CERTIFICATE OF STRUCTURAL STABILITY

This is to certify the structural stability of the Masonry wall/s that are affected by the inclusion
of wall mounted setup carrying antennas of Globe Telecoms Network Inc. Also, the steel framing setup
of the wall mounts and the affected region due to the weight of the Outdoor cabinets are part of this
certification. The said inclusions are post constructed and are located at the uppermost roof-deck of the
building. Added structure of such magnitude does not have the capacity to destabilize the structural integrity
of the building.

Structural appraisal involves site visit and/or visual inspection to ensure the added structures have
no visual damage that might affect its longevity and its users. Also, the location of the said additions was
identified to measure the “As-built” structural elements as well as the existing concrete elements of the
structure directly affected by the added loadings for structural investigation purposes.

Estimation or calculation needed to produce this output are all based on the standard and code
mandated by the law and by the profession of Civil Engineering in the Philippines. Here lies the references
used for the analysis extracted from the National Structural code of the Philippines 2015 (NSCP2015,
SEVENTH EDITION, VOLUME I):

• American Concrete Standard (ACI-318M)


• American Institute for Steel Construction (AISC360-16)
• American National Standard Institute (ANSI EIA/TIA-222-G.I.-2007)
• American Society of Civil Engineer (ASCE 7-22) for WIND LOAD ANALYSIS

Based on the reaction/s at the base of the added structures of Globe Telecoms networks, the weight it
would incur on the structure is much smaller compared with the design loading of the area affected by this
said inclusion. Therefore, the inclusion would not be going to affect the building’s structural stability,
deemed safe, and posts no danger to the user of the building. More importantly, the connection between
the masonry wall/s and the steel framing setup is theoretically checked for possible detachment and
pry out.

However, additional loadings due to alteration of the structure and improper usage outside the
jurisdiction of the code/s stated above are beyond the scope and responsibility of the undersigned.Moreover,
poor workmanship, modification, and construction are beyond the jurisdiction of the engineer involved
with the assessment of the structural stability of the existing building and outsidethe scope of this report.
Note: This structural investigation report shall not be construed as part of the construction
documents. This is prepared for information purposes only. This report contains the results of
the investigation into the structure.

AVAILABLE DATA

The engineers have gathered available data which will be used for analysis such as

As-built architectural and structural drawings of the building provided by the owner, and

actual conditions based on ocular inspection. The material properties and other design

considerations have been provided by the client and have been used as the basis for the

structural investigation.

Commentary: Lessor did not provide any data regarding their building. The design

checking was done only for the structural properties, and elements of the wall mounted

antennas. The dimensions of the affected region were measured on-site for assurance and

checking of hairline cracking throughout the wall/s of attachments. However, material

specifications and properties of the existing building are assumed to be at the most

conservative way (ex. Least standard Masonry strength governed by NSCP 2015 – Table.

705-1). Moreover, this type of post installed infrastructure does not have the capacity to

destabilize the building’s structural framing system but is important to be assessed for

possible failure, especially its anchorage.

Page 1 of 96
LIMITATION OF THIS DOCUMENT

This review presented herein is intended for the project entitled PROJECT
UNIVESE (PROJECT U) by Globe Telecoms Network located at Rizal Tower,
Singian St. Makati Ave., Makati city. The existing structure is owned by Nika Ng. This
document shall be read in conjunction with the following documents:

a. As-built drawings signed by the engineer in charge of the project

construction.

b. Structural and or soil investigation results

c. National Structural Code of the Philippines, 7th Ed. 2015

d. Other building codes specified in the design criteria

Should there be any inconsistencies; the precedence shall be as follows:

a. As-built drawings of the structure

b. National Structural Code of the Philippines, 7th Ed. 2015

c. The structural investigation results.

Page 2 of 96
I. INTRODUCTION
This report covers the structural investigation for the structural elements that are

affected by the inclusion of Nineteen (19) pole framing setup mounted with antennas, and

outdoor equipment cabinets that are situated in a concrete pedestal. Twelve (12) of which

are mounted through the masonry/parapet wall, and Seven (7) remaining are floor

mounted. Wall mounted connections are attached to a wall through post installed anchor

bolts with adhesive structural grouting. Wall mounted connection’s base plate/s are built-

up shapes of flat plates (ASTM-A36); therefore, no proper standard analysis can be made

except for Finite element analysis (FEA).

Wall mounted framing setup/s are consisting of Pipe3SCH40 (3.5” Outer Diameter,

0.20” Wall Thickness) for its main framing pole that is supporting the steel connectors or

appurtenances for antenna attachments, and U-bolt, vertical Pipe1-1/2SCH40 (1.90” Outer

Diameter, 0.14” Wall Thickness) for additional horizontal element/strut element (for your

reference, see Structural plan)

Figure 1. Shown above is a wall mounted setup that is part of this analysis as it has different
structural appearance compared to the remaining floor mounted antenna/s.

Page 3 of 96
Figure 2. Shown above are the Wall mounted and Floor mounted antennas owned by Globe Telecoms Network Inc. Red-highlighted
antenna setup is the critical pole setup as it carries the heaviest weight due to equipment attached. Due to similarities to structural
appearances, the critical antenna is picked for analysis.

The self-weight of equipment inclinedly attached, appurtenances, and other

attachments that are not part of the main framing system of the pole are extracted from the

manufacturer’s provided mechanical property manual (ex. Antenna weight).

For the performance of the analysis, the dimension of the concerned structural members

is measured upon the day of inspection and made sure that there are no early indications of

failure such as hairline cracking (that is not due to thermal changes) and improper weld of

two adjoining steel members. AISC-LRFD will be used as method of adequacy checking

for the steel members, ACI318-19M for anchorage through a masonry wall, anchor bolts

adequacy, and finite element analysis for checking of base plates, stiffener plates, and

welds.

Page 4 of 96
The aim of the report was to provide adequate justification for ensuring the structural

stability of the added structure by Globe Telecoms Network inc., and the affected structural

elements due to this said inclusion. Considerations for the possible loadings that may cause

failure are as follows; (1) Due to gravity loads, (2) Due to wind loads, (3) Combination of such

loadings and load factors. The parameters for such loadings especially for (2) and (3) are

extracted from the National Structural Code of the Philippines 2015 (NSCP, 2015) and

ASCE7-22 (MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR

BUILDINGS AND OTHER STRUCTURES).

To fulfill the objective, step by step procedure in chronological order are carried out:

1. Inspection and gathering of data.

2. Computer Aided Design (CAD) for layout

3. Load computation with the aid of Microsoft office

4. Structural Aided analysis of the framing and recommendation

Page 5 of 96
II. INPUTS

On this part of the report, the inputs such as code-based parameters, engineering

judgement or computation, would be discussed and certify with the assurance and justification

that each structural member would or would not meet the desired requirements. Regarding the

structural steel members, strength design method (AISC LRFD) was deemed efficient and up

to date as a method of design adequacy checking as it provides more adequacy checking than

Allowable stress design (ASD) based on the design software use for the base plates and

concrete pedestal (HILTI PROFIS ENGINEERING).

For the computation of dead-load due to self-weight of the attached equipment, extracted

mechanical data from the manufacturer’s manual was used and is converted into desired units

and load of transfer going through the main framing system of the pole through the masonry

wall/post-constructed concrete pedestal. For the wind-load, extracted data are from

combinations of National Structural Code of the Philippines 2015 (NSCP, 2015) code-

based design and Minimum Design Loads and Associated Criteria for Buildings and

Other Structure (ASCE/SEI 7-22). There are several types of infrastructure that the added

wall mounted setup can be considered, however, the steel pole framing setup fits the criteria

for Section.207D.4.2. SOLID ATTACHED SIGNS of NSCP 2015. The said governing

codes and procedural approaches are manually deciphered by the engineer in-charge of this

analysis and was computed through the help of Microsoft office (excel) software. Formulas

used, and criteria for judgement will be discussed further in this report.

Page 6 of 96
MATERIAL PROPERTIES (Parapet wall)

Specified Compressive Strength of Concrete Masonry Unit, fm’ = 1500 Psi or 10.30 Mpa

MATERIAL PROPERTIES (Structural steel members)

Yield strength of Structural steel, Fy = 248 Mpa (ASTM - A36) for all Prefabricated steel

members except anchor bolts. CONSERVATIVE ASSUMPTION SINCE THERE IS NO

DATA PROVIDED BY THE OWNER

Ultimate strength of Structural steel, Fu = 400 Mpa (ASTM - A36) CONSERVATIVE

ASSUMPTION SINCE THERE IS NO DATA PROVIDED BY THE OWNER

Tensile strength of Weld electrode, Fyw = 413 Mpa (E60XX) CONSERVATIVE

ASSUMPTION SINCE THERE IS NO DATA PROVIDED BY THE OWNER

II.I. PARAMETER FOR WIND ANALYSIS (FOR STEEL

FRAMING SYSTEM)

II.I.I. WALL MOUNTED 1

DESCRIPTION VALUE UNITS REMARKS

Roof top equipment


STRUCTURE TYPE and solid freestanding -
and attached signs

SUB STRUCTURE/CROSS SECTION All other cross sections

RISK CATEGORY IV -
Exposure Category C -
BASIC WIND SPEED 250 kmph
Ground elevation above sea level, Ze 13 m
Height of the building structure, z or h 33 m

Width of the building structure normal to the direction of


8.24 m
the wind, B

Page 7 of 96
Gross area of the building structure normal to the
271.92 sq.m.
direction of the wind, Bh

Height of the rooftop structure normal to the direction of


1.93 m
the wind, s

Width of the rooftop structure normal to the direction of


0.409 m
the wind, w

Vertical Projected Area of the Rooftop structure or


3.192229619 sq.m. NET AREA
equipment normal to the direction of the wind, Af

Gross area of a plane normal to the direction of the wind,


3.192229619 sq.m. GROSS AREA
Ag

WIND DIRECTIONALITY FACTOR, Kd 0.95 -


Velocity Pressure Coefficients, Kz 1.05637412 -
Topographic Factor, Kzt 1 - Use 1.0 for conservative approach
Ground Elevation Factor, Ke 0.998454196 - Use 1.0 for conservative approach
Rigid building or other structures are permitted
to be taken as 0.85,except for rooftop
Gust-effect factor, G 0.85 -
equipments and ground-mounted fixed-tilt solar
panel system
Combined Factor, GCr 1.9 - Factor for rooftop equipment

Force Coefficients, Cf 0.824602861 - SOLID FREESTANDING SIGNS

Ratio of Solid are to the Gross area (Af/Ag), ε 1 -


Clearance Ratio, s/h 0.058484848 -
APPLICABLE FOR ONLY CASE A AND B
Aspect Ratio, B/s 0.211917098 -
Round member
Diameter of a typical round member, D 0.0889 m
N/A
Velocity pressure, qz or qh 44.89974576 N/sq.m.
Design wind force, F 95.43888854 N

Area normal to
Plane normal Height or Depth Length of Force Design Wind
Material the wind
Description to direction of of the member's the member multiplier, Force, F'
Geometry direction, Af'
the wind face (m.) (m.) Ca (kN/m)
(sq.m.)

EQUIPMENT Y-Z Round 1.93 1.93 2.9255296 1.2 0.017171897


PIPE3SCH40 Y-Z Round 0.0889 3 0.2667 0.089691751
Σ(Af) 3.1922296

Page 8 of 96
II.I.II. WALL MOUNTED 2

DESCRIPTION VALUE UNITS REMARKS

Roof top equipment


STRUCTURE TYPE and solid freestanding -
and attached signs

SUB STRUCTURE/CROSS SECTION All other cross sections

RISK CATEGORY IV -
Exposure Category C -
BASIC WIND SPEED 250 kmph
Ground elevation above sea level, Ze 13 m
Height of the building structure, z or h 36 m

Width of the building structure normal to the direction of


4.64 m 8.24
the wind, B

Gross area of the building structure normal to the


8.24 sq.m. 4.64
direction of the wind, Bh

Height of the rooftop structure normal to the direction of


1.93 m
the wind, s

Width of the rooftop structure normal to the direction of


0.409 m
the wind, w

Vertical Projected Area of the Rooftop structure or


2.896613304 sq.m. NET AREA
equipment normal to the direction of the wind, Af

Gross area of a plane normal to the direction of the wind,


2.896613304 sq.m. GROSS AREA
Ag

WIND DIRECTIONALITY FACTOR, Kd 0.85 -


Velocity Pressure Coefficients, Kz 1.065051668 -
Topographic Factor, Kzt 1 - Use 1.0 for conservative approach
Ground Elevation Factor, Ke 0.998454196 - Use 1.0 for conservative approach
Rigid building or other structures are permitted
to be taken as 0.85,except for rooftop
Gust-effect factor, G 0.85 -
equipments and ground-mounted fixed-tilt solar
panel system
Combined Factor, GCr 1.648469259 - Factor for rooftop equipment

Force Coefficients, Cf 1.855 - SOLID FREESTANDING SIGNS

Ratio of Solid are to the Gross area (Af/Ag), ε 1 -


Clearance Ratio, s/h 0.053611111 -
APPLICABLE FOR ONLY CASE A AND B
Aspect Ratio, B/s 0.211917098 -
Round member
Diameter of a typical round member, D 0.0889 m
N/A
Velocity pressure, qz or qh 45.26857311 N/sq.m.
Design wind force, F 175.7393808 N

Page 9 of 96
Area normal to
Plane normal to Height or Depth Length of
Material the wind Force Design Wind
Description direction of the of the member's the member
Geometry direction, Af' multiplier Force, F' (kN/m)
wind face (m.) (m.)
(sq.m.)

EQUIPMENT Y-Z Channel 1.93 1.325 2.55725


PIPE3SCH40 Y-Z Round 0.0889 3 0.2667 0.182011918
PIPE2SCH40 Y-Z Channel 0.060452 1.202 0.072663 0.072926108
Σ(Af) 2.896613

Force Coefficients, Cf, for Case A and Case B

Aspec Ratio, B/s


Clearance Ratio, s/h

</=0.05 0.1 0.2 0.5 1 2 4 5 10 20 30 >/=45

1 1.8 1.7 1.65 1.55 1.45 1.4 1.35 1.35 1.3 1.3 1.3 1.3
0.9 1.85 1.75 1.7 1.6 1.55 1.5 1.45 1.45 1.4 1.4 1.4 1.4
0.7 1.9 1.85 1.75 1.7 1.65 1.6 1.6 1.55 1.55 1.55 1.55 1.55
0.5 1.95 1.85 1.8 1.75 1.75 1.7 1.7 1.7 1.7 1.7 1.7 1.75
0.3 1.95 1.9 1.85 1.8 1.8 1.8 1.8 1.8 1.8 1.85 1.85 1.85

0.2 1.95 1.9 1.85 1.8 1.8 1.8 1.8 1.8 1.85 1.9 1.9 1.95

</=0.16 1.95 1.9 1.85 1.85 1.8 1.8 1.85 1.85 1.85 1.9 1.9 1.95

Force Coefficients, Cf

Rounded Members
ε Flat-sided Members
D*sqrt(qz)</=5.3 D*sqrt(qz)>5.3

<0.1 2 1.2 0.8


0.1 to 0.29 1.8 1.3 0.9
0.3 to 0.7 1.6 1.5 1.1

Page 10 of 96
Table 26.10-1. Velocity Pressure Coefficients, Kh and Kz.

Height above Ground level, z or h Exposure


ft m B C D
0 0 0.57 0.7 0.85 1.03
15 4.6 0.57 0.7 0.85 1.03
20 6.1 0.62 0.7 0.9 1.08
25 7.6 0.66 0.7 0.94 1.12
30 9.1 0.7 0.7 0.98 1.16
40 12.2 0.74 0.74 1.04 1.22
50 15.2 0.79 0.79 1.09 1.27
60 18.3 0.83 0.83 1.13 1.31
70 21.3 0.86 0.86 1.17 1.34
80 24.4 0.9 0.9 1.21 1.38
90 27.44 0.92 0.92 1.24 1.4
100 30.5 0.95 0.95 1.26 1.43
120 36.6 1 1 1.31 1.48
140 42.7 1.04 1.04 1.34 1.52
160 48.8 1.08 1.08 1.39 1.55
180 54.9 1.11 1.11 1.41 1.58
200 61 1.14 1.14 1.44 1.61
250 76.2 1.21 1.21 1.51 1.68
300 91.4 1.27 1.27 1.57 1.73
350 106.7 1.33 1.33 1.62 1.78
400 121.9 1.38 1.38 1.66 1.82
450 137.2 1.42 1.42 1.7 1.86
500 152.4 1.46 1.46 1.74 1.89

Page 11 of 96
Figure 3. Shown above is the design wind load formula adequate for the analysis.

