EL-SOUB EL-ZERAYAA 220/22/22KV

To MV-page 2
LEGEND : DESCRIPTION

Color Laser Primary Fibre Optic SMART


RINGS LAN
SOE Printer GTW GTW Secondary
printer Modbus RS485 Serial link
NECC/ RCC NECC/ RCC Fx Ethernet FO Link
Tx Ethernet RJ45 Link
Busbar Fiber Optic
OUT of scope of supply

Bay

24" 24'’ 24" 24'’ 24'’

GPS clock

GTW 1 GTW 2
65" SERVER 2 OWS2 Common Common
SERVER 1 OWS1 EWS

Modbus RS485
Modbus RS485

Modbus RS485
Modbus RS485
services-1 services-2
BCU BCU

Main SW-2
From 11&33KV Metering From 11&33KV Metering
Up to 2kms per link / /
0.5KM between SW’s

Up to 2kms per link


Main SW-1

FULL PRP ARCHITECTURE – IEC61850

SYMBOL Description

220KV Feeder BCU 220/22/22KV 220KV TR x2


220KV B.C Bay control Units C264 – 80TE size
TR.220KVside-BCU
BCUx2 (AVR) Automatic Voltage Regulator-Third Party provider

Line Dist-M1 GE Reason RT430 GPS Clock to Synchronize SCS


TR.Diff-M1
P443 O.C & FM GE type – Out of GE scope of supply (T hird party provider)

EF P643 Managed switches Reason type S2024G

P141 To TR220KV BCU


T60 Modbus RS485
Px4x Protection relays 80TE Size

Line Dist-M2 GE/D60


TR. Diff-M2 Px4x Protection relays 60TE Size

Px4x Protection relays 40TE Size


B.B-P.U-1
M233-Measurement Unit (Busbar)
B.B-P.U
P743 220KV Line feeder x4
Metering device (WH , VARH)-Third party provider

P743 Line Differential Protection M2- GE/L90 & Load limiter F60

To central B.B-P.U-2
Busbar P741"220KV” Diff-M2 : Transformer Differntial Protection M2 - GE/T60

P743 REF-2 P141 Laser Graphical Printer

To central Dot Matrix Printer


Busbar P741"220KV”
Ethernet Switch Reason Type H49
To 220KV UGC
BCU Industrial PC “Advantech” for GTW , EWS & OWS
NEF P141 Modbus RS485
L.V-1
EGYPTIAN ELECTRICITY TRANSMISSION COMPANY (EETC)
MV 22KV feeders x 32
Syn NEF
P141
L.V-2 220/22/22KV
P143 EL-Soub AL-Zerayaa
220KV BUS-COUPLER X 1 Substation Automation System Preliminary Architecture
To Common Modbus RS485
220KV BB B.B-PU BCU
PROTECTION
P743 220,22KV METERING
220KV To central
B.B-C.U Busbar P741"220KV”

P741 AVR WHY


DATE

From peripherical units


220KV LINE FEEDER BAYS X 4 P743 in 220KV LAN 220/22KV TRANSFORMER BAYS X 2 A
8/05/20 19

13/03/20 19
Due to op timizatio n the cost

FI RST ISSUE
WYA

WYA
WYA

A2

1/2 2 B
EL-SOUB EL-ZERAYAA 220/22/22KV LEGEND : DESCRIPTION
Primary
Secondary
Fibre Optic SMART
RINGS LAN
From M.S-2 / From M.S-1 / Modbus RS485 Serial link
Fx Ethernet FO Link
page 1 page 1 Tx Ethernet RJ45 Link
Busbar Fiber Optic
OUT of scope of supply

Bay

MV 22KV

**REDUNDANT RSTP ARCHITECTURE – IEC61850


SYMBOL Description

Bay control Units C264 – 80TE size

(AVR) Automatic Voltage Regulator-Third Party provider

GE Reason RT430 GPS Clock to Synchronize SCS

FM GE type – Out of GE scope of supply (T hird party provider)

32X FEEDER MANAGER Managed switches Reason type S2024G

Px4x Protection relays 80TE Size

INCLUDED LOAD SHEDDING Px4x Protection relays 60TE Size

Px4x Protection relays 40TE Size

M233-Measurement Unit (Busbar)

Metering device (WH , VARH)-Third party provider

Line Differential Protection M2- GE/L90 & Load limiter F60

Diff-M2 : Transformer Differntial Protection M2 - GE/T60

Laser Graphical Printer

Dot Matrix Printer

Ethernet Switch Reason Type H49

Industrial PC “Advantech” for GTW , EWS & OWS

**REDUNDANT RSTP ARCHITECTURE – IEC61850 EGYPTIAN ELECTRICITY TRANSMISSION COMPANY (EETC)

220/22/22KV
EL-Soub AL-Zerayaa
**Note-1: Please note that , the max No. IED’s per each “RSTP” LAN - Shall not be exceeded than: 40 IED’s Substation Automation System Preliminary Architecture

**Note2: MV FM type shall be included for IEC61850 , and also combined for RSTP communication protocol

DATE
WHY

8/05/20 19 Due to op timizatio n the cost WYA WYA

A 13/03/20 19 FI RST ISSUE WYA A2

2/2 2 B