Download as pdf or txt
Download as pdf or txt
You are on page 1of 170

Model: 11393650200

Type: SD130
Engine: D7.5M
INTRODUCTION The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recom-
Thank you for purchasing this model of the standby
generator set product line by Generac Power Systems, mends that the operator read this Owner's Manual
Inc.. and thoroughly understand all instructions before
using this equipment. The manufacturer also strong-
Every effort was expended to make sure that the ly recommends instructing other users to properly
information and instructions in this manual were start and operate the unit. This prepares them if they
both accurate and current at the time the manual was need to operate the equipment in an emergency.
written. However, the manufacturer reserves the right
to change, alter or otherwise improve this product(s)
at any time without prior notice. ‹ OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety
‹ READ THIS MANUAL THOROUGHLY checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
If any portion of this manual is not understood, con- equipment checked periodically by an Authorized
tact the nearest Authorized Service Dealer for start- Service Dealer. Normal maintenance service and
ing, operating and servicing procedures. replacement of parts are the responsibility of the
Throughout this publication, and on tags and decals owner/operator and, as such, are not considered
affixed to the generator, DANGER, WARNING, defects in materials or workmanship within the
CAUTION and NOTE blocks are used to alert person- terms of the warranty. Individual operating habits
nel to special instructions about a particular service and usage contribute to the need for maintenance
or operation that may be hazardous if performed service.
incorrectly or carelessly. Observe them carefully. Proper maintenance and care of the generator ensure
Their definitions are as follows: a minimum number of problems and keep operating
expenses at a minimum. See an Authorized Service
DANGER Dealer for service aids and accessories.
After this heading, read instructions that, if not Operating instructions presented in this manual
strictly complied with, will result in personal injury assume that the standby electric system has been
or property damage. installed by an Authorized Service Dealer or other
competent, qualified contractor. Installation of this
equipment is not a “do-it-yourself” project.
After this heading, read instructions that, if not
strictly complied with, may result in personal injury ‹ HOW TO OBTAIN SERVICE
or property damage. When the generator requires servicing or repairs,
contact an Authorized Service Dealer for assistance.
Service technicians are factory-trained and are capa-
ble of handling all service needs.
After this heading, read instructions that, if not
strictly complied with, could result in damage to When contacting an Authorized Service Dealer about
equipment and/or property. parts and service, always supply the complete model
NOTE: number of the unit as given on the front cover of this
manual or on the DATA LABEL affixed to the unit.
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compli-
ance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates is as follows: AUTHORIZED SERVICE
 This symbol points out important safety infor- DEALER LOCATION
mation that, if not followed, could endanger To locate the nearest AUTHORIZED SERVICE
personal safety and/or property of others. DEALER, please call this number:

 This symbol points out potential explosion


hazard. 1-800-333-1322
 This symbol points out potential fire hazard.
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER
or visit the website at
 This symbol points out potential electrical shock
hazard. www.generac.com.
Table of Contents
Standby Generator Sets

Introduction ............................... Inside Front Cover Section 2 – Installation ........................................... 9


Read This Manual Thoroughly .....................................IFC STANDBY GENERATOR INSTALLATION ........................ 9
Operation and Maintenance .........................................IFC NFPA Standards .......................................................... 9
How to Obtain Service..................................................IFC
Authorized Service Dealer Locator Number .................... IFC Other Published Standards........................................ 10
BASIC STANDBY ELECTRIC SYSTEM ......................... 10
EMERGENCY CIRCUIT ISOLATION METHOD ............. 10
Safety Rules ............................................................... 2
TOTAL CIRCUIT ISOLATION METHOD ........................ 10
GROUNDING THE GENERATOR .................................. 10
Section 1 – General Information .......................... 4 GENERATOR AC NEUTRAL CONNECTIONS ............... 11
IDENTIFICATION RECORD ............................................ 4
TRANSFER SWITCH START SIGNAL
Data Label ................................................................... 4
CONNECTIONS ............................................................. 11
XPL Label .................................................................... 4
BATTERY INSTALLATION ............................................ 11
EQUIPMENT DESCRIPTION ........................................... 5
Vented Batteries ......................................................... 11
Standard Generator Features....................................... 5
PREPARATION BEFORE START-UP .............................. 12
ENGINE PROTECTIVE DEVICES ................................... 5
Prior to Initial Start-up .............................................. 12
Coolant Temperature Sender ....................................... 5
Start-up Inspection .................................................... 13
Low Coolant Level Sensor............................................ 5
Oil Pressure Sender ..................................................... 5
Section 3 – Operation ........................................... 13
Low Fuel Pressure Switch (Gas Units Only) ................. 5 GENERATOR CONTROL AND OPERATION .................. 13
Overspeed Shutdown ................................................... 5 OPERATING UNIT WITH MANUAL
Overcrank Shutdown ................................................... 5 TRANSFER SWITCH ..................................................... 13
RPM Sensor Loss Shutdown........................................ 5 Engine Start-up and Transfer .................................... 13
DC FUSES ...................................................................... 5 Retransfer and Shutdown .......................................... 14
FUEL SYSTEM................................................................ 6 OPERATING UNIT WITH AUTOMATIC
Fuel Requirements ....................................................... 6 TRANSFER SWITCH ..................................................... 14

