Professional Documents
Culture Documents
Vermes Technik - Micro Dispensing System MDS 3200A
Vermes Technik - Micro Dispensing System MDS 3200A
VTK-TS-MA-021 Revision 2
MANUAL MDS 3200A
Index
1. Introduction........................................................................................................................................ 3
1.1. Preamble....................................................................................................................................... 3
1.2. Product line MDS 3000 ................................................................................................................. 3
1.3. List of abbreviations ...................................................................................................................... 4
1.4. Safety Instructions ........................................................................................................................ 4
1.4.1. General................................................................................................................................... 4
1.4.2. Specified normal operation .................................................................................................... 4
1.4.3. Technical details..................................................................................................................... 5
1.4.4. Warning notices...................................................................................................................... 5
2. Mounting and implementation ......................................................................................................... 5
2.1. Scope of delivery .......................................................................................................................... 5
2.2. On-site Mounting of the MDS 3200A ............................................................................................ 5
2.3. Implementation and dispensing .................................................................................................... 5
2.4. Parameter Settings for the dispensing process............................................................................ 5
2.5. Starting the heating....................................................................................................................... 5
2.5.1. Introduction............................................................................................................................. 5
2.5.2. Safety instructions .................................................................................................................. 5
2.5.3. Function.................................................................................................................................. 5
2.5.4. Mounting................................................................................................................................. 5
2.5.5. Adjusting the theoretical heating value .................................................................................. 5
2.5.6. Adjust process........................................................................................................................ 5
2.5.7. Calibration .............................................................................................................................. 5
2.6. Shuting down the MicroDispensingSystem and exchange of single components ....................... 5
2.6.1. Change of the tappet.............................................................................................................. 5
2.6.2. MDT 301, Universal tool......................................................................................................... 5
3. Cleaning.............................................................................................................................................. 5
3.1. Cleaning methods ......................................................................................................................... 5
3.2. Compatibility of sealing material (material) with selected fluids ................................................... 5
4. MicroDispensingValve MDV 3200A ................................................................................................. 5
4.1. MDV modules ............................................................................................................................... 5
4.2. Technical data of the MDV ........................................................................................................... 5
4.3. Special features of the MicroDispensingValve ............................................................................. 5
4.3.1. Normally Open ....................................................................................................................... 5
4.3.2. Quick-Change Concept.......................................................................................................... 5
4.3.3. Modularity............................................................................................................................... 5
4.3.4. All installation positions possible............................................................................................ 5
4.3.5. Easy handling......................................................................................................................... 5
4.4. Materials applied........................................................................................................................... 5
5. MicroDispensingControl Unit MDC 3200A...................................................................................... 5
5.1. Description of the MDC module.................................................................................................... 5
5.2. Technical data of the MDC 3200A................................................................................................ 5
5.3. Control panel................................................................................................................................. 5
5.3.1. LCD display ............................................................................................................................ 5
5.3.2. Maintenance Indication .......................................................................................................... 5
5.3.3. Function keys ......................................................................................................................... 5
5.4. Operation ...................................................................................................................................... 5
5.4.1. Input of values ........................................................................................................................ 5
5.4.2. Error messages ...................................................................................................................... 5
5.4.3. Menu structure ....................................................................................................................... 5
5.5. Interfaces ...................................................................................................................................... 5
5.5.1. Serial Interface, Sub-D, 9-pin................................................................................................. 5
5.5.2. Using the Hyper Terminal ...................................................................................................... 5
5.5.3. PLC-Interface: Sub-D, 15-pin................................................................................................. 5
VTK-TS-MA-021 Revision 2
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2
MANUAL MDS 3200A
1. Introduction
1.1. Preamble
By buying a VERMES Technik MicroDispensingSystem of the MDS 3000 family you are provided with
a high-quality system manufactured with greatest care.
In this manual you will in general become acquainted with VERMES Technik ´s services and in detail
with the use of your system. We will show you, how easy and simple the start-up and use of your
MicroDispensingSystem is.
We kindly ask you to take a close look at this manual before you start operating your system. If there
are any questions about the use of the MicroDispensingSystem after having read the manual, please
get in touch with our customer service.
VERMES Technik
You get us all year round from Monday to Friday 8 a.m. to 5 p.m.
Tel: +49 8024 644-0/26
Fax: +49 8024 644-19
support@vermes.com
www.vermes.de
To cover a wide range of viscosity VERMES Technik developed three different types of valves which
can be used depending on the viscosity of the media.
