Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

2011The International Conference on Advanced Power System Automation and Protection

Strategy of Research and Application for the Microgrid Coordinated


Control
PAN Yuan*, LI PeiQiang, LI XinRan, LEI Bo& XU ZhenHua
College of Electrical and Information EngineeringˈHunan UniversityˈChangsha 410082;

Abstract: By studying the dynamic characteristics and the controllable quasi-load external characteristics of microgrid with
multiple distributed power supply, firstly, this paper proposes a PQ Control Strategy Inverter System based on a control of both
power and electrical current in order to improve the quality of electrical energy and increase the output of distributed power
supply. Secondly, based on the analysis of the characteristics of microgrid’s internal balanced load flow, it designs an outer ring
controller based on improving the sagging shape and solves the problem of controlling the frequency under island model in
microgrid. And then, it puts forward a coordinated control strategy of the microgrid which combined master-slave control
strategy and peer-to-peer control strategy between various types of distributed power supply without data correspondence.
With the coordinated control, the improvement in the availability of intermitted energy resource which cause distributed power
supply to join in the frequency adjustment of the microgrid is derived. At last the correctness and validity of this coordinated
control strategy is verified by converting the microgrid between the island model and grid-connected mode, this paper imitat-
ing and emulating of the varying characters with voltage and frequency under the transient operation of the island model.

Keywords: microgrid, distributed generation, coordinated control strategies, islanded operation, frequency control

1 Introduction state and isolated network state [3]. In network connection


state, microgrid absorbs or injects energy to the main grid.
Accompanied with the national economic growth, power When fault occurs in the grid, microgrid separates from the
load has witnessed a skyrocketing burst. At the beginning of main grid and turns into isolated network state which re-
summer in 2011, series factors like prices of coal and elec- quires the control and coordination of micro generations and
tricity being reversed have forced some provinces to switch energy storage devices to make its operation sustainable.
off to limit the supply of electricity. The shortage of energy The small-capacity and low-voltage microgrid consisted
has gradually become the bottleneck of economic develop- of DGs and energy storage devices not only meets the need
ment. Distributed generation (DG) was put forward against of power in high quality from customers but also operates
the conception of concentrated generation (CG). In order to independently and serves as a powerful support to the grid
solve the current problem that CG brought about, the injec- when large scale of fault occur. Besides, this environmental
tion of renewable generation into grid has found a break- friendly microgrid has taken full advantage of new energy
through. DG can be built in the center of load or rural coun- generation and reduced carbon emission effectively.
tryside which can remarkably improve the utilization effi- The actual problem yet to be solved by Microgrid is how
ciency of clean energy. However, after injection into the to realize the coordinating control. When load and network
system, DG gained characteristics of quasi-load. IEEE1547 structure change, how is to secure the safe, stable,
has set rules of the DG network connection standard which high-efficient and economic operation of microgrid under
requires operation withdrawal of each micro generation different operation modes by effective coordinating control
when system fault occurs. This has greatly limited of the of each elements. Paper [4–5] has theoretically studied the
full play of distributed energy efficiency and failed to meet control of microgrid and elaborated the mutual transforma-
the need of current grid operation [1]. For the sake of coor- tion process of network connection state and isolated net-
dinating the conflicts between the grid and DGs, fully ex- work state in microgrid. Paper [6] has established composite
ploiting the potential of distributed energy and prompting generation system of the multiple-micro generation of
larger scale of integration and application of DG technology, wind-illumination-diesel-storage which offered a possible
many scholars have strongly advocated the notion of mi- direction for microgrid study. Paper [7] has discussed the
crogrid [2]. Microgrid has made the large scope of DG net- control and relevant technical range of microgrid. Paper [8]
work connection possible. It operates at network connection has studied the structure of microgrid and constructed a
complete microgrid platform in Matlab/simulink to simulate
APAP2011 www.apap2011.org
*Corresponding author (email: panyuan268@vip.qq.com)
___________________________________
978-1-4244-9621-1/11/$26.00 ©2011 IEEE

