PROJECT NO: CT531

PROJECT NAME: Pueblo Viejo Plant Expansion (O2 CT)


VENDOR/CONTRACTOR: Industrial Water Cooling
CLIENT: Pueblo Viejo Dominicana

MODIFICATION NUMBER:
PURCHASE ORDER NUMBER / CONTRACT NO: 260739/Q
TAG NO. / EQUIPMENT NUMBERS: 4144-EVA-130A/B/C/D
DRS CATEGORIES:
EQUIPMENT TITLE: Oxygen Cooling Tower

STATUS STAMP

REMARKS

Andrew Bannerman - 002 - 001.


Previous comments "LIS instead of LIT" has been addressed

Oil level transmitter and vibration transducer

VENDOR NO:

DOCUMENT TITLE: CT531-LIS-006


REVISION: 2

SENET DOCUMENT NUMBER: SP0793-M087.00-I01-0065


SUBMISSION NUMBER: 04
SUBMISSION DATE: 03/08/2021

SP0793-M087.00-I01-0065
Client: Pueblo Veijo Dominicana Corporation
Project Name: Oxygen Plant Cooling Tower
Discription and package number: 259326
Client order number: 260739/Q
VDR number:
VDR sequentrial number:
IWC document number: CT531-LST-006
IWC job number: CT531
Document Title: Intrument Listing

Date created: 2020/11/18

Date revised:
Revision: A 2020/11/18
B 2021/02/02
0 2021/02/09
1 2021/06/09
2 2021/08/03
Refer to P&ID: SP0793-4144-PIDS-0004-001-Sht2 and Sht3

IWC
IWC P&ID
Client P&ID number Drawing Description Model Number Electrical Specification Flange size/thread size
number
Number
4144-VT-00106 N/A SP0793-4144-PIDS-0004-001-Sht2 N/A Monitran MTN 1185CM8-20F 12-32V DC (4-20mA) M8 x 1.25
4144-VT-00109 N/A SP0793-4144-PIDS-0004-001-Sht2 N/A Monitran MTN 1185CM8-20F 12-32V DC (4-20mA) M8 x 1.25
4144-VT-00206 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Monitran MTN 1185CM8-20F 12-32V DC (4-20mA) M8 x 1.25
4144-VT-00209 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Monitran MTN 1185CM8-20F 12-32V DC (4-20mA) M8 x 1.25
4144-LIS-00111 N/A SP0793-4144-PIDS-0004-001-Sht2 N/A Level SWITCHGAGE EL150X 10A,30V DC 1/2" BSP
4144-LIS-00112 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Level SWITCHGAGE EL150X 10A,30V DC 1/2" BSP
4144-LIS-00211 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Level SWITCHGAGE EL150X 10A,30V DC 1/2" BSP
4144-LIS-00212 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Level SWITCHGAGE EL150X 10A,30V DC 1/2" BSP
4144-LG-00111 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Oil Level sight glass FGM 2200 N/A 1/4" BSP
4144-LG-00112 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Oil Level sight glass FGM 2200 N/A 1/4" BSP
4144-LG-00211 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Oil Level sight glass FGM 2200 N/A 1/4" BSP
4144-LG-00212 N/A SP0793-4144-PIDS-0004-001-Sht3 N/A Oil Level sight glass FGM 2200 N/A 1/4" BSP
00-02-0171
06-11-10
Section 15