• MDV 3010A: for low viscous fluids (water-like fluids)
• MDV 3020A: for medium viscous fluids (e. g. ink, honey-like fluids)
• MDV 3200A: for high viscous fluids (e. g. grease, pastes)
VTK-TS-MA-021 Revision 2 3
MANUAL MDS 3200A
1.4.1. General
• Please pay attention to the danger and safety data sheets of the liquids to be dispensed.
• Wear protective clothing, face protection, glasses and gloves when dispensing aggressive, reactive
or toxic fluids.
VTK-TS-MA-021 Revision 2 4
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 5
MANUAL MDS 3200A
• When using a heating device, the upper temperature limit of the fluidic feed line, which is pressure-
dependent, has to be observed.
• The heating of the MDS 3200A can not exceed 80°C. During heating, it is not possible, to apply
Delay values smaller than 7 ms (please refer for dispensing parameters to 5.4.1).
For connection of the heating please refer to Figure 13
• The MDV 3200A works after the normally-open-concept. Though without impressed voltage is the
valve open and fluid may leak out. To avoid this please reduce the supply pressure to ambient
pressure before shutting down the control unit.
VTK-TS-MA-021 Revision 2 6
MANUAL MDS 3200A
Figure 2 : MDV 3200A, Fluid box-CC (10mL), NAN fix, NI, control unit MDC 3200A, 3 x tools, sensor- and actuator cabel,
(not shown: power cord, manual)
VTK-TS-MA-021 Revision 2 7
MANUAL MDS 3200A
2x Thread M4
Thread depth 4mm
Distance to center 45mm
All parts which contact the MDV 3200A (screws, fixing plates etc.) should be made of stainless steel,
non-ferrous metals or galvanized steel. Contact with non-refined ordinary steel may cause so called
“external rust”.
The MicroDispensingControl Unit MDC 3200A is designed as an insert for a 19” plug-in module. It
may be fixed in a place, sufficiently ventilated as well as easy to reach from the rear and the front side
in a 19” rack with 4 front side screws. The connecting cables have to be thoroughly guided. All
connectors must be fixed tight. A possible interchanging of plugs and sockets is prevented by
corresponding coding.
The connection of the MDV 3200A to the MDC 3200A is done via the 4-pin plug and the 5-pin plug
on the upper bottom of the valve. The plugs are protected against mix-up by a corresponding coding.
The red dots on the socket and the plug have to point to each other when connecting. The cable
marked with a red tension relief supplies the power for the piezo stack from -30V to 120V (bipolar
operation. Via the second cable (yellow tension relief) the data of the sensor integrated in the valve is
transferred. Disconnection is done by pulling the riffled bush axially backwards (Attention: Never
disconnect the cables from the valve while the system is still dispensing, this will lead to a damage of
the valve and the control unit. If the system is not operating, you can disconnect the valve and the
control unit. When the control unit is switched on without valve, the display will show: “Valve not
present”).
Figure 4: Connection scheme of the valve MDV 3200A and the MicroDispensingControl Unit MDC 3200A
VTK-TS-MA-021 Revision 2 8
MANUAL MDS 3200A
Adjust-process:
• Press on the MDC 3200A. The display will show “Unscrew Nozzle Press Enter”. Unscrew the
nozzle unit from the fluid box (approx. 1-2 turns) and press .
• Screw in carefully the nozzle unit until the green LED lights up. Continue screwing in the nozzle unit
until approx. 1100 (red LED will light up!). After 30 sec unscrew the nozzle unit unit no LED lights up
(now must be a stable value between 995 und 998 in the display. If this is not the case, please carry
out the adjust-process one more time or switch off the controller respectively). Then screw in the
nozzle unit again between 1015 and 1040 (green LED).
VTK-TS-MA-021 Revision 2 9
MANUAL MDS 3200A
• Optional: For the removal of air in the system (e. g. after change of a cartridge) save your
dispensing parameter (5.4.1) and enter the following: Rising 0.5, Open Time 1.5, Falling 0.17, Delay 5-
30, Needle Lift 75 and Number of Pulses 500-2000. Dispense by pressing approx. 500-2000 jets.
Then go back to the initial parameters.
• To start the dispensing press (a burst starts according to the entered parameters) or use the
order: VALVE:OPEN.
The green LED on the display will lighten up on all correctly adjusted systems. If this is not lightened
up, please conduct the adjust-process again. If you shut down the system and alter nothing
mechanically, you don’t have to perform the adjust-process again when switching the system on. But
then the green LED will not lighten up.
The adjust-process can be performed while fluid is already in the system but special attention needs to
be paid for the leaking of the fluid. If the fluid contains particles, the adjust-process with fluid is not
possible. It has to be performed then without fluid.