Authorized licensed use limited to: PES University Bengaluru. Downloaded on August 30,2023 at 02:46:01 UTC from IEEE Xplore. Restrictions apply.
2011The International Conference on Advanced Power System Automation and Protection

the condition of transient state and steady state of microgrid 3 Design of DG inversion system and its con-
in network connection model and isolated network model. troller
Based on the structure and general control strategy of mi-
crogrid, for the dispersion characteristics of DG and load,
this paper has designed control modes corresponding to 3.1 Design of DG inversion system with PQ control
different operation modes, studied the structure of DG in-
verter and the design of its inversion system, constructed a The control block of network connection inverter with PQ
inversion with PQ control [9], designed a improved an- control is shown in Figure 2. It made up of two control
ti-droop controller and then put forward a microgrid coor- loops: external power control loop and internal current con-
dinating control strategy that combination of master slave trol loop. PQ control can realize decoupling control of ac-
control and equivalent control is applied between different tive power and reactive power and acquire frequency sup-
types of DGs and data communication loop is not needed. port from the system by phase-locked loop technology.
As for the synchronous problem of microgrid and distribu-
tion network in the reconnection of microgrid, synchronous iId.ref uId.ref
Ppcc.ref
control strategy was put forward. And in Matlab/simulink Qpcc.ref
iIq.ref uIq.ref
environment, the steady-state and transient-state process of upcc.d iId
the switch of the two operation modes of microgrid was Ppcc Q upcc.q
pcc iIq iI.abc
upcc.abc
simulated and the validity of strategy was testified [10–11].
ipcc.abc

2 Structure of microgrid Figure 2 PQ control system block diagram

The basic structure of the microgrid mentioned in this paper


is shown in Figure 1. Multiple-generation and energy sto- 3.1.1 Design of power control loop with PQ control
rage elements are contained in the microgrid, those DGs and The output power of inversion system in steady state is
energy storage elements combined to supply electricity to asorbed by equivalent current source. Therefore, objective
the load. The distribution network viewed the entire micro- of corresponding power control of the inverter can be
grid as a whole which connected it through PCC. The mi- acomplished only by current regulation of voltage source
crogrid in this paper is consisted of two micro generations inverter. Generally, according to different condition, instan-
and their corresponding load. Then, it was connected to the taneous power method and average power method are cho-
low-voltage distribution network by relevant electric ele- sen for regulation. Concerning the application of instanta-
ments. Assuming that all the micro generations are DC neous power may lead to the impact on power quality when
source or rectified DC source and all the micro generations grid suffers disturbance, this paper has adopted the average
have been turned into three-phase AC by SPWM inverter. power method for control.
Adding LC filters aims to eliminate those high-order current In rotating frame, the power calculation of average power
harmonics around the frequency of controller switch. Sensi- control can be shown as:
tive load 1 has adopted DG1 with V/F control to secure re- P u d id  uq iq , Q u d iq  u q id (1)
liability of power supply and interruptible load 2 has In the power regulation shown in Figure 3, adjusting PI
adopted DG2 with P/Q control for power supply to secure according to the difference of P, Q and Pref, Qref to produce
economy and random cutoff. reference input Idref, Iqref for current loop.

Lf
Lf
+  PI
Cf
Pp c c .r e f - i Id .re f
P2  Q2
Cf Pp c c
P1  Q1 (a) Active Power
+  PI
Q p c c .re f - i Iq .re f
Q pcc
(b) Reactive power
Figure 1 Microgrid configuration
Figure 3 PI regulator power control block diagram

3.1.2 Design of current control loop


After acquiring current reference value from first grade
of regulation, current regulation was implemented. The


Authorized licensed use limited to: PES University Bengaluru. Downloaded on August 30,2023 at 02:46:01 UTC from IEEE Xplore. Restrictions apply.
2011The International Conference on Advanced Power System Automation and Protection

adoption of PI control in current control loop aims to com- The output impedance of the inverter designed in this
pare current reference value with actual current signal fed paper is inductive [14]. Hence, droop characteristics in reg-
back to the controller. Stated in Figure 4, swift regulation ular high-voltage power system could be applied in low-
according to the difference has resulted in correct reference voltage microgrid and acquired droop function as follow:
voltage. For example, the output current of inverter can Pmax  Pn Qmax
maintain constant regulation according to the reference val- a ,b (2)
f n  f min E 0  E min
ue given by power control loop to secure the tracking of
The design of power controller is shown in Figure 6.
output voltage to reference voltage. In the process of de-
With application of PLL phase-locked loop control, it is
signing current loop, decoupling operation is needed after
easier to measure frequency signal. Thus, phase control is
which loop current would be independent in rotating frame.
replaced with frequency control. The power in control loop
At the same time, in current loop regulation, adding
is the instantaneous output power of DG whose active pow-
feed-forward control would greatly reduce the impact that
er and reactive power should meet the requirement of
grid voltage had on system.
0<P<Pmax and -Qmax<Q<Qmax. The output of this controller
will be reference voltage of the control of next grade.
U Id
uId.ref
Zn
iId.ref Ppcc.ref GV Vld
ZL
iId iIq Pp c c Z
VG v  dqo
U Iq Vlq
uIq.ref Qpcc.ref V