Installation Instructions - Level Swichgage® Instruments for Engine Liquids –


Models L150, EL150K1, and EL150EX

BEFORE BEGINNING INSTALLATION OF THIS


MURPHY PRODUCT READ AND FOLLOW ALL
INSTALLATION INSTRUCTIONS.
• A visual inspection of this product for damage during
shipping is recommended before mounting.
• It is your responsibility to have a qualified person
Applications install this unit and make sure it conforms to NEC and
The primary use of these level Swichgage instruments is for local codes.
engine cooling systems, surge or expansion tanks, condenser
radiator or vapor phase systems, whether pressurized or • Disconnect all electrical power to the machine.
atmospheric. These instruments can also be used to monitor lube • Make sure the machine cannot operate during
oil, hydraulic fluid or diesel fuel reservoirs and activate alarms installation.
and/or shutdown at a predetermined minimum level. These
instruments are built for low pressure systems. • Follow all safety warnings of the machine
manufacturer.
COLD WEATHER WARNING
• Please contact FW Murphy immediately if you have
BEFORE FREEZING WEATHER COMES, CHECK TO BE SURE any questions.
YOUR L150 OR EL150 SERIES, COOLANT LEVEL
SWICHGAGE IS FILLED WITH ANTIFREEZE SOLUTION THE
CAUTION: Certain danger to human and to
SAME AS YOUR ENGINE BLOCK AND RADIATOR.
equipment such as applied in a mobile or marine
On many engines, such as condenser radiator systems, the application may occur if some equipment is
coolant in your level Swichgage remains static until the level falls stopped without pre-warning. It is therefore
to drain point. When ‘winterizing’ it is a good idea to make certain recommended that monitored functions be limited
all water drains from your level Swichgage, to check against
to alarm only or to alarm before shutdown in such
clogged connections, and then BE SURE IT REFILLS WITH
ANTIFREEZE. FAILURE TO OBSERVE THIS PRECAUTION applications.
COULD RESULT IN EQUIPMENT DAMAGE.

In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at
any time. The latest version of this manual can be found at www.fwmurphy.com.
Dimensions • P/N 15-00-0107 (PS) Accepts 1/4 in. (6mm) O.D.
copper tubing.
• P/N 15-01-0167 (PS Barbed) Barbed fitting accepts
1/4 in. (6mm) I.D. flexible tubing and hose clamp.
• P/N 15-01-0202 (PS-D) Accepts 1/2 in. (13mm) I.D.
hose; 1/4 in. (6mm) copper tube.
1. Determine the entry point into the radiator top tank. See
Level Swichgage Instrument Installation for proper
location. Drill 1/8 in. (16mm) diameter hole in top tank of
radiator. Be sure chips do not fall inside the tank. Remove
any burrs on the hole wall.
2. Insert the rubber grommet of the PS Blind Hold Fitting.
Tighten the jam nut while holding the fitting from turning in
the hold. The jam nut will pull the tapered grommet into the
hole from the inside of the top tank causing the grommet to
expand and seal the hole.
3. Attach the appropriate tubing or hose for the PS Fitting.

Level Swichgage Instrument Installation


WARNING: Perform all installations with the power
source “OFF”. Be sure engine and radiator have cooled
and coolant pressure has been relieved. SEVERE BURNS
can result. Never remove a hot radiator cap.

IMPORTANT: Operation of the L150/EL150K1 is different


for a pressurized cooling system than for an atmospheric
(non-pressurized system. Installation of the
L150/EL150K1 is only slightly different for each system.
Connection of the top tube connection is the major
difference. Differences will be noted in the installation
instructions.

Installation Notes
1. All top radiator connections must be away from the
return hose turbulence.
2. All bottom radiator connections must be away from
the suction hose.

Installation Instructions 3. If top tank and bottom tank entries are used on a pressurized
system, a restriction in the tubing will have to be added to
PS Fittings Installation prevent flow through the L150/EL150K1, bypassing the core.
Examples of restriction: 1/8" upper tubing, 1/4" lower tubing,
A Murphy PS fitting is used when there is no threaded fitting in the needle valve, or fixed small orifice.
top tank of the radiator to attach tubing for the L150/EL150 series 4. The L150/EL150K1 must be attached to a mounting plate on
level Swichgage instrument. the radiator or other framework.
CAUTION: If the L150/EL150K1 is NOT attached to the
radiator, use high temperature quality flexible hose for the
top and bottom connections to maintain the shock
mounting protection for the radiator.