In general: if the nozzle unit is screwed in too tight, the red LED will light up. It the nozzle unit is
screwed in too loose, no LED will be on. Between 1015 and 1040 is the correct position of the nozzle
unit.
VTK-TS-MA-021 Revision 2 10
MANUAL MDS 3200A
Stroke
valve is closed
valve is opened
Needle Lift
Rising
Raising Open Time Delay
Falling
time
If the open time is set to "external", the dispensing with the following
properties is started: for Rising, Falling, Delay, needle lift and
Number of Pulses are the values used which are set. The Open
Time, however, there has a maximum of 15ms. I.e. even if the signal
is not reset at logic 0, the valve closes after a maximum of 15ms.
Falling During this time the valve is closing and compressing the media in
the nozzle compression chamber. The time increment is 0.01 ms.
Delay This is the time between two dispense pulses. It is adjustable in 0.1
ms steps.
Please note: if a heating system is connected to the MDS 3200A, a
minimum Delay of 7 ms is given. Delay settings smaller than 7 ms
are not applicable in this case. The only way to apply values under 7
ms is, to run the heating system via an additional control unit.
Needle Lift This value corresponds to the stroke of the tappet. It is entered in
percent of the maximum stroke.
Table 2: Description of the Pulse-Parameters
After entering the dispensing parameters (5.4.1), you can start your dispensing process.
VTK-TS-MA-021 Revision 2 11
MANUAL MDS 3200A
2.5.3. Function
Technical data:
Dimensions Value Device / notice
Resistance All hydrous solvents Media , organic acid and base
Maximum heating array 80 °c
Dimensions (without cable) 57x 25 x 38 mm
Weight heating module (without ca.70 g
cable)
Supply Voltage 230 volt
Power consumption 18 watt
VTK-TS-MA-021 Revision 2 12
MANUAL MDS 3200A
The heating module is warmed up by a thermo device. The thermal transfer is going through the
2-dimensional connection to the nozzle adjustment and from there to the fluid (referring picture).
Valve
Heating module
Thermo device
2.5.4. Mounting
Step 1:
Plunge the heating module over the fluid box. The alignment is done by the nozzle adjustment
nut and the block-out of the heating module (picture 1).
Step 2:
Fix the locking screw. Notice: regard the green lamp of the adjust light. Maybe it is
recommended to readjust while pulling tight (picture 2).
picture1 nozzle heating plugged on the fluid box picture 2 position of the locking screw
Step 3:
Connect the Nozzle Heating and the Control Unit with the heater cable. Conntect the heater
cable to the thermo device socket 1 and the heating socket 1
VTK-TS-MA-021 Revision 2 13
MANUAL MDS 3200A
Heating socket 1
Heating socket 2
Step 4:
Connect the valve to the controller. Refer to chapter 2.2.
Heater 1
0 On / Off
to
80 °C
VTK-TS-MA-021 Revision 2 14
MANUAL MDS 3200A
The pictures are showing the Adjust of the nozzle adjustment nut.
2.5.7. Calibration
The following chapter shows the setting of the heating temperature calibration.
The calibration of the theoretical temperature values is needful to compensate irregular heating
temperatures between different control units.
However the heating is calibrated from start up delivery and anew calibration should be done only by
professional users in conversation with Vermes Technik.
The values set by the calibration are flashed in the storage of the MDC and are valid until a new
setting is done.
The adjustment values can be set in the submenu item “Calibration”.
To get access to the menu “Calibration” you need a pin code witch you can get from Vermes Technik.
The Menu “calibration” has three submenus:
“Direct Value Input” where you can set the values for “boiling point” and “ice point” directly.
“Value Measurement where you can collect the values with using a thermocouple.
“Value Verification” where you can control the settings by showing you the actual temperature.
Please note that before you do the calibration that the control unit has to be in a thermal steady state
condition. Therefore it is recommended that you run the MDC with connected heating system for 30
minutes before calibrate.
VTK-TS-MA-021 Revision 2 15
MANUAL MDS 3200A
VALUE MEASUREMENT:
To calibrate please press the ENTER button to reach the first menu area.
Use the arrow keys until you come to the menu item „Heating“.
If you are in the „Heater1“ menu, use the arrow keys until you get to the menu
item „Calibration H(eater)1“.
Please select the menu item „Calibration H(eater)1“ with pressing the ENTER
button.
Please select the service code by using the arrow keys and confirm with the
ENTER button.
Use the arrow keys until the menu item „Value Measurement“ is shown on the
display.
VTK-TS-MA-021 Revision 2 16
MANUAL MDS 3200A
Please be sure that the thermocouple (typeK) is connected and if not please wait
5 minutes after connecting. After that confirm the prompt „Put in a Type
KThermocouple!” by using the ENTER button.