Figure 4. Shown above is the force direction due to wind-load targeting the geometric center of the
structure.

Page 12 of 96
II.II. LOAD COMBINATIONS

II.II.I. DEAD LOADS

DEAD LOAD
Pole
Pole Descrip Wei Un Staad Un Length of the Pin Start End
Remarks Remarks length
No. tion ght its inputs its Connection (m) (m) (m)
(m)
WTG18-
W71SA
R-F
Per node
(MICRO 50 kg Packing Weight 0.4905 kN 1.48 0.965 0.74 0.74
connection
WAVE
P1 ANTEN
NA)
0.0568 Per node
Clamps 5.8 kg 1 UNIT kN 1.48 0.965 0.74 0.74
98 connection
WIRING 10% of the weight of the 0.0490 Per node
5 kg kN 1.48 0.965 0.74 0.74
S Antenna, assumed weight 5 connection

DEAD LOAD
Pole
Pole Descript Wei Un Staad Un Remark Length of the Pin Start End
Remarks length
No. ion ght its inputs its s Connection (m) (m) (m)
(m)
ASI4515 0.2305 Membe 1.18 2.46
47 kg Packing Weight kN 2.65 1.273
R3v06 35 r load 85 15
0.0284 Membe 1.18 2.46
Clamps 5.8 kg (2 Units) kN 2.65 1.273
49 r load 85 15
Downtilt 0.0304 Membe 2.46
3.1 kg Model: ASMDTF01 kN 2.65 1.273 -
Kit 11 r load 15
WIRING 10% of the weight of the 0.0230 Membe 1.18 2.46
4.7 kg kN 2.65 1.273
S Antenna, assumed weight 535 r load 85 15
ASI4515 0.2305 Membe 0.98 2.26
47 kg Packing Weight kN 2.65 1.273
R3v06 35 r load 85 15
0.0284 Membe 0.98 2.26
Clamps 5.8 kg (2 Units) kN 2.65 1.273
49 r load 85 15
Downtilt 0.0304 Membe 2.26
3.1 kg Model: ASMDTF01 kN 2.65 1.273 -
Kit 11 r load 15
P2
WIRING 10% of the weight of the 0.0230 Membe 0.98 2.26
4.7 kg kN 2.65 1.273
S Antenna, assumed weight 535 r load 85 15
RRU550 10% of the weight of the 0.2452 Membe 1.32
25 kg kN 2.65 - -
2 Antenna, assumed weight 5 r load 5
WIRING 10% of the weight of the 0.0245 Membe 1.32
2.5 kg kN 2.65 - -
S Antenna, assumed weight 25 r load 5
0.0304 Membe 1.32
Clamps 3.1 kg Model: ASMDTF01 kN 2.65 - -
11 r load 5
RRU550 10% of the weight of the 0.2452 Membe 1.82
25 kg kN 2.65 - -
2 Antenna, assumed weight 5 r load 5
WIRING 10% of the weight of the 0.0245 Membe 1.82
2.5 kg kN 2.65 - -
S Antenna, assumed weight 25 r load 5
0.0304 Membe 1.82
Clamps 3.1 kg Model: ASMDTF01 kN 2.65 - -
11 r load 5

Page 13 of 96
II.II.II. LOAD COMBINATIONS

1. 1.4DL
2. 1.2DL + 1.0 WL (PER DIRECTION)

Where:
DL = Dead loads
WL = Wind load

Page 14 of 96
III. OUTPUTS

In this part of the analysis report, values obtained from running the analysis from

Staad Pro connect edition 6 V22, would be provided and indication whether each

concerned structural steel framing element would be adequate for its intended purpose.

Loads combination, consideration for base support, resisting factor such as releases for

end supports of each steel element, would also be shown for the reader to check the

correctness of the analysis. Aside from providing adequacy checks, Staad Pro connect

edition 6 V22 provided the base reaction of the concerned pole setup and is imported

through HILTI PROFIS ENGINEERING for design checking of the base support

element such as base plate, anchor bolts, base plate, stiffener plate, and other adequacy

checking for concrete previously mentioned.

Page 15 of 96
Job No Sheet No Rev
1
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALLMOUNTED(1).STD Date/Time 15-Jun-2023 15:54

Job Information
Engineer Checked Approved

Name:
Date: 14-Jun-23

Project ID
Project Name

Structure Type SPACE FRAME

Number of Nodes 3 Highest Node 3


Number of Elements 2 Highest Beam 2

Number of Basic Load Cases 8


Number of Combination Load Cases 5

Included in this printout are data for:


All The Whole Structure

Included in this printout are results for load cases:


Type L/C Name

Primary 1 DL
Primary 2 WL(+X)
Primary 3 WL(-X)
Primary 4 WL(+Z)
Primary 5 WL(-Z)
Combination 6 1.4DL
Combination 7 1.2DL+1.0WL(+X)
Combination 8 1.2DL+1.0WL(-X)
Combination 9 1.2DL+1.0WL(+Z)
Combination 10 1.2DL+1.0WL(-Z)

Print Time/Date: 19/06/2023 11:16 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 1 of 6

Page 16 of 96
Job No Sheet No Rev
2
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALLMOUNTED(1).STD Date/Time 15-Jun-2023 15:54

Y
X
Z
Load 1

Whole Structure

3D Rendered View

Print Time/Date: 19/06/2023 11:16 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 2 of 6

Page 17 of 96
Job No Sheet No Rev
3
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALLMOUNTED(1).STD Date/Time 15-Jun-2023 15:54

Beams
Beam Node A Node B Length Property 
(m) (degrees)
1 1 3 0.350 1 0
2 3 2 2.650 1 0

Section Properties
Prop Section Area Iyy Izz J Material
(m2) (in4) (in4) (in4)
1 PIPS30 0.001 2.850 2.850 5.689 STEEL

Materials
Mat Name E  Density 
(kN/mm2) (kg/m3) (/°C)
1 STEEL 205.000 0.300 7.83E+3 12E -6
2 CONCRETE 21.718 0.170 2.4E+3 10E -6
3 ALUMINUM 68.948 0.330 2.71E+3 23E -6
4 STAINLESSSTEEL 197.930 0.300 7.83E+3 18E -6
5 STEEL_36_KSI 199.948 0.300 7.83E+3 11.7E -6
6 STEEL_50_KSI 199.948 0.300 7.83E+3 11.7E -6
7 STEEL_275_NMM2 205.000 0.300 7.85E+3 12E -6
8 STEEL_355_NMM2 205.000 0.300 7.85E+3 12E -6

Supports
Node X Y Z rX rY rZ
(kN/mm) (kN/mm) (kN/mm) (kN-m/deg) (kN-m/deg) (kN-m/deg)
1 Fixed Fixed Fixed Fixed Fixed Fixed
3 Fixed - Fixed Fixed - Fixed

Releases
There is no data of this type.

Reference Load Cases


Number Name Type

R1 EQUIPMENT&APPURTENANCES Dead
R2 WLX Wind
R3 WLZ Wind

Print Time/Date: 19/06/2023 11:16 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 3 of 6

Page 18 of 96
Job No Sheet No Rev
4
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALLMOUNTED(1).STD Date/Time 15-Jun-2023 15:54

Primary Load Cases


Number Name Type

1 DL Dead
2 WL(+X) Wind
3 WL(-X) Wind
4 WL(+Z) Wind
5 WL(-Z) Wind

Combination Load Cases


Comb. Combination L/C Name Primary Primary L/C Name Factor

6 1.4DL 1 DL 1.40
7 1.2DL+1.0WL(+X) 1 DL 1.20
2 WL(+X) 1.00
8 1.2DL+1.0WL(-X) 3 WL(-X) 1.00
1 DL 1.20
9 1.2DL+1.0WL(+Z) 1 DL 1.20
4 WL(+Z) 1.00
10 1.2DL+1.0WL(-Z) 5 WL(-Z) 1.00
1 DL 1.20

Reactions
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
1 1:DL 0 2.097 0 0 0 0
2:WL(+X) -0.016 0 0 0 0 0.001
3:WL(-X) 0.016 0 0 0 0 -0.001
4:WL(+Z) 0 -0.034 -0.016 -0.001 0 0
5:WL(-Z) 0 0.034 0.016 0.001 0 0
6:1.4DL 0 2.936 0 0 0 0
7:1.2DL+1.0WL(+X) -0.016 2.517 0 0 0 0.001
8:1.2DL+1.0WL(-X) 0.016 2.517 0 0 0 -0.001
9:1.2DL+1.0WL(+Z) 0 2.482 -0.016 -0.001 0 0
10:1.2DL+1.0WL(-Z) 0 2.551 0.016 0.001 0 0
3 1:DL 0 0 0 0 0 0
2:WL(+X) -0.322 0 0 0 0 0.433
3:WL(-X) 0.322 0 0 0 0 -0.433
4:WL(+Z) 0 0 -0.288 -0.377 0 0
5:WL(-Z) 0 0 0.288 0.377 0 0
6:1.4DL 0 0 0 0 0 0
7:1.2DL+1.0WL(+X) -0.322 0 0 0 0 0.433
8:1.2DL+1.0WL(-X) 0.322 0 0 0 0 -0.433
9:1.2DL+1.0WL(+Z) 0 0 -0.288 -0.377 0 0

Print Time/Date: 19/06/2023 11:16 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 4 of 6

Page 19 of 96
Job No Sheet No Rev
5
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALLMOUNTED(1).STD Date/Time 15-Jun-2023 15:54

Reactions Cont...
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
10:1.2DL+1.0WL(-Z) 0 0 0.288 0.377 0 0

Reaction Summary
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
Max FX 3 3:WL(-X) 0.322 0 0 0 0 -0.433
Min FX 3 2:WL(+X) -0.322 0 0 0 0 0.433
Max FY 1 6:1.4DL 0 2.936 0 0 0 0
Min FY 1 4:WL(+Z) 0 -0.034 -0.016 -0.001 0 0
Max FZ 3 5:WL(-Z) 0 0 0.288 0.377 0 0
Min FZ 3 4:WL(+Z) 0 0 -0.288 -0.377 0 0
Max MX 3 5:WL(-Z) 0 0 0.288 0.377 0 0
Min MX 3 4:WL(+Z) 0 0 -0.288 -0.377 0 0
Max MY 1 1:DL 0 2.097 0 0 0 0
Min MY 1 1:DL 0 2.097 0 0 0 0
Max MZ 3 2:WL(+X) -0.322 0 0 0 0 0.433
Min MZ 3 3:WL(-X) 0.322 0 0 0 0 -0.433

Reaction Envelope
Horizontal Vertical Horizontal Moment
Node Env FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
1 +ve 0.016 2.936 0.016 0.001 0 0.001
1 +ve Load: 3 Load: 6 Load: 5 Load: 5 - Load: 2
1 -ve -0.016 -0.034 -0.016 -0.001 0 -0.001
1 -ve Load: 2 Load: 4 Load: 4 Load: 4 - Load: 3
3 +ve 0.322 0 0.288 0.377 0 0.433
3 +ve Load: 3 - Load: 5 Load: 5 - Load: 2
3 -ve -0.322 0 -0.288 -0.377 0 -0.433
3 -ve Load: 2 - Load: 4 Load: 4 - Load: 3

Print Time/Date: 19/06/2023 11:16 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 5 of 6

Page 20 of 96
Job No Sheet No Rev
6
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALLMOUNTED(1).STD Date/Time 15-Jun-2023 15:54

Steel Design (Track 2) Beam 1 Check 1


|-----------------------------------------------------------------------------|
Member No: 1 Profile: ST PIPS30 (AISC SECTIONS)|
Utilization Ratio
Status: PASS Ratio: 0.010 Loadcase: 6 |
Location: 0.00 Ref: Cl.E3 |
Beam Analysis Design Actual Allowable Ratio Clause L/C Ax Iz Iy Ix
Pz: 2.936 C Vy: 0.000 Vx: 0.000 |
Property Property Ratio Ratio (Act./Allow.) (m2) (in4) (in4) (in4)
Tz: 0.000 My: 0.000 Mx: 0.000 |
1 PIPS30 PIPS30 0.010 1.000 0.010 Cl.E3
-----------------------------------------------------------------------------| 6 0.001 2.850 2.850 5.700
2 PIPS30 PIPS30 0.060 1.000 0.060 Eq.H1-1b
-----------------------------------------------------------------------------| 7 0.001 2.850 2.850 5.700
Member No: 2 Profile: ST PIPS30 (AISC SECTIONS)|
Status: PASS Ratio: 0.060 Loadcase: 7 |
Failed Members
Location: 0.00 Ref: Eq.H1-1b |
Pz:is no data2.473
There of this type. C Vy: 0.3064 Vx: 0.000 |
Tz: 0.000 My: 0.000 Mx: 0.4334 |
-----------------------------------------------------------------------------

Print Time/Date: 19/06/2023 11:16 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 6 of 6

Page 21 of 96
COMBINED STRESSES
CHECKING
TOP COMBINED STRESS BOTTOM COMBINED STRESS
Node COMB
SX. COMB SY. COMB SZ. COMB SX. COMB SY. COMB SZ. UTILIZATI ADEQUACY STEEL YIELD
(N/sq (N/sqmm.) (N/sqmm.) (N/sqmm.) (N/sqmm.) (N/sqmm.) ON RATIO CHECKING STENGTH, fy
mm.)
0.0108991
76 0.366 -0.901 -1.211 2.703 1.11 -0.12 PASS 248
94
0.0049717
77 1.233 -0.068 -0.167 0.846 -0.341 -0.376 PASS
74
0.0033104
78 0.77 -0.187 -0.215 0.821 -0.158 -0.176 PASS
84
0.0025040
79 0.621 -0.143 -0.167 0.615 -0.145 -0.174 PASS
32
0.0019596
80 0.486 -0.116 -0.156 0.486 -0.116 -0.155 PASS
77
0.0015201
81 0.377 -0.087 -0.149 0.377 -0.087 -0.149 PASS
61
0.0011491
82 0.285 -0.063 -0.147 0.285 -0.063 -0.147 PASS
94
0.0008306
83 0.206 -0.051 -0.148 0.206 -0.051 -0.148 PASS
45
0.0006088
84 0.142 -0.058 -0.151 0.142 -0.058 -0.151 PASS
71
0.0006088
85 0.091 -0.09 -0.151 0.091 -0.09 -0.151 PASS
71
0.0005967
86 0.054 -0.148 -0.146 0.054 -0.148 -0.146 PASS
74
0.0009153
87 0.028 -0.227 -0.129 0.028 -0.227 -0.129 PASS
23
0.0013064
88 0.011 -0.324 -0.092 0.011 -0.324 -0.092 PASS
52
0.0017620
89 0.002 -0.437 -0.034 0.002 -0.437 -0.034 PASS
97
0.0079112
90 -0.331 -0.406 -1.649 1.962 0.869 0.411 PASS
9
0.0041653
91 1.033 0.135 -0.388 0.651 -0.079 -0.68 PASS
23
0.0029112
92 0.666 -0.111 -0.404 0.722 -0.081 -0.361 PASS
9
0.0023467
93 0.582 -0.103 -0.303 0.574 -0.106 -0.309 PASS
74
0.0019314
94 0.479 -0.095 -0.266 0.479 -0.094 -0.265 PASS
52
0.0015846
95 0.393 -0.076 -0.245 0.393 -0.076 -0.245 PASS
77
0.0012540
96 0.311 -0.057 -0.233 0.311 -0.057 -0.233 PASS
32
0.0009516
97 0.236 -0.046 -0.222 0.236 -0.046 -0.222 PASS
13
0.0008467
98 0.172 -0.053 -0.21 0.172 -0.053 -0.21 PASS
74
0.0007943
99 0.123 -0.082 -0.197 0.123 -0.082 -0.197 PASS
55
0.0007258
100 0.084 -0.132 -0.18 0.084 -0.132 -0.18 PASS
06
0.0007943
101 0.054 -0.197 -0.155 0.054 -0.197 -0.155 PASS
55
0.0010927
102 0.026 -0.271 -0.113 0.026 -0.271 -0.113 PASS
42
0.0014556
103 0.005 -0.361 -0.044 0.005 -0.361 -0.044 PASS
45