iIq.ref Qpcc E0
ZL
iIq
iId
Figure 6 V/F Power controller block diagram

Figure 4 PI regulator current control block diagram 3.2.2 Design of internal loop control
After acquiring reference voltage from the control of
former grade, the major task is to give current and voltage
3.2 Design of a V/F controlled inversion system precise and dynamic regulation. This paper has adopted
based on improved anti-droop control voltage-current double-loop control, it is shown in Figure 7.
The internal loop controller has improved power quality,
The main unit of V/F control method is viewed as infinite raise the resonance damping of filter and limit the fault cur-
bus [12–13]. Because of traditional low-voltage distribution rent at the same time. More importantly, implementation of
network showing resistance, the primary job of this design the filter inductive current as the control variables can limit
is to make output impedance show inductive. By utilization the maximum output current of inverter which has made
of V/F control which resembles the droop characteristics of protection of inverter possible.
the first regulation of traditional grid to realize varied fre-
quency sharing between different DGs of a microgrid in I f  Id
isolated state, the support of voltage and frequency can be *
I ld ZLf
Vld - Vd
+  + 
achieved at the same time. This control method has enabled - PI - PI +


the changes of DG’s self-sensing frequency and voltage, Vd Vld


ZC f
reduced communication link and strengthened reliability of Vld
microgrid. V/F block is shown in Figure 5. Figure 7 Voltage and current loop control block diagram

Vi .abc
I i.abc 3.3 Control strategy of synchronous network con-
P1  Q1
nection of DG
upcc.abc After a period of operating at isolated state, microgrid needs
I i.abc
to be injected into grid. Its voltage and frequency should be
U Id iId Pref Qref synchronous with the main grid which may otherwise bring
Figure 5 V/F control system block diagram
power impulse and surge current to threaten the safety of
the main grid in the connection. Using sensors to check
whether the voltage differenceV, frequency differencef
3.2.1 Design of V/F control and power control loop and phase difference of voltage phase on the two sides of


Authorized licensed use limited to: PES University Bengaluru. Downloaded on August 30,2023 at 02:46:01 UTC from IEEE Xplore. Restrictions apply.
2011The International Conference on Advanced Power System Automation and Protection

PCC reach the standard of network connection. The stan- through transformer. DG1 has adopted V/F control. Since
dard of network connection of microgrid are [15]: Vİ load1 is a sensitive load, therefore, bus voltage and fre-
10%, fİ0.3Hz and¥İ5e. Shown in Figure 8, the quency stability should be secured. DG2 has adopted PQ
synchronous process of the network connection after mi- control, then, securing the constant output power of DG to
crogrid’s isolated state could be directly led by the increase BUS2 can guarantee stable output of DG.
of two PI loops as synchronous compensator in power con- In the example, the equivalence of system and value of
troller. load are marked in the figure. Reference active power of
DG1 and DG2 is 7KW and 5KW respectively. The two val-
ues of reference reactive power are 0. Reference active
'G power and reactive power of sensitive load 1 is 7.8KW and
GV Vld