Put the thermocouple into Icewater. The icewater should contain many little
broken ice pieces. Wait for 30seconds.
Then confirm the message „Put the Thermo(couple) into Icewater“.
After that putt the thermocouple into boiling water therefore it should not touch the
ground. The water should be boiling only a little to avoid steam bubbles cause of
the higher temperature. Wait for 30seconds and after that please confirm the
message “Put the Thermo(couple into boiling W(ater)” by pressing the ENTER
button.
If you have completed all points please safe the settings by confirm the shown
message „PRESS ENTER FOR SAVING DATA“ with the ENTER button.
If there occured any problems please leave the menu by using the ESC button
and make a new calibration.
VTK-TS-MA-021 Revision 2 17
MANUAL MDS 3200A
VALUE VERIFICATION:
This submenu shows the temperature value from the thermocouple which is connected with the MDC
The temperature value is cleared with the actual calibration data.
Therewith it is possible to estimate the correctnes of the calibration data. To get in the conformable
menu please do the same first Stepps as in Value Verifikation.
After typing in the service code please go to the menu “Calibration H1”.
After that use the arrow buttons to go to the menu item “Value Verification”.
Confirm the menu item „Value Verification with the ENTER button.
Confirm the menu item „Verify Values?“ with the ENTER button..
The actual temperature value is shown every time you press the ENTER button.
The now shown value is done according to the set Calibration Values and
therefore it indicates the correct values. A safe estimation could only be done by
measuring two known temperatures.
The temperature measurement can be left by pressing the ESC button..
Leave the menu by pressing the ESC button for several times.
After that use the arrow buttons to go to the menu item “Direct Val(ue) Inp(ut)”.
Confirm the menu item „Direct Val(ue) Inp(ut)” with the ENTER button.
VTK-TS-MA-021 Revision 2 18
MANUAL MDS 3200A
Confirm the menu item „Ice Point“ with the ENTER button.
Type in the correct value for the ice point by using the arrow keys and confirm with
ENTER.
Use the arrow keys (right/left) until the menu item „Boiling Point“ is shown and
confirm with ENTER.
Put in the known calibration temperature for the boiling point over the arrow keys
and confirm with the ENTER button.
Leave the menu by pressing the ESC button for several times.
VTK-TS-MA-021 Revision 2 19
MANUAL MDS 3200A
1 2 3
VTK-TS-MA-021 Revision 2 20
MANUAL MDS 3200A
A
Required parts for tappet change:
Art.nr./Art.no. Beschreibung/Description A
MDT310 Stößelwechselwerkzeug /
1008344
MDT310 Tappet changing tool A
*1008347 Stößel CT15 / Tappet CT15
*1010914 Stößel CT10 / Tappet CT10
*1010915 Stößel CT 7 / Tappet CT 7
1007067 Stößeldichtung GFD / Tappet sealing GFD A
For mounting the tappet protection it is necessary to remove the nozzle unit and the fluid box. To
protect the tappet (for example when sending back for maintenance or for storage uses) just screw the
tappet protection to the valve via the screw (1).
VTK-TS-MA-021 Revision 2 21
MANUAL MDS 3200A
Descripton:
Tool consisting of two parts screwed together.
“Adjustgrip": with the host for Nozzle adjusting nut.
"Sealmounter": with pin to push the tappet seal.
Purpose:
Application:
VTK-TS-MA-021 Revision 2 22
MANUAL MDS 3200A
• Push the tappet sealing in the borehole on the underside of the fluid
box until it is firmly seated.
• To press in the preformed tappet sealing correctly, put the tappet sealing on the pin side
of the Sealmounter.
• For the remounting of the sealing screw the tool apart and use the other
side (screw thread side).
• Face the tappet sealing from below out of the fluid box.
VTK-TS-MA-021 Revision 2 23
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 24
MANUAL MDS 3200A
3. Cleaning
Common details
Never use wire brushes or machines that cause a surface abrasion. Unsuitable cleaning fluids may
damage the valve.
Before using extremely aggressive cleaning liquids or solvents please check, that all fluid contacting
parts are resistant to them.
Table 3: CleaningToolKit.
For pre-cleaning purposes, please remove the dispensing fluid, connect the MicroDispensingSystem
to an empty and clean cartridge and push the residues of dispensing fluid with pressurized air through
the system.
The cleaning of the MicroDispensingValve can be carried out via:
• Rinsing with an appropriate cleaning media
To remove residues of the dispensed fluid, please rinse the system with an appropriate cleaning
media (please refer to the material safety data sheet of the dispensed media and suitable cleaning
suggestions). For this, equip the MicroDispensingSystem with a cartridge filled with an appropriate
cleaning solution and execute some free jetting (F1) and dispensing cycles.
