regulator shaft.
servomotor. Place and fasten the servomotor
so that there is no streching strain on the
cables.
7. Pull out the adjusting lever (A). Detach the 8. Open pipe nipples and detach the oil pipes
adjustable cam disc (B). Notice the wedge on from the oil regulator.
the shaft.
5.8.2 Disassembling
These instructions illustrate the disassemblying of the oil regulator valve (B309Y10...
Y30). Spare parts may be found from the spare parts catalog, group 16.
Uncover the components in numbered order Be careful not to damage the brass coating
on the dozing nozzle.
5.8.3 Assembling
1. Assemble and screw down the valve shaft (3) and attach the screws (2)
2. Assemble the dozing nozzle (4). Note! There is opening in the nozzle for allignment.
3. Attach the washers and the plate needle bearing.
4. Attach the spring and the tube connector.
5. Check the shaft rotation. The saft should roll 360° steady and smooth.
5.8.4 Attaching
When it is established, that the fault is not due to above mentioned, the individual burner
functions must be checked. Reset the burner control unit if it is in lockout position (signal
lamp lights). Burner starts, when the sequence switch has run to its start position and
other prerequisites for start are fulfilled (see chapter Burner Automation; Operation”).
Observe the burner functions.TheThe symbol appearing above the reading mark indicates
the possible kind of fault (see chapter ”Control Program under Fault Conditions and
Lockout Indication”). Measuring instruments can be used for finding of the fault.
6. Technical data
H
pic_101472.10_MODIFIED_TRu
1
LAL2.25 AS
br1
a b
I
b
a
ar2
ar1
4 12 6 7
RAR
22 23 24
5 13 14
V
FR
fr1 fr2
a b
IX (1) (2)
XI b a
XIII NTC
a a b
a b XII
b IV
AR XIV
a b
VII
a b
br2
ar3
L1 E M
BR II X VIII V VI III
A a b a b a b
IV b a a b
SM
3 21 2 15 16 18 17 19 9 20 11 10 8
*) The wire link B has been cut away at the factory. This allows an automatic repetition of
start-up sequence, if the flame extinguishes during burner operation. If the wire link B has
not been cut away, lockout occurs, if the flame is extinguished during burner operation.
TYPE RAR...
Min. required detector current with 230 VAC 6,5 μA
Max. permissible detector current without —
flame
Max. possible detector current 25 μA
Instrument's +pole to terminal 22
Cable run to detector in the same cable as not perm.
control lines
Cable run to detector with a separate cable RAR7: 30 m
in cable duct
Shielded cable (insulated shielding) RAR8: 100 m
Shielding to terminal
22 23 LAL2...
RAR...