Mics Modys ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
MANUAL AND AUTO START CONTROL MODULE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
FEATURES EMC Generic Emission Standard for
the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
SDMO Mics Modis controller can be When the module detects any of Safety of Information Technology Equipment,
including Electrical Business Equipment
user-configured for Auto or Manual the above faults it will automatically
Start operation using the genset shut down the engine. TEMPERATURE
BS EN 60068-2-1 o
Ab/Ae Cold Test -30 C
Alternatively the controller can be The module also has the capability BS EN 60068-2-2 o
ordered pre-configured. The to monitor battery charging by Bb/Be Dry Heat +70 C
Mics Modys offers an excellent utilising the WL terminal on the VIBRATION
range of engine monitoring and charge alternator. On detecting a BS EN 60068-2-6
protection features. battery charging fault, it will light Ten sweeps in each of three
major axes
the warning LED on the front panel. 5 Hz to 8 Hz @ +/-7.5 mm,
The module offers inputs to monitor 8 Hz to 500 Hz @ 2 gn
low oil pressure, high engine The Auto Start version can be HUMIDITY
temperature and overspeed and user-configured for Manual Start BS EN 60068-2-30
o
the manual start version also has a operation and the Manual Start Db Damp Heat Cyclic 20/55 C
@ 95% RH 48 Hours
user-defined auxiliary input. Auto version can be user-configured for
BS EN 60068-2-78
Start versions also include an input Auto Start operation. o
Cab Damp Heat Static 40 C
option for a start signal from a @ 93% RH 48 Hours
remote location. SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
sdmo Mics Modys DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous

CRANKING DROPOUTS
FEATURES
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is
achieved without the need for internal
batteries.

MANUAL AND AUTO MAXIMUM OPERATING CURRENT


26 mA at 12 V, 27 mA at 24 V

START CONTROL MAXIMUM STANDBY CURRENT


20 mA at 12 V, 21 mA at 24 V

MODULE CHARGE/FAIL EXCITATION RANGE


0 V to 35 V

OUTPUTS
START
Solid state 1.2 A negative grounding
terminal
KEY FEATURES KEY BENEFITS
RUN
• Configurable Auto and Manual
Solid state 1.2 A negative grounding
• Mics Modys comes Start versionspre- terminal
configured for frequency
AIR FLAP
• Remote start input available (speed fensing) Solid state 1.2 A negative grounding
but can be user-(when in Auto Start mode) configured terminal
for magnetic pick-up. GENERATOR
• Auxiliary shutdown input available VOLTAGE RANGE
15 V - 333 V AC (L-N)
• Uses DSE 813 USB
FREQUENCY RANGE
3.5 Hz to 75 Hz

DIMENSIONS
OVERALL
72 mm x 72 mm x 38 mm
2.8” x 2.8” x 1.5”
Excludes key switch

PANEL CUT-OUT
68 mm x 68 mm
2.7” x 2.7”

MAXIMUM PANEL THICKNESS


8 mm
0.3”