• Cleaning of the single parts
Please demount the system carefully according 2.2 If necessary, you can wipe off the actuator with a
cloth which is damped with isopropanol (IPA).
The single parts can be pre-cleaned by pushing pressurized air through them. Rinse them with
isopropanol and place the parts into a large enough beaker. Fill sufficient isopropanol into the beaker
and place it for 10 minutes in an ultrasonic bath. Following this strategy, leads in general to a sufficient
cleaning of the single parts. Now you can dry them on air or with compressed air and reassemble
them again.
If the single components are heavily polluted, you have to pre-clean the components mechanically
(this procedure is also advised for not so heavily polluted components). For this pre-cleaning, please
use our Cleaning Tool Kit. Please refer to the pictures below regarding which part to clean with which
device. This procedure should be followed by cleaning the single parts in isopropanol in an ultrasonic
bath. NI’s can be cleaned and pierced through with special NI wires (Attention: pay attention to the
diameter of the nozzle insert and the NI wire!).
VTK-TS-MA-021 Revision 2 25
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 26
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 27
MANUAL MDS 3200A
1
3
2
4
1
Electronic module contains the electronics for sensor and actuator signals. On top of the
electronics module body you will find the plugs for actuator and sensor cable; these will be
connected to the control unit.
The actuator system is the heart of the MicroDispensingValves. It contains the sensor the piezo
actuator and the mechanics for the tappet drive. The housing and the mechanics are
encapsulated to avoid contamination and intrusion of humidity.
Fluidic module (in short: fluid box) is separated thermally from the actuator system and easily to
demount by loosening two screws. This allows a stand-alone cleaning procedure.
The Nozzle Unit can be easily changed and cleaned according to the approved VERMES
Technik “Quick Change” technology. So you are able to go into new dispense tasks fast. The
nozzle insert is a consumable you can easily change by yourself.
VTK-TS-MA-021 Revision 2 28
MANUAL MDS 3200A
4.3.3. Modularity
All MicroDispensingSystems are built strictly modular. Single components can be exchanged fast. So
time and costs for repair can be remarkably reduced.
VTK-TS-MA-021 Revision 2 29
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 30
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 31
MANUAL MDS 3200A
maintenance interval for the tappet, press on the control panel. By pressing , you can see the
state of maintenance interval for the nozzle.
VTK-TS-MA-021 Revision 2 32
MANUAL MDS 3200A
Both maintenance intervals need to be set by the customer, for this, please refer to Figure 12. For
resetting the values, please choose “Reset Nozzle” and “Reset Tappet” respectively.
Both functionalities are set to infinite at VERMES Technik at the point of delivery.
VTK-TS-MA-021 Revision 2 33
MANUAL MDS 3200A
• Pressing this button, you reach the memory menu. The current
dispense parameter settings can be saved here.
• 10 settings may be saved.
• Each memory cell contains the specific values of the pulse
parameters and settings for heating and keylock.
• Pressing this button, you approve your menu selection and change
to the particular sub-menu.
... or ...
• Pressing this button, you confirm your input and at the same time
change to the next superior menu.
• Pressing this button, you cancel your input or action und at the
same time reach the next superior menu.
... or ...
• Pressing this button, you reach the next superior menu.
• Pressing this button, you reach the next superior menu level.
... or ...
• Pressing this button, you raise a numeric figure.
VTK-TS-MA-021 Revision 2 34
MANUAL MDS 3200A
• Pressing this button, the valve is opened. The current values for
raising and falling are retained. The valve stays open as long as
the button is pressed. The valve will close any way after
approximately 2 minutes to avoid causing damage to the actuator.
• Will be configured
5.4. Operation
5.4.1. Input of values
Numeric inputs are continuously processed according to the same scheme:
The definition of the input is shown in the upper LCD line. The current value to be changed is
shown in the lower LCD line. The “one”-column is blinking, it is active and can be changed.
• Arrow right or Arrow left cause a change of the adjusted value (for example on
becomes off and vice versa).
The input process is completed by . The active value is selected and the menu will return to
the next higher menu item.
Deleting your input without selection of a value is done with . A return to the next higher
menu item will happen, too.
VTK-TS-MA-021 Revision 2 35
MANUAL MDS 3200A
If the error message 11 BAD DATA occurs an invalid value was found in the memory of the
system. In order to prevent failures all memory elements are set to their default value. Stored
data will be overwritten during this process.
