Alltrend 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

This rung implements a logic flip flop for manual operation of the vacuum roughing valve.

The roughing valve is operated manually by a single momentary push button.


Push the button and the rouging valve opens, push it again and the roughing valve closes.
B3/7 provides a single scan pulse to trigger the flip flop, which toggles the state of B3/8. The flip flop is reset if the vacuum pump is off or the backfill valve opens.
VACUUM PUMP CHAMBER FILL VACUUM ROUGH OSR Roughing Valve
MOTOR STARTER GAS VALVE VALVE BUTTON Roughing Valve Flip-Flop
1MR_VERIFY 2SOL 9PB Button Trigger
I:0 O:0 I:0 B3:0 B3:0
0000 OSR
4 3 10 6 7
1761-Micro 1761-Micro 1761-Micro

Roughing Valve Roughing Valve Roughing Valve


Flip-Flop Flip-Flop Manual On
Trigger Trigger From PB Flip Flop
B3:0 B3:0 B3:0

7 7 8

Roughing Valve Roughing Valve


Manual On Manual On
From PB Flip Flop From PB Flip Flop
B3:0 B3:0

8 8

The next three rungs show a different way, and in someways a simpler way, you could do a flip flop.
Each time the button is pressed the counter will increment by 1. The first bit in the counter accumulator will change state.
IE
0000 = 0
0001 = 1
0010 = 2
0011 = 3
0100 = 4
0101 = 5
By looking at only that bit you have something that changes state each tme the button is pressed. The counter preset can be zero, there is no need to reset the counter
except to reset the flip flop.
VACUUM ROUGH
VALVE BUTTON
9PB
I:0 CTU
0001 Count Up CU
10 Counter C5:3
1761-Micro Preset 0< DN
Accum 0<

PUMP
DOWN Roughing Valve
CYCLE Manual On
COUNTER From PB Flip Flop
C5:0.ACC B3:0
0002
0 8

VACUUM PUMP
MOTOR STARTER
1MR_VERIFY
I:0 C5:3
0003 RES
4
1761-Micro

CHAMBER FILL
GAS VALVE
2SOL
O:0

3
1761-Micro

0004 END