This is to certify the structural stability of the Nine-meter (9-m.) Bi-pod pole tower (**Note:
Measured from the top to bottom of the main pole) carrying equipment and antennas necessary for the
cellular/internet services within the site vicinity. Also, an added concrete base pad that caters the safe bolting
of equipment cabinets that is superimposed through the same level of the bi-pod tower. And, the structural
connection between the Bi-pod pole tower and the building framing itself is ensured throughout this
certification.
Structural appraisal involves site visit and/or visual inspection to ensure that the added structures by
Globe Telecoms Network Inc. have no visual damage that might affect its longevity and its users. Also, the
location of the said additions was identified to measure the “As-built” structural elements as well as the
existing concrete elements of the structure directly affected by the added loadings for structural investigation
purposes.
Estimation or calculation needed to produce this output are all based on the standard and code
mandated by the law and by the profession of Civil Engineering in the Philippines. Here lies the references
used for the analysis extracted from the National Structural code of the Philippines 2015 (NSCP2015,
SEVENTH EDITION, VOLUME I):
Based on the results of the provided structural stability checking, the Bi-pod pole tower setup is adequate
for its intended use. The connection of the said structure to the existing concrete framed building is deemed
safe as it is analyzed within the most conservative approach due to detail/data insufficiency. Moreover, no
load combination that is checked separately/iterated throughout different mode of failure that is represented
by utilization ratio, for anchorage through concrete element exceeded the maximum utilization ratio of 100%.
Thus, different base supports are adequate for its intended use.
Additionally, the weight of the equipment that can be represented by a loading area (in kPA unit) does
not exceed the design live loadings of the floor where it resides. Thus, the location and or critical area affected
by the said inclusion are theoretically safe.
However, additional loadings due to alteration of the structure and improper usage outside the
jurisdiction of the code/s stated above are beyond the scope and responsibility of the undersigned. Moreover,
poor workmanship, modification, and construction are beyond the jurisdiction of the engineer involved with
the assessment of the structural stability of the existing building and outsidethe scope of this report.
Note: This structural investigation report shall not be construed as part of the construction
documents. This is prepared for information purposes only. This report contains the results of
the investigation into the structure.
AVAILABLE DATA
The engineers have gathered available data which will be used for analysis such as
As-built architectural and structural drawings of the building provided by the owner, and
actual conditions based on ocular inspection. The material properties and other design
considerations have been provided by the client and have been used as the basis for the
structural investigation.
LIMITATION OF THIS DOCUMENT
This review presented herein is intended for the project entitled PROJECT
UNIVERSE (PROJECT U.) by Globe Telecoms Network. The existing structure is
located at 2769 F. Buencamino St. Brgy. Poblacion Makati City. owned by Megaland
168, Inc. This document shall be read in conjunction with the following documents:
construction.
constructed Nine-meter (9-m.) Bi-pod pole tower setup (Measured from the base of the
main pole to the upper most pole mounting frame) carrying antennas/equipment necessary
connected to the existing concrete framed building through pedestal, anchor bolts, and base
plates. The main pole is assumed to be fixedly connected; thus, it resists axial forces and
rotation for all possible plains and axes. The strut supports are assumed to be pin connected
as the purpose of this said element is to resist horizontal forces such as earthquakes and
wind loadings.
The structural steel framing setup is measured in actual and was found out that it was
confirming with the standard section properties of ASTM (American Society for Testing
and Materials). The reinforced concrete pedestal is measured in actual as well, though we
cannot determine the structural design of the concrete pedestal, geometrical dimension of
the concrete pedestal was obtained through actual measurements and analyzed
conservatively.
The Bi-pod pole tower is located at an accessible roof deck for a suggested feasible
equipment inclinedly attached, appurtenances, and other attachments that are not part of
the main framing system of the steel structure are extracted from the manufacturer’s
Page 1
For the performance of the analysis, the dimension of the concerned structural members
is measured upon the day of inspection and made sure that there are no early indications of
failure such as hairline cracking for concrete elements, improper weld of two adjoining
AISC360 (LRFD METHOD) was used as method of adequacy checking for the steel
members for failures such as slenderness checking, compression failure, tension failure,
bending, torsional, and combination of each failure. From STAAD pro connect edition
v22 update 6, the said design checking was performed as well as extraction of base support
loadings due to different load combination. This reaction is necessary to provide checking
elements such as concrete breakout, concrete side face breakout, concrete edge breakout;
as well as for the anchor bolts, whether it can carry out tension failure, anchor pull out,
shear failure, and pry-out. Finite element analysis was performed through structural
The aim of the report was to provide adequate justification to ensure that the added
structure is safe for its intended usage, ensuring the safety of its users, and the vicinity
Page 2
Thus, provided analysis vastly considers the estimated reaction due to possible loadings
due to different factors. It may be caused by the earthquake, wind forces, self-weight, or
combination of such said forces. All assumptions and factors used for the computation of
said forces are extracted from the National Structural Code of the Philippines (NSCP
2015, volume 7) and other references that is bounded by the said code. To fulfil the
Page 3
II. INPUTS
On this part of the report, the inputs such as code-based parameters, engineering
judgement or computation, would be discussed and certify with the assurance and justification
that each structural member would or would not meet the desired requirements. Regarding the
structural steel members, Load and Resistance Factor Design (AISC LRFD) was deemed
efficient and up to date as a method of design adequacy checking as it provides more adequacy
checking than Allowable stress design (ASD) based on the design software use for the base
For the computation of dead-load due to self-weight of the attached equipment, extracted
mechanical data from the manufacturer’s manual was used and is converted into desired units
and load of transfer going through the main framing system of the floor mounted setup. For
the wind-load, extracted data are from combinations of National Structural Code of the
Standard for Antenna Supporting Structures and Antennas and Small Wind Turbine
Support Structures). The combination of the stated codes was utilized as our local code only
referenced from the latter stated code. Commentaries and explanations for the procedural
approaches for wind loadings are more specific, descriptive, and updated for the ANSI/TIA-
222-H-2017 than our local code, thus, combination of the two are justified. The said governing
codes and procedural approaches are manually deciphered by the engineer in-charge of this
analysis and was computed through the help of Microsoft office (excel) software. Formulas
used, and criteria for judgement will be discussed further in this report.
Page 4
MATERIAL PROPERTIES (Reinforced Concrete Elements of the
Building)
• Yield strength of Structural steel, Fy = 60 kSI for Diameter 16 mm and larger reinforcing
deformed bars.
• Lower level to level 3, Suspended slabs decking, RC wall, Columns, and Beams,
• Miscellaneous, Equipment pads & Foundations’ Retaining Wall, fc’ = 3000 psi
Yield strength of Reinforcing bars, Fy = 227 Mpa (Grade 33 steel) for Diameters 10 mm and
above (Conservative approach since Globe did not provide any details regarding the added
concrete element)
Compressive strength at 28th day, Fc’ = 2500 psi (17.24 MPa) in 6-in-diameter (150-mm-
diameter) cores at 28 days. (Conservative approach since Globe did not provide any details
Page 5
• Mortar strength, fm ≥ 30 N/mm2 → Grouting for adhesive connection between steel
members and concrete elements. (Conservative approach since Globe did not provide any
members except anchor bolts. (Conservative approach since Globe did not provide any
approach since Globe did not provide any details regarding their added structure)
• Tensile strength of Weld electrode, Fyw = 413 Mpa (E70XX) (Conservative approach
since Globe did not provide any details regarding their added structure)
• Hex head, Fy = 248 Mpa (Grade 36, ASTM F1554 formerly known as ASTM A307 grade
C) (Conservative approach since Globe did not provide any details regarding their added
structure)
• Hex head, Fu = 400 Mpa (Grade 36, ASTM F1554 formerly known as ASTM A307 grade
C) (Conservative approach since Globe did not provide any details regarding their added
structure)
Page 6
II.I. PARAMETER FOR WIND ANALYSIS (FOR MAIN
Page 7
11 Parapet Height ANSI/TIA-222-H Hp 0.4 m
12 Parapet Height + (Xb/5) ANSI/TIA-222-H H1 2.54146 m
13 Width of the windward face of the building ANSI/TIA-222-H Ws 18.409 m
14 Height of the windward of the building ANSI/TIA-222-H Hs 18 m
15 Height above roof ANSI/TIA-222-H Zr 9 m
16 Parapet Height + Lesser of Hs or Ws ANSI/TIA-222-H H2 18.4 m
17 - - Ws/Hs 1 -
18 Rooftop wind speed-up factor from Hs to H1 ANSI/TIA-222-H Ks 1 - Zr < H1
19 Rooftop wind speed-up factor from H1 to H2 ANSI/TIA-222-H Ks 1.3 - H1 < Zr </= H2
20 Rooftop wind speed-up factor for >H2 to Zr ANSI/TIA-222-H Ks 1 - Zr > H2
21 Ground elevation factor NSCP Ke 1 1.0 Shall be permitted for
2015/ANSI/TIA- any ground elevation
222-H
22 Gust effect factor NSCP 2015 Gh 0.95
Page 8
II.II. PARAMETER FOR WIND ANALYSIS (FOR SIMPLE
MOUNTING FRAMES)
Page 9
Horizontal Distance from windward face to
10 ANSI/TIA-222-H Xb 10.7073 m
center of the structure
11 Parapet Height ANSI/TIA-222-H Hp 0.4 m
12 Parapet Height + (Xb/5) ANSI/TIA-222-H H1 2.54146 m
13 Width of the windward face of the building ANSI/TIA-222-H Ws 18.409 m
14 Height of the windward of the building ANSI/TIA-222-H Hs 18 m
15 Height above roof ANSI/TIA-222-H Zr 9 m
16 Parapet Height + Lesser of Hs or Ws ANSI/TIA-222-H H2 18.4 m
17 - - Ws/Hs 1 -
18 Rooftop wind speed-up factor from Hs to H1 ANSI/TIA-222-H Ks 1 - Zr < H1
19 Rooftop wind speed-up factor from H1 to H2 ANSI/TIA-222-H Ks 1.3 - H1 < Zr </= H2
20 Rooftop wind speed-up factor for >H2 to Zr ANSI/TIA-222-H Ks 1 - Zr > H2
NSCP 1.0 Shall be
21 Ground elevation factor 2015/ANSI/TIA- Ke 1 permitted for any
222-H ground elevation
22 Gust effect factor NSCP 2015 Gh 0.85
23 Velocity Pressure ANSI/TIA-222-H qz 15.52566787 N/sq.m.
NSCP
24 Cross section of the Tower 2015/ANSI/TIA- - Triangular -
222-H
Sumation of the Projected Areas of flat
25 ANSI/TIA-222-H ∑Af 0.946404
components of the mounting frame
Summation of the Projected Area of round
26 ANSI/TIA-222-H ∑Ar 0
components of the mounting frame
Gross area of the frame as if it were solid
27 defined by the largest outside dimensions of ANSI/TIA-222-H Ag 3 sq.m. One face only
the elements included in Af and Ar
NSCP
Solidity ratio of mounting frame without (Af+Ar)/Ag of one
28 2015/ANSI/TIA- ε 0.315468 -
antennas and mounting pipes face
222-H
29 Shielding Factor Ka 1 -
Relative angle between azimuth associated
ANSI/TIA-222-H
30 with the normal face of the θ 15 degrees
(Figure 2-6)
appurtenances/framing and the wind direction
ANSI/TIA-222-H
32 Geometric type of mounting frame - Plane Frame -
(Figure 2-7)
For square and
triangular truss
mounting frames
ANSI/TIA-222-H
(refer to Figure 2-7),
31 Force coefficient for a mounting frame (Section Cas 1.689301295 -
Cas shall be equal to
2.6.11.2.2)
Cf in accordance
with 2.6.11.1
(ANSI/TIA-222-H)
33 Geometric type of mounting frame ANSI/TIA-222-H Rrf 0.639808024
Effective projected area of the frame
34 ANSI/TIA-222-H (EPA)MN 1.598761503
(Mounting Frame)
Projected area of flat components supporting
35 the mounting frame without regard to ANSI/TIA-222-H Afs
shielding or overlapping members.
Projected area of round components
36 supporting the mounting frame without ANSI/TIA-222-H Ars
regard to shielding or overlapping members
Effective projected area in a plane parallel to
37 the face of the mounting frame of all ANSI/TIA-222-H (EPA)FN 0.005043401
members supporting mounting frame
It shall be
permissible to use
Effective projected area associated with the
the larger value of
38 windward face normal to the azimuth of the ANSI/TIA-222-H (EPA)N 1.603804905
(EPA)N or (EPA)T
appurtenance
for (EPA)A for all
wind directions
The effective projected area in a plane
transverse to the face of the mounting frame
39 of a frame/truss supporting the mounting ANSI/TIA-222-H (EPA)FT 0.036576
frame (the larger frame/truss when more than
one is present)
The effective projected area in a plane
40 ANSI/TIA-222-H Σ(EPA)Fti 0.036576
tranverse to the face of the mounting frame of
Page 10
any additional frames/trusses supporting the
mounting frame
The effective projected area, in a plane
transverse to the face of the mounting frame,
of all mounting frame members and all other
miscellaneous suppport members (i.e.
