Factory Internal Test Report 28.08.2023

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

FACTORY INTERNAL TEST REPORT 28.08.

2023

Customer : M/s. PROVIDENCE GENERAL SERVICES, DOHA, QATAR.


Equipment : 11KV 630A 1POLE MOLI OUTDOOR SINGLE PANEL.
W.O.No : 224077
Quantity : 3 Nos
Serial No. : OLI230801, OLI230802, OLI230803.

Acceptance Actual
Tolerance Test Result

1. Dimensional check : Checked and found O.K


As per Approved drawing
Length : 1400 mm ±5mm 1400 mm
Breadth : 700 mm ±5mm 700 mm
Height : 1765 mm ±5mm 1765 mm

2. Bus Bar Size : Checked and Found O.K as per Approved Drawing.
Material : COPPER
Main Bus : 1RUN x 50 x 10 mm ±5mm 50 x 10 mm
Raiser : 1RUN x 50 x 10 mm ±5mm 50 x 10 mm
Earth Bus : 1RUN x 40 x 6 mm ±5mm 40 x 6 mm

3. OLI Closing Time : 2-3 Sec 2 Sec

4. OLI Open Time : 2-3 Sec 2 Sec

5. Painting : Checked and found O.K


As per Approved drawing (SIEMENS GREY)

6. Make of Components: Checked as per Approved BOM and Found O.K

7. Functional Tests : The functional tests are carried out.


Checked and Found O.K

a. Local mode - Isolator Mechanical / Electrical “ON/OFF” Operations Checked


b. Remote mode - Isolator Electrical “ON/OFF” Operations Checked
c. Isolator Mechanical / Electrical “ON/OFF” Indications Checked
d. Fuse Failure Indication, Relay Operation Checked
e. LS1 Limit Switch Failure Indication, Relay Operation Checked
f. LS2 Limit Switch Failure Indication, Relay Operation Checked
g. C1 Contactor Failure Indication, Relay Operation Checked
h. C2 Contactor Failure Indication, Relay Operation Checked
i. Safety Interlock Limit Switch Operation Checked at Manual Operation.

1
FACTORY INTERNAL TEST REPORT 28.08.2023

8. Isolator Aux. Contact NO / NC Operations Checked with “Isolator OFF” Condition.

Result
SL No TB No Ferrule No Contact
OLI230801 OLI230802 OLI230803
1 44,45 U41,U42 NC OK OK OK
2 46,47 U43,U44 NC OK OK OK
3 48,49 U45,U46 NC OK OK OK
4 50,51 U47,U48 NC OK OK OK
5 52,53 U49,U50 NO OK OK OK
6 54,55 U51,U52 NO OK OK OK
7 56,57 U53,U54 NO OK OK OK
8 58,59 U55,U56 NO OK OK OK

9. Contact Resistance Measurement test: Checked and found O.K


(Values are in Micro ohms.)

Measured Values Acceptance Tolerance Actual Test Result


SL No
(Micro Ohms) (Micro Ohms) (Micro Ohms)
OLI230801 58 55 – 70 58
OLI230802 60 55 – 70 60
OLI230803 61 55 – 70 61

10. Insulation Resistance Measurement test (5KV Megger used):

Acceptance Tolerance Actual Test Result


Phases Closed Condition
(M. Ohms) (M. Ohms)
5000- Above 10000
Before H.V Phase to Earth Above 10000 M. Ohms Above 10000 M. Ohms
M. Ohms
5000- Above 10000
After H.V Phase to Earth Above 10000 M. Ohms Above 10000 M. Ohms
M. Ohms

11. High Voltage Test:

Phases Applied voltage in KV Result


Phase to Earth 28 Withstood
Across the Isolator Distance 32 Withstood

WITNESSED BY: TESTED BY:

Mr. Kalev Lumiste Mr. Kaur Parna


Technical - Engineer Testing Engineer
M/s. Hamzavi Manufacturing, Estonia. M/s. Hamzavi Manufacturing, Estonia.