Z
1.5KW respectively and reference active power and reactive
VG v  dqo power of interruptible load 2 is 5.5KW and 1.5KW respec-
Vlq
V tively. The voltage of Line 1 and Line 2 are both 380V. The
parameters of the low-voltage lines are: R=0.642 ¡ /km,
'V X=0.101¡/km, R/X=7.7. The nominal capacity is 600 KW
and voltage level is 0.4kV/10kV in the parameters of trans-
Figure 8 Network synchronization controller block diagram
former. The parameters of control system are: Voltage on
DC side Vdc is 780V, frequency of grid f is 50Hz, carrier
4 Design of filter to improve the power quality frequency f is 3000Hz. The parameters of filter is: filter
resistance R=0.01¡, L=0.8mH, C=1800­f. The coefficient
The interface of DG inverter can reinforce the network of droop control is: 1/a=4e-5, 1/b=2.8e-4. Then, this model
connection performance of DG but will bring large amount was put into Matlab/simulink for simulation with digital
of harmonic pollution. The inverter in this paper has runge-kutta calculation method.
adopted SPWM whose output voltage produces harmonics Figure 9 to Figure 12 have reflected the state of con-
at switch frequency in relatively high switch frequency. As a nected network operation of microgrid and distribution
result, controllable filters are needed. This paper recom- network, isolated operation of microgrid after separating
mends LC filters [9]. LC filters will help to eliminate high- from distribution network and reconnection to distribution
order current harmonics around switch frequency. Parameter network respectively.
L and C of filter are constrained by regulation below: DG1 has adopted V/F control and DG2 PQ control. Be-
Fundamental wave loss triggered by inductor should be fore 0.8s, all the output of DG connected to microgrid and
as small as possible. Fundamental wave loss in capacitor distribution network was stable. At 0.8s, as what shown in
should be as small as possible. Series connected resonant Figure 8 and Figure 9, microgrid was separated from distri-
frequency of induction and capacitor should be kept far bution and fell into isolated operation. Because of load ab-
away from the low-order harmonic frequency of inverter’s sorbing some active power from distribution network before
output voltage and high-order harmonic current around separation, DG1’s output has seen a considerable growth
switch frequency. As a result, the empirical formula of filter and DG2 has remained constant power operation. At 1.6s,
design is: microgrid was reconnected to the distribution network and it
started to absorb power. Now, DG1’s output has witnessed a
1 1
10 f1   f s , f c 2S L f C f (3) decrease but was still slightly higher than the before separa-
f c 10 tion.
In the high power application, switch frequency would Shown in Figure 10, the operating voltage of DG1’s bus
not be relatively high. Generally speaking, it would be un- 1 has slightly fallen but in the range of 5% right after the
der 3KHz which formula above can’t meet. Therefore, separation occurred. Then, after the reconnection at 1.6s, the
comprehensively compare all the occurrence: voltage recovered to a slightly higher value than that before
1 separation but basically remained stable reaching the na-
 2Sf s L (4)
2Sf s C f tional standard.
Follow the requirement to design LC filter could give Presented in Figure 11, because of distribution network
birth to a LC filter that can effectively filter high-order losing frequency support, the output of DG1 has soared with
harmonic current and curb low-order harmonic voltage. the frequency of PCC in microgrid falling by 0.04Hz at 0.8s
when the separation occurred. After the reconnection opera-
tion at 1.6s, the frequency has recovered to the
5 Example simulation same-frequency operation with distribution network for
acquiring power supply from the distribution network.
As Figure 1 stated, a microgrid made up of two parallel
connected DGs are injected to the distribution network


Authorized licensed use limited to: PES University Bengaluru. Downloaded on August 30,2023 at 02:46:01 UTC from IEEE Xplore. Restrictions apply.
2011The International Conference on Advanced Power System Automation and Protection

8000 DG1
6 Conclusion
DG2
6000
This paper has designed a PQ control system based on with
P(w)

4000
power-current double loop control strategy and a V/F con-
2000
trol system based on the improved anti-droop which could
0 well maintain the external characteristics of the controllable
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 loads of network connected DG to enable the adaptive op-
T(s)
eration between DGs parallel operating in grid without
Figure 9 Active power output of DG1 and DG2 communication and strengthen the reliability of microgrid.
For various DGs, different control strategies are applied. PQ
6000
control strategy is applied in control system of intermittent
DG1
DG2
energy generation like wind and illumination to optimize
4000 their operation. Meanwhile, connection controller that can
effectively reduce the impact of connection to distribution
Q(w)

2000
network and improve the dynamic characteristics of system
0 is designed. DG with VF control can not only offer internal
frequency support for microgrid in isolated operation but
-2000
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 also secure power supply requirement of important custom-
T(s)
ers which is in line with the request to secure power quality
Figure 10 DG1 and DG2 reactive power output
to important customers in future smart grid.
The DGs in this paper are assumed DC source or rectified
DC source all the while the changes of power of the genera-
330 tion unit controlled by controller in an acceptable range. A
300
microgrid coordinating control strategy that combination of
master slave control and equivalent control is applied between
U/V

0 different types of DGs without data communication loop has


enabled smooth switching between the modes of network
-300 connection and isolated operation and other two modes. At the
-330 same time, the requirement of securing high power quality to
0.6 0.8 1 1.2
T(S)
1.4 1.6 1.8 2 important customers is met while the utilization ratio of ener-
gy has been improved. In the whole process, the safe, reliable
Figure 11 Microgrid bus 1 voltage
and economic operation of microgrid has been maintained.