41 ANSI/TIA-222-H Σ(EPA)MT 1.2234672
tiebacks) without regard to shielding or
overlapping members determined using a
drag factor 2.0 appied to flat members and a
drag factor of 1.2 applied to round members
Effective projected area associated with the
42 windward side face of the ANSI/TIA-222-H (EPA)T 0.6665976
appurtenance/mounting frame
Effective projected area of the mounting
43 ANSI/TIA-222-H (EPA)A 1.310307691
frames
44 Design wind force ANSI/TIA-222-H FA 17.29189172 N
ANTENNAS/APPURTENANCES)
Page 11
NSCP
3 Exposure Category 2015/ANSI/TIA- - B -
222-H
Nominal height of NSCP
4 atmospheric boundary 2015/ANSI/TIA- Zg 366 m Needs clarification
layer 222-H
3-second gust wind NSCP
5 speed power law 2015/ANSI/TIA- α' 7 -
exponent 222-H
Height above ground NSCP
Needs clarification especially if the
6 level at the base of the 2015/ANSI/TIA- Z 28.5 m
structure is located at the roofdeck
structure 222-H
Minimum value for
7 Velocity Pressure NSCP 2015 Kzmin 0.7 -
Coefficient
Velocity Pressure
8 NSCP 2015 Kz 0.969265713 -
Coefficient
NSCP Method 1. Category 1 **No abrupt
9 Topographic Factor 2015/ANSI/TIA- Kzt 1 changes in general topography, e.g.
222-H flat or rolling terrain
Horizontal Distance
10 from windward face to ANSI/TIA-222-H Xb 0.666666667 m
center of the structure
Parapet Height ANSI/TIA-222-H Hp 0.3 m
Parapet Height +
11 ANSI/TIA-222-H H1 0.433333333 m
(Xb/5)
Width of the windward
12 ANSI/TIA-222-H Ws 8.4 m
face of the building
Height of the windward
13 ANSI/TIA-222-H Hs 24 m
of the building
Measured at the centerline of the
14 Height above roof ANSI/TIA-222-H Zr 4.5 m
Appurtenance
Parapet Height + Lesser
15 ANSI/TIA-222-H H2 8.7 m
of Hs or Ws
16 - - Ws/Hs 0.35 -
Rooftop wind speed-up
17 ANSI/TIA-222-H Ks 1 - Zr < H1
factor from Hs to H1
Rooftop wind speed-up
18 ANSI/TIA-222-H Ks 1.105 - H1 < Zr </= H2
factor from H1 to H2
Rooftop wind speed-up
19 ANSI/TIA-222-H Ks 1 - Zr > H2
factor for >H2 to Zr
NSCP
1.0 Shall be permitted for any
20 Ground elevation factor 2015/ANSI/TIA- Ke 1
ground elevation
222-H
The horizontal dessign wind force
for the strength design of
appurtenances and their connections
to supporting structures shall be
21 Gust effect factor NSCP 2015 Gh 1 determined using a gust factor of 1.0
and a wind direction probability
factor determined from Table 2-2.
No shielding from the structure shall
be considered.
22 Velocity Pressure ANSI/TIA-222-H qz 13.40226194 N/sq.m.
NSCP
Cross section of the
23 2015/ANSI/TIA- - Square -
tower
222-H
Sumation of the
Projected Areas of flat
24 ANSI/TIA-222-H ∑Af 1.8
components of the
mounting frame
Summation of the
Projected Area of round
25 ANSI/TIA-222-H ∑Ar 0
components of the
mounting frame
Gross area of the frame
as if it were solid
26 ANSI/TIA-222-H Ag - sq.m. One face only
defined by the largest
outside dimensions of
Page 12
the elements included
in Af and Ar
Solidity ratio of
NSCP
mounting frame
27 2015/ANSI/TIA- ε - - (Af+Ar)/Ag of one face
without antennas and
222-H
mounting pipes
For antennas and antenna mounting
configurations that do not project
above the top of the structure (when
subcritical force coefficients are
considered only) such as side arms,
T-arms, stand-offs, etc. when 3 or
28 Shielding Factor Ka 0.8 -
more mounts are located at the same
relative elevation. Shielding from
the mounting configuration and
shielding of mounting members
from antennas is excluded except as
provided in 2.6.11.2.1.
Relative angle between
azimuth associated with
ANSI/TIA-222-H
29 the normal face of the θ 0 degrees
(Figure 2-6)
appurtenances/framing
and the wind direction
Equivalent flat plate areas based on
revision C of this standard shall be
multiplied by a force coefficient, Ca,
ANSI/TIA-222-H
30 Force Coefficient Ca - - equal to 2.0 except when the
(Table 2-9)
appurtenance is made up of round
members only, a force coefficient of
1.8 may be applied.
The effective projected area of a
Projected area of a
mounting pipe above and below the
component of the
shielded portion of the mounting
appurtenance. The
pipe in accordance with 2.6.11.4
additional projected
shall be inclued in the term
31 area of ice shall be Aa -
Σ(CaAa)N with Ca equal to 1.0. The
considered as a round
effective projected area of the entire
component for loading
mounting pipe shall be included in
combinations that
the term Σ(CaAa)T with Ca
include ice.
determined from Table 2-9.
For square and triangular truss
mounting frames (refer to Figure 2-
32 Cas - - 7), Cas shall be equal to Cf in
accordance with 2.6.11.1
(ANSI/TIA-222-H)
33 Rrf - -
Effective projeted area
34 of the frame (Mounting (EPA)MN - sq.m.
Frame)
Projected area of flat
components supporting
the mounting frame
35 Afs - sq.m.
without regard to
shielding or
overlapping members.
Projected area of round
components supporting
the mounting frame
36 Ars - sq.m.
without regard to
shielding or
overlapping members
Effective projected area
in a plane parallel to the
face of the mounting
37 (EPA)FN - sq.m.
frame of all members
supporting mounting
frame
Effective projected area It shall be permissible to use the
38 associated with the (EPA)N - sq.m. larger value of (EPA)N or (EPA)T
windward face normal for (EPA)A for all wind directions
Page 13
to the azimuth of the
appurtenance
Effective projected area
associated with the It shall be permissible to use the
windward side face of larger value of (EPA)N or (EPA)T
39 (EPA)T - sq.m.
the for (EPA)A for all wind directions
appurtenance/mounting (For appurtenances)
frame
Effective projected area
of the appurtenance
40 including ice for (EPA)A - sq.m.
loading combinations
that include ice
41 Design wind force ANSI/TIA-222-H Fst - N
Figure 4. Shown below is the Basic wind speed of the area for occupancy category type IV.
Common Data
ASCE – 7 – 2016
Building Classification Category : Category IV
Basic Wind Speed : 250 kPh
Exposure Category : Exposure B
Structure Type : Building Structures
Height above sea level : 4-m.
Building Height : 13.875 m (Note : Measured from the Road finish to the roofdeck finish floor
line)
Page 14
Building Length along the direction of the wind (L) : 17.3 m. (Note : L and B can be interchanged
for computation of windward,leeward, and sidewall computation for all sides of the building)
Building Length along the direction of the wind (B): 12.130 (Note: L and B can be interchanged for
computation of windward,leeward, and sidewall computation for all sides of the building)
Figure 5. Shown above is the distance between the site and the nearest active fault line.
SEISMIC PARAMETERS
Description Values Unit Remarks
Zone 4 -
Occupancy Category IV -
Zone Factor, Z 0.4 -
Importance Factor, I 1 -
Known nearest active fault
West Valley Fault Line -
line
Distance away from the fault
4.1 km
line
Maximum moment This magnitude is not from Tebbo fault. However, this comes from the most
7.2
magnitude, M destructive earthquake written in the history of the vicinity.
Seismic Source Type A
Near-Source Factor, Na 1.29 Manual extraction through linear interpolation
Near-Source Factor, Nv 1.72 Manual extraction through linear interpolation
Reinforce concrete moment-
Type of frame
resisting Frames
Ct value 0.0731
Height of the Building Above
17.35
ground , hn
Structure Period, T (Method
0.621429672
A)
Page 15
Basic Seismic-Force Ordinary reinforced concrete
Resisting System moment frames
Seismic Modification Factor,
3.5
R
Soil Profile Type 3
Page 16
II.VI. LOAD COMPUTATION
Figure 6. Actual picture of the Bi-pod pole tower located at the roof deck of the residential building
(Dated: MM/DD/YR 04/28/2023)
Density of steel = 7850 kg/m3 → The software used has its own way to compute the
weight of the structure by simply clicking self-weight on the design analysis. However,
this is the density of steel used multiplied to the volume of the structural elements used.
DEAD LOAD
Pole
MAIN Pole Wei Un Rem Staad Un Rem Length of the Pin d1 d2
Description length
POLE No. ght its arks inputs its arks Connection (m) (m) (m)
(m)
TOP 32.1 0.31529 0.13
kG kN 1 0
CONNECTION 4 34 65
N/A
BOTTOM 29.0 0.28488 0.13
kG kN 1 0
CONNECTION 4 24 65
TOWE ASI4517R3v06 52.8 kG 1.273
P1
R CLAMP
0 kG
(ASI4517R3v06)
N/A
DOWNTILT N/A
3.1 kG
(ASI4517R3v06)
Wirings 5.28 kG
Page 17
0.32471
CONNECTION 33.1 kG kN N/A 0.8 0
1
RRU 5502 25 kG MID
CLAMP 3.1 kG N/A
N/A
WIRINGS 5 kG
0.26585
CONNECTION 27.1 kG kN N/A 0.2 0
1
RRU 5508 20 kG MID
CLAMP 3.1 kG N/A
N/A
WIRINGS 4 kG
TOP 21.5 0.21140
kG kN 1 0.6 0
CONNECTION 5 55
N/A
BOTTOM 18.4 0.18099 0.80
kG kN 1 0
CONNECTION 5 45 5
P2 AAU5639W (3700
27 kG 0.795
MHZ)
CLAMP 3.6 kG N/A
DOWNTILT 3.1 kG N/A
Wirings 2.7 kG
TOP 21.5 0.21140
kG kN 1 0.6 0
CONNECTION 5 55
N/A
BOTTOM 18.4 0.18099 0.80
kG kN 1 0
CONNECTION 5 45 5
AAU5639W (3700
27 kG 0.795
MHZ)
CLAMP 3.6 kG N/A
P3 DOWNTILT 3.1 kG N/A
Wirings 2.7 kG
0.26585
CONNECTION 27.1 kG kN N/A 0.8 0
1
RRU 3276 20 kG MID
CLAMP 3.1 kG N/A
N/A
WIRINGS 4 kG
TOP 32.1 0.31529 0.13
kG kN 1 0
CONNECTION 4 34 65
N/A
BOTTOM 29.0 0.28488 0.13
kG kN 1 0
CONNECTION 4 24 65
ASI4517R3v06 52.8 kG 1.273
P4
CLAMP
0 kG
(ASI4517R3v06)
N/A
DOWNTILT N/A
3.1 kG
(ASI4517R3v06)
Wirings 5.28 kG
0.26585
CONNECTION 27.1 kG kN N/A 0.8 0
1
RRU 3276 20 kG MID
CLAMP 3.1 kG N/A
N/A
WIRINGS 4 kG
P5
0.26585
CONNECTION 27.1 kG kN N/A 0.2 0
1
RRU 5508 20 kG MID
CLAMP 3.1 kG N/A
N/A
WIRINGS 4 kG
TOP 0.18050 0.14
18.4 kG kN 1 0
CONNECTION 4 3
N/A
BOTTOM 0.16186 0.14
16.5 kG kN 1 0
CONNECTION 5 3
AMB4520R0 30 kG 1.286
P6
CLAMP
0 kG
(AMB4520R0)
N/A
Downtilting kit N/A
1.9 kG
(ASMDT0C01)
Wirings 3 kG
Page 18
TOP 21.5 0.21140
kG kN 1 0.3 0
CONNECTION 5 55
N/A
BOTTOM 18.4 0.18099 0.50
kG kN 1 0
CONNECTION 5 45 5
P7 AAU5639W (3700
27 kG 0.795
MHZ)
CLAMP 3.6 kG N/A
DOWNTILT 3.1 kG N/A
Wirings 2.7 kG
0.32471
CONNECTION 33.1 kG kN 1 N/A
1
P8 RRU 5502 25 kG MID
CLAMP 3.1 kG N/A
N/A
WIRINGS 5 kG
TOP 0.18050 0.14
18.4 kG kN 1 0
CONNECTION 4 3
N/A
BOTTOM 0.16186 0.14
16.5 kG kN 1 0
CONNECTION 5 3
AMB4520R0 30 kG 1.286
P9
CLAMP
0 kG
(AMB4520R0)
N/A
Downtilting kit N/A
1.9 kG
(ASMDT0C01)
Wirings 3 kG
WALL DATA
CHB DESCRIPTION VALUES UNITS
COMMERCIAL SIZE 6" INCHES
WALL HEIGHT 0.4 METERS
WALL LENGTH 1 METERS
MORTAR TYPE N -
PLASTERING BOTH SIDES -
OUTPUT DATA
WALL THICKNESS 0.1778 METERS
WIDTH,W 0.1524 METERS
HEIGHT, H 3 METERS
LENGTH, L 0.4 METERS
HOLE, a 0.073025 METERS
HOLE, b 0.0635 METERS
GROUTED MORTAR (IN ROWS) 3 LAYERS
GROUTED MORTAR (IN COLUMNS) 4 LAYERS
NUMBER OF CHB REQUIRED 5 PIECES
WEIGHT OF PLASTERING 0.48 KPA
WEIGHT PER CHB 18 KG
WEIGHT PER METER LENGTH (CHB) 0.8829 Kn/M
WEIGHT PER METER LENGTH (MORTAR-FILLER) 0.400492449 Kn/M
WEIGHT PER METER LENGTH (MORTAR GROUTGROUT) 1.26139354 Kn/M
WEIGHT PER METER LENGTH (WALL) 2.736785989 Kn/M
• SLAB = 2.45 kPa (This is based on the commonly used theoretical loading for a reinforced concrete element
Page 19
II.VI.II. LIVE LOAD
Live Load = 1.9 Kpa (Since no provided architectural plans, all floor levels are based
on the purpose of the whole building or occupancy.)