Page 22 of 96
0.0073104
104 -0.527 -0.189 -1.813 1.591 0.643 0.67 PASS
84
0.0030040
105 0.662 0.156 -0.373 0.42 0.053 -0.745 PASS
32
0.0022096
106 0.516 0.012 -0.502 0.548 0.028 -0.45 PASS
77
0.0019637
107 0.487 -0.039 -0.386 0.483 -0.041 -0.393 PASS
1
0.0017661
108 0.437 -0.06 -0.34 0.438 -0.06 -0.339 PASS
29
0.0015685
109 0.389 -0.061 -0.316 0.389 -0.061 -0.316 PASS
48
0.0013548
110 0.336 -0.044 -0.309 0.336 -0.044 -0.309 PASS
39
0.0011854
111 0.266 -0.032 -0.294 0.266 -0.032 -0.294 PASS
84
0.0010806
112 0.202 -0.033 -0.268 0.202 -0.033 -0.268 PASS
45
0.0009758
113 0.152 -0.06 -0.242 0.152 -0.06 -0.242 PASS
06
0.0008669
114 0.114 -0.109 -0.215 0.114 -0.109 -0.215 PASS
35
0.0007580
115 0.08 -0.166 -0.188 0.08 -0.166 -0.188 PASS
65
0.0008508
116 0.042 -0.211 -0.148 0.042 -0.211 -0.148 PASS
06
0.0010564
117 0.005 -0.262 -0.064 0.005 -0.262 -0.064 PASS
52
0.0074032
118 -0.756 -0.037 -1.836 1.284 0.425 0.679 PASS
26
0.0029153
119 0.383 0.182 -0.341 0.224 0.156 -0.723 PASS
23
0.0020040
120 0.343 0.094 -0.497 0.354 0.095 -0.44 PASS
32
0.0016612
121 0.376 0.025 -0.404 0.375 0.024 -0.412 PASS
9
0.0015403
122 0.382 -0.026 -0.366 0.382 -0.025 -0.365 PASS
23
0.0015241
123 0.378 -0.05 -0.347 0.378 -0.05 -0.347 PASS
94
0.0014677
124 0.364 -0.05 -0.352 0.364 -0.05 -0.352 PASS
42
0.0015080
125 0.338 -0.01 -0.374 0.338 -0.01 -0.374 PASS
65
0.0013629
126 0.24 -0.006 -0.338 0.24 -0.006 -0.338 PASS
03
0.0011532
127 0.175 -0.018 -0.286 0.175 -0.018 -0.286 PASS
26
0.0010080
128 0.139 -0.085 -0.25 0.139 -0.085 -0.25 PASS
65
0.0009354
129 0.099 -0.133 -0.232 0.099 -0.133 -0.232 PASS
84
0.0008225
130 0.026 -0.152 -0.204 0.026 -0.152 -0.204 PASS
81
0.0004919
131 0.004 -0.122 -0.083 0.004 -0.122 -0.083 PASS
35
0.0067741
132 -1.027 0.107 -1.68 1.032 0.447 0.597 PASS
94
0.0025483
133 0.156 0.23 -0.277 0.034 0.238 -0.632 PASS
87
0.0017298
134 0.192 0.153 -0.429 0.194 0.148 -0.375 PASS
39
0.0014919
135 0.269 0.066 -0.361 0.27 0.067 -0.37 PASS
35

Page 23 of 96
0.0013790
136 0.324 -0.001 -0.342 0.324 -0.001 -0.341 PASS
32
0.0014717
137 0.365 -0.047 -0.333 0.365 -0.047 -0.333 PASS
74
0.0016129
138 0.4 -0.071 -0.343 0.4 -0.071 -0.343 PASS
03
0.0017137
139 0.425 -0.064 -0.389 0.425 -0.064 -0.389 PASS
1
0.0019838
140 0.445 0.083 -0.492 0.445 0.083 -0.492 PASS
71

Figure 5. Shown above is the contour stress distribution per target element size of the
built-up shape steel.

Figure 6. Shown above is the 3d-rendered view of the built-up-shaped-baseplate. Lines


resembles the target element size for the Finite Element Analysis (FEA).

Page 24 of 96
Description Smax Smin Von Mis Tresca Checking
Pl Load Top Bottom Top Bottom Top Bottom Top Bottom Utilizat Ade Yield
at Combina (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm ion qua Strength
e tion mm) m) mm) m) mm) m) mm) m) Ratio cy (N/sqmm)
7 8.8709
1 DL 0.011 0.011 -0.011 -0.011 0.019 0.019 0.022 0.022 Pass 248
6 7E-05
0.0026
2 WL(+X) 0.169 0.169 -0.478 -0.478 0.581 0.581 0.647 0.647 Pass
08871
0.0026
3 WL(-X) 0.478 0.478 -0.169 -0.169 0.581 0.581 0.647 0.647 Pass
08871
0.0003
4 WL(+Z) -0.036 -0.036 -0.087 -0.088 0.076 0.076 0.087 0.088 Pass
54839
0.0003
5 WL(-Z) 0.087 0.088 0.036 0.036 0.076 0.076 0.087 0.088 Pass
54839
0.0001
6 1.4DL 0.015 0.015 -0.015 -0.015 0.026 0.026 0.03 0.03 Pass
20968
7
0.0025
1.2DL+1. 0.158 0.158 -0.467 -0.468 0.563 0.564 0.626 0.626 Pass
24194
0WL(+X)
8
0.0026
1.2DL+1. 0.489 0.489 -0.18 -0.18 0.599 0.6 0.669 0.669 Pass
97581
0WL(-X)
9
0.0003
1.2DL+1. -0.035 -0.034 -0.088 -0.089 0.077 0.078 0.088 0.089 Pass
58871
0WL(+Z)
10
0.0003
1.2DL+1. 0.093 0.092 0.03 0.031 0.082 0.081 0.093 0.092 Pass
75
0WL(-Z)
7 8.8709
1 DL 0.01 0.01 -0.011 -0.011 0.019 0.019 0.022 0.022 Pass
7 7E-05
0.0023
2 WL(+X) 0.197 0.197 -0.391 -0.392 0.519 0.519 0.588 0.588 Pass
70968
0.0023
3 WL(-X) 0.391 0.392 -0.197 -0.197 0.519 0.519 0.588 0.588 Pass
70968
0.0003
4 WL(+Z) -0.021 -0.02 -0.076 -0.077 0.068 0.069 0.076 0.077 Pass
10484
0.0003
5 WL(-Z) 0.076 0.077 0.021 0.02 0.068 0.069 0.076 0.077 Pass
10484
0.0001
6 1.4DL 0.015 0.015 -0.016 -0.016 0.026 0.026 0.03 0.03 Pass
20968
7
0.0022
1.2DL+1. 0.185 0.185 -0.38 -0.38 0.499 0.499 0.565 0.565 Pass
78226
0WL(+X)
8
0.0024
1.2DL+1. 0.403 0.403 -0.209 -0.209 0.539 0.539 0.612 0.612 Pass
67742
0WL(-X)
9
0.0003
1.2DL+1. -0.016 -0.015 -0.081 -0.083 0.075 0.077 0.081 0.083 Pass
34677
0WL(+Z)
10
0.0003
1.2DL+1. 0.076 0.076 0.02 0.02 0.068 0.068 0.076 0.076 Pass
06452
0WL(-Z)
7 8.4677
1 DL 0.01 0.01 -0.011 -0.011 0.018 0.018 0.021 0.021 Pass
8 4E-05
0.0022
2 WL(+X) 0.236 0.236 -0.32 -0.32 0.484 0.484 0.556 0.556 Pass
41935

Page 25 of 96
0.0022
3 WL(-X) 0.32 0.32 -0.236 -0.236 0.484 0.484 0.556 0.556 Pass
41935
0.0002
4 WL(+Z) -0.004 -0.003 -0.061 -0.063 0.059 0.061 0.061 0.063 Pass
54032
0.0002
5 WL(-Z) 0.061 0.063 0.004 0.003 0.059 0.061 0.061 0.063 Pass
54032
0.0001
6 1.4DL 0.014 0.014 -0.015 -0.015 0.026 0.026 0.03 0.03 Pass
20968
7
0.0021
1.2DL+1. 0.223 0.223 -0.308 -0.308 0.462 0.462 0.531 0.532 Pass
45161
0WL(+X)
8
0.0023
1.2DL+1. 0.332 0.332 -0.249 -0.249 0.505 0.505 0.581 0.581 Pass
42742
0WL(-X)
9
0.0003
1.2DL+1. 0.005 0.006 -0.071 -0.072 0.073 0.076 0.075 0.079 Pass
18548
0WL(+Z)
10
0.0002
1.2DL+1. 0.055 0.056 0.009 0.008 0.052 0.053 0.055 0.056 Pass
25806
0WL(-Z)
7 8.4677
1 DL 0.01 0.01 -0.011 -0.011 0.018 0.018 0.021 0.021 Pass
9 4E-05
0.0021
2 WL(+X) 0.283 0.283 -0.258 -0.259 0.469 0.469 0.541 0.542 Pass
85484
0.0021
3 WL(-X) 0.258 0.259 -0.283 -0.283 0.469 0.469 0.541 0.542 Pass
85484
0.0002
4 WL(+Z) 0.013 0.015 -0.043 -0.045 0.051 0.054 0.056 0.06 Pass
41935
0.0002
5 WL(-Z) 0.043 0.045 -0.013 -0.015 0.051 0.054 0.056 0.06 Pass
41935
0.0001
6 1.4DL 0.015 0.015 -0.015 -0.015 0.025 0.025 0.029 0.029 Pass
16935
7
0.0020
1.2DL+1. 0.27 0.27 -0.246 -0.246 0.447 0.447 0.516 0.516 Pass
80645
0WL(+X)
8
0.0022
1.2DL+1. 0.271 0.271 -0.296 -0.296 0.491 0.491 0.567 0.567 Pass
8629
0WL(-X)
9
0.0003
1.2DL+1. 0.025 0.027 -0.055 -0.057 0.071 0.074 0.08 0.084 Pass
3871
0WL(+Z)
10
0.0001
1.2DL+1. 0.033 0.034 -0.003 -0.004 0.034 0.037 0.035 0.039 Pass
57258
0WL(-Z)
8 8.4677
1 DL 0.011 0.011 -0.01 -0.01 0.018 0.018 0.021 0.021 Pass
0 4E-05
0.0021
2 WL(+X) 0.336 0.336 -0.203 -0.204 0.472 0.472 0.539 0.539 Pass
73387
0.0021
3 WL(-X) 0.203 0.204 -0.336 -0.336 0.472 0.472 0.539 0.539 Pass
73387
0.0002
4 WL(+Z) 0.03 0.032 -0.023 -0.025 0.046 0.049 0.052 0.057 Pass
29839
0.0002
5 WL(-Z) 0.023 0.025 -0.03 -0.032 0.046 0.049 0.052 0.057 Pass
29839
0.0001
6 1.4DL 0.015 0.015 -0.015 -0.015 0.026 0.026 0.029 0.029 Pass
16935
7
0.0020
1.2DL+1. 0.324 0.324 -0.191 -0.191 0.451 0.451 0.515 0.515 Pass
76613
0WL(+X)
8
0.0022
1.2DL+1. 0.216 0.216 -0.348 -0.348 0.492 0.493 0.563 0.564 Pass
74194
0WL(-X)

Page 26 of 96
9
0.0003
1.2DL+1. 0.042 0.044 -0.035 -0.037 0.067 0.071 0.078 0.082 Pass
30645
0WL(+Z)
10
0.0001
1.2DL+1. 0.01 0.013 -0.017 -0.019 0.024 0.027 0.027 0.031 Pass
25
0WL(-Z)
8 8.4677
1 DL 0.011 0.011 -0.01 -0.01 0.018 0.018 0.021 0.021 Pass
1 4E-05
0.0022
2 WL(+X) 0.397 0.397 -0.157 -0.157 0.494 0.494 0.553 0.554 Pass
33871
0.0022
3 WL(-X) 0.157 0.157 -0.397 -0.397 0.494 0.494 0.553 0.554 Pass
33871
0.0001
4 WL(+Z) 0.045 0.047 -0.001 -0.002 0.045 0.048 0.045 0.049 Pass
97581
0.0001
5 WL(-Z) 0.001 0.002 -0.045 -0.047 0.045 0.048 0.045 0.049 Pass
97581
0.0001
6 1.4DL 0.015 0.015 -0.014 -0.014 0.026 0.026 0.03 0.03 Pass
20968
7
0.0021
1.2DL+1. 0.386 0.386 -0.145 -0.145 0.476 0.476 0.531 0.531 Pass
41129
0WL(+X)
8
0.0023
1.2DL+1. 0.168 0.168 -0.407 -0.408 0.513 0.513 0.576 0.576 Pass
22581
0WL(-X)
9
0.0002
1.2DL+1. 0.057 0.059 -0.012 -0.014 0.063 0.067 0.068 0.072 Pass
90323
0WL(+Z)
10
0.0001
1.2DL+1. -0.008 -0.006 -0.036 -0.037 0.033 0.034 0.036 0.037 Pass
49194
0WL(-Z)
8 8.8709
1 DL 0.011 0.011 -0.011 -0.011 0.019 0.019 0.022 0.022 Pass
2 7E-05
0.0023
2 WL(+X) 0.472 0.472 -0.123 -0.123 0.544 0.544 0.595 0.595 Pass
99194
0.0023
3 WL(-X) 0.123 0.123 -0.472 -0.472 0.544 0.544 0.595 0.595 Pass
99194
0.0002
4 WL(+Z) 0.059 0.06 0.022 0.02 0.051 0.053 0.059 0.06 Pass
41935
0.0002
5 WL(-Z) -0.022 -0.02 -0.059 -0.06 0.051 0.053 0.059 0.06 Pass
41935

Figure 7. Shown above is the contour stress distribution per target element size of the
built-up shape steel.

Page 27 of 96
Figure 8. Shown above is the 3d-rendered view of the built-up-shaped-baseplate. Lines
resembles the target element size for the Finite Element Analysis (FEA).