This work was supported by the National Natural Science Foundation of


 China (Grant No. 50977023) and the Hunan Provincial National Science
 Foundation-funded projects (Grant No. 10JJ2043).

I +]


1 Lu Z X, Wang C X, Min Y, et al. Microgrid research. Automation of
Electric Power Systems, 2007, 31(19): 100-107

           2 Lasseter B. Microgrids. IEEE Power Engineering Society Winter
W V Meeting, Columbus, Jan, 2001: 146-149
3 Guo X Q, Wu W Y. Non-devastating Islanding Detection for Micro-
Figure 12 The frequency of microgrid system grids without Non-detection Zone. Proceedings of the CSEE, 2009,
29(25): 7-12
4 Wang C S, Xiao C X, Wang S X. Synthetical Control and Analysis of
Microgrid. Automation of Electric Power System, 2008, 32(7):
The simulation result above has demonstrated that the con- 98-103
troller designed in this paper can realize smooth switching 5 Mou X C, Bi D Q, Ren X W. Study on Control Strategies of a Low
between modes of network connection and isolated operation. Voltage Microgrid. Automation of Electric Power System, 2010,
A microgrid coordinating control strategy that combination of 34(19): 91-96
6 Mao M Q, Yu S J, Su J H, et al. The Developing of Experiment Set
master slave control and equivalent control is applied between for Wind-solar-diesel-battery Hybrid Power System and its Intelli-
different types of DGs without data communication loop is put gence Control. Acta Energiae Solaris Sinica, 2003, 24(1): 18-21
forward to enable the participation of DGs in frequency regu- 7 Huang W, Sun C H, Wu Z P, et al. A Review on Microgrid Technolo-
gy Containing Distributed Generation System. Power System Tech-
lation of microgird.
nology, 2009, 33(9): 14-19
8 Wang L, Li P Q, Li X R, et al. Modeling of Micro-powers and its Ap-
plication in Microgrid Simulintion. Proceedings of the CSU2EPSA,
2009, 33(9): 14-19


Authorized licensed use limited to: PES University Bengaluru. Downloaded on August 30,2023 at 02:46:01 UTC from IEEE Xplore. Restrictions apply.
2011The International Conference on Advanced Power System Automation and Protection

9 Wang Z Q, Zhu S Z, Zhou S X. Controller Design for Inverter-based 12 J.A. Peças Lopes, C.L. Moreira, A.G. Madureira. Defining Control
Distributed Generation. Automation of Electric Power Systems, 2004, Strategies for MicroGrids Islanded Operation. IEEE Transactions on
28(24): 61-66 Power Systems, 2006, 21(2): 916-924
10 GIL N. J, LOPES G, PECAS A. Hierarchical Frequency Control- 13 LOPES J, MOREIRA C, MADUREIRA A. Control Strategies for
scheme for Islanded Multi-microgrids Operation. Proceedings of Microgrids Emergency Operation. International Conference on Fu-
2007 IEEE Lausanne Powertech. Lausanne, Switzerland, 2007: ture Power Systems. Amsterdam, Netherlands, 2005: 1-6.
473-478 14 Pecas Lopes,J.A, Moreira,C.L, Madureira.A.G., Resende.F.O. Control
11 BOSE S, LIU Y, BAHEI-ELDIN K, et al. Tieline Controls in Micro- Strategies for MicroGrids Emergency Operation. 2005 International
grid Applications. Proceedings of 2007 iREP Symposium-Bulk Pow- Conference on Future Power Systems, 2005,16(18): 1-6
er System Dynamics and Control-VII, Revitalizing Operational Re- 15 Yao Y, Zhu G P, Liu X C. Harmonics Influences on the Operation of
liability, Charleston, SC, USA, 2007: 1-9 LV Microgrids. Electric Power, 2010, 43(10): 11-14


Authorized licensed use limited to: PES University Bengaluru. Downloaded on August 30,2023 at 02:46:01 UTC from IEEE Xplore. Restrictions apply.

You might also like