Sieyuan

TECHNICAL SPECIFICATION
CAPACITOR BANK
TBB115-15000
<FOR QUOTATION>

SN:SY-2022-11-1008

SIEYUAN ELECTRIC CO.,LTD.


Sieyuan
Content

1. Introduction........................................................................................................................... 3

1.1 Scope.............................................................................................................................. 3

1.2 Application standard......................................................................................................3

2. Service Conditions...............................................................................................................3

2.1 Service ambient conditions.......................................................................................... 3

2.2 Service system conditions............................................................................................4

3. Supply scope........................................................................................................................ 4

4. Electrical connection diagram............................................................................................5

2
SIEYUAN ELECTRIC CO.,LTD.
Sieyuan
1. Introduction

1.1 Scope

This Capacitor Bank is used for rated voltage 115kV, rated frequency AC power
system 60Hz, to improve the power factor of power grid, improve power system voltage
quality, give full play to the economic efficiency of power transmission equipment, reduce
power loss and improve power utilization level.

1.2 Application standard

CFE V8000-53 69kV to 161kV Substation type capacitor bank


CFE V4200-25 15kV to 145kV Disconnect switch with manual operation
CFE V8000-67 Power capacitors for electrical system distribution and transmission
IEC 60871-1 Shunt capacitors for A.C.power systems having a rated voltage above
1000V-Part1:General
IEC 60071-1 Insulation co-ordination Part 1: Definitions, principles and rules
IEC 61936-1 Power installations exceeding 1kV a.c.-Part1: Common rules
IEC 60076-6 Power transformers-Part 6: Reactors
IEC 62271-100 High voltage switchgear and controlgear- Part100 alternating-current
circuit-breakers
IEC62271-102 High-voltage switchgear and controlgear-Part 102:Alternating current
disconnectors and earthing switches
IEC 61869-2 Instrument transformers-Part 2:Additional requirements for current
transformers
IEC 60099-4 Surge arresters-Part 4:Metal-oxide surge arresters without gaps for a.c.
systems
IEC 60273 Characteristics of indoor and outdoor post insulators for systems with nominal
voltages greater than 1000V

2. Service Conditions

2.1 Service ambient conditions

Location: outdoor
Ambient Temperature:-10℃~55℃
Altitude:Below 2500 m A.S.L
Pollution Level: 25mm/kV
Seismic regionalization:Zone A (Low intensity)

3
SIEYUAN ELECTRIC CO.,LTD.
Sieyuan
2.2 Service system conditions

Nominal voltage:115kV
Maximum voltage: 123kV
Rated frequency: 60Hz
Short-circuit current: 40kA
System grounding method: solid ground

3. Supply scope

Table 1 Supply scope


No. Part name Model QTY. Remark
1 Capacitor Bank TBB115-15000 1set
Each capacitor bank contains - TBB115-15000
1 Capacitor unit SYC13.28-100 150
2 Fuse 15kV,12A 150
Monopolar
3 630A,BIL 150kV,25kA 15
disconnect switch
Resistor potential
4 69kV,BIL 350kV 1
divider
5 Post insulator 145kV,BIL 650kV,30kN 1set
6 Post insulator 40.5kV,BIL250kV,30kN 1set
7 Post insulator 24kV,BIL150kV,8kN 1set
8 Steel structures 1lot
9 Accessories 1lot
Each spare part contains
1 Capacitor unit SYC13.28-100 8
2 Fuse 15kV,12A 23
3 Fuse support 8sets

4
SIEYUAN ELECTRIC CO.,LTD.
Sieyuan
4. Electrical connection diagram

Figure 1 Electrical connection diagram

5
SIEYUAN ELECTRIC CO.,LTD.