Diesel Fuel System ....................................................... 6


LP Fuel System ............................................................ 6 Section 4 – Maintenance ...................................... 14
SERVICE SCHEDULE ................................................... 14
Natural Gas Fuel System ............................................. 6
Authorized Operator Maintenance Functions ............. 14
Combination LP/Natural Gas Fuel System ................... 6
Authorized Service Technician
Propane Vapor Withdrawal Fuel System....................... 7
Maintenance Functions .............................................. 14
SPECIFICATIONS............................................................ 7
PERIODIC MAINTENANCE ........................................... 15
Generator .................................................................... 7
Test Standby Generator System
Engine.......................................................................... 7 Operation and Components ....................................... 15
Engine Oil Recommendations ...................................... 8 Inspect Battery ........................................................... 15
Coolant ........................................................................ 8 Battery Replacement .................................................. 16
Fuel System Requirements and Check Fluids.............................................................. 16
Recommendations ....................................................... 8
Inspect Exhaust System ............................................. 16
GENERATOR AC LEAD CONNECTIONS ........................ 8
Inspect/Test Fuel Supply System ................................ 16
Four-lead, Single-phase Stator ..................................... 8
REPAIR PARTS ............................................................. 16
GENERATOR AND LOAD COMPATIBILITY ..................... 8
Generator Set XPL Label ........................................... 16
STARTING AIDS ............................................................. 9
How to Order Parts .................................................... 17
Engine Coolant Heaters ............................................... 9
Battery Chargers .......................................................... 9
Section 5 – Warranty........................................................ 18

SD 7.5L Liter – 01.06 1


Important Safety Instructions
Standby Generator Sets

 
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted in potential hazard areas. Safety should be stressed to all operators,
potential operators, and service and repair technicians for this equipment.

 
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.

 WARNING:   GENERAL HAZARDS 


The engine exhaust from this product • For safety reasons, the manufacturer recommends
contains chemicals known to the state that this equipment be installed, serviced and
of California to cause cancer, birth repaired by an Authorized Service Dealer or other
defects or other reproductive harm.
competent, qualified electrician or installation
technician who is familiar with applicable codes,

 WARNING: 
standards and regulations. The operator also must
comply with all such codes, standards and regula-
This product contains or emits chemicals tions.
known to the state of California to cause • Installation, operation, servicing and repair of this
cancer, birth defects or other reproductive harm. (and related) equipment must always comply with
applicable codes, standards, laws and regulations.
Adhere strictly to local, state and national electri-
cal and building codes. Comply with regulations
Study these SAFETY RULES carefully before install- the Occupational Safety and Health Administration
ing, operating or servicing this equipment. Become (OSHA) has established. Also, ensure that the
familiar with this Owner’s Manual and with the generator is installed, operated and serviced in
unit. The generator can operate safely, efficiently and accordance with the manufacturer’s instructions
reliably only if it is properly installed, operated and and recommendations. Following installation, do
maintained. Many accidents are caused by failing to nothing that might render the unit unsafe or in
follow simple and fundamental rules or precautions. noncompliance with the aforementioned codes,
The manufacturer cannot anticipate every possible standards, laws and regulations.
circumstance that might involve a hazard. The warn- • The engine exhaust fumes contain carbon monox-
ings in this manual, and on tags and decals affixed ide gas, which can be DEADLY. This dangerous gas,
to the unit are, therefore, not all-inclusive. If using a if breathed in sufficient concentrations, can cause
procedure, work method or operating technique that unconsciousness or even death. For that reason,
the manufacturer does not specifically recommend, adequate ventilation must be provided. Exhaust
ensure that it is safe for others. Also make sure the gases must be piped safely away from any building
procedure, work method or operating technique uti- or enclosure that houses the generator to an area
lized does not render the generator unsafe. where people, animals, etc., will not be harmed.
This exhaust system must be installed properly, in
strict compliance with applicable codes and stan-
DANGER dards.
• Keep hands, feet, clothing, etc., away from drive
 Despite the safe design of this generator, operating
this equipment imprudently, neglecting its mainte-
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
nance or being careless can cause possible injury is operating.
or death. Permit only responsible and capable
• Adequate, unobstructed flow of cooling and venti-
persons to install, operate or maintain this equip- lating air is critical in any room or building hous-
ment. ing the generator to prevent buildup of explosive
 Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
gases and to ensure correct generator operation.
Do not alter the installation or permit even partial
render the machine safe before attempting to blockage of ventilation provisions, as this can seri-
work on the generator. ously affect safe operation of the generator.
• Keep the area around the generator clean and
 Parts of the generator are rotating and/or hot
during operation. Exercise care near running
uncluttered. Remove any materials that could
become hazardous.
generators.
• When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
2
Important Safety Instructions
Standby Generator Sets