Page 28 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) / 2078494 HIT-HY
100 (adhesive)
Effective embedment depth: hef = 6.03 cm
Material: 5.8
Evaluation Service Report: ER-547
Issued I Valid: 12/1/2022 | 5/31/2023
Proof: Design Method LRFD (AC58) Masonry + ACI 318-14
Stand-off installation: eb = 0.00 cm (no stand-off); t = 1.00 cm

Anchor plate :
R lx x ly x t = 30.00 cm x 30.00 cm x 1.00 cm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked Grout-filled CMU, f=1500, f = 10,340.00 kN/m , L x W x H: 40.64 cm x 20.32 cm x 20.32 cm;
Solid Head Joint: yes; open ended unit: no
Temp. short/long: 0 °C / 0 °C
Joints: vertical: 0.95 cm; horizontal: 0.95 cm
Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [cm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Page 29 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

Geometry [cm] & Loading [kN, kNm]

1.1 Load combination and design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 DL N = 0.000; Vx = 0.000; Vy = -2.097; no 19
Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 WL(+Z) N = 0.000; Vx = 0.016; Vy = 0.000; no 1


Mx = 0.000; My = 0.000; Mz = -0.001;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

3 WL(-Z) N = 0.000; Vx = -0.016; Vy = 0.000; no 1


Mx = 0.000; My = 0.000; Mz = 0.001;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

4 WL(+X) N = 0.016; Vx = 0.000; Vy = 0.034; no 1


Mx = 0.001; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

5 WL(-X) N = -0.016; Vx = 0.000; Vy = -0.034; no 1


Mx = -0.001; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

6 1.4DL N = 0.000; Vx = 0.000; Vy = -2.936; no 26


Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Page 30 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
7 1.2DL+1.0WL(+X) N = 0.000; Vx = 0.016; Vy = -2.517; no 23
Mx = 0.000; My = 0.000; Mz = -0.001;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

8 1.2DL+1.0WL(-X) N = 0.000; Vx = -0.016; Vy = -2.517; no 23


Mx = 0.000; My = 0.000; Mz = 0.001;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

9 1.2DL+1.0WL(+Z) N = 0.016; Vx = 0.000; Vy = -2.482; no 22


Mx = 0.001; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

10 1.2DL+1.0WL(-Z) N = -0.016; Vx = 0.000; Vy = -2.551; no 23


Mx = -0.001; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

Controlling load case: 6 1.4DL


3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
x
1 0.000 0.734 0.000 -0.734
2 0.000 0.734 0.000 -0.734
3 0.000 0.734 0.000 -0.734
4 0.000 0.734 0.000 -0.734
1 2
max. concrete compressive strain: 0.00 [‰]
max. concrete compressive stress: 0.00 [kN/m ]
2

resulting tension force in (x/y)=(0.00/0.00): 0.000 [kN]


resulting compression force in (x/y)=(0.00/0.00): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Page 31 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

3 Shear load
Load [kN] Capacity [kN] Utilization bV [%] Status
Steel 0.734 8.994 9 OK
Pryout bond 2.936 11.330 26 OK
Masonry crushing strength 0.734 11.248 7 OK
Masonry breakout in direction y- 2.936 35.065 9 OK

3.1 Steel strength

Vsa = ESR value refer to ICC-ES ER-547


f Vsa ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1

Vsa [kN] f f Vsa [kN] Vua [kN]


14.990 0.600 8.994 0.734

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Page 32 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

3.2 Pryout strength (Bond strength controls)

Vmpg =min(kcp · Nmag, kcp · Nmbg)


f Vmpg ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
2
ANa0 = (2 cNa) ACI 318-14 Eq. (17.4.5.1c)
t uncr,m
cNa = 10 da √ 1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0


a,min

ac
ACI 318-14 Eq. (17.4.5.4b)
Nba,m = l a · t cr,m · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
2
kcp da [cm] hef [cm] ca,min [cm] t cr,m [kN/m ]
1 0.95 6.03 31.27 2,241.53

asat atop ec1,N [cm] ec2,N [cm] la


1.000 1.000 0.00 0.00 1.000

Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na y ec1,Na y ec2,Na
0.00 42,516 10,629 1.000 1.000 1.000

y cp,Na Nba,m [kN]


1.000 4.046

Results
Vmpg [kN] f f Vmpg [kN] Vua [kN]
16.185 0.700 11.330 2.936

3.3 Masonry crushing strength

f Vmc ³ Vua AC58 Table 3.2


1
4
Vmc = 1750 · (f'm · Ase,V) AC58 Eq. 3-1

Variables
' 2 2
fm [kN/m ] Ase,v [mm ]
10,340.00 30

Results
Vmc [kN] f f Vmc [kN] Vua [kN]
22.495 0.500 11.248 0.734

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Page 33 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

3.4 Masonry breakout strength y-

Vmbg = (AA ) y
Vm

Vm0
ec,V,m y ed,V,m y c,V,m y h,V,m y parallel,V Vb,m ACI 318-14 Eq. (17.5.2.1b)
f Vmbg ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
AVm see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
2
AVm0 = 4.5 ca1 ACI 318-14 Eq. (17.5.2.1c)

( )
1
'
y ec,V,m = 2ev £ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1

y ed,V,m = 0.7 + 0.3 (1.5c


c
) £ 1.0
a2

a1
ACI 318-14 Eq. (17.5.2.6b)

y h,V,m = √1.5ch ³ 1.0a


a1
ACI 318-14 Eq. (17.5.2.8)

= (7 ( ) √ d ) l
0.2
l
Vb,m e
a a √f'm c1.5
a1 ACI 318-14 Eq. (17.5.2.2a)
d a

Variables
2 2 ' 2
le [cm] da [cm] ca1 [cm] ca2 [cm] AVm [mm ] AVm0 [mm ] fm [kN/m ]
6.03 0.95 82.55 31.27 1,000,552 3,066,526 10,340.00

Calculations
y ed,V,m y parallel,V ec,V [cm] y ec,V,m y m,V y h,V,m
0.776 1.000 0.00 1.000 1.000 1.000

Results
Vb,m [kN] f f Vmbg [kN] Vua [kN]
197.903 0.700 35.065 2.936

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Page 34 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

4 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• /

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Page 35 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

5 Installation data
2
Anchor plate, steel: ASTM A36; E = 199,947,970.00 kN/m ; fyk = 248,211.00 Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
2
kN/m
Profile: no profile Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) /
2078494 HIT-HY 100 (adhesive)
Hole diameter in the fixture: df = 1.11 cm Maximum installation torque: 0.020 kNm
Plate thickness (input): 1.00 cm Hole diameter in the base material: 1.11 cm
Recommended plate thickness: not calculated Hole depth in the base material: 6.03 cm
Drilling method: Drilled in hammer mode Minimum thickness of the base material: 19.37 cm
Cleaning: No cleaning of the drilled hole is required

Hilti HIT-V threaded rod with HIT-HY 100 injection mortar with 6.0325 cm embedment h_ef, 3/8, Steel galvanized, Hammer drilled installation per
ER-547

y
15.00 15.00

6.11

3 4
15.00
17.78

x
15.00

1 2
6.11

6.11 17.78 6.11

Coordinates Anchor [cm]


Anchor x y c-x c+x c-y c+y
1 -8.89 -8.89 41.91 49.53 82.55 100.33
2 8.89 -8.89 59.69 31.75 82.55 100.33
3 -8.89 8.89 41.91 49.53 100.33 82.55
4 8.89 8.89 59.69 31.75 100.33 82.55

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Page 36 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 Date: 6/16/2023
Fastening point:

6 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Page 37 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) / 2078494 HIT-HY
100 (adhesive)
Effective embedment depth: hef = 6.03 cm
Material: 5.8
Evaluation Service Report: ER-547
Issued I Valid: 12/1/2022 | 5/31/2023
Proof: Design Method LRFD (AC58) Masonry + ACI 318-14
Stand-off installation: eb = 0.00 cm (no stand-off); t = 1.02 cm

Anchor plate :
R lx x ly x t = 30.48 cm x 30.48 cm x 1.02 cm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked Grout-filled CMU, f=1500, f = 10,340.00 kN/m , L x W x H: 40.64 cm x 20.32 cm x 20.32 cm;
Solid Head Joint: yes; open ended unit: no
Temp. short/long: 0 °C / 0 °C
Joints: vertical: 0.95 cm; horizontal: 0.95 cm
Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [cm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Page 38 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

Geometry [cm] & Loading [kN, kNm]

1.1 Load combination and design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 WL(+Z) N = 0.000; Vx = 0.322; Vy = 0.000; no 33
Mx = 0.000; My = 0.000; Mz = -0.433;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 WL(-Z) N = 0.000; Vx = -0.322; Vy = 0.000; no 33


Mx = 0.000; My = 0.000; Mz = 0.433;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

3 WL(+X) N = 0.288; Vx = 0.000; Vy = 0.000; no 41


Mx = 0.377; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

4 WL(-X) N = -0.288; Vx = 0.000; Vy = 0.000; no 30


Mx = -0.377; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

5 1.2DL+1.0WL(+X) N = 0.000; Vx = 0.322; Vy = 0.000; no 33


Mx = 0.000; My = 0.000; Mz = -0.433;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

6 1.2DL+1.0WL(-X) N = 0.000; Vx = -0.322; Vy = 0.000; no 33


Mx = 0.000; My = 0.000; Mz = 0.433;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Page 39 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
7 1.2DL+1.0WL(+Z) N = 0.288; Vx = 0.000; Vy = 0.000; no 41
Mx = 0.377; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

8 1.2DL+1.0WL(-Z) N = -0.288; Vx = 0.000; Vy = 0.000; no 30


Mx = -0.377; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

Controlling load case: 7 1.2DL+1.0WL(+Z)


3 4

Tension
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
x
1 0.032 0.000 0.000 0.000
2 0.032 0.000 0.000 0.000
3 0.928 0.000 0.000 0.000
4 0.928 0.000 0.000 0.000
1 2
max. concrete compressive strain: 0.02 [‰]
max. concrete compressive stress: 187.74 [kN/m ]
2

resulting tension force in (x/y)=(0.00/8.29): 1.921 [kN] Compression


resulting compression force in (x/y)=(0.00/-13.34): 1.633 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load [kN] Capacity [kN] Utilization bN [%] Status
Steel 0.928 16.249 6 OK
Bond 1.921 4.762 41 OK
Masonry breakout 1.921 10.087 20 OK

3.1 Steel strength

Nsa = ESR value refer to ICC-ES ER-547


f Nsa ³ Nua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1

Nsa [kN] f f Nsa [kN] Nua [kN]


24.998 0.650 16.249 0.928

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Page 40 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

3.2 Bond strength

Nmag = (AA ) · y
Na0
Na
ec1,Na · y ec2,Na · y ed,Na · Nba,m ACI 318-14 Eq. (17.4.5.1b)
f Nmag ³ Nua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
2
ANa0 = (2 cNa) ACI 318-14 Eq. (17.4.5.1c)
t uncr,m
cNa = 10 da √ 1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
'
y ec,Na = eN £ 1.00 ACI 318-14 Eq. (17.4.5.3)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.00


a,min

Na
ACI 318-14 Eq. (17.4.5.4b)
Nba,m = l a · t cr,m · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
da [cm] hef [cm] ca,min [cm] t cr,m [kN/m ]
2
asat atop
0.95 6.03 31.27 2,241.53 1.000 1.000

ec1,N [cm] ec2,N [cm] la


0.00 8.29 1.000

Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
6.86 75,221 18,805 1.000

y ec1,Na y ec2,Na Nba,m [kN]


1.000 0.453 4.046

Results
Nmag [kN] f f Nmag [kN] f Nua [kN]
7.327 0.650 4.762 1.921

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Page 41 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

3.3 Masonry breakout strength

ANm
Nmbg = · y ec,N,m y ed,N,m · y c,N,m · Nb,m ACI 318-14 Eq. (17.4.2.1b)
ANm0
f Nmbg ³ Nua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANm see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
2
ANm0 = 9 · hef ACI 318-14 Eq. (17.4.2.1c)

( )
1
'
y ec,N,m = 2 eN £ 1.00 ACI 318-14 Eq. (17.4.2.4)
1+
3 · hef
c
y ed,N = 0.7 + 0.3 a,min £ 1.0 ACI 318-14 Eq. (17.4.2.5b)
1.5 · hef
1.5
Nb,m = km · l a · √ '
fm · hef ACI 318-14 Eq. (17.4.2.2a)

Variables
hef [cm] ec1,N,m [cm] ec2,N,m [cm] ca,min [cm] y c,N,m kc
6.03 0.00 8.29 31.27 1.000 12
' 2
la fm [kN/m ]
1.000 10,340.00

Calculations
ANm [mm ]
2
ANm0 [mm ]
2
y ec1,N,m y ec2,N,m y ed,N,m Nb,m [kN]
128,720 32,752 1.000 0.522 1.000 7.566

Results
Nmbg [kN] f f Nmbg [kN] Nua [kN]
15.518 0.650 10.087 1.921

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Page 42 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

4 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• /

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Page 43 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

5 Installation data
2
Anchor plate, steel: ASTM A36; E = 199,947,970.00 kN/m ; fyk = 248,211.00 Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
2
kN/m
Profile: no profile Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) /
2078494 HIT-HY 100 (adhesive)
Hole diameter in the fixture: df = 1.11 cm Maximum installation torque: 0.020 kNm
Plate thickness (input): 1.02 cm Hole diameter in the base material: 1.11 cm
Recommended plate thickness: not calculated Hole depth in the base material: 6.03 cm
Drilling method: Drilled in hammer mode Minimum thickness of the base material: 19.37 cm
Cleaning: No cleaning of the drilled hole is required

Hilti HIT-V threaded rod with HIT-HY 100 injection mortar with 6.0325 cm embedment h_ef, 3/8, Steel galvanized, Hammer drilled installation per
ER-547

y
15.24 15.24

6.35

3 4
15.24
17.78

x
15.24

1 2
6.35

6.35 17.78 6.35

Coordinates Anchor [cm]


Anchor x y c-x c+x c-y c+y
1 -8.89 -8.89 41.91 49.53 82.55 100.33
2 8.89 -8.89 59.69 31.75 82.55 100.33
3 -8.89 8.89 41.91 49.53 100.33 82.55
4 8.89 8.89 59.69 31.75 100.33 82.55

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Page 44 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 14, 2023 Date: 6/16/2023
Fastening point:

6 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Page 45 of 96
Job No Sheet No Rev
1
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Job Information
Engineer Checked Approved

Name:
Date: 14-Jun-23

Project ID
Project Name

Structure Type SPACE FRAME

Number of Nodes 6 Highest Node 6


Number of Elements 5 Highest Beam 5

Number of Basic Load Cases 6


Number of Combination Load Cases 5

Included in this printout are data for:


All The Whole Structure

Included in this printout are results for load cases:


Type L/C Name

Primary 1 DL
Primary 2 WL(+Z)
Primary 3 WL(-Z)
Primary 4 WL(+X)
Primary 5 WL(-X)
Combination 6 1.4DL
Combination 7 1.2DL+1.0WL(+X)
Combination 8 1.2DL+1.0WL(-X)
Combination 9 1.2DL+1.0WL(+Z)
Combination 10 1.2DL+1.0WL(-Z)

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 1 of 8

Page 46 of 96
Job No Sheet No Rev
2
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Y 2
X
Z
Load 1

Whole Structure

3D Rendered View

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 2 of 8

Page 47 of 96
Job No Sheet No Rev
3
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Beams
Beam Node A Node B Length Property 
(m) (degrees)
1 1 2 1.000 2 0
2 2 3 0.520 2 0
3 3 4 1.480 2 0
4 3 5 1.202 1 0
5 3 6 1.202 1 0

Section Properties
Prop Section Area Iyy Izz J Material
(m2) (in4) (in4) (in4)
1 PIPS20 0.001 0.627 0.627 1.254 STEEL
2 PIPS30 0.001 2.850 2.850 5.689 STEEL

Materials
Mat Name E  Density 
(kN/mm2) (kg/m3) (/°C)
1 STEEL 205.000 0.300 7.83E+3 12E -6
2 CONCRETE 21.718 0.170 2.4E+3 10E -6
3 ALUMINUM 68.948 0.330 2.71E+3 23E -6
4 STAINLESSSTEEL 197.930 0.300 7.83E+3 18E -6
5 STEEL_36_KSI 199.948 0.300 7.83E+3 11.7E -6
6 STEEL_50_KSI 199.948 0.300 7.83E+3 11.7E -6
7 STEEL_275_NMM2 205.000 0.300 7.85E+3 12E -6
8 STEEL_355_NMM2 205.000 0.300 7.85E+3 12E -6

Supports
Node X Y Z rX rY rZ
(kN/mm) (kN/mm) (kN/mm) (kN-m/deg) (kN-m/deg) (kN-m/deg)
1 Fixed Fixed Fixed Fixed Fixed Fixed
2 Fixed - Fixed Fixed - Fixed
5 Fixed Fixed Fixed - Fixed Fixed
6 Fixed Fixed Fixed - Fixed Fixed

Releases
Beam ends not shown in this table are fixed in all directions.
Beam Node x y z rx ry rz

4 3 Fixed Fixed Fixed Fixed Fixed Fixed


5 3 Fixed Fixed Fixed Fixed Fixed Fixed

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 3 of 8

Page 48 of 96
Job No Sheet No Rev
4
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Reference Load Cases


Number Name Type

R1 ANTENNA/EQUIPMENT Dead

Primary Load Cases


Number Name Type

1 DL Dead
2 WL(+Z) Wind
3 WL(-Z) Wind
4 WL(+X) Wind
5 WL(-X) Wind

Combination Load Cases


Comb. Combination L/C Name Primary Primary L/C Name Factor

6 1.4DL 1 DL 1.40
7 1.2DL+1.0WL(+X) 1 DL 1.20
4 WL(+X) 1.00
8 1.2DL+1.0WL(-X) 1 DL 1.20
5 WL(-X) 1.00
9 1.2DL+1.0WL(+Z) 1 DL 1.20
2 WL(+Z) 1.00
10 1.2DL+1.0WL(-Z) 1 DL 1.20
3 WL(-Z) 1.00