Page 20
II.VI.IV. Wind Load (Member distributed load-SIMPLE
MOUNTING FRAME)
Page 21
II.VI.V. Wind Load (Member distributed load-
APPURTENANCES)
Page 22
II.VI.VI. LOAD COMBINATIONS
FOR TOWER
1. 1.4DL
2. 1.2DL + 1.0 WL (+X)
3. 1.2DL + 1.0 WL (-X)
4. 1.2DL + 1.0 WL (+Z)
5. 1.2DL + 1.0 WL (-X)
FOR BUILDING
1. 1.4DL
2. 1.2DL + F1LL
3. 1.2DL + 0.5WL (+X)
4. 1.2DL + 0.5WL (-X)
5. 1.2DL + 0.5WL (+Z)
6. 1.2DL + 0.5WL (-Z)
7. 1.2DL + 1.0WL (+X) +f1LL
8. 1.2DL + 1.0WL (-X) + f1LL
9. 1.2DL + 1.0WL (+Z) + f1LL
10. 1.2DL + 1.0WL (-Z) + f1LL
11. 1.2DL + 1.0 EQ (+X) + f1LL
12. 1.2DL + 1.0 EQ (-X) + f1LL
13. 1.2DL + 1.0 EQ (+Z) + f1LL
14. 1.2DL + 1.0 EQ (-Z) + f1LL
Where:
DL = Dead Loads
WL = Wind Loads
EQ = Earthquake Loads
f1 = 1.0 for floods in places of public assembly, for live loads in excess of 4.8
kPa, and for garage live loads, or 0.5 for other live loads.
Page 23
III. OUTPUTS
In this part of the analysis report, values obtained from running the analysis from
Staad Pro connect edition 6 V22, would be provided and indication whether each
concerned structural steel framing element would be adequate for its intended purpose.
Loads combination, consideration for base support, resisting factor such as releases for
end supports of each steel element, would also be shown for the reader to check the
correctness of the analysis. Aside from providing adequacy checks, Staad Pro connect
edition 6 V22 provided the base reaction of the concerned Bi-pod pole tower setup and
is imported to another structural software for design checking of the base support
element such as base plate, anchor bolts, base plate, stiffener plate, and other adequacy
checking for concrete previously mention (HILTI PROFIS ENGINEER). The
purpose of the multiplier is to transpose the sign convention to change the direction of
the loading reaction.
STAAD
POLE CONNECT NO LOAD Fx Fy Fz Mx My Mz
NUMBER ION DE COMBINATION (kN) (kN) (kN) (kNm) (kNm) (kNm)
DL 0.01 -1.973 1.524 0 0 0
WL (+X) 0.059 0.006 -0.04 0 0 0
WL (-X) -0.035 -0.005 0.05 0 0 0
WL (+Z) -0.051 -0.985 0.589 0 0 0
PINNED WL (-Z) 0.029 1.513 -0.895 0 0 0
3
SUPPORT 1 1.4DL 0.014 -2.763 2.133 0 0 0
1.2DL+1.0WL(+X) 0.071 -2.362 1.788 0 0 0
1.2DL+1.0WL(-X) -0.023 -2.373 1.879 0 0 0
1.2DL+1.0WL(+Z) -0.039 -3.353 2.417 0 0 0
1.2DL+1.0WL(-Z) 0.041 -0.855 0.933 0 0 0
DL 1.526 -1.978 0.01 0 0 0
TOWER
WL (+X) 0.732 -1.239 -0.053 0 0 0
WL (-X) -0.821 1.384 0.031 0 0 0
WL (+Z) -0.03 0.005 0.058 0 0 0
PINNED WL (-Z) 0.056 -0.005 -0.034 0 0 0
23
SUPPORT 2 1.4DL 2.136 -2.769 0.014 0 0 0
1.2DL+1.0WL(+X) 2.563 -3.613 -0.041 0 0 0
1.2DL+1.0WL(-X) 1.01 -0.99 0.043 0 0 0
1.2DL+1.0WL(+Z) 1.801 -2.369 0.07 0 0 0
1.2DL+1.0WL(-Z) 1.887 -2.379 -0.022 0 0 0
FIXED DL -1.536 -16.046 -1.534 -0.271 0 0.271
1
SUPPORT WL (+X) -0.104 1.233 0.093 0.017 0.048 0.028
Page 24
WL (-X) 0.122 -1.379 -0.081 -0.015 0 -0.033
WL (+Z) 0.081 0.98 -0.06 -0.018 -0.016 -0.015
WL (-Z) -0.085 -1.508 0.143 0.038 -0.032 0.015
1.4DL -2.15 -22.464 -2.147 -0.379 0 0.38
1.2DL+1.0WL(+X) -1.947 -18.022 -1.747 -0.308 0.048 0.354
1.2DL+1.0WL(-X) -1.721 -20.634 -1.921 -0.34 0 0.292
1.2DL+1.0WL(+Z) -1.762 -18.275 -1.901 -0.343 -0.016 0.311
1.2DL+1.0WL(-Z) -1.929 -20.763 -1.697 -0.287 -0.032 0.341
HILTI
LOAD CASE Vx (kN) Vy (kN) N (kN) Mx (kNm) My (kNm) Mz (kNm)
EQ (+X) -0.189 -1.54 -8.525 2.167 -0.215 0.406
EQ (-X) 0.189 1.54 8.525 -2.167 0.215 -0.406
EQ (+Z) -1.509 -0.159 8.525 0.181 -2.133 -0.043
EQ (-Z) 1.509 0.159 -8.525 -0.181 2.133 0.043
DL -0.205 0.084 -4.315 -0.086 -0.253 0.005
WL (+X) -0.156 -1.046 -7.47 1.509 -0.177 0.328
WL (-X) 0.154 1.094 7.379 -1.562 0.175 -0.327
WL (+Z) -1.064 -0.132 7.392 0.15 -1.53 -0.026
WL (-Z) 1.022 0.131 -7.47 -0.15 1.483 0.027
1 1.2DL+1.0EQ(+X) -0.435 -1.439 -13.703 2.064 -0.518 0.413
1.2DL+1.0EQ(-X) -0.056 1.64 3.347 -2.27 -0.088 -0.4
1.2DL+1.0EQ(+Z) -1.309 -0.031 2.214 0.048 -1.833 -0.02
1.2DL+1.0EQ(-Z) 1.264 0.259 -13.703 -0.284 1.83 0.05
1.4DL -0.286 0.117 -6.041 -0.12 -0.354 0.008
1.2DL+1.0WL(+X) -0.401 -0.946 -12.648 1.407 -0.48 0.335
1.2DL+1.0WL(-X) -0.091 1.194 2.202 -1.664 -0.128 -0.321
1.2DL+1.0WL(+Z) -1.309 -0.031 2.214 0.048 -1.833 -0.02
1.2DL+1.0WL(-Z) 0.776 0.232 -12.648 -0.253 1.179 0.033
EQ (+X) 4.913 0.167 8.611 0 0 0
EQ (-X) -4.913 -0.167 -8.611 0 0 0
EQ (+Z) 0.019 -0.17 0.072 0 0 0
EQ (-Z) -0.019 0.17 -0.072 0 0 0
DL -0.102 -0.02 -0.269 0 0 0
WL (+X) 4.4 0.137 7.541 0 0 0
WL (-X) -4.314 -0.136 -7.45 0 0 0
WL (+Z) 0.016 -0.087 0.06 0 0 0
WL (-Z) -0.016 0.083 -0.06 0 0 0
2 1.2DL+1.0EQ(+X) 4.791 0.143 8.288 0 0 0
1.2DL+1.0EQ(-X) -5.035 -0.191 -8.933 0 0 0
1.2DL+1.0EQ(+Z) -0.106 -0.111 -0.262 0 0 0
1.2DL+1.0EQ(-Z) -0.141 0.146 -0.395 0 0 0
1.4DL -0.142 -0.028 -0.376 0 0 0
1.2DL+1.0WL(+X) 4.278 0.112 7.218 0 0 0
1.2DL+1.0WL(-X) -4.437 -0.16 -7.772 0 0 0
1.2DL+1.0WL(+Z) -0.106 -0.111 -0.262 0 0 0
1.2DL+1.0WL(-Z) -0.138 0.059 -0.382 0 0 0
EQ (+X) 0.022 -0.142 -0.086 0 0 0
EQ (-X) -0.022 0.142 0.086 0 0 0
EQ (+Z) 4.911 0.14 -8.597 0 0 0
EQ (-Z) -4.911 -0.14 8.597 0 0 0
DL 0.225 0.018 -0.521 0 0 0
WL (+X) 0.019 -0.061 -0.071 0 0 0
3 WL (-X)
WL (+Z)
-0.019
4.321
0.068
0.115
0.07
-7.452
0
0
0
0
0
0
WL (-Z) -4.397 -0.115 7.53 0 0 0
1.2DL+1.0EQ(+X) 0.292 -0.121 -0.711 0 0 0
1.2DL+1.0EQ(-X) 0.247 0.164 -0.539 0 0 0
1.2DL+1.0EQ(+Z) 4.591 0.137 -8.077 0 0 0
1.2DL+1.0EQ(-Z) -4.641 -0.118 7.972 0 0 0
Page 25
1.4DL 0.315 0.025 -0.729 0 0 0
1.2DL+1.0WL(+X) 0.289 -0.04 -0.696 0 0 0
1.2DL+1.0WL(-X) 0.251 0.09 -0.555 0 0 0
1.2DL+1.0WL(+Z) 4.591 0.137 -8.077 0 0 0
1.2DL+1.0WL(-Z) -4.128 -0.093 6.905 0 0 0
In this part of the report, the results for the critical reinforced concrete element of the
building where the equipment/tower of Globe Telecoms Network inc., is located. Shown below
is the analysis for flexure and shear of the said critical beams.
Figure 9. Shown above is a moment diagram of each structural beam element of the roof deck caused
by earthquake loadings (+X direction).