-2-
4. For most applications, the bottom tube connection is made
Pressurized and Atmospheric Systems at the drain cock. Remove the drain cock and install a brass
1. Drain the cooling system. tee. Reinstall the drain cock into the tee. Attach a copper or
other suitable tube to the remaining opening of the tee and
2. For a Pressurized System (see Figure 1) determine the point
to the bottom connection of the L150/EL150K1.
of entry (tube connection) in the radiator top tank (away from
the top hose connection). Many radiators have a pipe nipple
If a drain cock is not provided, you must attach a fitting or
provided. If a connection is not provided, you must either
use a Murphy PS fitting the same as for the top tank
weld or solder a fitting or use one of the Murphy PS fittings.
instructions.
See PS Fittings Installation. This connection should be as
close to the radiator core as possible. 5. Wire according to appropriate alarm or shutdown circuits
(See Standard Electrical Diagrams).
6. Refill the cooling system according to manufacturer’s
instructions.
7. Start the engine and allow it to run until the thermostat
opens. Increase engine speed to the FULL operating speed
and observe that the indicating pointer remains at or near
the full position. If the pointer drops to the LOW position,
shutdown or alarm will occur due to coolant flow through
the L150/EL150K1. If alarm or shutdown occurs, drain the
coolant – or clamp off the upper and lower hoses.
For MARINE AND MOBILE EQUIPMENT installations, the
top tank connection should be near the vertical centerline of 8. CAUTION: BE SURE SYSTEM PRESSURE IS RELIEVED
the radiator. This will compensate for changing level due to AND HOT COOLANT CANNOT ESCAPE. Remove the four
roll and pitch of the machine during operation. (4) mounting screws holding the cover assembly. Invert the
float chamber so that the 1/2 NPT connection is on top and
the 1/4 NPT connection is on bottom. Reinstall the float and
3. For an ATMOSPHERIC SYSTEM a tube connection in the
cover assembly in the upright position. Install larger I.D.
top tank may not be required. Determine the lowest desired
tubing from the top of the float chamber (1/2 NPT) to the
level of coolant in the top tank. Mount the L150/EL150K1 so
radiator top tank. The smaller 1/4 NPT connection on the
that the mounting ears are approximately 1/4 in (6mm) above
bottom will restrict coolant outflow from the L150/EL150K1.
that level (see Figure 2).
Check for unrestricted float movement by rotating the
A back mounting option is available for the L150 and switch test knob.
EL150K1 for radiators with fabricated steel top tank and/or
for use with some condenser cooling systems. Refill the cooling system and repeat step 7.
9. Place a catch basin under the drain cock. Open the drain
cock and observe that coolant is leaving the radiator.

For a PRESSURIZED cooling system, shutdown will occur


when coolant drops below the entry point of the top tank tube
connection.

For an ATMOSPHERIC OR CROSS FLOW PRESSURIZED


cooling system, shutdown will occur when coolant drops
approximately 1/4 in. (6 mm) below the level of the case
mounting ears. If shutdown does not occur, adjust the
L150/EL150K1 mounting as described above.
CAUTION: DO NOT ALLOW ENGINE TO RUN WHEN
COOLANT DRAINS BELOW THE UPPER TANK. ENGINE
DAMAGE CAN OCCUR.
Install a 1/4 in. (6mm) diameter tube in the top fitting of the
L150/EL150K1. This tube MUST EXTEND ABOVE the top 10. Periodically test switch operation by rotating the test
tank. Form the tube into a cane so that the open end of the knob on the face of the L150/EL150K1. Rotating the
tube points down but still extends ABOVE the HIGHEST knob forces the pointer mechanism against the
coolant level. The tube can be connected to the top tank if contact screw (L150) or the snap switch actuator
desired. Follow instructions for a PRESSURIZED (EL150K1).
SYSTEM.