Reactions
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
1 1:DL 0 0.543 0 0 0 0
2:WL(+Z) 0 0 -0.091 -0.015 0 0
3:WL(-Z) 0 0 0.091 0.015 0 0
4:WL(+X) -0.091 -0.003 0 0 0 0.015
5:WL(-X) 0.091 -0.003 0 0 0 -0.015
6:1.4DL 0 0.760 0 0 0 0
7:1.2DL+1.0WL(+X) -0.091 0.649 0 0 0 0.015
8:1.2DL+1.0WL(-X) 0.091 0.649 0 0 0 -0.015
9:1.2DL+1.0WL(+Z) 0 0.651 -0.091 -0.015 0 0
10:1.2DL+1.0WL(-Z) 0 0.651 0.091 0.015 0 0
2 1:DL 0 0 0 0 0 0
2:WL(+Z) 0 0 -0.625 -0.342 0 0

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 4 of 8

Page 49 of 96
Job No Sheet No Rev
5
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Reactions Cont...
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
3:WL(-Z) 0 0 0.625 0.342 0 0
4:WL(+X) 0.333 0 0 0 0 -0.061
5:WL(-X) -0.333 0 0 0 0 0.061
6:1.4DL 0 0 0 0 0 0
7:1.2DL+1.0WL(+X) 0.333 0 0 0 0 -0.061
8:1.2DL+1.0WL(-X) -0.333 0 0 0 0 0.061
9:1.2DL+1.0WL(+Z) 0 0 -0.625 -0.342 0 0
10:1.2DL+1.0WL(-Z) 0 0 0.625 0.342 0 0
5 1:DL 0.127 0.241 0 0 0 0.005
2:WL(+Z) 0 0 -0.003 -0.006 -0.007 0
3:WL(-Z) 0 0 0.003 0.006 0.007 0
4:WL(+X) -0.464 -0.657 0 0 0 0.012
5:WL(-X) 0.411 0.659 0 0 0 -0.001
6:1.4DL 0.177 0.338 0 0 0 0.007
7:1.2DL+1.0WL(+X) -0.312 -0.367 0 0 0 0.018
8:1.2DL+1.0WL(-X) 0.563 0.949 0 0 0 0.005
9:1.2DL+1.0WL(+Z) 0.152 0.290 -0.003 -0.006 -0.007 0.006
10:1.2DL+1.0WL(-Z) 0.152 0.290 0.003 0.006 0.007 0.006
6 1:DL -0.127 0.241 0 0 0 -0.005
2:WL(+Z) 0 0 -0.003 -0.006 0.007 0
3:WL(-Z) 0 0 0.003 0.006 -0.007 0
4:WL(+X) -0.411 0.659 0 0 0 0.001
5:WL(-X) 0.464 -0.657 0 0 0 -0.012
6:1.4DL -0.177 0.338 0 0 0 -0.007
7:1.2DL+1.0WL(+X) -0.563 0.949 0 0 0 -0.005
8:1.2DL+1.0WL(-X) 0.312 -0.367 0 0 0 -0.018
9:1.2DL+1.0WL(+Z) -0.152 0.290 -0.003 -0.006 0.007 -0.006
10:1.2DL+1.0WL(-Z) -0.152 0.290 0.003 0.006 -0.007 -0.006

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 5 of 8

Page 50 of 96
Job No Sheet No Rev
6
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Reaction Summary
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
Max FX 5 8:1.2DL+1.0WL(-X) 0.563 0.949 0 0 0 0.005
Min FX 6 7:1.2DL+1.0WL(+X) -0.563 0.949 0 0 0 -0.005
Max FY 6 7:1.2DL+1.0WL(+X) -0.563 0.949 0 0 0 -0.005
Min FY 5 4:WL(+X) -0.464 -0.657 0 0 0 0.012
Max FZ 2 3:WL(-Z) 0 0 0.625 0.342 0 0
Min FZ 2 2:WL(+Z) 0 0 -0.625 -0.342 0 0
Max MX 2 3:WL(-Z) 0 0 0.625 0.342 0 0
Min MX 2 2:WL(+Z) 0 0 -0.625 -0.342 0 0
Max MY 6 2:WL(+Z) 0 0 -0.003 -0.006 0.007 0
Min MY 5 2:WL(+Z) 0 0 -0.003 -0.006 -0.007 0
Max MZ 2 5:WL(-X) -0.333 0 0 0 0 0.061
Min MZ 2 4:WL(+X) 0.333 0 0 0 0 -0.061

Reaction Envelope
Horizontal Vertical Horizontal Moment
Node Env FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
1 +ve 0.091 0.760 0.091 0.015 0 0.015
1 +ve Load: 5 Load: 6 Load: 3 Load: 3 - Load: 4
1 -ve -0.091 -0.003 -0.091 -0.015 0 -0.015
1 -ve Load: 4 Load: 4 Load: 2 Load: 2 - Load: 5
2 +ve 0.333 0 0.625 0.342 0 0.061
2 +ve Load: 4 - Load: 3 Load: 3 - Load: 5
2 -ve -0.333 0 -0.625 -0.342 0 -0.061
2 -ve Load: 5 - Load: 2 Load: 2 - Load: 4
5 +ve 0.563 0.949 0.003 0.006 0.007 0.018
5 +ve Load: 8 Load: 8 Load: 3 Load: 3 Load: 3 Load: 7
5 -ve -0.464 -0.657 -0.003 -0.006 -0.007 -0.001
5 -ve Load: 4 Load: 4 Load: 2 Load: 2 Load: 2 Load: 5
6 +ve 0.464 0.949 0.003 0.006 0.007 0.001
6 +ve Load: 5 Load: 7 Load: 3 Load: 3 Load: 2 Load: 4
6 -ve -0.563 -0.657 -0.003 -0.006 -0.007 -0.018
6 -ve Load: 7 Load: 5 Load: 2 Load: 2 Load: 3 Load: 8

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 6 of 8

Page 51 of 96
Job No Sheet No Rev
7
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Steel Design (Track 2) Beam 1 Check 1


|-----------------------------------------------------------------------------|
Member No: 1 Profile: ST PIPS30 (AISC SECTIONS)|
Utilization Ratio
Status: PASS Ratio: 0.003 Loadcase: 9 |
Location: 0.00 Ref: Eq.H1-1b |
Beam Analysis Design Actual Allowable Ratio Clause L/C Ax Iz Iy Ix
Pz: 0.6515 C Vy: 0.000 Vx: -.9101E-01 2 |
Property Property Ratio Ratio (Act./Allow.) (m ) (in4) (in4) (in4)
Tz: 0.000 My: 0.1517E-01 Mx: 0.000 |
1 PIPS30 PIPS30 0.003 1.000 0.003 Eq.H1-1b
-----------------------------------------------------------------------------| 9 0.001 2.850 2.850 5.700
2 PIPS30 PIPS30 0.046 1.000 0.046 Eq.H1-1b
-----------------------------------------------------------------------------| 9 0.001 2.850 2.850 5.700
3 PIPS30
Member No: PIPS30
2 0.027 1.000
Profile: ST PIPS30 0.027 Eq.H1-1b 7 0.001
(AISC SECTIONS)| 2.850 2.850 5.700
4 PIPS20
Status: PIPS20
PASS 0.020
Ratio: 1.000 0.0460.020 Eq.H1-1b
Loadcase: 9 90.001 | 0.627 0.627 1.254
5 PIPS20
Location: PIPS20
0.00 0.020
Ref: 1.000
Eq.H1-1b 0.020 Eq.H1-1b 9 0.001 | 0.627 0.627 1.254
Pz: 0.5284 C Vy: 0.000 Vx: -.5338 |
Tz: 0.000 My: 0.3574 Mx: 0.000 |
-----------------------------------------------------------------------------|
-----------------------------------------------------------------------------|
Member No: 3 Profile: ST PIPS30 (AISC SECTIONS)|
Status: PASS Ratio: 0.027 Loadcase: 7 |
Location: 0.00 Ref: Eq.H1-1b |
Pz: 0.8979 C Vy: 0.2694 Vx: 0.000 |
Tz: 0.000 My: 0.000 Mx: 0.1993 |
-----------------------------------------------------------------------------|
-----------------------------------------------------------------------------|
Member No: 4 Profile: ST PIPS20 (AISC SECTIONS)|
Status: PASS Ratio: 0.020 Loadcase: 9 |
Location: 0.00 Ref: Eq.H1-1b |
Pz: 0.2643 C Vy: 0.1436E-01 Vx: 0.8490E-01 |
Tz: -.8903E-02 My: -.5035E-01 Mx: 0.3499E-04 |
-----------------------------------------------------------------------------|
-----------------------------------------------------------------------------|
Member No: 5 Profile: ST PIPS20 (AISC SECTIONS)|
Status: PASS Ratio: 0.020 Loadcase: 9 |
Location: 0.00 Ref: Eq.H1-1b |
Pz: 0.2643 C Vy: 0.1436E-01 Vx: -.8490E-01 |
Tz: 0.8903E-02 My: 0.5035E-01 Mx: 0.3499E-04 |
-----------------------------------------------------------------------------

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 7 of 8

Page 52 of 96
Job No Sheet No Rev
8
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref

By Date14-Jun-23 Chd

Client File WALL MOUNTED (2).STDDate/Time 14-Jun-2023 11:35

Failed Members
There is no data of this type.

Print Time/Date: 19/06/2023 11:18 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 8 of 8

Page 53 of 96
Description Smax Smin Von Mis Tresca Checking
Pl Load Top Bottom Top Bottom Top Bottom Top Bottom Utilizat Ade Yield
at Combina (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm ion qua Strength
e tion mm) m) mm) m) mm) m) mm) m) Ratio cy (N/sqmm)
4 0.0001 PAS
1 DL 0.028 0.017 -0.004 0.001 0.03 0.017 0.032 0.017 248
6 29032 S
0.0036 PAS
2 WL(+X) 0.382 0.126 -0.526 -0.326 0.789 0.404 0.907 0.452
57258 S
0.0036 PAS
3 WL(-X) 0.526 0.326 -0.382 -0.126 0.789 0.404 0.907 0.452
57258 S
0.0161 PAS
4 WL(+Z) 2.501 -0.557 -1.28 -4.007 3.331 3.76 3.781 4.007
57258 S
0.0161 PAS
5 WL(-Z) 1.28 4.007 -2.501 0.557 3.331 3.76 3.781 4.007
57258 S
0.0001 PAS
6 1.4DL 0.039 0.024 -0.006 0.001 0.042 0.024 0.045 0.024
81452 S
7
0.0037 PAS
1.2DL+1. 0.401 0.146 -0.517 -0.325 0.797 0.418 0.918 0.471
01613 S
0WL(+X)
8
0.0036 PAS
1.2DL+1. 0.535 0.327 -0.363 -0.106 0.783 0.391 0.899 0.433
25 S
0WL(-X)
9
0.0161 PAS
1.2DL+1. 2.497 -0.539 -1.249 -4.003 3.304 3.763 3.746 4.003
41129 S
0WL(+Z)
10
0.0161 PAS
1.2DL+1. 1.311 4.011 -2.505 0.574 3.358 3.757 3.816 4.011
73387 S
0WL(-Z)
4 0.0001 PAS
1 DL 0.021 0.021 -0.006 -0.012 0.024 0.029 0.027 0.033
7 33065 S
0.0032 PAS
2 WL(+X) -0.155 0.691 -0.814 0.235 0.748 0.609 0.814 0.691
82258 S
0.0032 PAS
3 WL(-X) 0.814 -0.235 0.155 -0.691 0.748 0.609 0.814 0.691
82258 S
0.0318 PAS
4 WL(+Z) 4.843 1.272 -3.053 -5.208 6.896 5.946 7.896 6.479
3871 S
0.0318 PAS
5 WL(-Z) 3.053 5.208 -4.843 -1.272 6.896 5.946 7.896 6.479
3871 S
0.0001 PAS
6 1.4DL 0.029 0.03 -0.008 -0.017 0.034 0.041 0.037 0.047
89516 S
7
0.0032 PAS
1.2DL+1. -0.139 0.708 -0.811 0.229 0.751 0.626 0.811 0.708
70161 S
0WL(+X)
8
0.0032 PAS
1.2DL+1. 0.817 -0.24 0.17 -0.676 0.747 0.593 0.817 0.676
94355 S
0WL(-X)
9
0.0317 PAS
1.2DL+1. 4.837 1.296 -3.029 -5.222 6.872 5.976 7.866 6.518
17742 S
0WL(+Z)
10
0.0319 PAS
1.2DL+1. 3.077 5.194 -4.849 -1.247 6.921 5.917 7.926 6.441
59677 S
0WL(-Z)
4 0.0001 PAS
1 DL 0.021 0.018 -0.01 -0.013 0.027 0.028 0.031 0.032
8 29032 S
0.0070 PAS
2 WL(+X) -0.342 1.739 -1.143 0.426 1.016 1.57 1.143 1.739
12097 S
0.0070 PAS
3 WL(-X) 1.143 -0.426 0.342 -1.739 1.016 1.57 1.143 1.739
12097 S
0.0463 PAS
4 WL(+Z) 5.827 3.286 -5.265 -8.216 9.61 10.261 11.092 11.502
79032 S
0.0463 PAS
5 WL(-Z) 5.265 8.216 -5.827 -3.286 9.61 10.261 11.092 11.502
79032 S
0.0001 PAS
6 1.4DL 0.029 0.026 -0.014 -0.019 0.038 0.039 0.043 0.044
77419 S

Page 54 of 96
7
0.0070 PAS
1.2DL+1. -0.329 1.739 -1.143 0.432 1.019 1.568 1.143 1.739
12097 S
0WL(+X)
8
0.0070 PAS
1.2DL+1. 1.143 -0.42 0.355 -1.739 1.013 1.572 1.143 1.739
12097 S
0WL(-X)
9
0.0465 PAS
1.2DL+1. 5.816 3.308 -5.241 -8.231 9.579 10.291 11.056 11.538
24194 S
0WL(+Z)
10
0.0462 PAS
1.2DL+1. 5.29 8.201 -5.838 -3.265 9.641 10.232 11.128 11.466
33871 S
0WL(-Z)
4 0.0001 PAS
1 DL 0.02 0.018 -0.014 -0.017 0.03 0.031 0.034 0.035
9 41129 S
0.0124 PAS
2 WL(+X) -0.861 3.095 -1.391 0.616 1.216 2.838 1.391 3.095
79839 S
0.0124 PAS
3 WL(-X) 1.391 -0.616 0.861 -3.095 1.216 2.838 1.391 3.095
79839 S
0.0686 PAS
4 WL(+Z) 7.697 5.984 -5.916 -11.049 11.823 14.966 13.613 17.032
77419 S
0.0686 PAS
5 WL(-Z) 5.916 11.049 -7.697 -5.984 11.823 14.966 13.613 17.032
77419 S
0.0002 PAS
6 1.4DL 0.028 0.025 -0.02 -0.024 0.042 0.043 0.048 0.05
01613 S
7
0.0124 PAS
1.2DL+1. -0.842 3.095 -1.403 0.616 1.223 2.837 1.403 3.095
79839 S
0WL(+X)
8
0.0124 PAS
1.2DL+1. 1.379 -0.614 0.88 -3.096 1.21 2.839 1.379 3.096
83871 S
0WL(-X)
9
0.0688 PAS
1.2DL+1. 7.68 6.004 -5.892 -11.069 11.788 15.001 13.572 17.073
42742 S
0WL(+Z)
10
0.0685 PAS
1.2DL+1. 5.94 11.029 -7.714 -5.963 11.859 14.931 13.655 16.991
12097 S
0WL(-Z)
5 0.0001 PAS
1 DL 0.022 0.021 -0.019 -0.02 0.035 0.036 0.041 0.041
0 65323 S
0.0104 PAS
2 WL(+X) 0.191 1.684 -0.412 -0.904 0.534 2.275 0.603 2.588
35484 S
0.0104 PAS
3 WL(-X) 0.412 0.904 -0.191 -1.684 0.534 2.275 0.603 2.588
35484 S
0.0987 PAS
4 WL(+Z) 13.717 9.09 -6.864 -15.409 18.15 21.451 20.581 24.499
8629 S
- 0.0987 PAS
5 WL(-Z) 6.864 15.409 -9.09 18.15 21.451 20.581 24.499
13.717 8629 S
0.0002 PAS
6 1.4DL 0.031 0.03 -0.026 -0.028 0.049 0.05 0.057 0.058
33871 S
7
0.0106 PAS
1.2DL+1. 0.191 1.708 -0.408 -0.926 0.53 2.314 0.599 2.634
20968 S
0WL(+X)
8
0.0102 PAS
1.2DL+1. 0.418 0.882 -0.193 -1.66 0.541 2.236 0.611 2.542
5 S
0WL(-X)
9
0.0989 PAS
1.2DL+1. 13.695 9.115 -6.838 -15.432 18.11 21.492 20.533 24.547
79839 S
0WL(+Z)
10
0.0985 PAS
1.2DL+1. 6.89 15.386 -13.74 -9.065 18.191 21.409 20.629 24.45
8871 S
0WL(-Z)
5 0.0001 PAS
1 DL 0.019 0.02 -0.022 -0.021 0.035 0.036 0.041 0.041
1 65323 S
0.0209 PAS
2 WL(+X) 2.457 -0.798 1.413 -5.195 2.136 4.846 2.457 5.195
47581 S