Page 26
Page 27
Page 28
ONE-WAY SHEAR REINFORCEMENT
Remarks
Description Values Units Limiting Limiting
Commentation
value/s Value/s
fyt 275 Mpa
fc' 21 Mpa
Normal Weight
Type of Concrete -
Concrete
Width, B 250 mm
Depth, H 450 mm
Concrete Cover, Cc 60 mm
Legs 2 pcs
Vc 72.06269868 kN Vc < 0
SHEAR REINFORCEMENT
φVc 54.04702401 kN
IS REQUIRED
Page 29
Cross sectional dimensions
CROSS-SECTIONAL Vu ≤
shall be selected to satisfy Eq. 213.0578935 kN
DIMENSION CHECKED φ(Vc+0.67*sqrt(fc')*Bd
422.5.1.2
Vs <
Vs 159.8285263 kN 159.8285263 Governing value
0.66*sqrt(fc')*Bd
Vn 231.8912249 kN
Page 30
Job No Sheet No Rev
1
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
3D Rendered View
Job Information
Engineer Checked Approved
Name:
Date: 13-Sep-23
Project ID
Project Name
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 1 of 29
Page 31
Job No Sheet No Rev
2
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Primary 1 DL
Primary 2 WL (+X)
Primary 3 WL (-X)
Primary 4 WL (+Z)
Primary 5 WL (-Z)
Combination 6 1.4DL
Combination 7 1.2DL+1.0WL(+X)
Combination 8 1.2DL+1.0WL(-X)
Combination 9 1.2DL+1.0WL(+Z)
Combination 10 1.2DL+1.0WL(-Z)
Beams
Beam Node A Node B Length Property
(m) (degrees)
1 1 4 0.220 1 0
2 4 5 2.780 1 0
3 5 6 0.400 1 0
4 6 7 2.600 1 0
5 7 9 0.400 1 0
6 9 32 0.350 1 0
9 3 21 1.459 2 0
11 3 19 1.869 2 0
12 5 14 1.594 3 0
15 14 43 1.487 2 0
20 17 14 0.200 2 0
21 17 19 1.498 2 0
22 19 5 2.374 2 0
23 4 19 2.008 2 0
24 19 21 0.702 3 0
25 21 17 1.654 2 0
26 22 86 0.100 2 0
27 6 22 1.429 2 0
28 23 27 1.459 2 0
29 23 26 1.869 2 0
30 5 24 1.594 3 0
31 24 44 1.487 2 0
32 25 24 0.200 2 0
33 25 26 1.498 2 0
34 26 5 2.374 2 0
35 4 26 2.008 2 0
36 26 27 0.702 3 0
37 27 25 1.654 2 0
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 2 of 29
Page 32
Job No Sheet No Rev
3
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
38 28 87 0.100 2 0
39 6 28 1.429 2 0
40 21 27 3.367 3 0
41 24 14 2.254 3 0
42 26 19 2.374 3 0
46 14 39 0.090 3 0
48 32 48 0.250 1 0
49 32 34 1.594 3 0
50 34 31 0.250 3 0
58 39 34 3.660 3 0
59 32 41 1.594 3 0
60 41 40 0.250 3 0
63 42 41 3.660 3 0
64 42 39 2.254 3 0
65 24 42 0.090 3 0
66 41 34 2.254 3 0
67 43 22 0.200 2 0
68 44 28 0.200 2 0
69 47 46 0.150 1 0
70 41 47 2.636 3 0
71 34 47 2.636 3 0
72 48 49 1.000 1 0
73 49 47 0.850 1 0
74 48 50 0.500 3 0
75 49 51 0.500 3 0
76 50 51 1.000 4 0
77 51 52 1.000 4 0
78 50 53 1.000 4 0
79 50 54 0.500 3 0
80 51 55 0.500 3 0
81 50 56 0.500 3 0
82 51 57 0.500 3 0
83 49 59 0.500 3 0
84 58 59 1.000 4 0
85 59 60 1.000 4 0
86 58 61 1.000 4 0
87 58 62 0.500 3 0
88 59 63 0.500 3 0
89 58 64 0.500 3 0
90 59 65 0.500 3 0
91 48 66 0.500 3 0
92 49 67 0.500 3 0
93 66 67 1.000 4 0
94 67 68 1.000 4 0
95 66 69 1.000 4 0
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 3 of 29
Page 33
Job No Sheet No Rev
4
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
96 66 70 0.500 3 0
97 67 71 0.500 3 0
98 66 72 0.500 3 0
99 67 73 0.500 3 0
100 55 73 0.366 3 0
101 71 65 0.366 3 0
102 63 57 0.366 3 0
103 54 72 0.366 3 0
104 70 64 0.366 3 0
105 62 56 0.366 3 0
106 56 57 1.000 4 0
107 62 63 1.000 4 0
108 64 65 1.000 4 0
109 70 71 1.000 4 0
110 72 73 1.000 4 0
111 54 55 1.000 4 0
112 55 74 1.000 4 0
113 57 75 1.000 4 0
114 63 76 1.000 4 0
115 65 77 1.000 4 0
116 71 78 1.000 4 0
117 73 79 1.000 4 0
118 54 80 1.000 4 0
119 56 81 1.000 4 0
120 62 82 1.000 4 0
121 64 83 1.000 4 0
122 70 84 1.000 4 0
123 72 85 1.000 4 0
124 48 58 0.500 3 0
125 28 22 1.241 3 0
126 86 9 1.968 2 0
127 87 9 1.968 2 0
128 86 34 2.263 3 0
129 87 41 2.263 3 0
Section Properties
Prop Section Area Iyy Izz J Material
(m2) (in4) (in4) (in4)
1 PIPS40 0.002 6.820 6.820 13.635 STEEL_36_KSI
2 PIPS35 0.002 4.520 4.520 9.043 STEEL_36_KSI
3 PIPS25 0.001 1.450 1.450 2.891 STEEL_36_KSI
4 PIPS30 0.001 2.850 2.850 5.689 STEEL_36_KSI
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 4 of 29
Page 34
Job No Sheet No Rev
5
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Materials
Mat Name E Density
(kN/mm2) (kg/m3) (/°C)
1 STEEL 205.000 0.300 7.83E+3 12E -6
2 CONCRETE 21.718 0.170 2.4E+3 10E -6
3 ALUMINUM 68.948 0.330 2.71E+3 23E -6
4 STAINLESSSTEEL 197.930 0.300 7.83E+3 18E -6
5 STEEL_36_KSI 199.948 0.300 7.83E+3 11.7E -6
6 STEEL_50_KSI 199.948 0.300 7.83E+3 11.7E -6
7 STEEL_275_NMM2 205.000 0.300 7.85E+3 12E -6
8 STEEL_355_NMM2 205.000 0.300 7.85E+3 12E -6
Supports
Node X Y Z rX rY rZ
(kN/mm) (kN/mm) (kN/mm) (kN-m/deg) (kN-m/deg) (kN-m/deg)
1 Fixed Fixed Fixed Fixed Fixed Fixed
3 Fixed Fixed Fixed - - -
23 Fixed Fixed Fixed - - -
Releases
Beam ends not shown in this table are fixed in all directions.
Beam Node x y z rx ry rz
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 5 of 29
Page 35
Job No Sheet No Rev
6
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Releases Cont...
Beam Node x y z rx ry rz
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 6 of 29
Page 36
Job No Sheet No Rev
7
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Releases Cont...
Beam Node x y z rx ry rz
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 7 of 29
Page 37
Job No Sheet No Rev
8
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
R1 DL Dead
R2 WL - TOWER - (+X) Wind
R3 WL - TOWER - (-X) Wind
R4 WL - TOWER - (+Z) Wind
R5 WL - TOWER - (-Z) Wind
R6 WL - MOUNTINGFRAME - (+X) Wind
R7 WL - MOUNTINGFRAME - (-X) Wind
R8 WL - MOUNTINGFRAME - (+Z) Wind
R9 WL - MOUNTINGFRAME - (-Z) Wind
R10 WL - APPURTENANCES - (+X) Wind
R11 WL - APPURTENANCES - (-X) Wind
R12 WL - APPURTENANCES - (+Z) Wind
R13 WL - APPURTENANCES - (-Z) Wind
1 DL Dead
2 WL (+X) Dead
3 WL (-X) Dead
4 WL (+Z) Dead
5 WL (-Z) Dead
6 1.4DL 1 DL 1.40
7 1.2DL+1.0WL(+X) 1 DL 1.20
2 WL (+X) 1.00
8 1.2DL+1.0WL(-X) 1 DL 1.20
3 WL (-X) 1.00
9 1.2DL+1.0WL(+Z) 1 DL 1.20
4 WL (+Z) 1.00
10 1.2DL+1.0WL(-Z) 1 DL 1.20
5 WL (-Z) 1.00
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 8 of 29
Page 38
Job No Sheet No Rev
9
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Y
X
Z
Load 1
Whole Structure
Reactions
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
1 1:DL 1.536 16.046 1.534 0.271 0.000 -0.271
2:WL (+X) 0.104 -1.233 -0.093 -0.017 -0.048 -0.028
3:WL (-X) -0.122 1.379 0.081 0.015 -0.000 0.033
4:WL (+Z) -0.081 -0.980 0.060 0.018 0.016 0.015
5:WL (-Z) 0.085 1.508 -0.143 -0.038 0.03206 -0.015
6:1.4DL 2.150 22.464 2.147 0.379 0.000 -0.380
7:1.2DL+1.0WL(+X) 1.947 18.022 1.747 0.308 -0.048 -0.354
8:1.2DL+1.0WL(-X) 1.721 20.634 1.921 0.340 -0.000 -0.292
9:1.2DL+1.0WL(+Z) 1.762 18.275 1.901 0.343 0.016061 -0.311
10:1.2DL+1.0WL(-Z) 1.929 20.763 1.697 0.287 0.032 -0.341
3 1:DL -0.010 1.973 -1.524 0 0 0
2:WL (+X) -0.059 -0.006 0.040 0 0 0
3:WL (-X) 0.035 0.005 -0.050 0 0 0
4:WL (+Z) 0.051 0.985 -0.589 0 0 0
5:WL (-Z) -0.029 -1.513 0.895 0 0 0
6:1.4DL -0.014 2.763 -2.133 0 0 0
7:1.2DL+1.0WL(+X) -0.071 2.362 -1.788 0 0 0
8:1.2DL+1.0WL(-X) 0.023 2.373 -1.879 0 0 0
9:1.2DL+1.0WL(+Z) 0.039 3.353 -2.417 0 0 0
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 9 of 29
Page 39
Job No Sheet No Rev
10
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Reactions Cont...
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
10:1.2DL+1.0WL(-Z) -0.041 0.855 -0.933 0 0 0
23 1:DL -1.526 1.978 -0.010 0 0 0
2:WL (+X) -0.732 1.239 0.053 0 0 0
3:WL (-X) 0.821 -1.384 -0.031 0 0 0
4:WL (+Z) 0.030 -0.005 -0.058 0 0 0
5:WL (-Z) -0.056 0.005 0.034 0 0 0
6:1.4DL -2.136 2.769 -0.014 0 0 0
7:1.2DL+1.0WL(+X) -2.563 3.613 0.041 0 0 0
8:1.2DL+1.0WL(-X) -1.010 0.990 -0.043 0 0 0
9:1.2DL+1.0WL(+Z) -1.801 2.369 -0.070 0 0 0
10:1.2DL+1.0WL(-Z) -1.887 2.379 0.022 0 0 0
Reaction Summary
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
Max FX 1 6:1.4DL 2.150 22.464 2.147 0.379 0.000 -0.380
Min FX 23 7:1.2DL+1.0WL(+X) -2.563 3.613 0.041 0 0 0
Max FY 1 6:1.4DL 2.150 22.464 2.147 0.379 0.000 -0.380
Min FY 3 5:WL (-Z) -0.029 -1.513 0.895 0 0 0
Max FZ 1 6:1.4DL 2.150 22.464 2.147 0.379 0.000 -0.380
Min FZ 3 9:1.2DL+1.0WL(+Z) 0.039 3.353 -2.417 0 0 0
Max MX 1 6:1.4DL 2.150 22.464 2.147 0.379 0.000 -0.380
Min MX 1 5:WL (-Z) 0.085 1.508 -0.143 -0.038 0.03206 -0.015
Max MY 1 10:1.2DL+1.0WL(-Z) 1.929 20.763 1.697 0.287 0.032 -0.341
Min MY 1 2:WL (+X) 0.104 -1.233 -0.093 -0.017 -0.048 -0.028
Max MZ 1 3:WL (-X) -0.122 1.379 0.081 0.015 -0.000 0.033
Min MZ 1 6:1.4DL 2.150 22.464 2.147 0.379 0.000 -0.380
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 10 of 29
Page 40
Job No Sheet No Rev
11
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Reaction Envelope
Horizontal Vertical Horizontal Moment
Node Env FX FY FZ MX MY MZ
(kN) (kN) (kN) (kN-m) (kN-m) (kN-m)
1 +ve 2.150 22.464 2.147 0.379 0.032 0.033
1 +ve Load: 6 Load: 6 Load: 6 Load: 6 Load: 10 Load: 3
1 -ve -0.122 -1.233 -0.143 -0.038 -0.048 -0.380
1 -ve Load: 3 Load: 2 Load: 5 Load: 5 Load: 2 Load: 6
3 +ve 0.051 3.353 0.895 0 0 0
3 +ve Load: 4 Load: 9 Load: 5 - - -
3 -ve -0.071 -1.513 -2.417 0 0 0
3 -ve Load: 7 Load: 5 Load: 9 - - -
23 +ve 0.821 3.613 0.053 0 0 0
23 +ve Load: 3 Load: 7 Load: 2 - - -
23 -ve -2.563 -1.384 -0.070 0 0 0
23 -ve Load: 7 Load: 3 Load: 9 - - -
Utilization Ratio
Beam Analysis Design Actual Allowable Ratio Clause L/C Ax Iz Iy Ix
Property Property Ratio Ratio (Act./Allow.) (m2) (in4) (in4) (in4)
1 PIPS40 PIPS40 0.078 1.000 0.078 Eq.H1-1b 6 0.002 6.820 6.820 13.640
2 PIPS40 PIPS40 0.058 1.000 0.058 Cl.E3 6 0.002 6.820 6.820 13.640
3 PIPS40 PIPS40 0.043 1.000 0.043 Eq.H1-1b 6 0.002 6.820 6.820 13.640
4 PIPS40 PIPS40 0.043 1.000 0.043 Cl.E3 6 0.002 6.820 6.820 13.640
5 PIPS40 PIPS40 0.032 1.000 0.032 Cl.E3 6 0.002 6.820 6.820 13.640
6 PIPS40 PIPS40 0.034 1.000 0.034 Eq.H1-1b 6 0.002 6.820 6.820 13.640
9 PIPS35 PIPS35 0.007 1.000 0.007 Eq.H1-1b 7 0.002 4.520 4.520 9.040
11 PIPS35 PIPS35 0.012 1.000 0.012 Eq.H1-1b 7 0.002 4.520 4.520 9.040
12 PIPS25 PIPS25 0.008 1.000 0.008 Eq.H1-1b 6 0.001 1.450 1.450 2.900
15 PIPS35 PIPS35 0.017 1.000 0.017 Eq.H1-1b 9 0.002 4.520 4.520 9.040
20 PIPS35 PIPS35 0.019 1.000 0.019 Eq.H1-1b 9 0.002 4.520 4.520 9.040
21 PIPS35 PIPS35 0.008 1.000 0.008 Cl.E3 6 0.002 4.520 4.520 9.040
22 PIPS35 PIPS35 0.009 1.000 0.009 Eq.H1-1b 7 0.002 4.520 4.520 9.040
23 PIPS35 PIPS35 0.011 1.000 0.011 Eq.H1-1b 6 0.002 4.520 4.520 9.040
24 PIPS25 PIPS25 0.002 1.000 0.002 Eq.H1-1b 6 0.001 1.450 1.450 2.900
25 PIPS35 PIPS35 0.017 1.000 0.017 Eq.H1-1b 9 0.002 4.520 4.520 9.040
26 PIPS35 PIPS35 0.017 1.000 0.017 Eq.H1-1b 7 0.002 4.520 4.520 9.040
27 PIPS35 PIPS35 0.005 1.000 0.005 Cl.E3 10 0.002 4.520 4.520 9.040
28 PIPS35 PIPS35 0.007 1.000 0.007 Eq.H1-1b 9 0.002 4.520 4.520 9.040
29 PIPS35 PIPS35 0.012 1.000 0.012 Eq.H1-1b 9 0.002 4.520 4.520 9.040
30 PIPS25 PIPS25 0.008 1.000 0.008 Eq.H1-1b 6 0.001 1.450 1.450 2.900
31 PIPS35 PIPS35 0.018 1.000 0.018 Eq.H1-1b 7 0.002 4.520 4.520 9.040
32 PIPS35 PIPS35 0.020 1.000 0.020 Eq.H1-1b 7 0.002 4.520 4.520 9.040
33 PIPS35 PIPS35 0.008 1.000 0.008 Cl.E3 6 0.002 4.520 4.520 9.040
34 PIPS35 PIPS35 0.009 1.000 0.009 Eq.H1-1b 9 0.002 4.520 4.520 9.040
35 PIPS35 PIPS35 0.011 1.000 0.011 Eq.H1-1b 6 0.002 4.520 4.520 9.040
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 11 of 29
Page 41
Job No Sheet No Rev
12
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 12 of 29
Page 42
Job No Sheet No Rev
13
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Failed Members
There is no data of this type.