-3-
Condensor/Radiator System Replacing the Float and Cover Assembly for the L150 and
1. Mount the L150/EL150K1 so that the horizontal EL150K1
center line of the L150/EL150K1 is approximately 1/4
in. (6 mm) above the minimum coolant level in the
WARNING: Perform the following operation with
engine head.
the power source “OFF”. Be sure engine and
NOTE: on some engines it is possible to use the back connection radiator have cooled and coolant pressure has
option and attach the L150/EL150K1 directly to the engine been relieved. SEVERE BURNS can result. Never
cylinder. Kits are also available for some engines. remove radiator cap on a hot engine.
2. Attach a copper tube from the top connection of the
1. As applicable, shut off liquid to the Swichgage
L150/EL150K1 to the radiator top tank.
instrument or drain the system level below the
3. Wire and test the system according to the above Swichgage instrument.
instructions for Pressurized and Atmospheric
systems. 2. Disconnect electrical lead(s), one at a time, and tag
for reinstallation.
Standard Electrical Diagrams 3. Disconnect conduit on EL150K1.
4. Remove the four screws that secure the float and
WARNING: Perform all installations with glass assembly to the case.
the power source “OFF”. 5. Remove and discard the old float and cover
assembly.
6. Remove and discard the old gasket.
7. Install the new gasket.
8. Install the new float and cover assembly and secure
it with four screws.
9. Re-connect the conduit on EL150K1.
NOTE: All models shown with pointer in full position.
10. Reconnect the electrical lead(s).
EL150EX-D 11. As applicable, open valves to the Swichgage instrument or
refill the system to proper level.
12. Check the Swichgage instrument for proper operation at the
full indicating position. (Alarm not operated/engine continues
to operate.)
13. Check the Swichgage instrument, alarm/shutdown circuit, by
rotating the test knob toward the low level point of the dial;
alarm is operated/engine shuts down.
14. Check for unrestricted float movement by rotating the switch
test knob.
15. Replacement of the float and cover assembly is complete.

WARNING: On some high voltage CD ignition


Repair Kits systems, it may be necessary to coat the L150
contact screw head with RTV to prevent
Repair kits are available for the L150, EL150K1 and EL150EX “tracking” and false contact operation during wet
models. When ordering a repair kit, specify model repair kit or high humidity conditions. Use of the EL150K1
number from chart below: is recommended in these cases.
Model Components Repair Kit No.
L150 15-00-0138
Case//body assembly 15-00-0101
EL150K1 All parts except case/body 15-00-0139
Lens and switch assembly 15-00-0100
Case/body assembly 15-00-0101
EL150EX Cover and float assembly 15-00-0110
Lid assembly 15-00-0108
Switch/Terminal assembly 15-00-0109

-4-
MTN/1185 Series
4-20mA velocity transducer for PLC interface

General purpose, top-entry velocity transducer with DC output. Made from robust stainless steel throughout
for continuous vibration monitoring in harsh environments. Sealed to IP67 with industry standard two-wire
4-20mA output proportional to sensor range that can connect directly to PLC, DCS and other industrial
controllers. Includes integral 3-pin 62GB connector and is available with a wide range of mountings.

MTN/1185 Applications

• Air handling units


• Building services
• Fans

Technical

Output current 4-20mA DC proportional to rms velocity (mm/s)

Supply voltage 12-32V DC (4-20mA)

Frequency response 2Hz to 1kHz ±10%

Mounted base resonance 5kHz (nominal)

Isolation Base isolated


Dimensions
Dynamic range 50g peak

Transverse sensitivity Less than 5%

Operating temperature -25 to 90°C

Temperature sensitivity 0.08%/°C

Case material Stainless steel

Mating connector MTN/MH008

Mounting torque 8Nm

Weight 140g (nominal)