Page 55 of 96
0.0209 PAS
3 WL(-X) -1.413 5.195 -2.457 0.798 2.136 4.846 2.457 5.195
47581 S
- 0.0986 PAS
4 WL(+Z) 6.574 15.311 -9.147 18.066 21.404 20.432 24.458
13.858 20968 S
0.0986 PAS
5 WL(-Z) 13.858 9.147 -6.574 -15.311 18.066 21.404 20.432 24.458
20968 S
0.0002 PAS
6 1.4DL 0.026 0.028 -0.031 -0.03 0.049 0.05 0.057 0.058
33871 S
7
0.0209 PAS
1.2DL+1. 2.456 -0.788 1.41 -5.207 2.135 4.861 2.456 5.207
95968 S
0WL(+X)
8
0.0209 PAS
1.2DL+1. -1.415 5.184 -2.459 0.807 2.137 4.831 2.459 5.184
03226 S
0WL(-X)
9
- 0.0988 PAS
1.2DL+1. 6.549 15.334 -9.172 18.025 21.445 20.384 24.506
13.836 14516 S
0WL(+Z)
10
0.0984 PAS
1.2DL+1. 13.88 9.122 -6.6 -15.287 18.106 21.362 20.48 24.409
23387 S
0WL(-Z)
5 0.0001 PAS
1 DL 0.014 0.017 -0.02 -0.018 0.03 0.031 0.034 0.035
2 41129 S
0.0249 PAS
2 WL(+X) 3.402 -1.387 1.681 -6.177 2.946 5.614 3.402 6.177
07258 S
0.0249 PAS
3 WL(-X) -1.681 6.177 -3.402 1.387 2.946 5.614 3.402 6.177
07258 S
0.0688 PAS
4 WL(+Z) 5.716 10.943 -7.532 -6.126 11.509 14.977 13.248 17.069
26613 S
0.0688 PAS
5 WL(-Z) 7.532 6.126 -5.716 -10.943 11.509 14.977 13.248 17.069
26613 S

Figure 9. Shown above is the contour stress distribution per target element size of the
built-up shape steel.

Page 56 of 96
Figure 10. Shown above is the 3d-rendered view of the built-up-shaped-baseplate. Lines
resembles the target element size for the Finite Element Analysis (FEA).

Description Smax Smin Von Mis Tresca Checking


Pl Load Top Bottom Top Bottom Top Bottom Top Bottom Utilizat Ade Yield
at Combina (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm ion qua Strength
e tion mm) m) mm) m) mm) m) mm) m) Ratio cy (N/sqmm)
2
0.0013
3 1 DL 0.248 0.233 -0.095 -0.099 0.307 0.296 0.343 0.333 PAS 248
83065
4 S
0.0008 PAS
2 WL(+X) 0.104 0.055 -0.101 -0.04 0.177 0.083 0.205 0.095
26613 S
0.0008 PAS
3 WL(-X) 0.102 0.041 -0.103 -0.055 0.178 0.083 0.205 0.096
26613 S
0.0003 PAS
4 WL(+Z) 0.086 0.021 0.012 -0.028 0.08 0.043 0.086 0.049
46774 S
0.0003 PAS
5 WL(-Z) -0.012 0.028 -0.086 -0.021 0.08 0.043 0.086 0.049
46774 S
0.0019 PAS
6 1.4DL 0.347 0.327 -0.133 -0.139 0.429 0.414 0.48 0.466
35484 S
7
0.0024
1.2DL+1. 0.397 0.326 -0.211 -0.15 0.535 0.422 0.608 0.477 PAS
51613
0WL(+X) S
8
0.0013
1.2DL+1. 0.207 0.239 -0.025 -0.093 0.22 0.297 0.232 0.332 PAS
3871
0WL(-X) S
9
0.0018
1.2DL+1. 0.375 0.301 -0.094 -0.147 0.43 0.396 0.469 0.448 PAS
91129
0WL(+Z) S
10
0.0014
1.2DL+1. 0.223 0.259 -0.137 -0.091 0.315 0.315 0.36 0.35 PAS
51613
0WL(-Z) S

Page 57 of 96
2
0.0013
3 1 DL 0.243 0.188 -0.076 -0.136 0.289 0.282 0.319 0.324 PAS
06452
5 S
0.0005 PAS
2 WL(+X) 0.136 0.013 0.002 -0.095 0.135 0.103 0.136 0.108
48387 S
0.0005 PAS
3 WL(-X) 0 0.095 -0.135 -0.012 0.135 0.101 0.135 0.107
44355 S
0.0005 PAS
4 WL(+Z) 0.102 0.041 -0.043 -0.004 0.129 0.043 0.145 0.045
84677 S
0.0005 PAS
5 WL(-Z) 0.043 0.004 -0.102 -0.041 0.129 0.043 0.145 0.045
84677 S
0.0018 PAS
6 1.4DL 0.341 0.263 -0.106 -0.19 0.404 0.395 0.447 0.454
30645 S
7
0.0019
1.2DL+1. 0.4 0.233 -0.061 -0.252 0.434 0.421 0.461 0.486 PAS
59677
0WL(+X) S
8
0.0013
1.2DL+1. 0.205 0.225 -0.139 -0.079 0.299 0.273 0.343 0.304 PAS
83065
0WL(-X) S
9
0.0021
1.2DL+1. 0.393 0.266 -0.133 -0.167 0.474 0.379 0.527 0.434 PAS
25
0WL(+Z) S
10
0.0013
1.2DL+1. 0.192 0.185 -0.049 -0.159 0.221 0.298 0.241 0.344 PAS
87097
0WL(-Z) S
2
0.0013
3 1 DL 0.213 0.179 -0.093 -0.15 0.272 0.285 0.306 0.329 PAS
26613
6 S
0.0004 PAS
2 WL(+X) 0.089 0.035 -0.023 -0.066 0.103 0.089 0.112 0.101
51613 S
0.0004 PAS
3 WL(-X) 0.025 0.066 -0.089 -0.034 0.103 0.088 0.113 0.1
55645 S
0.0008 PAS
4 WL(+Z) 0.142 0.051 -0.075 -0.007 0.191 0.055 0.218 0.058
79032 S
0.0008 PAS
5 WL(-Z) 0.075 0.007 -0.142 -0.051 0.191 0.055 0.218 0.058
79032 S
0.0018 PAS
6 1.4DL 0.298 0.251 -0.131 -0.21 0.38 0.4 0.428 0.461
58871 S
7
0.0018
1.2DL+1. 0.317 0.234 -0.107 -0.231 0.382 0.403 0.424 0.465 PAS
75
0WL(+X) S
8
0.0013
1.2DL+1. 0.211 0.205 -0.131 -0.138 0.299 0.299 0.342 0.344 PAS
87097
0WL(-X) S
9
0.0023
1.2DL+1. 0.397 0.265 -0.187 -0.187 0.517 0.393 0.584 0.451 PAS
54839
0WL(+Z) S
10
0.0013
1.2DL+1. 0.114 0.165 -0.038 -0.174 0.137 0.294 0.152 0.339 PAS
66935
0WL(-Z) S
2
0.0011
3 1 DL 0.195 0.158 -0.09 -0.14 0.252 0.257 0.285 0.297 PAS
97581
7 S
0.0005 PAS
2 WL(+X) 0.091 0.041 -0.046 -0.04 0.12 0.07 0.137 0.081
52419 S
0.0005 PAS
3 WL(-X) 0.047 0.042 -0.091 -0.042 0.121 0.072 0.138 0.083
56452 S
0.0013 PAS
4 WL(+Z) 0.213 0.064 -0.12 -0.045 0.292 0.095 0.333 0.109
42742 S
0.0013 PAS
5 WL(-Z) 0.12 0.045 -0.213 -0.064 0.292 0.095 0.333 0.109
42742 S
0.0016 PAS
6 1.4DL 0.273 0.221 -0.126 -0.195 0.353 0.36 0.399 0.416
77419 S

Page 58 of 96
7
0.0014
1.2DL+1. 0.269 0.185 -0.098 -0.162 0.33 0.301 0.368 0.348 PAS
83871
0WL(+X) S
8
0.0015
1.2DL+1. 0.227 0.205 -0.144 -0.183 0.324 0.336 0.371 0.387 PAS
60484
0WL(-X) S
9
0.0026
1.2DL+1. 0.435 0.238 -0.217 -0.198 0.575 0.378 0.651 0.436 PAS
25
0WL(+Z) S
10
0.0011
1.2DL+1. 0.105 0.15 -0.071 -0.147 0.153 0.257 0.176 0.297 PAS
97581
0WL(-Z) S
2
0.0012
3 1 DL 0.192 0.167 -0.113 -0.142 0.267 0.267 0.305 0.308 PAS
41935
8 S
0.0006 PAS
2 WL(+X) 0.114 -0.016 -0.036 -0.165 0.136 0.158 0.15 0.165
65323 S
0.0006 PAS
3 WL(-X) 0.038 0.167 -0.115 0.014 0.138 0.16 0.153 0.167
73387 S
0.0025 PAS
4 WL(+Z) 0.49 -0.064 -0.149 -0.47 0.579 0.442 0.639 0.47
76613 S
0.0025 PAS
5 WL(-Z) 0.149 0.47 -0.49 0.064 0.579 0.442 0.639 0.47
76613 S
0.0017 PAS
6 1.4DL 0.269 0.233 -0.158 -0.199 0.374 0.374 0.427 0.432
41935 S
7
0.0011
1.2DL+1. 0.226 0.062 -0.054 -0.214 0.257 0.251 0.28 0.276 PAS
29032
0WL(+X) S
8
0.0020
1.2DL+1. 0.253 0.354 -0.235 -0.143 0.422 0.443 0.487 0.497 PAS
04032
0WL(-X) S
9
0.0039
1.2DL+1. 0.709 -0.14 -0.274 -0.365 0.878 0.319 0.983 0.365 PAS
6371
0WL(+Z) S
10
1.2DL+1. 0.05 0.654 -0.295 -0.09 0.323 0.703 0.345 0.744 0.003 PAS
0WL(-Z) S
2
0.0011
3 1 DL 0.185 0.165 -0.089 -0.113 0.242 0.242 0.274 0.278 PAS
20968
9 S
0.0024 PAS
2 WL(+X) 0.157 -0.117 0.076 -0.598 0.136 0.549 0.157 0.598
1129 S
0.0024 PAS
3 WL(-X) -0.074 0.599 -0.158 0.117 0.137 0.55 0.158 0.599
15323 S
0.0047 PAS
4 WL(+Z) 0.725 0.138 -0.458 -0.951 1.033 1.027 1.183 1.089
70161 S
0.0047 PAS
5 WL(-Z) 0.458 0.951 -0.725 -0.138 1.033 1.027 1.183 1.089
70161 S
0.0015 PAS
6 1.4DL 0.259 0.231 -0.125 -0.158 0.339 0.339 0.384 0.389
68548 S
7
0.0024
1.2DL+1. 0.319 -0.051 0.029 -0.602 0.305 0.578 0.319 0.602 PAS
27419
0WL(+X) S
8
0.0028
1.2DL+1. 0.134 0.7 -0.252 0.079 0.339 0.664 0.386 0.7 PAS
22581
0WL(-X) S
9
0.0059
1.2DL+1. 0.934 0.005 -0.552 -0.755 1.301 0.758 1.486 0.76 PAS
91935
0WL(+Z) S
10
0.0057
1.2DL+1. 0.373 1.148 -0.526 -0.272 0.782 1.305 0.898 1.42 PAS
25806
0WL(-Z) S
2
0.0008
4 1 DL 0.145 0.134 -0.076 -0.086 0.194 0.192 0.221 0.22 PAS
91129
0 S

Page 59 of 96
0.0028 PAS
2 WL(+X) 0.184 -0.003 -0.06 -0.706 0.22 0.705 0.244 0.706
46774 S
0.0028 PAS
3 WL(-X) 0.059 0.705 -0.183 0.006 0.219 0.702 0.242 0.705
42742 S
0.0085 PAS
4 WL(+Z) 1.004 0.513 -0.698 -1.607 1.482 1.916 1.702 2.12
48387 S
0.0085 PAS
5 WL(-Z) 0.698 1.607 -1.004 -0.513 1.482 1.916 1.702 2.12
48387 S

Figure 11. Shown above is the contour stress distribution per target element size of the
built-up shape steel.

Figure 12. Shown above is the 3d-rendered view of the built-up-shaped-baseplate. Lines
resembles the target element size for the Finite Element Analysis (FEA).

Page 60 of 96
Description Smax Smin Von Mis Tresca Checking
Pl Load Top Bottom Top Bottom Top Bottom Top Bottom Utilizat Ade Yield
at Combina (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm (N/sq (N/sqm ion qua Strength
e tion mm) m) mm) m) mm) m) mm) m) Ratio cy (N/sqmm)
6 0.0004 PAS
1 DL 0.109 0.089 0.02 -0.005 0.1 0.092 0.109 0.094 248
9 39516 S
2 WL 0.0019 PAS
0.486 0.169 0.144 -0.11 0.432 0.244 0.486 0.28
(+X) 59677 S
0.0026 PAS
3 WL (-X) -0.217 0.206 -0.657 -0.121 0.579 0.287 0.657 0.328
49194 S
4 WL 0.0008 PAS
0.215 -0.051 0.086 -0.131 0.187 0.115 0.215 0.131
(+Z) 66935 S
0.0008 PAS
5 WL (-Z) -0.086 0.131 -0.215 0.051 0.187 0.115 0.215 0.131
66935 S
0.0006 PAS
6 1.4DL 0.152 0.125 0.027 -0.007 0.141 0.128 0.152 0.132
12903 S
7
0.0024
1,2DL+1. 0.614 0.273 0.169 -0.113 0.55 0.343 0.614 0.385 PAS
75806
0WL(+X) S
8
0.0021
1,2DL+1. -0.187 0.22 -0.532 -0.034 0.468 0.239 0.532 0.254 PAS
45161
0WL(-X) S
9
0.0013
1,2DL+1. 0.345 0.021 0.111 -0.103 0.305 0.114 0.345 0.123 PAS
91129
0WL(+Z) S
10
0.0008
1,2DL+1. -0.055 0.218 -0.092 0.066 0.08 0.193 0.092 0.218 PAS
79032
0WL(-Z) S
7 0.0004 PAS
1 DL 0.098 0.054 0.003 -0.05 0.096 0.09 0.098 0.104
0 19355 S
2 WL 0.0020 PAS
0.497 0.016 0.13 -0.389 0.446 0.397 0.497 0.405
(+X) 04032 S
0.0028 PAS
3 WL (-X) -0.215 0.62 -0.706 0.071 0.627 0.587 0.706 0.62
46774 S
4 WL 0.0011 PAS
0.277 -0.008 0.075 -0.286 0.248 0.282 0.277 0.286
(+Z) 53226 S
0.0011 PAS
5 WL (-Z) -0.075 0.286 -0.277 0.008 0.248 0.282 0.277 0.286
53226 S
0.0005 PAS
6 1.4DL 0.137 0.075 0.005 -0.07 0.135 0.126 0.137 0.145
84677 S
7
0.0024
1,2DL+1. 0.609 0.073 0.139 -0.442 0.553 0.483 0.609 0.515 PAS
55645
0WL(+X) S
8
0.0024
1,2DL+1. -0.194 0.582 -0.605 0.113 0.535 0.535 0.605 0.582 PAS
39516
0WL(-X) S
9
0.0015
1,2DL+1. 0.386 0.008 0.088 -0.298 0.35 0.302 0.386 0.306 PAS
56452
0WL(+Z) S
10
0.0012
1,2DL+1. -0.047 0.301 -0.183 -0.002 0.165 0.303 0.183 0.304 PAS
25806
0WL(-Z) S
7 0.0004 PAS
1 DL 0.118 0.027 0.002 -0.094 0.117 0.11 0.118 0.121
1 87903 S
2 WL 0.0026 PAS
0.654 -0.109 0.143 -0.628 0.595 0.582 0.654 0.628
(+X) 37097 S
0.0038 PAS
3 WL (-X) -0.242 0.959 -0.94 0.232 0.845 0.866 0.94 0.959
66935 S
4 WL 0.0018 PAS
0.414 -0.147 0.14 -0.448 0.365 0.396 0.414 0.448
(+Z) 06452 S
0.0018 PAS
5 WL (-Z) -0.14 0.448 -0.414 0.147 0.365 0.396 0.414 0.448
06452 S
0.0006 PAS
6 1.4DL 0.165 0.038 0.003 -0.132 0.164 0.154 0.165 0.17
85484 S