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 13 of 29
Page 43
Job No Sheet No Rev
14
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 14 of 29
Page 44
Job No Sheet No Rev
15
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 15 of 29
Page 45
Job No Sheet No Rev
16
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 16 of 29
Page 46
Job No Sheet No Rev
17
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 17 of 29
Page 47
Job No Sheet No Rev
18
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 18 of 29
Page 48
Job No Sheet No Rev
19
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 19 of 29
Page 49
Job No Sheet No Rev
20
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 20 of 29
Page 50
Job No Sheet No Rev
21
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 21 of 29
Page 51
Job No Sheet No Rev
22
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 22 of 29
Page 52
Job No Sheet No Rev
23
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 23 of 29
Page 53
Job No Sheet No Rev
24
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 24 of 29
Page 54
Job No Sheet No Rev
25
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 25 of 29
Page 55
Job No Sheet No Rev
26
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 26 of 29
Page 56
Job No Sheet No Rev
27
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 27 of 29
Page 57
Job No Sheet No Rev
28
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 28 of 29
Page 58
Job No Sheet No Rev
29
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date13-Sep-23 Chd
Print Time/Date: 19/09/2023 15:54 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 29 of 29
Page 59
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Specifier's comments:
1 Anchor Design
1.1 Input data
CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 60
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 61
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 62
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Variables
2 2
Ase,N [mm ] futa [N/mm ]
157 500.00
Calculations
Nsa [kN]
78.500
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
78.500 0.650 51.025 2.259
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 63
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-19 Eq. (17.6.5.1b)
f Nag ³ Nua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa
Na
ACI 318-19 Eq. (17.6.5.4.1b)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)
Variables
t k,c,uncr [N/mm ]
2
da [cm] hef [cm] ca,min [cm] aoverhead 2
t k,c [N/mm ]
13.50 1.60 12.50 12.31 1.000 7.30
Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
21.25 248,522 180,631 0.874
Results
Nag [kN] f bond f Nag [kN] Nua [kN]
45.184 0.650 29.369 4.852
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 64
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1b)
f Ncbg ³ Nua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
2
ANc0 = 9 hef ACI 318-19 Eq. (17.6.2.1.4)
( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
1+
3 hef
ef
ACI 318-19 Eq. (17.6.2.4.1b)
= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-19 Eq. (17.6.2.2.1)
Variables
hef [cm] ec1,N [cm] ec2,N [cm] ca,min [cm] y c,N
12.50 2.17 2.28 12.31 1.000
'
cac [cm] kc la fc [psi]
20.32 17 1.000 2,500
Calculations
ANc [mm ]
2
ANc0 [mm ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
219,668 140,625 0.896 0.891 0.897 1.000 41.278
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
46.216 0.650 30.040 4.852
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 65
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Variables
2 2
Ase,V [mm ] futa [N/mm ]
157 500.00
Calculations
Vsa [kN]
47.000
Results
Vsa [kN] f steel f eb f Vsa [kN] Vua [kN]
47.000 0.600 0.800 22.560 0.521
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 66
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
M aM · M s
Vs = bending equation for stand-off
Lb
Ms = Ms
0
(1 - fNN )
ua
sa
resultant flexural resistance of anchor
0
Ms = (1.2) (S) (fu,min) characteristic flexural resistance of anchor
( N
1 - f ua
Nsa ) reduction for tensile force acting simultaneously with a shear force on the anchor
3
p(d)
S = elastic section modulus of anchor bolt at concrete surface
32
Lb = z + (n)(d0) internal lever arm adjusted for spalling of the surface concrete
f VM
s ³ Vua ACI 318-19 Table 17.5.2
Variables
aM fu,min [N/mm ]
2
Nua [kN] f Nsa [kN] z [cm] n d0 [cm]
2.00 500.00 2.259 51.025 2.00 0.500 1.60
Calculations
0
Ms [kNm] (1 - fNN )
ua
sa Ms [kNm] Lb [cm]
0.166 0.956 0.159 2.80
Results
M
Vs [kN] f steel f VM
s [kN] Vua [kN]
11.346 0.600 6.808 0.512
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 67
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa
Na
ACI 318-19 Eq. (17.6.5.4.1b)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)
Variables
kcp aoverhead t k,c,uncr [N/mm ]
2
da [cm] hef [cm] ca,min [cm]
2
t k,c [N/mm ]
2 1.000 13.50 1.60 12.50 12.31 7.30
Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
21.25 332,990 180,631 0.874
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
147.767 0.700 103.437 3.038
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 68
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 10
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Vcb = (AA ) y
Vc
Vc0
ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1a)
f Vcb ³ Vua ACI 318-19 Table 17.5.2
AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-19 Eq. (17.7.2.1.3)
y h,V = √
1.5ca1
ha ³
1.0 ACI 318-19 Eq. (17.7.2.6.1)
(7 (dl ) )l
0.2
Vb = e
√ da a √f'c c1.5
a1 ACI 318-19 Eq. (17.7.2.2.1a)
a
Variables
ca1 [cm] ca2 [cm] y c,V ha [cm] le [cm]
12.50 24.00 1.000 28.00 12.50
'
la da [cm] fc [psi] y parallel,V
1.000 1.60 2,500 1.000
Calculations
AVc [mm ]
2
AVc0 [mm ]
2
y ed,V y h,V Vb [kN]
70,312 70,312 1.000 1.000 20.350
Results
Vcb [kN] f concrete f Vcb [kN] Vua [kN]
20.350 0.700 14.245 3.038
1.5 Combined tension and shear loads, per ACI 318-19 section 17.8
z z
bNV = bN + bV <= 1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Page 69
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 11
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates as per current regulations (ETAG 001/Annex C, EOTA TR029,
etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum
required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• ACI 318 does not specifically address anchor bending when a stand-off condition exists. PROFIS Engineering calculates a shear load
corresponding to anchor bending when stand-off exists and includes the results as a shear Design Strength!
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-19,
Section 26.7.
• The anchor design methods in PROFIS Engineering require rigid anchor plates, as per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means that the anchor plate should be sufficiently rigid to prevent load re-distribution to the anchors due to elastic/plastic
displacements. The user accepts that the anchor plate is considered close to rigid by engineering judgment."
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Page 70
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 12
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Hilti HAS-U threaded rod with HVU2 capsule mortar with 12.5 cm embedment h_ef, M16, Steel galvanized, Hammer drilled installation per
ESR-4372
y
17.00 17.00
5.31
3 2
17.00
11.69
4 1
x
11.69
17.00
5 6
5.31
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12
Page 71
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 13
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
2.2 Summary
Description Profile Stiffeners Anchor plate Welds [%] Concrete [%]
sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] Hole bearing
[%]
1 DL 98.58 0.00 25.44 0.00 21.32 0.00 1 18 3
2 WL (+X) 6.99 0.00 1.78 0.00 6.01 0.00 1 2 1
3 WL (-X) 5.12 0.00 1.36 0.00 0.67 0.00 1 1 1
4 WL (+Z) 4.80 0.00 1.18 0.00 4.39 0.00 1 1 1
5 WL (-Z) 8.55 0.00 2.32 0.00 2.19 0.00 1 2 1
6 1.4DL 137.98 0.00 35.60 0.00 29.83 0.00 1 25 3
7 1.2DL+1.0WL 112.71 0.00 28.96 0.00 24.60 0.00 1 20 3
(+X)
8 1.2DL+1.0WL 123.31 0.00 31.86 0.00 25.88 0.00 1 22 3
(-X)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
13
Page 72
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 14
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
User accepted to consider the selected anchor plate as rigid by his/her engineering judgement. This means the anchor design guidelines can be
applied.
2.4 Profile/Stiffeners/Plate
Profile and stiffeners are verified at the level of the steel to concrete connection. The connection design does not replace the steel design for critical
cross sections, which should be performed outside of PROFIS Engineering.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
14
Page 73
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 15
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
248.21 N/mm²
0.00 N/mm²
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
15
Page 74
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 16
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
5.00%
0.00%
2.4.2 Plate hole bearing resistance, AISC 360-16 Section J3
Decisive load combination: 6 - 1.4DL
Equations
FRn = 0.75 Rn
V ≤ FRn
Variables
lc [cm] t [cm] Fu [N/mm²] d [cm] Rn [kN]
Anchor 1 3.66 1.00 399.90 1.60 153.560
Anchor 2 2.69 1.00 399.90 1.60 128.948
Anchor 3 6.77 1.00 399.90 1.60 153.560
Anchor 4 22.93 1.00 399.90 1.60 153.560
Anchor 5 28.93 1.00 399.90 1.60 153.560
Anchor 6 13.54 1.00 399.90 1.60 153.560
Results
V [kN] FRn [kN] Utilization [%] Status
Anchor 1 0.505 115.170 1 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
16
Page 75
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 17
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
2.5 Welds
Profiles are modeled without taking the corner radius into account. Special rules for welding (e.g. for cold-formed profiles ...) are not taken into
account by the software.
Equations
FRn = F Fnw Aw
Fn
Utilization =
F Rn
Variables
Edge Xu Th [cm] Ls [cm] L [cm] Lc [cm] FEXX [N/mm²] Q [°] Aw [mm²]
Member 1 E70xx 0.40 0.57 38.84 1.21 482.63 63.0 49
Results
Edge Fn [kN] FRn [kN] Utilization [%] Status
Member 1 1.301 14.976 9 OK
Equations
FRn = F Fnw Aw
Fn
Utilization =
F Rn
Variables
Edge Xu Th [cm] Ls [cm] L [cm] Lc [cm] FEXX [N/mm²] Q [°] Aw [mm²]
Stiffener0 E70xx 0.40 0.57 9.90 0.99 482.63 71.0 40
(Anchor plate)
Stiffener0 E70xx 0.40 0.57 9.90 0.99 482.63 38.8 40
(Anchor plate) 1
Stiffener1 E70xx 0.40 0.57 9.90 0.99 482.63 27.2 40
(Anchor plate)
Stiffener1 E70xx 0.40 0.57 9.90 0.99 482.63 62.3 40
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
17
Page 76
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 18
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
18
Page 77
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 19
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Results
Edge Fn [kN] FRn [kN] Utilization [%] Status
Stiffener0 (Anchor plate) 0.476 12.554 4 OK
Stiffener0 (Anchor plate) 1 0.514 10.731 5 OK
Stiffener1 (Anchor plate) 0.515 9.928 6 OK
Stiffener1 (Anchor plate) 1 0.388 12.182 4 OK
Stiffener2 (Anchor plate) 0.424 11.291 4 OK
Stiffener2 (Anchor plate) 1 0.365 8.883 5 OK
Stiffener3 (Anchor plate) 0.207 12.901 2 OK
Stiffener3 (Anchor plate) 1 0.292 9.090 4 OK
Stiffener4 (Anchor plate) 0.427 8.834 5 OK
Stiffener4 (Anchor plate) 1 0.349 12.328 3 OK
Stiffener5 (Anchor plate) 0.399 12.871 4 OK
Stiffener5 (Anchor plate) 1 0.497 9.664 6 OK
Stiffener0 (Member 1-arc 1) 1.885 9.012 21 OK
Stiffener0 (Member 1-arc 1) 2.431 9.920 25 OK
1
Stiffener1 (Member 1-arc 6) 1.709 9.375 19 OK
Stiffener1 (Member 1-arc 6) 1.628 9.550 18 OK
1
Stiffener2 (Member 1-arc 11) 0.247 10.048 3 OK
Stiffener2 (Member 1-arc 11) 0.457 9.343 5 OK
1
Stiffener3 (Member 1-arc 17) 0.851 8.955 10 OK
Stiffener3 (Member 1-arc 17) 1.077 9.754 12 OK
1
Stiffener4 (Member 1-arc 22) 0.658 9.843 7 OK
Stiffener4 (Member 1-arc 22) 0.472 9.495 5 OK
1
Stiffener5 (Member 1-arc 27) 1.227 9.059 14 OK
Stiffener5 (Member 1-arc 27) 1.415 9.156 16 OK
1
2.6 Concrete
Decisive load combination: 6 - 1.4DL
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
19
Page 78
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 20
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
0.00 N/mm²
2.6.2 Concrete block compressive strength resistance check, AISC 360-16 Section J8
Equations
Fp = F fp,max
A A
2 2
fp,max = 0.85 fc' √( ) ≤ 1.7 fc; √( )≤2
A A
1 1
N
s = A
1
Utilization =
s
Fp
Variables
N [kN] fc' [N/mm²] F A1 [mm²] A2 [mm²]
19.733 17.24 0.65 57,738 163,768
Results
Load combination Fp [N/mm²] s [N/mm²] Utilization [%] Status
DL 16.04 0.34 3 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
20
Page 79
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 21
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
2.8 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
anchor plate may not behave rigid. Please, validate the results with a professional designer and/or structural engineer to ensure suitability and
adequacy for your specific jurisdiction and project requirements.