Sealing IP67

ISO 9001 : 2008


Monitran Ltd | Monitor House | 33 Hazlemere Road | Penn | Bucks | UK | HP10 8AD Registered Company

Telephone +44 (0)1494 816569 | E-mail info@monitran.com | Website www.monitran.com sira


We reserve the right to alter specifications without prior notice. DS0224.1Page 1 of 2
MTN/1185 Series
4-20mA velocity transducer for PLC interface

Studs and grub screws Mounting adapters

Part # From To Part # From To


MS036 ¼"-28 UNF Male M6 Male MS005 Q/F Male ¼"-28 UNF Female
MS039 ¼"-28 UNF Male 10-32 UNF Male MS007 Q/F Male 10-32 UNF Female
MS067 ¼"-28 UNF Male M8 Male MS008 Q/F Male M8 Female
MS068 ¼"-28 UNF Male ¼"-28 UNF Male MS011 ¼"-28 UNF Male Q/F Female
MS124 ¼"-28 UNF Male M10 Male MS013 ¼"-28 UNF Male Glue base
MS132 ¼"-28 UNF Male M12 Male MS033 ¼"-28 UNF Male Q/F Female
MS038 Q/F Male M8 Conical Male
MS061 ¼"-28 UNF Male 10-32 UNF Male
Quick fit adapters MS079 ¼"-28 UNF Male Q/F Female
MS106 Q/F Male M10 Female

Part # From To
Isolation
MS001 Q/F Male Glue base
MS002 Q/F Male M8 Male
Part # From To
MS003 Q/F Male M10 Male
MS034 ¼"-28 UNF Male ¼"-28 UNF Female
MS004 Q/F Male ¼"-28 UNF Male
MS093 Q/F Male M8 Male
MS006 Q/F Male M6 Male

Options System connection


Filters
Mounting threads
Mating cable and connector assemblies
High temperatures
Other velocities (see below)

xx = Optional
Part # Mounting Velocity
(mm/s rms)
0-10
MTN/1185-xx ¼"UNF Female
0-20
0-25
0-50
MTN/1185Q-xx Q/F Female
0-100

ISO 9001 : 2008


Monitran Ltd | Monitor House | 33 Hazlemere Road | Penn | Bucks | UK | HP10 8AD Registered Company

Telephone +44 (0)1494 816569 | E-mail info@monitran.com | Website www.monitran.com sira


We reserve the right to alter specifications without prior notice. DS0224.1Page 2 of 2
Level SWICHGAGE® Series LEL-00072B
Effective 06-00

For Engine Liquids


Replaces L-6795B
Catalog Section 15
(00-02-0058)

L150/ EL150K1 Series


■ Monitors Level of Coolant, Lube Oil,
Diesel Fuel And Hydraulic Fluid.
■ Indicating Gauge
L150
■ Low Limit Switch
EL150K1
■ Float Operated
■ Explosion-Proof Model Is Available.

** Products covered by this bulletin comply with EMC


Council directive 89/336/EEC regarding electromagnetic
EL150EX compatibility except as noted.

EL150EX Models are CSA Listed for Class I,


Division 1, Group C & D Hazardous Locations.