Page 61 of 96
7
0.0031
1,2DL+1. 0.791 -0.085 0.15 -0.732 0.727 0.694 0.791 0.732 PAS
89516
0WL(+X) S
8
0.0035
1,2DL+1. -0.226 0.871 -0.812 0.239 0.726 0.779 0.812 0.871 PAS
12097
0WL(-X) S
9
0.0022
1,2DL+1. 0.548 -0.168 0.15 -0.508 0.491 0.448 0.548 0.508 PAS
09677
0WL(+Z) S
10
0.0017
1,2DL+1. -0.117 0.422 -0.293 0.092 0.255 0.385 0.293 0.422 PAS
01613
0WL(-Z) S
7 0.0006 PAS
1 DL 0.148 0.008 0.006 -0.153 0.145 0.157 0.148 0.161
2 49194 S
2 WL 0.0038 PAS
0.816 -0.187 0.192 -0.943 0.739 0.864 0.816 0.943
(+X) 02419 S
0.0056 PAS
3 WL (-X) -0.317 1.394 -1.164 0.333 1.042 1.261 1.164 1.394
20968 S
4 WL 0.0022 PAS
0.503 -0.066 0.118 -0.546 0.455 0.516 0.503 0.546
(+Z) 01613 S
0.0022 PAS
5 WL (-Z) -0.118 0.546 -0.503 0.066 0.455 0.516 0.503 0.546
01613 S
0.0009 PAS
6 1.4DL 0.207 0.012 0.008 -0.214 0.203 0.22 0.207 0.226
1129 S
7
0.0045
1,2DL+1. 0.988 -0.185 0.204 -1.118 0.903 1.038 0.988 1.118 PAS
08065
0WL(+X) S
8
0.0049
1,2DL+1. -0.294 1.232 -1.002 0.322 0.892 1.106 1.002 1.232 PAS
67742
0WL(-X) S
9
0.0027
1,2DL+1. 0.67 -0.117 0.135 -0.668 0.613 0.618 0.67 0.668 PAS
01613
0WL(+Z) S
10
0.0019
1,2DL+1. -0.086 0.46 -0.349 -0.022 0.315 0.471 0.349 0.482 PAS
43548
0WL(-Z) S
7 0.0009 PAS
1 DL 0.198 -0.003 0.008 -0.227 0.195 0.225 0.198 0.227
3 15323 S
2 WL 0.0051 PAS
1.042 -0.266 0.231 -1.283 0.948 1.172 1.042 1.283
(+X) 73387 S
0.0074 PAS
3 WL (-X) -0.38 1.845 -1.458 0.444 1.31 1.668 1.458 1.845
39516 S
4 WL 0.0027 PAS
0.619 -0.189 0.201 -0.69 0.547 0.617 0.619 0.69
(+Z) 82258 S
0.0027 PAS
5 WL (-Z) -0.201 0.69 -0.619 0.189 0.547 0.617 0.619 0.69
82258 S
0.0012 PAS
6 1.4DL 0.278 -0.004 0.011 -0.318 0.272 0.315 0.278 0.318
82258 S
7
0.0062
1,2DL+1. 1.276 -0.278 0.246 -1.546 1.172 1.428 1.276 1.546 PAS
33871
0WL(+X) S
8
0.0064
1,2DL+1. -0.356 1.595 -1.234 0.418 1.1 1.433 1.234 1.595 PAS
31452
0WL(-X) S
9
0.0035
1,2DL+1. 0.848 -0.276 0.22 -0.878 0.763 0.778 0.848 0.878 PAS
40323
0WL(+Z) S
10
0.0022
1,2DL+1. -0.164 0.568 -0.408 0.035 0.355 0.551 0.408 0.568 PAS
90323
0WL(-Z) S
7 0.0013 PAS
1 DL 0.285 -0.033 0.031 -0.331 0.271 0.316 0.285 0.331
4 34677 S
2 WL 0.0065 PAS
1.296 -0.38 0.304 -1.622 1.174 1.47 1.296 1.622
(+X) 40323 S

Page 62 of 96
0.0089 PAS
3 WL (-X) -0.463 2.229 -1.721 0.577 1.543 2.004 1.721 2.229
87903 S
4 WL 0.0028 PAS
0.648 -0.19 0.202 -0.705 0.574 0.632 0.648 0.705
(+Z) 42742 S
0.0028 PAS
5 WL (-Z) -0.202 0.705 -0.648 0.19 0.574 0.632 0.648 0.705
42742 S
0.0018 PAS
6 1.4DL 0.399 -0.047 0.044 -0.464 0.379 0.443 0.399 0.464
70968 S
7
0.0081
1,2DL+1. 1.635 -0.43 0.345 -2.011 1.493 1.834 1.635 2.011 PAS
08871
0WL(+X) S
8
0.0074
1,2DL+1. -0.416 1.859 -1.388 0.509 1.234 1.664 1.388 1.859 PAS
95968
0WL(-X) S
9
0.0040
1,2DL+1. 0.981 -0.323 0.249 -1.009 0.884 0.893 0.981 1.009 PAS
68548
0WL(+Z) S
10
0.0022
1,2DL+1. -0.129 0.51 -0.341 -0.052 0.299 0.538 0.341 0.562 PAS
66129
0WL(-Z) S
7 0.0020 PAS
1 DL 0.417 -0.095 0.083 -0.503 0.383 0.463 0.417 0.503
5 28226 S
2 WL 0.0077 PAS
1.525 -0.512 0.396 -1.917 1.371 1.719 1.525 1.917
(+X) 29839 S
0.0096 PAS
3 WL (-X) -0.523 2.392 -1.843 0.68 1.645 2.135 1.843 2.392
45161 S
4 WL 0.0024 PAS
0.611 -0.166 0.165 -0.612 0.547 0.548 0.611 0.612
(+Z) 67742 S
0.0024 PAS
5 WL (-Z) -0.165 0.612 -0.611 0.166 0.547 0.548 0.611 0.612
67742 S

Figure 13. Shown above is the contour stress distribution per target element size of the
built-up shape steel.

Page 63 of 96
Figure 14. Shown above is the 3d-rendered view of the built-up-shaped-baseplate. Lines
resembles the target element size for the Finite Element Analysis (FEA).

Page 64 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) / 2078494 HIT-HY
100 (adhesive)
Effective embedment depth: hef = 6.03 cm
Material: 5.8
Evaluation Service Report: ER-547
Issued I Valid: 12/1/2022 | 5/31/2023
Proof: Design Method LRFD (AC58) Masonry + ACI 318-14
Stand-off installation: eb = 0.00 cm (no stand-off); t = 1.00 cm

Anchor plate :
R lx x ly x t = 30.00 cm x 30.00 cm x 1.00 cm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked Grout-filled CMU, f=1500, f = 10,340.00 kN/m , L x W x H: 40.64 cm x 20.32 cm x 20.32 cm;
Solid Head Joint: yes; open ended unit: no
Temp. short/long: 0 °C / 0 °C
Joints: vertical: 0.95 cm; horizontal: 0.95 cm
Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [cm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Page 65 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Geometry [cm] & Loading [kN, kNm]

1.1 Load combination and design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 DL N = 0.000; Vx = 0.000; Vy = -0.543; no 5
Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 WL(+Z) N = 0.091; Vx = 0.000; Vy = 0.000; no 3


Mx = 0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

3 WL(-Z) N = -0.091; Vx = 0.000; Vy = 0.000; no 1


Mx = -0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

4 WL(+X) N = 0.000; Vx = 0.091; Vy = 0.003; no 2


Mx = 0.000; My = 0.000; Mz = -0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

5 WL(-X) N = 0.000; Vx = -0.091; Vy = 0.003; no 2


Mx = 0.000; My = 0.000; Mz = 0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

6 1.4DL N = 0.000; Vx = 0.000; Vy = -0.760; no 7


Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Page 66 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
7 1.2DL+1.0WL(+X) N = 0.000; Vx = 0.091; Vy = -0.649; no 9
Mx = 0.000; My = 0.000; Mz = -0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

8 1.2DL+1.0WL(-X) N = 0.000; Vx = -0.091; Vy = -0.649; no 9


Mx = 0.000; My = 0.000; Mz = 0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

9 1.2DL+1.0WL(+Z) N = 0.091; Vx = 0.000; Vy = -0.651; no 6


Mx = 0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

10 1.2DL+1.0WL(-Z) N = -0.091; Vx = 0.000; Vy = -0.651; no 6


Mx = -0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

Controlling load case: 8 1.2DL+1.0WL(-X)


3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
x
1 0.000 0.183 -0.002 -0.183
2 0.000 0.141 -0.002 -0.141
3 0.000 0.189 -0.044 -0.183
4 0.000 0.148 -0.044 -0.141
1 2
max. concrete compressive strain: 0.00 [‰]
max. concrete compressive stress: 0.00 [kN/m ]
2

resulting tension force in (x/y)=(0.00/0.00): 0.000 [kN]


resulting compression force in (x/y)=(0.00/0.00): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Page 67 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3 Shear load
Load [kN] Capacity [kN] Utilization bV [%] Status
Steel 0.189 8.994 3 OK
Pryout bond 0.655 7.412 9 OK
Masonry crushing strength 0.189 11.248 2 OK
Masonry breakout in direction y- 0.655 34.744 2 OK

3.1 Steel strength

Vsa = ESR value refer to ICC-ES ER-547


f Vsa ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1

Vsa [kN] f f Vsa [kN] Vua [kN]


14.990 0.600 8.994 0.189

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Page 68 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3.2 Pryout strength (Bond strength controls)

Vmpg =min(kcp · Nmag, kcp · Nmbg)


f Vmpg ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
2
ANa0 = (2 cNa) ACI 318-14 Eq. (17.4.5.1c)
t uncr,m
cNa = 10 da √ 1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0


a,min

ac
ACI 318-14 Eq. (17.4.5.4b)
Nba,m = l a · t cr,m · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
2
kcp da [cm] hef [cm] ca,min [cm] t cr,m [kN/m ]
1 0.95 6.03 31.27 2,241.53

asat atop ec1,N [cm] ec2,N [cm] la


1.000 1.000 2.27 0.32 1.000

Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na y ec1,Na y ec2,Na
0.00 42,516 10,629 1.000 0.695 0.942

y cp,Na Nba,m [kN]


1.000 4.046

Results
Vmpg [kN] f f Vmpg [kN] Vua [kN]
10.589 0.700 7.412 0.655

3.3 Masonry crushing strength

f Vmc ³ Vua AC58 Table 3.2


1
4
Vmc = 1750 · (f'm · Ase,V) AC58 Eq. 3-1

Variables
' 2 2
fm [kN/m ] Ase,v [mm ]
10,340.00 30

Results
Vmc [kN] f f Vmc [kN] Vua [kN]
22.495 0.500 11.248 0.189

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Page 69 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3.4 Masonry breakout strength y-

Vmbg = (AA ) y
Vm

Vm0
ec,V,m y ed,V,m y c,V,m y h,V,m y parallel,V Vb,m ACI 318-14 Eq. (17.5.2.1b)
f Vmbg ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
AVm see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
2
AVm0 = 4.5 ca1 ACI 318-14 Eq. (17.5.2.1c)

( )
1
'
y ec,V,m = 2ev £ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1

y ed,V,m = 0.7 + 0.3 (1.5c


c
) £ 1.0
a2

a1
ACI 318-14 Eq. (17.5.2.6b)

y h,V,m = √1.5ch ³ 1.0a


a1
ACI 318-14 Eq. (17.5.2.8)

= (7 ( ) √ d ) l
0.2
l
Vb,m e
a a √f'm c1.5
a1 ACI 318-14 Eq. (17.5.2.2a)
d a

Variables
2 2 ' 2
le [cm] da [cm] ca1 [cm] ca2 [cm] AVm [mm ] AVm0 [mm ] fm [kN/m ]
6.03 0.95 82.55 31.27 1,000,552 3,066,526 10,340.00

Calculations
y ed,V,m y parallel,V ec,V [cm] y ec,V,m y m,V y h,V,m
0.776 1.000 1.14 0.991 1.000 1.000

Results
Vb,m [kN] f f Vmbg [kN] Vua [kN]
197.903 0.700 34.744 0.655

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Page 70 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

4 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• /

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Page 71 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

5 Installation data
2
Anchor plate, steel: ASTM A36; E = 199,947,970.00 kN/m ; fyk = 248,211.00 Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
2
kN/m
Profile: no profile Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) /
2078494 HIT-HY 100 (adhesive)
Hole diameter in the fixture: df = 1.11 cm Maximum installation torque: 0.020 kNm
Plate thickness (input): 1.00 cm Hole diameter in the base material: 1.11 cm
Recommended plate thickness: not calculated Hole depth in the base material: 6.03 cm
Drilling method: Drilled in hammer mode Minimum thickness of the base material: 19.37 cm
Cleaning: No cleaning of the drilled hole is required

Hilti HIT-V threaded rod with HIT-HY 100 injection mortar with 6.0325 cm embedment h_ef, 3/8, Steel galvanized, Hammer drilled installation per
ER-547

y
15.00 15.00

6.11

3 4
15.00
17.78

x
15.00

1 2
6.11

6.11 17.78 6.11

Coordinates Anchor [cm]


Anchor x y c-x c+x c-y c+y
1 -8.89 -8.89 41.91 49.53 82.55 100.33
2 8.89 -8.89 59.69 31.75 82.55 100.33
3 -8.89 8.89 41.91 49.53 100.33 82.55
4 8.89 8.89 59.69 31.75 100.33 82.55

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Page 72 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

6 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Page 73 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) / 2078494 HIT-HY
100 (adhesive)
Effective embedment depth: hef = 6.03 cm
Material: 5.8
Evaluation Service Report: ER-547
Issued I Valid: 12/1/2022 | 5/31/2023
Proof: Design Method LRFD (AC58) Masonry + ACI 318-14
Stand-off installation: eb = 0.00 cm (no stand-off); t = 1.00 cm

Anchor plate :
R lx x ly x t = 30.00 cm x 30.00 cm x 1.00 cm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked Grout-filled CMU, f=1500, f = 10,340.00 kN/m , L x W x H: 40.64 cm x 20.32 cm x 20.32 cm;
Solid Head Joint: yes; open ended unit: no
Temp. short/long: 0 °C / 0 °C
Joints: vertical: 0.95 cm; horizontal: 0.95 cm
Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [cm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Page 74 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Geometry [cm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Page 75 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

1.1 Load combination and design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 WL(-Z) N = -0.091; Vx = 0.000; Vy = 0.000; no 1
Mx = -0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 WL(+X) N = 0.000; Vx = 0.091; Vy = 0.003; no 2


Mx = 0.000; My = 0.000; Mz = -0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

3 WL(-X) N = 0.000; Vx = -0.091; Vy = 0.003; no 2


Mx = 0.000; My = 0.000; Mz = 0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

4 1.4DL N = 0.000; Vx = 0.000; Vy = -0.760; no 7


Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

5 1.2DL+1.0WL(+X) N = 0.000; Vx = 0.091; Vy = -0.649; no 9


Mx = 0.000; My = 0.000; Mz = -0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

6 1.2DL+1.0WL(-X) N = 0.000; Vx = -0.091; Vy = -0.649; no 9


Mx = 0.000; My = 0.000; Mz = 0.015;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

