T.L. = 8.7 KVA T.L. = 3.62 KVA T.L. = 3.62 KVA T.L. = 3.61 KVA T.L. = 3.

2 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 3.61 KVA T.L. = 10.17 KVA T.L. = 2.92 KVA T.L. = 2.92 KVA T.L. = 2.92 KVA T.L. = 3.49 KVA T.L. = 3.49 KVA
D.L. = 6.96 KVA D.L. = 2.90 KVA D.L. = 2.89KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 2.89 KVA D.L. = 8.13 KVA D.L. = 2.33 KVA D.L. = 2.33 KVA D.L. = 2.33 KVA D.L. = 2.79 KVA D.L. = 2.79 KVA
IN OFF-501 IN OFF-502 IN OFF-503 IN OFF-504 IN OFF-505 IN OFF-506 IN OFF-507 IN OFF-508 IN OFF-509 IN OFF-510 IN OFF-511 IN OFF-512 IN OFF-513
AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE

FOR OFF-501 FOR OFF-502 FOR OFF-503 FOR OFF-504 FOR OFF-505 FOR OFF-506 FOR OFF-507 FOR OFF-508 FOR OFF-509 FOR OFF-510 FOR OFF-511 FOR OFF-512 FOR OFF-513
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 Note:-
1- * WIRED AS SINGLE PHASE.

2- THE CONTRACTOR SHALL VERIFY THE FINAL LOADS IN COORDINATION WITH OTHER
TRADES. ACCORDINGLY FINAL SIZES OF CABLES AND CIRCUIT BREAKERS SHALL
BE ADJUSTED.
3- ALL CIRCUIT BREAKER RATINGS SHOWN ON DRAWING ARE PRESENTING THE THERMAL
TRIP SETTING AND FRAME SIZE. CIRCUIT BREAKERS RATED 100A AND ABOVE SHALL BE
EQUIPPED WITH ADJUSTABLE TRIP SETTING.

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 4- THE CONTRACTOR SHALL SUBMIT THE FOLLOWING CALCULATIONS AND STUDIES
FOR APPROVAL :
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB - LOAD SCHEDULES FOR ALL DISTRIBUTION BOARDS FOR RETAILS AND
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA AND SERVICES (IF ANY CHANGES)
- CABLE SIZING AND VOLTAGE DROP CALCULATIONS (IF ANY CHANGES)
- SHORT CIRCUIT CALCULATIONS AT EACH BUS (IF ANY CHANGES)
- DISCRIMINATION STUDY & CIRCUIT BREAKERS SETTING VALUES
OBTAINED FROM THE MANUFACTURER.
100A TP
MCCB
18 KA

2 2

T.L. = 3.49 KVA T.L. = 3.49 KVA T.L. = 4.38 KVA T.L. = 5.54 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 4.01 KVA T.L. = 7.23KVA T.L. = 5.18 KVA
D.L. = 2.79 KVA D.L. = 2.79 KVA D.L. = 3.5 KVA D.L. = 4.43 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 3.21 KVA D.L. = 5.78 KVA D.L. = 4.14 KVA
IN OFF-514 IN OFF-515 IN OFF-516 IN OFF-517 IN OFF-518 IN OFF-519 IN OFF-520 IN OFF-521 IN OFF-522 IN OFF-523 IN OFF-524 IN OFF-525 IN OFF-526
AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR

40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO.

2
4Cx16mm CU/PVC/PVC
2
+ 1Cx16mm CU/PVC/ECC SPARE

FOR OFF-514 FOR OFF-515 FOR OFF-516 FOR OFF-517 FOR OFF-518 FOR OFF-519 FOR OFF-520 FOR OFF-521 FOR OFF-522 FOR OFF-523 FOR OFF-524 FOR OFF-525 FOR OFF-526
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
HWK 0000.0

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

100A TP SMDB-5TH-OFF1 SMDB-5TH-OFF2 SMDB-5TH-OFF3


MCCB IN ELEC. RM IN ELEC. RM IN ELEC. RM
18 KA AT 5TH FL AT 5TH FL AT 5TH FL
LIGHTING, S.POWER LIGHTING, S.POWER LIGHTING, S.POWER

2 2

2 SPARE

2
For Tender

T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.58 KVA T.L. = 3.00 KVA T.L. = 3.01 KVA T.L. = 3.00 KVA T.L. = 3.01 KVA T.L. = 2.96 KVA So a 2 O ICE BUILDING
D.L. = 2.86 KVA
IN OFF-527
D.L. = 2.86 KVA
IN OFF-528
D.L. = 2.86 KVA
IN OFF-529
D.L. = 2.86 KVA
IN OFF-530
D.L. = 2.86 KVA
IN OFF-531
D.L. = 2.86 KVA
IN OFF-532
D.L. = 2.86 KVA
IN OFF-533
D.L. = 2.4 KVA
IN OFF-534
AT 5TH FLOOR
D.L. = 2.40 KVA
IN OFF-535
D.L. = 2.40 KVA
IN OFF-536
D.L. = 2.40 KVA
IN OFF-537
D.L. = 2.37 KVA
IN OFF-538
AT 5TH FLOOR
100A TP 100A TP 80A TP 100A TP
AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR AT 5TH FLOOR
MCCB MCCB MCCB MCCB
-
40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 40A TP ISO. 25 KA 25 KA 25 KA 25 KA 24B.

2
4Cx16mm CU/PVC/PVC 250A TP MOBIL :01024440717
2
+ 1Cx16mm CU/PVC/ECC SPARE SPACE MCCB E-MAIL : m.amer@mod-eg.com
WEB SITE : WWW.mod-eg.com
25 KA 26 JULY CORRIDOR
AVENUE MALL, SHEIKH ZAYED, GIZA, EGYPT

FOR OFF-527 FOR OFF-528 FOR OFF-529 FOR OFF-530 FOR OFF-531 FOR OFF-532 FOR OFF-533 FOR OFF-534 FOR OFF-535 FOR OFF-536 FOR OFF-537 FOR OFF-538
HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0 HWK 0000.0
HWK 0000.0

2 2

40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP 40A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA 18 KA

80A TP
MCCB
18 KA