● The anchor is modeled considering stiffness values determined from load displacement curves tested in an independent laboratory. Please
note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution results.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
21
Page 80
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 22
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
3 Summary of results
Design of the anchor plate, anchors, welds and other elements are based on CBFEM (component based finite element method) and AISC.
Load combination Max. utilization Status
Anchors 1.4DL 22% OK
Anchor plate 1.4DL 13% OK
Welds 1.4DL 25% OK
Stiffeners 1.4DL 15% OK
Concrete DL 3% OK
Profile 1.4DL 56% OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
22
Page 81
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 23
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
23
Page 82
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HVU2 + HAS-U 5.8 M16
Item number: 2223830 HAS-U 5.8 M16x190 (element) / 2164508 HVU2
M16x125 (capsule)
Effective embedment depth: hef,act = 12.50 cm, hnom = 12.50 cm
Material: 5.8
Evaluation Service Report: ESR-4372
Issued I Valid: 6/1/2022 | 6/1/2024
Proof: Design Method ACI 318-19 / Chem
Stand-off installation: eb = 0.00 cm (no stand-off); t = 2.50 cm
Anchor plate :
R lx x ly x t = 50.00 cm x 30.00 cm x 2.50 cm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, 2500, fc' = 2,500 psi; h = 29.00 cm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry, Installation direction: vertical downward
Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 83
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 84
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 85
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 0.403 28.200 2 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength controls)** 2.417 193.760 2 OK
Concrete edge failure in direction y-** 2.417 110.548 3 OK
Variables
2 2
Ase,V [mm ] futa [N/mm ]
157 500.00
Calculations
Vsa [kN]
47.000
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
47.000 0.600 28.200 0.403
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 86
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa
Na
ACI 318-19 Eq. (17.6.5.4.1b)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)
Variables
kcp aoverhead t k,c,uncr [N/mm ]
2
da [cm] hef [cm] ca,min [cm]
2
t k,c [N/mm ]
2 1.000 13.50 1.60 12.50 64.00 7.30
Calculations
cNa [cm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
21.25 545,035 180,631 1.000
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
276.800 0.700 193.760 2.417
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 87
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1b)
f Vcbg ³ Vua ACI 318-19 Table 17.5.2
AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-19 Eq. (17.7.2.1.3)
( )
1
'
y ec,V = ev £ 1.0 ACI 318-19 Eq. (17.7.2.3.1)
1+
1.5ca1
y h,V = √1.5ca1
h ³ 1.0
a
ACI 318-19 Eq. (17.7.2.6.1)
(7 (dl ) )l
0.2
Vb = e
√ da a √f'c c1.5
a1 ACI 318-19 Eq. (17.7.2.2.1a)
a
Variables
ca1 [cm] ca2 [cm] ecV [cm] y c,V ha [cm]
64.00 164.00 0.00 1.000 29.00
'
le [cm] la da [cm] fc [psi] y parallel,V
12.50 1.000 1.60 2,500 1.000
Calculations
AVc [mm ]
2
AVc0 [mm ]
2
y ec,V y ed,V y h,V Vb [kN]
678,600 1,843,200 1.000 1.000 1.819 235.763
Results
Vcbg [kN] f concrete f Vcbg [kN] Vua [kN]
157.926 0.700 110.548 2.417
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 88
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-19,
Section 26.7.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 89
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
6 Installation data
Anchor type and diameter: HVU2 + HAS-U 5.8 M16
Profile: no profile Item number: 2223830 HAS-U 5.8 M16x190 (element) /
2164508 HVU2 M16x125 (capsule)
Hole diameter in the fixture: df = 1.80 cm Maximum installation torque: 80 Nm
Plate thickness (input): 2.50 cm Hole diameter in the base material: 1.80 cm
Recommended plate thickness: not calculated Hole depth in the base material: 12.50 cm
Drilling method: Hammer drilled Minimum thickness of the base material: 16.00 cm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
Hilti HAS-U threaded rod with HVU2 capsule mortar with 12.5 cm embedment h_ef, M16, Steel galvanized, Hammer drilled installation per
ESR-4372
-0.00
y
25.00 25.00
4.00
4 5 6
15.00
22.00
0.00
x
15.00
1 2 3
4.00
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 90
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 91
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 1
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HVU2 + HAS-U 5.8 M16
Item number: 2223830 HAS-U 5.8 M16x190 (element) / 2164508 HVU2
M16x125 (capsule)
Effective embedment depth: hef,act = 12.50 cm, hnom = 12.50 cm
Material: 5.8
Evaluation Service Report: ESR-4372
Issued I Valid: 6/1/2022 | 6/1/2024
Proof: Design Method ACI 318-19 / Chem
Stand-off installation: eb = 0.00 cm (no stand-off); t = 2.50 cm
Anchor plate :
R lx x ly x t = 50.00 cm x 30.00 cm x 2.50 cm; (Recommended plate thickness: not calculated)
Profile: no profile
Base material: uncracked concrete, 2500, fc' = 2,500 psi; h = 29.00 cm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry, Installation direction: vertical downward
Reinforcement: tension: not present, shear: not present; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 92
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 2
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 93
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 3
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 94
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 4
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 0.427 28.200 2 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 2.563 274.430 1 OK
Strength controls)**
Concrete edge failure in direction y-** 2.563 154.767 2 OK
Variables
2 2
Ase,V [mm ] futa [N/mm ]
157 500.00
Calculations
Vsa [kN]
47.000
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
47.000 0.600 28.200 0.427
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 95
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 5
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Nc0
ec,N y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
2
ANc0 = 9 hef ACI 318-19 Eq. (17.6.2.1.4)
( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
1+
3 hef
ef
ACI 318-19 Eq. (17.6.2.4.1b)
= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-19 Eq. (17.6.2.2.1)
Variables
kcp hef [cm] ec1,N [cm] ec2,N [cm] ca,min [cm]
2 12.50 0.00 0.00 64.00
'
y c,N cac [cm] kc la fc [psi]
1.000 19.58 24 1.000 2,500
Calculations
ANc [mm ]
2
ANc0 [mm ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
473,025 140,625 1.000 1.000 1.000 1.000 58.275
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
392.043 0.700 274.430 2.563
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 96
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 6
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1b)
f Vcbg ³ Vua ACI 318-19 Table 17.5.2
AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-19 Eq. (17.7.2.1.3)
( )
1
'
y ec,V = ev £ 1.0 ACI 318-19 Eq. (17.7.2.3.1)
1+
1.5ca1
y h,V = √1.5ca1
h ³ 1.0
a
ACI 318-19 Eq. (17.7.2.6.1)
(7 (dl ) )l
0.2
Vb = e
√ da a √f'c c1.5
a1 ACI 318-19 Eq. (17.7.2.2.1a)
a
Variables
ca1 [cm] ca2 [cm] ecV [cm] y c,V ha [cm]
64.00 164.00 0.00 1.400 29.00
'
le [cm] la da [cm] fc [psi] y parallel,V
12.50 1.000 1.60 2,500 1.000
Calculations
AVc [mm ]
2
AVc0 [mm ]
2
y ec,V y ed,V y h,V Vb [kN]
678,600 1,843,200 1.000 1.000 1.819 235.763
Results
Vcbg [kN] f concrete f Vcbg [kN] Vua [kN]
221.096 0.700 154.767 2.563
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 97
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 7
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-19,
Section 26.7.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 98
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 8
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
6 Installation data
Anchor type and diameter: HVU2 + HAS-U 5.8 M16
Profile: no profile Item number: 2223830 HAS-U 5.8 M16x190 (element) /
2164508 HVU2 M16x125 (capsule)
Hole diameter in the fixture: df = 1.80 cm Maximum installation torque: 80 Nm
Plate thickness (input): 2.50 cm Hole diameter in the base material: 1.80 cm
Recommended plate thickness: not calculated Hole depth in the base material: 12.50 cm
Drilling method: Hammer drilled Minimum thickness of the base material: 16.00 cm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
Hilti HAS-U threaded rod with HVU2 capsule mortar with 12.5 cm embedment h_ef, M16, Steel galvanized, Hammer drilled installation per
ESR-4372
-0.00
y
25.00 25.00
4.00
4 5 6
15.00
22.00
0.00
x
15.00
1 2 3
4.00
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 99
Hilti PROFIS Engineering 3.0.88
www.hilti.com.ph
Company: Power Acts Network Inc. Page: 9
Address: Upper Ground 6 Cityland Herrera Towers, V.A. Rufin Specifier: Aldrin Jonas
Phone I Fax: 09175602146 | E-Mail: ajdeduarte.poweracts@gmail.com
Design: Concrete - Sep 19, 2023 (1) Date: 9/19/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Page 100
Job No Sheet No Rev
1
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
3D Rendered View
Job Information
Engineer Checked Approved
Name:
Date: 19-Sep-23
Project ID
Project Name
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 1 of 22
Page 101
Job No Sheet No Rev
2
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Primary 1 EQ (+X)
Primary 2 EQ (-X)
Primary 3 EQ (+Z)
Primary 4 EQ (-Z)
Primary 5 DL
Primary 6 LL
Primary 7 WL (+X)
Primary 8 WL (-X)
Primary 9 WL (+Z)
Primary 10 WL (-Z)
Combination 11 1.4DL
Combination 12 1.2DL+1.6LL
Combination 13 1.2DL+F1LL
Combination 14 1.2DL+0.5WL(+X)
Combination 15 1.2DL+0.5WL(-X)
Combination 16 1.2DL+0.5WL(+Z)
Combination 17 1.2DL+0.5WL(-Z)
Combination 18 1.2DL+1.0WL(+X)+F1LL
Combination 19 1.2DL+1.0WL(-X)+F1LL
Combination 20 1.2DL+1.0WL(+Z)+F1LL
Combination 21 1.2DL+1.0WL(-Z)+F1LL
Combination 22 1.2DL+1.0EQ(+X)+F1LL
Combination 23 1.2DL+1.0EQ(-X)+F1LL
Combination 24 1.2DL+1.0EQ(+Z)+F1LL
Combination 25 1.2DL+1.0EQ(-Z)+F1LL
Beams
Beam Node A Node B Length Property
(m) (degrees)
25 1 17 3.475 12 90
26 2 18 3.475 12 0
27 3 19 3.475 12 0
28 4 20 3.475 12 90
29 5 21 3.475 12 90
30 6 22 3.475 12 90
31 7 23 3.475 12 90
32 8 24 3.475 12 90
33 9 25 3.475 12 90
34 10 26 3.475 12 90
35 11 27 3.475 12 90
36 12 28 3.475 12 90
37 13 29 3.475 12 90
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 2 of 22
Page 102
Job No Sheet No Rev
3
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
38 14 30 3.475 12 0
39 15 31 3.475 12 0
40 16 32 3.475 12 90
41 17 33 2.050 3 0
42 18 37 2.275 3 0
43 19 60 3.625 3 0
44 21 34 2.050 4 0
45 22 38 2.275 4 0
46 23 64 2.275 4 0
47 25 35 2.050 4 0
48 26 39 2.275 4 0
49 27 65 2.275 4 0
50 29 36 2.050 3 0
51 30 40 2.275 3 0
52 31 63 3.625 3 0
53 17 21 3.325 3 0
54 21 54 0.601 3 0
55 25 29 3.325 3 0
56 18 41 1.550 4 0
57 22 58 0.601 4 0
58 26 43 1.775 4 0
59 19 44 1.550 4 0
60 23 45 1.840 4 0
61 27 46 1.775 4 0
62 20 24 3.325 3 0
63 24 28 3.680 3 0
64 28 32 3.325 3 0
65 33 18 2.275 3 0
66 34 22 2.275 4 0
67 35 26 2.275 4 0
68 36 30 2.275 3 0
69 37 19 3.075 3 0
70 38 23 3.075 4 0
71 39 27 3.075 4 0
72 40 31 3.075 3 0
73 33 34 3.650 6 0
74 34 50 0.826 6 0
75 35 36 3.650 6 0
76 37 47 1.650 6 0
77 38 48 2.065 6 0
78 39 49 2.000 6 0
79 41 22 1.775 4 0
80 42 59 1.239 4 0
81 43 30 1.550 4 0
82 44 23 1.775 4 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 3 of 22
Page 103
Job No Sheet No Rev
4
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
83 45 27 1.840 4 0
84 46 31 1.550 4 0
85 47 38 2.000 6 0
86 48 39 2.065 6 0
87 49 40 1.650 6 0
88 47 44 3.300 5 0
89 41 47 2.300 5 0
90 48 45 3.300 5 0
91 42 48 2.300 5 0
92 49 46 3.300 5 0
93 43 49 2.300 5 0
94 50 53 2.478 6 0
97 53 35 0.826 6 0
98 54 57 2.478 3 0
101 57 25 0.601 3 0
102 58 42 1.239 4 0
103 59 26 0.601 4 0
104 54 50 2.150 5 0
105 50 58 2.300 5 0
106 57 53 2.150 5 0
107 53 59 2.300 5 0
108 60 20 1.700 3 0
109 61 24 1.700 4 0
110 62 28 1.700 4 0