VTK-TS-MA-021 Revision 2 36
MANUAL MDS 3200A
Heating
Heater 1
0 On / Off
to
80 °C
VTK-TS-MA-021 Revision 2 37
MANUAL MDS 3200A
Heating
Heater 1
0 On / Off
to
80 °C
VTK-TS-MA-021 Revision 2 38
MANUAL MDS 3200A
5.5. Interfaces
power switch no function yet
electric supply
Attention!!!
Be sure to mount the connectors proper (screw tightly!) to the control unit, otherwise
malfunctions may appear.
You can connect the optional heating via heating socket 1 and thermal element socket 1.
VTK-TS-MA-021 Revision 2 39
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 40
MANUAL MDS 3200A
Now create a new name for the connection and choose any symbol.
Confirm with OK
Please select now the type of the connection between PC and MDC. (in most cases COM1) and
confirm with OK..
VTK-TS-MA-021 Revision 2 41
MANUAL MDS 3200A
Now a new window opens where you can select the properties of the connection.
To confirm the selected settings please confirm with APPLY and the press OK.
VTK-TS-MA-021 Revision 2 42
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 43
MANUAL MDS 3200A
For testing the connection you can type in the command *idn?.
Now the reply should be the actual software no. and the type of the system.
For example:
ENTRY: *idn?
Enter:
RESPONSE: HV.701.4XX.XXX
VTK-TS-MA-021 Revision 2 44
MANUAL MDS 3200A
1. using the key panel: After pressing the key , a trigger pulse with the pre-set values starts.
2. using EIA-232: You can also initiate the trigger pulse with the command VALVE:OPEN.
3. using a PLC signal with predefined Open Time: through this signal a dispensing impulse is initiated
which follows the preset parameters. The maximum frequency is 200 1 / s.
4. using a PLC signal and the External-Control-Mode: If the Open Time is set to “external“ a
dispensing impulse with the following properties is started. For Raising, Falling, Delay, Needle Lift and
Number of Pulses the preset values will be considered. The Open Time lasts as long as the signal is
set to logic 1. If the signal is reset to logic 0 then the valve closes and the next impulse will be
accepted
VTK-TS-MA-021 Revision 2 45
MANUAL MDS 3200A
VTK-TS-MA-021 Revision 2 46
MANUAL MDS 3200A
2. *IDN?
Description: Returns the device descriptor; the description format:
company, model, software version
Example:
Input: *IDN?
Result: VERMES, MDV30xx, 065.411.001
Return: VERMES, MDV30xx, 065.411.001
3. ADJUST:?
Description: If you want to recall the adjust-status, use this command. The following
situations may appear:
Status unknown (showing 0): The system does not know the status yet.
This should be the exception. If this happens, try a new adjust or turn the
MicroDispensingControl Unit off and on again.
Nozzle too far down (showing 1): Nozzle is extended too far and has to
be screwed in. Arrange a new adjust.
Nozzle in the middle (showing 2): The nozzle is in the ideal position.
Nozzle too far up (showing 3): Nozzle is not extended enough and has to
be screwed out. Arrange a new adjust.
Example:
Input: ADJUST:?
Result: The system tells you, if the nozzle is in the correct position.
Return: 2
… the nozzle is in the right place.
4. ADJUST:START
Description: The adjust process is started with this command. The purpose is to bring
the nozzle into the ideal position.
Example:
Input: ADJUST:START
Result: The adjust process is started.
Return: OK
5. EEPROM:CONF:RECALL:<memory cell>
Description: Herewith a saved valve configuration is recalled. This contains the
following parameters amongst others:
Raising, Open Time, Falling, Delay, Needle Lift, Number of Pulses,
Setpoint of heating, heating switch (on/off), keylock switch (on/off), Cal.
Piezo value.
VTK-TS-MA-021 Revision 2 47
MANUAL MDS 3200A
Example:
Input: EEPROM:CONF:RECALL:1
Result: The parameters of memory cell 1 are loaded down.
Return: OK
6. EEPROM:CONF:SAVE:<memory cell>
Description: Herewith the current pulse parameters are saved in 10 available cells.
The following pulse parameters are stored amongst others:
Rising, Open Time, Falling, Delay, Needle Lift, Number of Pulses,
Setpoint of heating, heating switch (on/off), keylock switch (on/off), Cal.
Piezo value.
Example:
Input: EEPROM:CONF:SAVE:1
Result: The current pulse parameters are saved on memory cell
number 1.
Return: OK
7. HEATER:1:OFF
Description: This command de-activates the heating connected to socket 1. This
could be either a fluid box or a nozzle heating.
Example:
Input: HEATER:1:OFF
Result: The connected heating is turned off.
Return: OK
8. HEATER:1:ON
Description: This command activates the heating connected to socket 1. This could be
either a fluid box or a nozzle heating.