7 1.2DL+1.0WL(+Z) N = 0.091; Vx = 0.000; Vy = -0.651; no 6


Mx = 0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

8 1.2DL+1.0WL(-Z) N = -0.091; Vx = 0.000; Vy = -0.651; no 6


Mx = -0.015; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

9 WL(+Z) N = 0.625; Vx = 0.000; Vy = 0.000; no 42


Mx = 0.342; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

10 WL(-Z) N = -0.625; Vx = 0.000; Vy = 0.000; no 24


Mx = -0.342; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

11 WL(+X) N = 0.000; Vx = -0.333; Vy = 0.000; no 7


Mx = 0.000; My = 0.000; Mz = 0.061;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

12 WL(-X) N = 0.000; Vx = 0.333; Vy = 0.000; no 7


Mx = 0.000; My = 0.000; Mz = -0.061;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

13 1.2DL+1.0WL(+X) N = 0.000; Vx = -0.333; Vy = 0.000; no 7


Mx = 0.000; My = 0.000; Mz = 0.061;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Page 76 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
14 1.2DL+1.0WL(-X) N = 0.000; Vx = 0.333; Vy = 0.000; no 7
Mx = 0.000; My = 0.000; Mz = -0.061;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

15 1.2DL+1.0WL(+Z) N = 0.625; Vx = 0.000; Vy = 0.000; no 42


Mx = 0.342; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

16 1.2DL+1.0WL(-Z) N = -0.625; Vx = 0.000; Vy = 0.000; no 24


Mx = -0.342; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

Controlling load case: 15 1.2DL+1.0WL(+Z)


3 4

Tension
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
x
1 0.045 0.000 0.000 0.000
2 0.045 0.000 0.000 0.000
3 0.950 0.000 0.000 0.000
4 0.950 0.000 0.000 0.000
1 2
max. concrete compressive strain: 0.02 [‰]
max. concrete compressive stress: 174.01 [kN/m ]
2

resulting tension force in (x/y)=(0.00/8.09): 1.990 [kN] Compression


resulting compression force in (x/y)=(0.00/-13.26): 1.365 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load [kN] Capacity [kN] Utilization bN [%] Status
Steel 0.950 16.249 6 OK
Bond 1.990 4.826 42 OK
Masonry breakout 1.990 10.205 20 OK

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Page 77 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3.1 Steel strength

Nsa = ESR value refer to ICC-ES ER-547


f Nsa ³ Nua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1

Nsa [kN] f f Nsa [kN] Nua [kN]


24.998 0.650 16.249 0.950

3.2 Bond strength

Nmag = (AA ) · y
Na0
Na
ec1,Na · y ec2,Na · y ed,Na · Nba,m ACI 318-14 Eq. (17.4.5.1b)
f Nmag ³ Nua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
2
ANa0 = (2 cNa) ACI 318-14 Eq. (17.4.5.1c)
t uncr,m
cNa = 10 da √ 1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
'
y ec,Na = eN £ 1.00 ACI 318-14 Eq. (17.4.5.3)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.00


a,min

Na
ACI 318-14 Eq. (17.4.5.4b)
Nba,m = l a · t cr,m · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
da [cm] hef [cm] ca,min [cm] t cr,m [kN/m ]
2
asat atop
0.95 6.03 31.27 2,241.53 1.000 1.000

ec1,N [cm] ec2,N [cm] la


0.00 8.09 1.000

Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
6.86 75,221 18,805 1.000

y ec1,Na y ec2,Na Nba,m [kN]


1.000 0.459 4.046

Results
Nmag [kN] f f Nmag [kN] f Nua [kN]
7.425 0.650 4.826 1.990

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Page 78 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3.3 Masonry breakout strength

ANm
Nmbg = · y ec,N,m y ed,N,m · y c,N,m · Nb,m ACI 318-14 Eq. (17.4.2.1b)
ANm0
f Nmbg ³ Nua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANm see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
2
ANm0 = 9 · hef ACI 318-14 Eq. (17.4.2.1c)

( )
1
'
y ec,N,m = 2 eN £ 1.00 ACI 318-14 Eq. (17.4.2.4)
1+
3 · hef
c
y ed,N = 0.7 + 0.3 a,min £ 1.0 ACI 318-14 Eq. (17.4.2.5b)
1.5 · hef
1.5
Nb,m = km · l a · √ '
fm · hef ACI 318-14 Eq. (17.4.2.2a)

Variables
hef [cm] ec1,N,m [cm] ec2,N,m [cm] ca,min [cm] y c,N,m kc
6.03 0.00 8.09 31.27 1.000 12
' 2
la fm [kN/m ]
1.000 10,340.00

Calculations
ANm [mm ]
2
ANm0 [mm ]
2
y ec1,N,m y ec2,N,m y ed,N,m Nb,m [kN]
128,720 32,752 1.000 0.528 1.000 7.566

Results
Nmbg [kN] f f Nmbg [kN] Nua [kN]
15.699 0.650 10.205 1.990

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Page 79 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

4 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• /

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Page 80 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

5 Installation data
2
Anchor plate, steel: ASTM A36; E = 199,947,970.00 kN/m ; fyk = 248,211.00 Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
2
kN/m
Profile: no profile Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) /
2078494 HIT-HY 100 (adhesive)
Hole diameter in the fixture: df = 1.11 cm Maximum installation torque: 0.020 kNm
Plate thickness (input): 1.00 cm Hole diameter in the base material: 1.11 cm
Recommended plate thickness: not calculated Hole depth in the base material: 6.03 cm
Drilling method: Drilled in hammer mode Minimum thickness of the base material: 19.37 cm
Cleaning: No cleaning of the drilled hole is required

Hilti HIT-V threaded rod with HIT-HY 100 injection mortar with 6.0325 cm embedment h_ef, 3/8, Steel galvanized, Hammer drilled installation per
ER-547

y
15.00 15.00

6.11

3 4
15.00
17.78

x
15.00

1 2
6.11

6.11 17.78 6.11

Coordinates Anchor [cm]


Anchor x y c-x c+x c-y c+y
1 -8.89 -8.89 41.91 49.53 82.55 100.33
2 8.89 -8.89 59.69 31.75 82.55 100.33
3 -8.89 8.89 41.91 49.53 100.33 82.55
4 8.89 8.89 59.69 31.75 100.33 82.55

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Page 81 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

6 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Page 82 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) / 2078494 HIT-HY
100 (adhesive)
Effective embedment depth: hef = 6.03 cm
Material: 5.8
Evaluation Service Report: ER-547
Issued I Valid: 12/1/2022 | 5/31/2023
Proof: Design Method LRFD (AC58) Masonry + ACI 318-14
Stand-off installation: eb = 0.00 cm (no stand-off); t = 1.00 cm

Anchor plate :
R lx x ly x t = 15.00 cm x 25.00 cm x 1.00 cm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked Grout-filled CMU, f=1500, f = 10,340.00 kN/m , L x W x H: 40.64 cm x 20.32 cm x 20.32 cm;
Solid Head Joint: yes; open ended unit: no
Temp. short/long: 0 °C / 0 °C
Joints: vertical: 0.95 cm; horizontal: 0.95 cm
Installation: Face installation, Drill hole: Hammer drilled, Installation condition: Dry

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [cm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Page 83 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Geometry [cm] & Loading [kN, kNm]

1.1 Load combination and design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 DL N = 0.000; Vx = 0.127; Vy = -0.241; no 4
Mx = 0.000; My = 0.000; Mz = 0.005;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 WL(+Z) N = 0.003; Vx = 0.000; Vy = 0.000; no 2


Mx = 0.006; My = -0.007; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

3 WL(-Z) N = -0.003; Vx = 0.000; Vy = 0.000; no 2


Mx = -0.006; My = 0.007; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

4 WL(+X) N = 0.000; Vx = 0.411; Vy = -0.659; no 8


Mx = 0.000; My = 0.000; Mz = -0.001;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

5 WL(-X) N = 0.000; Vx = -0.464; Vy = 0.657; no 11


Mx = 0.000; My = 0.000; Mz = 0.012;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

6 1.4DL N = 0.000; Vx = 0.177; Vy = -0.338; no 6


Mx = 0.000; My = 0.000; Mz = 0.007;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Page 84 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
7 1.2DL+1.0WL(+X) N = 0.000; Vx = 0.563; Vy = -0.949; no 11
Mx = 0.000; My = 0.000; Mz = 0.005;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

8 1.2DL+1.0WL(-X) N = 0.000; Vx = -0.312; Vy = 0.367; no 10


Mx = 0.000; My = 0.000; Mz = 0.018;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

9 1.2DL+1.0WL(+Z) N = 0.003; Vx = 0.152; Vy = -0.290; no 5


Mx = 0.006; My = -0.007; Mz = 0.006;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

10 1.2DL+1.0WL(-Z) N = -0.003; Vx = 0.152; Vy = -0.290; no 5


Mx = -0.006; My = 0.007; Mz = 0.006;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

Controlling load case: 7 1.2DL+1.0WL(+X)

3 4
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
x
1 0.000 0.291 0.152 -0.248
2 0.000 0.272 0.152 -0.226
3 0.000 0.280 0.130 -0.248
1 2
4 0.000 0.261 0.130 -0.226

max. concrete compressive strain: 0.00 [‰]


max. concrete compressive stress: 0.00 [kN/m ]
2

resulting tension force in (x/y)=(0.00/0.00): 0.000 [kN]


resulting compression force in (x/y)=(0.00/0.00): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Page 85 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3 Shear load
Load [kN] Capacity [kN] Utilization bV [%] Status
Steel 0.291 8.994 4 OK
Pryout bond 1.103 10.081 11 OK
Masonry crushing strength 0.291 11.248 3 OK
Masonry breakout in direction y- 1.103 35.895 4 OK

3.1 Steel strength

Vsa = ESR value refer to ICC-ES ER-547


f Vsa ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1

Vsa [kN] f f Vsa [kN] Vua [kN]


14.990 0.600 8.994 0.291

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Page 86 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3.2 Pryout strength (Bond strength controls)

Vmpg =min(kcp · Nmag, kcp · Nmbg)


f Vmpg ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
2
ANa0 = (2 cNa) ACI 318-14 Eq. (17.4.5.1c)
t uncr,m
cNa = 10 da √ 1100
ACI 318-14 Eq. (17.4.5.1d)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0


a,min

ac
ACI 318-14 Eq. (17.4.5.4b)
Nba,m = l a · t cr,m · p · da · hef ACI 318-14 Eq. (17.4.5.2)

Variables
2
kcp da [cm] hef [cm] ca,min [cm] t cr,m [kN/m ]
1 0.95 6.03 34.50 2,241.53

asat atop ec1,N [cm] ec2,N [cm] la


1.000 1.000 0.39 0.23 1.000

Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na y ec1,Na y ec2,Na
0.00 42,516 10,629 1.000 0.930 0.957

y cp,Na Nba,m [kN]


1.000 4.046

Results
Vmpg [kN] f f Vmpg [kN] Vua [kN]
14.402 0.700 10.081 1.103

3.3 Masonry crushing strength

f Vmc ³ Vua AC58 Table 3.2


1
4
Vmc = 1750 · (f'm · Ase,V) AC58 Eq. 3-1

Variables
' 2 2
fm [kN/m ] Ase,v [mm ]
10,340.00 30

Results
Vmc [kN] f f Vmc [kN] Vua [kN]
22.495 0.500 11.248 0.291

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Page 87 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

3.4 Masonry breakout strength y-

Vmbg = (AA ) y
Vm

Vm0
ec,V,m y ed,V,m y c,V,m y h,V,m y parallel,V Vb,m ACI 318-14 Eq. (17.5.2.1b)
f Vmbg ³ Vua AC58 Table 3.2 + ACI 318-14 Table 17.3.1.1
AVm see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
2
AVm0 = 4.5 ca1 ACI 318-14 Eq. (17.5.2.1c)

( )
1
'
y ec,V,m = 2ev £ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1

y ed,V,m = 0.7 + 0.3 (1.5c


c
) £ 1.0
a2

a1
ACI 318-14 Eq. (17.5.2.6b)

y h,V,m = √1.5ch ³ 1.0a


a1
ACI 318-14 Eq. (17.5.2.8)

= (7 ( ) √ d ) l
0.2
l
Vb,m e
a a √f'm c1.5
a1 ACI 318-14 Eq. (17.5.2.2a)
d a

Variables
2 2 ' 2
le [cm] da [cm] ca1 [cm] ca2 [cm] AVm [mm ] AVm0 [mm ] fm [kN/m ]
6.03 0.95 85.77 34.50 1,039,629 3,310,731 10,340.00

Calculations
y ed,V,m y parallel,V ec,V [cm] y ec,V,m y m,V y h,V,m
0.780 1.000 0.23 0.998 1.000 1.000

Results
Vb,m [kN] f f Vmbg [kN] Vua [kN]
209.609 0.700 35.895 1.103

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Page 88 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

4 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically – checking required(!): Noncompliance can lead to significantly different distribution of forces
and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)! While
installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the mortar
joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2018, 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state-of the art guidelines!
• /

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Page 89 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

5 Installation data
2
Anchor plate, steel: ASTM A36; E = 199,947,970.00 kN/m ; fyk = 248,211.00 Anchor type and diameter: HY 100 + threaded rod 5.8 3/8
2
kN/m
Profile: no profile Item number: 385418 HAS 5.8 3/8"x4-3/8" (element) /
2078494 HIT-HY 100 (adhesive)
Hole diameter in the fixture: df = 1.11 cm Maximum installation torque: 0.020 kNm
Plate thickness (input): 1.00 cm Hole diameter in the base material: 1.11 cm
Recommended plate thickness: not calculated Hole depth in the base material: 6.03 cm
Drilling method: Drilled in hammer mode Minimum thickness of the base material: 19.37 cm
Cleaning: No cleaning of the drilled hole is required

Hilti HIT-V threaded rod with HIT-HY 100 injection mortar with 6.0325 cm embedment h_ef, 3/8, Steel galvanized, Hammer drilled installation per
ER-547

y
7.50 7.50
6.83

12.50

3 4
11.33

1 2
12.50
6.83

1.83 11.33 1.83

Coordinates Anchor [cm]


Anchor x y c-x c+x c-y c+y
1 -5.67 -5.67 45.13 46.31 85.77 97.11
2 5.67 -5.67 56.47 34.97 85.77 97.11
3 -5.67 5.67 45.13 46.31 97.11 85.77
4 5.67 5.67 56.47 34.97 97.11 85.77

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Page 90 of 96
Hilti PROFIS Engineering 3.0.85

www.hilti.com
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Masonry - Jun 16, 2023 (2) Date: 6/16/2023
Fastening point:

6 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Page 91 of 96
V. DISCUSSION OF THE RESULTS

The used of utilization ratio is to compare the designed capacity of the member in question to the

computed designed load that a particular member experienced. The load that a particular member is

compared to is the one that is governing. The utilization ratio for different modes of failure/s reaches

1.00 signifies that the designed actual computation is already at 100% designed capacity of the material

that was examined. As shown from the given data, the Prefabricated steel members were analyzed to

resist axial failure, torsional failure, and slenderness ratio adequacy throughout carrying different load

cases/load combination inputs. The maximum slenderness ratio for compression members is at 200 and

300 for tension members. Each structural member that was analyzed acts as compression member and

tension member at the different loading cases, thus checking for different maximum slenderness ratio

was performed. The Analysis and adequacy were performed for the Prefabricated steel members, Base

plate with Stiffener plates, Anchor bolts, and concrete pedestal below the base of the Floor mounted pole.

Based on the results, the floor mounted poles are deemed safe and adequate to carry out the loads imposed

on it. Another, based on the Use or Occupancy of the area where the equipment and wall mounted

antennas are located, the weight of the Outdoor cabinets does not exceed the live loadings for a roof deck.

Page 92 of 96
APPENDICES

Here lie the references and pictures that were obtained upon the day of the inspection.

Figure 15. Shown above is the front view of the building where the Globe structures and equipment are located.

Page 93 of 96
Figure 16. 16.
Figure Shown above
Shown is the
above sideside
is the viewview
of the building
of the where
building the the
where Globe
Globe
structures andand
structures equipment are are
equipment located. SeeSee
located. the the
top top
portion of the
portion building
of the building
showing wallwall
showing mounted antennas
mounted andand
antennas other PolePole
other framing setup.
framing setup.

Page 94 of 96
Figure 17. Shown above is the pole framing setup not yet showed from previous pages.