111 63 32 1.700 3 0
112 60 68 1.650 5 0
113 62 67 1.800 5 0
114 64 61 1.350 4 0
115 65 62 1.350 4 0
116 64 66 1.865 7 0
117 66 65 1.865 7 0
118 45 66 2.375 5 0
119 67 63 1.650 5 0
120 46 67 3.725 6 0
121 68 61 1.800 5 0
122 44 68 3.725 6 0
123 17 69 2.775 13 90
124 18 70 2.775 13 0
125 19 71 2.775 13 0
126 20 72 2.775 14 90
127 21 73 2.775 13 90
128 22 74 2.775 13 90
129 23 75 2.775 13 90
130 24 76 2.775 13 90
131 25 77 2.775 13 90
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 4 of 22
Page 104
Job No Sheet No Rev
5
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
132 26 78 2.775 13 90
133 27 79 2.775 13 90
134 28 80 2.775 13 90
135 29 81 2.775 13 90
136 30 82 2.775 13 0
137 31 83 2.775 13 0
138 32 84 2.775 14 90
139 69 85 2.150 1 0
140 70 89 2.275 1 0
141 71 93 3.625 1 0
142 72 76 3.425 1 0
143 76 80 3.680 1 0
144 80 84 3.425 1 0
145 96 84 1.800 1 0
146 92 83 3.075 1 0
147 86 82 2.275 1 0
148 77 81 3.325 1 0
149 103 77 0.601 1 0
150 69 73 3.325 1 0
151 94 76 1.800 1 0
152 90 75 3.125 1 0
153 87 74 2.325 1 0
154 95 80 1.800 1 0
155 91 79 3.125 1 0
156 88 78 2.325 1 0
157 70 74 3.425 1 0
158 74 107 0.601 1 0
159 78 82 3.425 1 0
160 71 99 1.650 1 0
161 75 79 3.680 1 0
162 79 100 1.775 1 0
163 85 70 2.275 1 0
164 81 86 2.150 1 0
165 73 87 2.150 1 0
166 77 88 2.150 1 0
167 85 87 3.650 6 0
168 87 111 0.826 6 0
169 88 86 3.650 6 0
170 89 71 3.075 1 0
171 74 90 2.325 1 0
172 78 91 2.325 1 0
173 82 92 2.275 1 0
174 89 101 1.650 6 0
175 90 91 4.130 6 0
176 91 102 2.000 6 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 5 of 22
Page 105
Job No Sheet No Rev
6
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
177 93 72 1.800 1 0
178 97 94 1.350 1 0
179 98 95 1.350 1 0
180 83 96 3.625 1 0
181 93 94 3.475 6 0
183 95 96 3.475 6 0
184 75 97 2.325 1 0
185 79 98 2.325 1 0
186 97 98 3.780 8 0
187 99 75 1.775 1 0
188 100 83 1.650 1 0
189 101 90 2.000 6 0
190 102 92 1.650 6 0
191 101 99 3.000 6 0
192 102 100 3.000 6 0
193 106 103 2.478 1 0
196 73 106 0.601 1 0
197 107 110 2.478 1 0
200 110 78 0.601 1 0
201 111 114 2.478 6 0
204 114 88 0.826 6 0
205 111 107 2.325 6 0
206 106 111 2.500 6 0
207 114 110 2.325 6 0
208 103 114 2.500 6 0
209 122 103 0.800 2 0
210 121 106 0.800 2 0
211 117 69 0.500 2 0
212 118 81 0.500 2 0
213 119 73 0.750 2 0
214 120 77 0.750 2 0
215 117 119 3.708 9 0
216 116 121 0.200 2 0
217 119 121 0.678 9 0
218 115 122 0.200 2 0
219 120 118 3.708 9 0
220 122 120 0.678 9 0
221 116 115 2.178 9 0
222 69 123 2.775 13 90
223 70 124 2.775 13 0
224 71 125 2.775 13 0
225 72 126 2.775 14 90
226 73 127 2.775 13 90
227 74 128 2.775 13 90
228 75 129 2.775 13 90
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 6 of 22
Page 106
Job No Sheet No Rev
7
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
229 76 130 2.775 13 90
230 77 131 2.775 13 90
231 78 132 2.775 13 90
232 79 133 2.775 13 90
233 80 134 2.775 13 90
234 81 135 2.775 13 90
235 82 136 2.775 13 0
236 83 137 2.775 13 0
237 84 138 2.775 14 90
238 123 139 2.775 15 90
239 124 140 2.775 15 0
240 125 141 2.775 15 0
241 126 142 2.775 14 90
242 127 143 2.775 15 90
243 128 144 2.775 15 90
244 129 145 2.775 15 90
245 130 146 2.775 15 90
246 131 147 2.775 15 90
247 132 148 2.775 15 90
248 133 149 2.775 15 90
249 134 150 2.775 15 90
250 135 151 2.775 15 90
251 136 152 2.775 15 0
252 137 153 2.775 15 0
253 138 154 2.775 14 90
254 139 155 2.775 15 90
255 140 156 2.775 15 0
256 141 157 2.775 15 0
257 142 158 2.775 14 90
258 143 159 2.775 15 90
259 144 160 2.775 15 90
260 145 161 2.775 15 90
261 146 162 2.775 15 90
262 147 163 2.775 15 90
263 148 164 2.775 15 90
264 149 165 2.775 15 90
265 150 166 2.775 15 90
266 151 167 2.775 15 90
267 152 168 2.775 15 0
268 153 169 2.775 15 0
269 154 170 2.775 14 90
270 123 171 2.150 2 0
271 124 175 2.275 2 0
272 125 179 3.625 2 0
273 126 130 3.425 2 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 7 of 22
Page 107
Job No Sheet No Rev
8
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
274 130 134 3.680 2 0
275 134 138 3.425 2 0
276 182 138 1.800 2 0
277 178 137 3.075 2 0
278 172 136 2.275 2 0
279 131 135 3.325 2 0
280 189 131 0.601 2 0
281 123 127 3.325 2 0
282 180 130 1.800 1 0
283 176 129 3.125 1 0
284 173 128 2.325 1 0
285 181 134 1.800 1 0
286 177 133 3.125 1 0
287 174 132 2.325 1 0
288 124 128 3.425 1 0
289 128 191 0.601 1 0
290 132 136 3.425 1 0
291 125 185 1.650 1 0
292 129 133 3.680 1 0
293 133 186 1.775 1 0
294 171 124 2.275 2 0
295 135 172 2.150 2 0
296 127 173 2.150 1 0
297 131 174 2.150 1 0
298 171 173 3.700 10 0
299 173 193 0.826 10 0
300 174 172 3.700 10 0
301 175 125 3.075 2 0
302 128 176 2.325 1 0
303 132 177 2.325 1 0
304 136 178 2.275 2 0
305 175 187 1.700 10 0
306 176 177 4.130 10 0
307 177 188 2.000 10 0
308 179 126 1.800 2 0
309 183 180 1.350 1 0
310 184 181 1.350 1 0
311 137 182 3.625 2 0
312 179 180 3.525 10 0
313 181 182 3.525 10 0
314 129 183 2.325 1 0
315 133 184 2.325 1 0
316 183 184 3.780 11 0
317 185 129 1.775 1 0
318 186 137 1.650 1 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 8 of 22
Page 108
Job No Sheet No Rev
9
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
319 187 176 2.000 10 0
320 188 178 1.700 10 0
321 187 185 3.025 10 0
322 188 186 3.025 10 0
323 190 189 2.478 2 0
324 127 190 0.601 2 0
325 191 192 2.478 1 0
326 192 132 0.601 1 0
327 193 194 2.478 10 0
328 194 174 0.826 10 0
329 193 191 2.500 10 0
330 190 193 2.500 10 0
331 194 192 2.500 10 0
332 189 194 2.500 10 0
333 202 189 0.800 2 0
334 201 190 0.800 2 0
335 197 123 0.500 2 0
336 198 135 0.500 2 0
337 199 127 0.750 2 0
338 200 131 0.750 2 0
339 197 199 3.708 10 0
340 196 201 0.200 2 0
341 199 201 0.678 10 0
342 195 202 0.200 2 0
343 200 198 3.708 10 0
344 202 200 0.678 10 0
345 196 195 2.178 10 0
346 139 203 2.200 2 0
347 140 207 2.500 2 0
348 141 211 3.625 2 0
349 142 146 3.425 2 0
350 146 150 3.680 2 0
351 150 154 3.600 2 0
352 214 154 1.800 2 0
353 210 153 3.075 2 0
354 204 152 2.275 2 0
355 147 151 3.325 2 0
356 221 147 0.601 2 0
357 139 143 3.325 2 0
358 212 146 1.850 2 0
359 208 145 3.150 2 0
360 205 144 2.350 2 0
361 213 150 1.850 2 0
362 209 149 3.150 2 0
363 206 148 2.350 2 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 9 of 22
Page 109
Job No Sheet No Rev
10
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
364 140 144 3.475 2 0
365 144 223 0.601 2 0
366 148 152 3.475 2 0
367 141 217 1.700 2 0
368 145 149 3.680 2 0
369 149 218 1.775 2 0
370 203 140 2.500 2 0
371 151 204 2.200 2 0
372 143 205 2.200 2 0
373 147 206 2.200 2 0
374 203 205 3.700 10 0
375 205 225 0.826 10 0
376 206 204 3.700 10 0
377 207 141 3.075 2 0
378 144 208 2.350 2 0
379 148 209 2.350 2 0
380 152 210 2.275 2 0
381 207 219 1.700 10 0
382 208 209 4.130 10 0
383 209 220 2.000 10 0
384 211 142 1.800 2 0
385 215 212 1.350 2 0
386 216 213 1.350 2 0
387 153 214 3.625 2 0
388 211 212 3.550 10 0
389 213 214 3.550 10 0
390 145 215 2.350 2 0
391 149 216 2.350 2 0
392 215 216 3.830 11 0
393 217 145 1.775 2 0
394 218 153 1.700 2 0
395 219 208 2.000 10 0
396 220 210 1.700 10 0
397 219 217 3.050 10 0
398 220 218 3.050 10 0
399 222 221 2.478 2 0
400 143 222 0.601 2 0
401 223 224 2.478 2 0
402 224 148 0.601 2 0
403 225 226 2.478 10 0
404 226 206 0.826 10 0
405 225 223 2.500 10 0
406 222 225 2.500 10 0
407 226 224 2.500 10 0
408 221 226 2.500 10 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 10 of 22
Page 110
Job No Sheet No Rev
11
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
409 234 221 0.800 2 0
410 233 222 0.800 2 0
411 229 139 0.500 2 0
412 230 151 0.500 2 0
413 231 143 0.750 2 0
414 232 147 0.750 2 0
415 229 231 3.708 10 0
416 228 233 0.200 2 0
417 231 233 0.678 10 0
418 227 234 0.200 2 0
419 232 230 3.708 10 0
420 234 232 0.678 10 0
421 228 227 2.178 10 0
498 155 267 2.775 15 90
499 156 268 2.775 15 0
500 157 269 2.775 15 0
501 158 270 2.775 14 90
502 159 271 2.775 15 90
503 160 272 2.775 15 90
504 161 273 2.775 15 90
505 162 274 2.775 15 90
506 163 275 2.775 15 90
507 164 276 2.775 15 90
508 165 277 2.775 15 90
509 166 278 2.775 15 90
510 167 279 2.775 15 90
511 168 280 2.775 15 0
512 169 281 2.775 15 0
513 170 282 2.775 14 90
514 267 283 2.200 7 0
515 268 287 2.275 7 0
516 269 291 3.625 7 0
517 270 274 3.425 7 0
518 274 278 3.680 7 0
519 278 282 3.425 7 0
520 294 282 1.800 7 0
521 290 281 3.075 7 0
522 284 280 2.275 7 0
523 275 279 3.325 7 0
524 301 275 0.601 7 0
525 267 271 3.325 7 0
526 292 274 1.850 7 0
527 288 273 3.150 7 0
528 285 272 2.350 7 0
529 293 278 1.850 7 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 11 of 22
Page 111
Job No Sheet No Rev
12
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
530 289 277 3.150 7 0
531 286 276 2.350 7 0
532 268 272 3.475 7 0
533 272 276 3.680 7 0
534 276 280 3.475 7 0
535 269 297 1.700 7 0
536 273 277 3.680 7 0
537 277 298 1.775 7 0
538 283 268 2.275 7 0
539 279 284 2.200 7 0
540 271 285 2.200 7 0
541 275 286 2.200 7 0
542 283 285 3.750 10 0
543 285 286 4.130 10 0
544 286 284 3.750 10 0
545 287 269 3.075 7 0
546 272 288 2.350 7 0
547 276 289 2.350 7 0
548 280 290 2.275 7 0
549 287 299 1.750 10 0
550 288 289 4.130 10 0
551 289 300 2.000 10 0
552 291 270 1.800 7 0
553 295 292 1.350 7 0
554 360 293 0.850 7 0
555 281 294 3.625 7 0
556 291 292 3.625 10 0
557 293 294 3.625 10 0
558 273 295 2.350 7 0
559 277 296 2.350 7 0
560 295 296 3.880 5 0
561 297 273 1.775 7 0
562 298 359 1.000 7 0
563 299 288 2.000 10 0
564 300 290 1.750 10 0
565 299 297 3.075 5 0
566 300 298 3.075 5 0
567 302 301 2.478 7 0
568 271 302 0.601 7 0
577 314 301 0.800 2 0
578 313 302 0.800 2 0
579 309 267 0.500 2 0
580 310 279 0.500 2 0
581 311 271 0.750 2 0
582 312 275 0.750 2 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 12 of 22
Page 112
Job No Sheet No Rev
13
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
583 309 311 3.708 10 0
584 308 313 0.200 2 0
585 311 313 0.678 10 0
586 307 314 0.200 2 0
587 312 310 3.708 10 0
588 314 312 0.678 10 0
589 308 307 2.178 10 0
590 155 315 2.200 2 0
591 156 319 2.500 2 0
592 157 323 3.625 2 0
593 158 162 3.425 2 0
594 162 166 3.680 2 0
595 166 170 3.600 2 0
596 326 170 1.800 2 0
597 322 169 3.075 2 0
598 316 168 2.275 2 0
599 163 167 3.325 2 0
600 333 163 0.601 2 0
601 155 159 3.325 2 0
602 324 162 1.850 2 0
603 320 161 3.150 2 0
604 317 160 2.350 2 0
605 325 166 1.850 2 0
606 321 165 3.150 2 0
607 318 164 2.350 2 0
608 156 160 3.475 2 0
609 160 335 0.601 2 0
610 164 168 3.475 2 0
611 157 329 1.700 2 0
612 161 165 3.680 2 0
613 165 330 1.775 2 0
614 315 156 2.500 2 0
615 167 316 2.200 2 0
616 159 317 2.200 2 0
617 163 318 2.200 2 0
618 315 317 3.700 10 0
619 317 337 0.826 10 0
620 318 316 3.700 10 0
621 319 157 3.075 2 0
622 160 320 2.350 2 0
623 164 321 2.350 2 0
624 168 322 2.275 2 0
625 319 331 1.700 10 0
626 320 321 4.130 10 0
627 321 332 2.000 10 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 13 of 22
Page 113
Job No Sheet No Rev
14
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
628 323 158 1.800 2 0
629 327 324 1.350 2 0
630 328 325 1.350 2 0
631 169 326 3.625 2 0
632 323 324 3.550 10 0
633 325 326 3.550 10 0
634 161 327 2.350 2 0
635 165 328 2.350 2 0
636 327 328 3.830 11 0
637 329 161 1.775 2 0
638 330 169 1.700 2 0
639 331 320 2.000 10 0
640 332 322 1.700 10 0
641 331 329 3.050 10 0
642 332 330 3.050 10 0
643 334 333 2.478 2 0
644 159 334 0.601 2 0
645 335 336 2.478 2 0
646 336 164 0.601 2 0
647 337 338 2.478 10 0
648 338 318 0.826 10 0
649 337 335 2.500 10 0
650 334 337 2.500 10 0
651 338 336 2.500 10 0
652 333 338 2.500 10 0
653 346 333 0.800 2 0
654 345 334 0.800 2 0
655 341 155 0.500 2 0
656 342 167 0.500 2 0
657 343 159 0.750 2 0
658 344 163 0.750 2 0
659 341 343 3.708 10 0
660 340 345 0.200 2 0
661 343 345 0.678 10 0
662 339 346 0.200 2 0
663 344 342 3.708 10 0
664 346 344 0.678 10 0
665 340 339 2.178 10 0
666 89 175 2.325 16 0
667 92 178 2.325 16 0
668 175 207 2.325 17 0
669 178 210 2.325 17 0
670 207 319 2.325 17 0
671 210 322 2.325 17 0
672 89 37 2.325 16 0
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 14 of 22
Page 114
Job No Sheet No Rev
15
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Beams Cont...