Description O-rings: Saturated Nitrile, are suitable for Wire: (3) 18 AWG x 14 in. (1 mm2 x 356 mm).
The L150 Series Level SWICHGAGE® is a com- coolant or hydrocarbons. Maximum temperature Shipping Weight: 42 oz. (1.2 kg.).
bination liquid level gauge and low limit switch; 250°F (121°C). Shipping Dimensions: 5-1/4 x 5-1/4 x
each unit includes (1) a chamber with pivotal Gasket: Neo-cork. 5-1/2 in. (133 x 133 x 140 mm).
float, (2) an indicating dial with pointer, and (3) Vent Tube: 1/4 x 5 in. (6 x 127 mm) copper
a low level contact. When properly installed and cane with 1/4 NPT x 1/4 in. (6 mm) tube fitting. EL150EX Specifications
maintained, the float operates the pointer which, Contact Rating: 2 A @ 30 VAC/DC. Case: Sand cast aluminum, painted; approxi-
in turn, both indicates level during normal opera-
Wire: (1) 16 AWG x 26 in. (1.5 mm2 x 660 mm) mate dimensions; 6-1/2 x 5-3/4 x 5-1/4 in. (165
tion, and closes a switching circuit if the level
falls to the low-limit set point. with terminals. x 146 x 133 mm).
Shipping Weight: 29 oz. (0.82 kg.). Mounting Holes: (2) 5/16 in. (8 mm) diameter
Applications Shipping Dimensions: 5-1/4 x 5-1/4 x at 5-1/2 in. (140 mm) on center.
5-1/2 in. (133 x 133 x 140 mm). Float: 304 Stainless steel.
The primary use of the L150/EL150K1 is for
engine cooling systems, surge or expansion Lens: Tempered glass.
tanks, condenser radiator or vapor phase sys- EL150K1 Specifications O-rings: Saturated Nitrile, are suitable for
tems, pressurized or atmospheric systems. The Case: Die cast aluminum, poly-urethane coated; coolant or hydrocarbons. Maximum temperature
Level SWICHGAGE® can also be used to moni- approximate dimensions; 5 x 4-3/4 x 2-3/4 in. 250°F (121°C).
tor lube oil, hydraulic fluid or diesel fuel reser- (127 x 121 x 70 mm). Gasket: Neo-cork.
voirs and activates alarms and/or shut-down at a Mounting Holes: (2) 9/32 in. (7 mm) diameter Vent Tube: 1/4 x 5 in. (6 x 127 mm) copper
predetermined minimum level. at 4-1/2 in. (114 mm) on center. cane with 1/4 NPT x 1/4 in. (6 mm) tube fitting
These instruments are built for low pressure systems
with a maximum of 25 psi (172 kPa) [1.72 bar]. Float: Brass. and 1/2 NPT to 1/4 NPT reducer fitting.
Lens: Polycarbonate. Snap-Switch: SPDT rated 10 A @ 125 VAC;
L150 Specifications O-rings: Saturated Nitrile, are suitable for 0.5 A @ 125 VDC; 10 A 30 VDC.
Case: Die cast aluminum, poly-urethane coated; coolant or hydrocarbons. Maximum temperature Wire: Wired to terminal block.
approximate dimensions; 4-1/2 x 4-3/4 x 250°F (121°C). Laboratory Approvals:
2-3/4 in. (114 x 121 x 70 mm). Gasket: Neo-cork. CSA Listed for Hazardous Locations Class I,
Mounting Holes: (2) 9/32 in. (7 mm) diameter Vent Tube: 1/4 x 5 in. (6 x 127 mm) copper Division 1, Groups C & D.
at 4-1/2 in. (114 mm) on center. cane with 1/4 NPT x 1/4 in. (6 mm) tube fitting. Shipping Weight: 5 lbs. (2.26 kg.).
Float: Brass. Snap-Switch: SPDT rated 10 A @ 125 VAC; Shipping Dimensions: 6-1/2 x 6-3/4 x 6-3/8 in.
Lens: Polycarbonate. 0.5 A @ 125 VDC; 10 A 30 VDC. (165 x 171 x 162 mm).
Dimensions Radiator Fittings
Murphy PS, PS Barbed and PS-D fittings allow the installation of
L150 2-3/4 in.
3-25/32 in.
(70 mm)
1/4 NPT the L150/EL150K1 to the radiator when a fitting is not available.
(96 mm)
• 15-00-0107 (PS): thin wall, 1/4 in. (6 mm) tube fitting.
Test
• 15-01-0167 (PS-Barbed): thin wall, 1/4 in. (6 mm) tubing or hose.
9/32 in. (7 mm)
Knob
diameter holes • 15-01-0202 (PS-D): for diesel or oil, thick wall (to 1/4 in. [6 mm]),
2 places 4-13/16 in.
(122 mm) accepts 1/2 in. (13 mm) I.D. hose or 1/4 in. (6 mm) O.D. tubing.