Example:
Input: HEATER:1:ON
Result: The connected heating is turned on.
Return: OK
9. KEY:ENTER
Description: This command sends an enter signal to the control unit. The signal is
10. KEY:ESCAPE
Description: This command sends an escape signal to the control unit. The signal is
11. LCD?
Description: Use this command to show the current text of the LCD signal.
Example:
Input: LCD?
Result: Right after turning on the system, our company name is
shown.
Return: VERMES Technik
VTK-TS-MA-021 Revision 2 48
MANUAL MDS 3200A
12. SYSTEM:KLOCK:OFF
Description: This command unlocks the key panel.
Example:
Input: SYSTEM:KLOCK:OFF
Result: The key panel is unlocked.
Return: OK
13. SYSTEM:KLOCK:ON
Description: This command locks the key panel so no one can change the pulse
parameters unauthorized.
Example:
Input: SYSTEM:KLOCK:ON
Result: The key panel is locked.
Return: OK
14. TEMP:?
Description: This command makes a query for the current temperature, shown in
degree Celsius (°C).
Example:
Input: TEMP:?
Result: 70
… this equals 70 °C.
Return: 70
16. TRIGGER:SET:?
Description: The current pulse parameters will be displayed with this command. They
come in this order:
Rising, Open Time, Falling, Needle Lift, Number of Pulses, Delay
All parameters relating to time, except „Falling“, are still shown as 1 / 10
ms (so 10 equals to 1 msec). The „Falling“ is shown as 1/100 ms (so
100 equals to 1,00 msec)
If the system is set to External-Control-Mode the Open Time will be
displayed as “EXTERNAL”.
Example:
Input: TRIGGER:SET:?
Result: You see the current pulse parameters.
Rising: 10 equals 1.0 ms (ms = millisecond)
Open time: 10 equals 1.0 ms
Falling: 15 equals 0.15 ms
Needle lift: 90 %
Number of pulses: 20
Delay: 8 equals 0.8 ms
Return: 10,10,15,90,20,8
VTK-TS-MA-021 Revision 2 49
MANUAL MDS 3200A
18. VALVE:OPEN
Description: This command initiates a dispense series with the current parameters.
Example:
Input: VALVE:OPEN
Result: Assuming the parameters:
Rising: 10 equals 1.0 ms (ms = millisecond)
OpenTime: 10 equals 1.0 ms
Falling: 15 equals 0.15 ms
Needle Lift: 90 %
Number of Pulses: 20
Delay: 8 equals 0.8 ms
The command starts a dispense series with this
parameters.
Return: OK
VTK-TS-MA-021 Revision 2 50
MANUAL MDS 3200A
Example:
Input: VALVE:OPEN: 10,10,15,90,20,8
Result: A dispense series with the following parameters is initiated:
Rising: 10 equals 1.0 ms (ms = millisecond)
OpenTime: 10 equals 1.0 ms
Falling: 15 equals 0.15 ms
Needle Lift: 90 %
Number of Pulses: 20
Delay: 8 equals 0.8 ms
Return: OK
20. VALVE:UP
Description: This command opens the valve until the command VALVE:DOWN is
send. The maximum open time is about two minutes. Within this time
only the command VALVE:DOWN can be processed. This ensures the
protection of the valve.
Example:
Input: VALVE:UP
Result: The valve is opened.
Return: OK
21. VALVE:DOWN
Description: This command closes the valve after the command VALVE:UP. If you
did not use VALVE:UP before, VALVE:DOWN does not achieve a result.
Example:
Input: VALVE:DOWN
Result: The valve will be closed.
Return: OK
22. WRITE:LCD:<text>
Description: This command writes a 32 characters ASCII text on the LCD-display.
Example:
Input: WRITE:LCD:Hello World
Result: the LCD-display shows: …
Hello World
Return: OK
23. SYSTEM:SHOW:CYCLES
Description: This command reads the value of the cycle counter.
Example:
Input: SYSTEM:SHOW:CYCLES
Result: actual value of the cycle counter in a string
Return: 1235000
24. SYSTEM:SHOW:VALVEID
Description: This command reads the valve ID.
Example:
Input: SYSTEM:SHOW:VALVEID
Result: actual ID of the connected valve
Return: 11CW36
25. SYSTEM:SHOW:CONTROLLERID
Description: This command reads the controller ID.
Example:
Input: SYSTEM:SHOW:CONTROLLER
Result: actual ID of the controller
Return: 3050
VTK-TS-MA-021 Revision 2 51
MANUAL MDS 3200A
26. *OPC?
Description: Monitoring the last trigger impulses.