Beam Node A Node B Length Property
(m) (degrees)
673 40 92 2.325 16 0
674 319 287 2.326 17 0
675 322 290 2.325 17 0
688 277 358 0.280 18 0
689 359 281 0.700 7 0
690 296 360 0.500 7 0
691 359 361 0.290 19 90
692 360 362 0.290 19 0
Section Properties
Prop Section Area Iyy Izz J Material
(m2) (in4) (in4) (in4)
1 Rect 0.45x0.35 0.157 3.86E+3 6.39E+3 8.11E+3 CONCRETE
2 Rect 0.45x0.30 0.135 2.43E+3 5.47E+3 5.71E+3 CONCRETE
3 Rect 0.55x0.35 0.192 4.72E+3 11.7E+3 11.4E+3 CONCRETE
4 Rect 0.55x0.40 0.220 7.05E+3 13.3E+3 15.6E+3 CONCRETE
5 Rect 0.35x0.25 0.0875 1.09E+3 2.15E+3 2.45E+3 CONCRETE
6 Rect 0.30x0.25 0.075 938.490 1.35E+3 1.86E+3 CONCRETE
7 Rect 0.45x0.25 0.112 1.41E+3 4.56E+3 3.68E+3 CONCRETE
8 Rect 0.35x0.30 0.105 1.89E+3 2.58E+3 3.67E+3 CONCRETE
9 Rect 0.40x0.25 0.100 1.25E+3 3.2E+3 3.06E+3 CONCRETE
10 Rect 0.40x0.20 0.08 640.676 2.56E+3 1.76E+3 CONCRETE
11 Rect 0.35x0.30 0.105 1.89E+3 2.58E+3 3.67E+3 CONCRETE
12 Rect 0.45x0.45 0.202 8.21E+3 8.21E+3 13.9E+3 CONCRETE
13 Rect 0.45x0.35 0.157 3.86E+3 6.39E+3 8.11E+3 CONCRETE
14 Rect 0.35x0.35 0.122 3E+3 3E+3 5.07E+3 CONCRETE
15 Rect 0.45x0.30 0.135 2.43E+3 5.47E+3 5.71E+3 CONCRETE
16 Rect 0.40x0.20 0.08 640.676 2.56E+3 1.76E+3 CONCRETE
17 Rect 0.35x0.15 0.0525 236.500 1.29E+3 691.297 CONCRETE
18 Rect 0.60x0.60 0.360 25.9E+3 25.9E+3 43.8E+3 CONCRETE
19 Rect 0.90x0.60 0.540 38.9E+3 87.6E+3 91.4E+3 CONCRETE
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 15 of 22
Page 115
Job No Sheet No Rev
16
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Materials
Mat Name E Density
(kN/mm2) (kg/m3) (/°C)
1 STEEL 205.000 0.300 7.83E+3 12E -6
2 CONCRETE 21.718 0.170 2.4E+3 10E -6
3 ALUMINUM 68.948 0.330 2.71E+3 23E -6
4 STAINLESSSTEEL 197.930 0.300 7.83E+3 18E -6
5 STEEL_36_KSI 199.948 0.300 7.83E+3 11.7E -6
6 STEEL_50_KSI 199.948 0.300 7.83E+3 11.7E -6
7 STEEL_275_NMM2 205.000 0.300 7.85E+3 12E -6
8 STEEL_355_NMM2 205.000 0.300 7.85E+3 12E -6
Y
X
Z
Load 25
Whole Structure
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 16 of 22
Page 116
Job No Sheet No Rev
17
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Supports
Node X Y Z rX rY rZ
(kN/mm) (kN/mm) (kN/mm) (kN-m/deg) (kN-m/deg) (kN-m/deg)
1 Fixed Fixed Fixed Fixed Fixed Fixed
2 Fixed Fixed Fixed Fixed Fixed Fixed
3 Fixed Fixed Fixed Fixed Fixed Fixed
4 Fixed Fixed Fixed Fixed Fixed Fixed
5 Fixed Fixed Fixed Fixed Fixed Fixed
6 Fixed Fixed Fixed Fixed Fixed Fixed
7 Fixed Fixed Fixed Fixed Fixed Fixed
8 Fixed Fixed Fixed Fixed Fixed Fixed
9 Fixed Fixed Fixed Fixed Fixed Fixed
10 Fixed Fixed Fixed Fixed Fixed Fixed
11 Fixed Fixed Fixed Fixed Fixed Fixed
12 Fixed Fixed Fixed Fixed Fixed Fixed
13 Fixed Fixed Fixed Fixed Fixed Fixed
14 Fixed Fixed Fixed Fixed Fixed Fixed
15 Fixed Fixed Fixed Fixed Fixed Fixed
16 Fixed Fixed Fixed Fixed Fixed Fixed
Releases
Beam ends not shown in this table are fixed in all directions.
Beam Node x y z rx ry rz
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 17 of 22
Page 117
Job No Sheet No Rev
18
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Releases Cont...
Beam Node x y z rx ry rz
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 18 of 22
Page 118
Job No Sheet No Rev
19
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Releases Cont...
Beam Node x y z rx ry rz
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 19 of 22
Page 119
Job No Sheet No Rev
20
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
Releases Cont...
Beam Node x y z rx ry rz
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 20 of 22
Page 120
Job No Sheet No Rev
21
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
R1 DL (TOWER) Dead
R2 WL - TOWER (+X) Wind
R3 WL - TOWER (-X) Wind
R4 WL - TOWER (+Z) Wind
R5 WL - TOWER (-Z) Wind
R6 DL - WALL Dead
R7 DL - SLAB Dead
1 EQ (+X) Seismic
2 EQ (-X) Seismic
3 EQ (+Z) Seismic
4 EQ (-Z) Seismic
5 DL Dead
6 LL Live
7 WL (+X) Wind
8 WL (-X) Wind
9 WL (+Z) Wind
10 WL (-Z) Wind
11 1.4DL 5 DL 1.40
12 1.2DL+1.6LL 5 DL 1.20
6 LL 1.60
13 1.2DL+F1LL 5 DL 1.20
6 LL 0.50
14 1.2DL+0.5WL(+X) 5 DL 1.20
7 WL (+X) 0.50
15 1.2DL+0.5WL(-X) 5 DL 1.20
8 WL (-X) 0.50
16 1.2DL+0.5WL(+Z) 5 DL 1.20
9 WL (+Z) 0.50
17 1.2DL+0.5WL(-Z) 5 DL 1.20
10 WL (-Z) 0.50
18 1.2DL+1.0WL(+X)+F1LL 5 DL 1.20
7 WL (+X) 1.00
6 LL 0.50
19 1.2DL+1.0WL(-X)+F1LL 5 DL 1.20
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 21 of 22
Page 121
Job No Sheet No Rev
22
Software licensed to only @ ::LAVTeam:: (R) Part
CONNECTED User: User is not logged in to CONNECTION Client.
Job Title Ref
By Date19-Sep-23 Chd
8 WL (-X) 1.00
6 LL 0.50
20 1.2DL+1.0WL(+Z)+F1LL 5 DL 1.20
9 WL (+Z) 1.00
6 LL 0.50
21 1.2DL+1.0WL(-Z)+F1LL 5 DL 1.20
10 WL (-Z) 1.00
6 LL 0.50
22 1.2DL+1.0EQ(+X)+F1LL 5 DL 1.20
1 EQ (+X) 1.00
6 LL 0.50
23 1.2DL+1.0EQ(-X)+F1LL 5 DL 1.20
2 EQ (-X) 1.00
6 LL 0.50
24 1.2DL+1.0EQ(+Z)+F1LL 5 DL 1.20
3 EQ (+Z) 1.00
6 LL 0.50
25 1.2DL+1.0EQ(-Z)+F1LL 5 DL 1.20
4 EQ (-Z) 1.00
6 LL 0.50
Print Time/Date: 04/10/2023 13:47 STAAD.Pro CONNECT Edition 22.06.00.138 Print Run 22 of 22
Page 122
IV. DISCUSSION OF THE RESULTS
The used of utilization ratio is to compare the actual designed computation to the criteria bind by the code,
when the value for utilization ratio for different mode of failure/s reaches 1.00 that signifies that the designed
actual computation are already at 100% designed capacity of the material that was examined. It is safe to assume
that the utilization ratio should not be equal to or greater than the obtained design capacity for a certain design
criterion. During the design stage it is advisable to have less than or equal to 10% of utilization ratio for the strength
capacity of anchor bolts. This consideration is based on the judgement of the designer. However, since the structure
is already built in the analysis is performed after the tower is designed, it exceeds the usual 10% utilization rate,
but it is still safe as it is below the safe value as stated. This is considered safe as we conservatively analyzed the
concrete pedestal through the criteria of Condition B for provisions of ACI 318-14 (Chapter 17 – ANCHORING
TO CONCRETE) wherein it is stated in this conditional analysis that “where supplementary reinforcement is not
present, and for pullout or pry out strength. Also, there is a safety factor of 0.70 (Multiplier for the design capacity)
for shear and tension loads when considering the said condition.
As shown from the given data from pages. 31-59, the Prefabricated steel members were analyzed to resist
axial failure, torsional failure, and slenderness ratio adequacy throughout carrying different load cases/load
combination inputs. The maximum slenderness ratio for compression members is at 200 and 300 for tension
members. The governing mode of failure would be provided and written as “Ref:” along with the governing
equation for mode of failure. The word “ratio: “indicates the design checking ratio for a particular governing mode
of failure for a particular steel member. “Track 2” on page. 21 indicates that LRFD method are used.
As shown from the given data from pages. 59 – 103, finite element analysis was performed to check the
adequacy of steel element materials and welds of the base steel material of the tower. As shown, the actual and
existing design is deemed safe and adequate. However, for welds, it cannot be relied on 100% as most failures are
Page 123
due to workmanship. The thickness of the weld is assumed to be at its minimum acceptable value.
As shown from the data obtained through analyzing an existing design flexural and shear design of beams,
then compared with the actual loadings imposed by the tower, from pages. 26 – 30. The design of the beam is still
Based on the results, the structure is deemed SAFE, AND ADEQUATE to carry out the loads imposed
on it and would not post danger to the users of the building for its original intended purpose.