OC & EF RELAY TRIP TIME CALCULATOR

RELAY SETTING ###


###
Input Current Set (Is) = 2500.00 ###
Input TMS = 0.02 ###
Select Curve Type = IEC S Inverse ###
###
CHARACTERISTIC ###

K ###
Trip time t = Tx +L
( I / Is ) - 1
α ###
###

INJECTION CURRENT AND RESULTANT TIME

Input Current Injected (I) = 3315.00


Calculated Trip time = 0.495 Secs
MSETCL
CTR- 200:1
OC-
IDMT 200A TMS-0.075s 100%
DMT 1000A T=0.100 s 5Times
EARTH FAULT-
IDMT 260A TMS-0.075s 30%
DMT 1000A T=0.100 s 5Times
33 KV INCOMER PROTECTION Indorama

Function Configuration CT/ VT Configuration Current Setting

Ph OC Enable Ph Curr I/P 1A Ph OC


Volt Cont OC Disable Ph CT Ratio Pri 150A 51-1 Element Enable
Cold Load Disable Ph CT Ratio Sec 1A 51-1 Setting 150 A
Derived EF Enable Earth Curr I/P 1A 51-1 Char IEC-NI
Measured EF Disable Earth CT Ratio Pri 150A 51-1 TMS 0.050 s
Restricted EF Disable Earth CT Ratio Sec 1A 50-1 Element Enable
NPS OC Disable Ph Rotation ABC 50-1 Setting 750 A
Under Curr Disable Voltage Protection 50-1 Delay 0.050 s
Thermal Disable Ph U/O Voltage Derived EF
Line Check Disable 29/57-1 Element Enable 51N-1 Element Enable
Ph U/O Volt Enable 29/57-1 Operation Over 51N-1 Setting 30 A 20% of 150

U/O Freq Disable 29/57-1 Setting 126.5 V 115% of 110 V 51N-1 Char IEC-NI
Trip Ckt Supervision Enable 29/57-1 Delay 2s 51N-1 TMS 0.050 s
29/57-1 U/V Guarded Yes 50N-1 Element Enable
29/57-3 Element Enable 50N-1 Setting 433 A
29/57-3 Setting 77.0 V 85% of 110 V 50N-1 Delay 0.050 s
29/57-3 Delay 2s
29/57-3 U/V Guarded Yes
Transformer feeder Protection 1,2 & 3
Function Configuration CT/ VT Configuration TRAFO RELAY- 1, OC & EF TRAFO REALY- 2,STANDBY EARTH FAULT
Ph OC Enable Ph Curr I/P 1A Curr Protection Measured EF
Volt Cont OC Disable Ph CT Ratio Pri 75A Ph OC 51G-1 Element
Cold Load Disable Ph CT Ratio Sec 1.00A 51-1 Element Enable 51G-1 Setting 400 A
Derived EF Enable Earth Curr I/P 1A 51-1 Setting 58 A 51G-1 Char IEC-NI
Measured EF Disable Earth CT Ratio Pri 2000A 51-1 Char IEC-NI 51G-1 TMS 0.050 s
Restricted EF Disable Earth CT Ratio Sec 1.00A 51-1 TMS 0.050 s 50G-1 Element Enable
NPS OC Disable Ph Rotation ABC 50-1 Element Enable 50G-1 Setting 5.7 KA
Under Curr Disable TRAFO PRI AMP 43.73 50-1 Setting 750 A 50G-1 Delay 0s
Thermal Disable 50-1 Delay 0s
Line Check Disable Derived EF
Ph U/O Volt Enable 51N-1 Element Enable
U/O Freq Disable 51N-1 Setting 15 A 15% of 58
HT AMP- 58A
Trip Ckt Supervision Enable 51N-1 Char IEC-NI LT AMP- 4450A
51N-1 TMS 0.050 s TRAFO RATED-3333 A
50N-1 Element Enable 1.3 TIMES OVERLOAD On HT SIDE
50N-1 Setting 167 A
50N-1 Delay 0s
Restricted EF
64H Element DISABLE
64H Setting
64H Delay
LT TRAFO INCOMER PROTECTION
Feeder Protection Type L&T Release Siemens Relay
Overload 4000 A T-0.500 S 4000A TMS-0.200 S
Trafo 1,2&3 Short Circuit 32000 A TMS- 0.020 S (I2T ON) 30000 A TMS-0.075 S
(Short Ckt-44 KA) Earth Fault 800 A TMS- 0.100 S (I2T OFF) 400 A TMS-0.050 S 10 % OF 4000
Instanteneous 40000A T-0 S 40000 A T-0 S
Overload 800 A TMS- 0.500 S HT AMP- 52A
Short Circuit 4800 A TMS- 0.020 S (I2T ON) LT AMP- 4000A
MCC-1 315 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF) TRAFO RATED-3333 A
Instanteneous 4800 A T-0 S 1.2 TIMES OVERLOAD On LT Side
Overload 800 A TMS- 0.500 S

Short Circuit 4000 A TMS- 0.020 S (I2T ON) FOR L&T RELEASE EARTH FAULT MIN SETTING IS 0.2 XIn
MCC-2 315 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF)

Instanteneous 4800 A T-0 S


Overload 1600 A TMS- 0.500 S

MCC-3 (Short Short Circuit 8000 A TMS- 0.020 S (I2T ON)


720 KW CONNECTED LOAD
Ckt-26 KA) Earth Fault 320 A TMS- 0.100 S (I2T OFF)

Instanteneous 9600 A T-0 S


Overload 800 A TMS- 0.500 S

Short Circuit 4000 A TMS- 0.020 S (I2T ON)


MCC-4 193 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF)

Instanteneous 4800 A T-0 S


Overload 1600 A TMS- 0.500 S

Short Circuit 8000 A TMS- 0.020 S (I2T ON)


MCC-5 560 KW CONNECTED LOAD
Earth Fault 320 A TMS- 0.100 S (I2T OFF)

Instanteneous 9600 A T-0 S


Overload 800 A TMS- 0.500 S

Short Circuit 4000 A TMS- 0.020 S (I2T ON)


HCC 375 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF)

Instanteneous 4800 A T-0 S


Overload 2500 A TMS- 0.500 S

MCC-7 (UTILITY) Short Circuit 12500 A TMS- 0.100 S (I2T ON)


845 KW CONNECTED LOAD (APPROX)
(Short Ckt-24 KA) Earth Fault 500 A TMS- 0.100 S (I2T OFF)

Instanteneous 15000 A T-0 S


Overload 2500 A TMS- 0.500 S

Short Circuit 12500 A TMS- 0.100 S (I2T ON)


MCC-8 (UTILITY) 595KW CONNECTED LOAD (APPROX)
Earth Fault 500 A TMS- 0.100 S (I2T OFF)

Instanteneous 15000 A T-0 S