Example:
Input: *OPC?
Result: Number of the last trigger impulses as string, counter reset
to zero
Return: 3264
27. TAPPET:SET:?
Description: This command writes the tappet maintenance cycle.
Example:
Input: TAPPET:SET:500000
Result: actual tappet cycle set to 500000 cycles
Return: OK
28. TAPPET:CLEAR
Description: This command resets the tappet maintenance cycle indicator.
Example:
Input: TAPPET:CLEAR
Result: Set tappet cycle indicator to 0
Return: OK
29. NOZZLE:SET:?
Description: This command writes the nozzle maintenance cycle.
Example:
Input: NOZZLE:SET:500000
Result: actual nozzle cycle set to 500000 cycles
Return: OK
30. NOZZLE:CLEAR
Description: This command resets the nozzle maintenance cycle indicator.
Example:
Input: NOZZLE:CLEAR
Result: Set nozzle cycle indicator to 0
Return: OK
31. SYSTEM:SHOW:AKTORTEMP
Description: This command shows the actual temperature of the actuator.
Example:
Input: SYSTEM:SHOW:AKTORTEMP
Result: Temperature of the actuator in °C.
Return: 80
(All commands can be tested for example with “Hyper Terminal”, which you find at Windows XP under
Programs/Accessories/Communication).
VTK-TS-MA-021 Revision 2 52
MANUAL MDS 3200A
6. Spare parts
Fluid box connector (art.no.: 1007059) Cartridge connector MDX 3080-CC (art.no.: 3
mL: 1009776; 10 mL: 1009480; 30 mL:
1009724)
Fluid box standard MDF 3070 Fluid box hollow screw consits Fluid box MDF 3070-CC
art.no. 1007042 of MDF 3070, cartridge base integrated cartridge connector
(art.no. 1009150), art.no.: 1009470
(incl. Tappet centering piece
and tappet sealing GFD) hollow screw (art.no.: (incl. Tappet centering piece
1008551), and tappet sealing GFD,
Set of sealing hollow screw cartridge base PEEK, tighting
(art.no.: 1007065, NBR) screw and Luer-Lock fluid box
connector))
Luer-Lock Fluid box connector Tappet sealing GFD Tappet centering piece
art.no.: 1007060 art.no.: 1007067 art.no.: 1009419
VTK-FE-UM-25 Revision 2 53
MANUAL MDS 3200A
Nozzle adjustment nut Nozzle adjustment nut needle Nozzle adjustment nut fix
universal protection art.no.: 1010549
art.no.: 1009012 art.no.: 1009451
tappet MDV3100A CTK CleaningToolKit MDF 3070, Fluid box UNF1/4“-
art.no.: 1008347 art.no.: 1010320 28
art.no.: 1010047
Nozzle insert hard metal Cartridge O-ring-sealing N (for tappet
N11-70: 1010343 3 mL: 1007091 guidance)
N11-100: 1009837 10 mL: 1008361 NBR: 1007063
N11-120: 1010344 30 mL: 1007087 EPDM: 1007064
N11-150: 1009838 Viton: 1008762
N11-200: 1009839 Silicon: 1010037
VTK-FE-UM-25 Revision 2 54
MANUAL MDS 3200A
VTK-FE-UM-25 Revision 2 55
MANUAL MDS 3200A
7.2. Return
Each MicroDispensingSystem which has been in contact with toxic chemicals, human body liquids or
other harmful materials has to be decontaminated before being returned to VERMES Technik.
This declaration is absolutely necessary even for unused MicroDispensingSystems. In case the
MicroDispensingSystem was used, the liquids, which were in contact with the valve, need to be
communicated in written form in the decontamination declaration to VERMES Technik. The signed
certificate needs to be fixed outside on the transport packing.
If a rented or lended MicroDispensingSystem is returned uncleaned it will be sent back to the
customer. The rent period is automatically extended until the system arrives properly cleaned at
VERMES Technik. The additional rent time will be charged to the customer. Alternatively VERMES
Technik will assign an external company to clean and decontaminate the MicroDispensingSystem.
The customer will bear the costs.
Any unclean MicroDispensingSystems which are returned for maintenance or repair reasons will also
be sent back to the customer on his costs.
In any case the customer is liable for defects caused by insufficient decontamination. This includes
explicitly damage to persons and property.
Each returned system needs to be accompanied by a “status-sheet”. All information about the system
has to be provided by the customer to VERMES Technik (e. g. system returned for maintenance, for
repair, dispensing parameter, a.s.o.).
VTK-FE-UM-25 Revision 2 56
MANUAL MDS 3200A
A
MANUAL MDS 3200A