1/2 NPT
Mounting
Back Connect
Ears (2)
(optional)

4-1/2 in. 1/2-14 NPT


(114 mm)
Mounting Holes 15-00-0107 (PS) 15-01-0167 (PS Barbed)

EL150K1 Repair Kits Accessories


2-3/4 in. L150 Specify Description
1/4 NPT
(70 mm)
4-15/16 in. 15-00-0138 All parts except 15-00-0107 Radiator fitting (PS)
(125 mm)
case and body 15-01-0202 Radiator fitting (PS-D)
Test 15-00-0101 Case/body assembly 15-01-0167 Radiator fitting (PS Barbed)
11/16 in. Knob
(17 mm) EL150K1
4-13/16 in.
(122 mm)
15-00-0139 All parts except
case and body
15-00-0101 Case/body assembly
1/2 NPT 15-00-0100 Lens/switch assembly
Back Connect
(optional) EL150EX
4-1/2 in.
15-00-0110 Cover and float assembly
9/32 in. (7 mm)
(114 mm) diameter holes
1/2-14 NPT 15-00-0108 Lid assembly
Mounting Holes 2 places 15-00-0109 Switch/terminal assembly

EL150EX Standard Electrical Diagrams


4-11/16 in. 6 in.
(119 mm) (152 mm) WARNING: This typical wiring diagram is shown for clarity only.
It is not intended for use as installation instructions.

1/2 NPT
Connection 5-9/16 in. L150 EL150K1 EL150EX
(141 mm)

Full NC-Red Full Full


NC
NO-Black
5/16 in. (8 mm) NO
diameter holes Common-
Low White C
2 places Low
Low
5-1/2 in.
(140 mm) 1/2-14 NPT
Mounting Holes

Fittings Kits Order Separately


15010235 FM3
Warranty
A limited warranty on materials and workmanship is given with this FW 15010236 FM4
Murphy product. A copy of the warranty may be viewed or printed by 15010237 FM5
going to www.fwmurphy.com/support/warranty.htm 15010238 FM12
15010349 CECO

CONTROL SYSTEMS & SERVICES DIVISION FRANK W. MURPHY, LTD. MACQUARRIE CORPORATION
P.O. Box 1819; Rosenberg, Texas 77471; USA Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. 1620 Hume Highway
+1 281 633 4500 fax +1 281 633 4588 +44 1722 410055 fax +44 1722 410088 Campbellfield, Vic 3061; Australia
e-mail sales@fwmurphy.com e-mail sales@fwmurphy.co.uk +61 3 9358 5555 fax +61 3 9358 5558
FW Murphy
MURPHY DE MEXICO, S.A. DE C.V. www.fwmurphy.co.uk e-mail murphy@macquarrie.com.au
P.O. Box 470248
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje MURPHY SWITCH OF CALIFORNIA
Tulsa, Oklahoma 74147 USA
San Luis Potosí, S.L.P.; México 78384 41343 12th Street West
+1 918 317 4100 +52 444 8206264 fax +52 444 8206336 Palmdale, California 93551-1442; USA
D
RE

fax +1 918 317 4266 GI


E

Villahermosa Office +52 993 3162117 +1 661 272 4700 fax +1 661 947 7570
STER

USA–ISO 9001:2000 FM 28221


e-mail sales@fwmurphy.com e-mail ventas@murphymex.com.mx e-mail sales@murphyswitch.com UK–ISO 9001:2000 FM 29422

www.fwmurphy.com www.murphymex.com.mx www.murphyswitch.com


In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Printed in U.S.A.

LEL-00072B page 2 of 2

You might also like