• Inspect the generator regularly, and promptly • Generators installed with an automatic transfer
repair or replace all worn, damaged or defective switch will crank and start automatically when
parts using only factory-approved parts. NORMAL (UTILITY) source voltage is removed
• Before performing any maintenance on the gen- or is below an acceptable preset level. To prevent
erator, disconnect its battery cables to prevent such automatic start-up and possible injury to
accidental start-up. Disconnect the cable from the personnel, disable the generator’s automatic start
battery post indicated by a NEGATIVE, NEG or (–) circuit (battery cables, etc.) before working on or
first. Reconnect that cable last. around the unit. Then, place a “Do Not Operate”
• Never use the generator or any of its parts as a tag on the generator control panel and on the
step. Stepping on the unit can stress and break transfer switch.
parts, and may result in dangerous operating con- • In case of accident caused by electric shock, imme-
ditions from leaking exhaust gases, fuel leakage, diately shut down the source of electrical power. If
oil leakage, etc. this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT
 ELECTRICAL HAZARDS  WITH THE VICTIM. Use a nonconducting imple-
ment, such as a dry rope or board, to free the vic-
• All generators covered by this manual produce tim from the live conductor. If the victim is uncon-
dangerous electrical voltages and can cause fatal scious, apply first aid and get immediate medical
electrical shock. Utility power delivers extremely help.
high and dangerous voltages to the transfer switch • Never wear jewelry when working on this equip-
as well as the standby generator. Avoid contact with ment. Jewelry can conduct electricity resulting in
bare wires, terminals, connections, etc., on the gen- electric shock, or may get caught in moving com-
erator as well as the transfer switch, if applicable. ponents causing injury.
Ensure all appropriate covers, guards and barriers
are in place before operating the generator. If work
must be done around an operating unit, stand on  FIRE HAZARDS 
an insulated, dry surface to reduce shock hazard.
• Keep a fire extinguisher near the generator at all
• Do not handle any kind of electrical device while times. Do NOT use any carbon tetra-chloride type
standing in water, while barefoot, or while hands
or feet are wet. DANGEROUS ELECTRICAL extinguisher. Its fumes are toxic, and the liquid
SHOCK MAY RESULT. can deteriorate wiring insulation. Keep the extin-
• If people must stand on metal or concrete while guisher properly charged and be familiar with its
installing, operating, servicing, adjusting or repair- use. If there are any questions pertaining to fire
ing this equipment, place insulative mats over a extinguishers, consult the local fire department.
dry wooden platform. Work on the equipment only
while standing on such insulative mats.
• The National Electrical Code (NEC), Article 250
 EXPLOSION HAZARDS 
requires the frame and external electrically con-
ductive parts of the generator to be connected to • Properly ventilate any room or building housing
an approved earth ground and/or grounding rods. the generator to prevent build-up of explosive gas.
This grounding will help prevent dangerous electri- • Do not smoke around the generator. Wipe up any
cal shock that might be caused by a ground fault fuel or oil spills immediately. Ensure that no com-
condition in the generator set or by static electric- bustible materials are left in the generator com-
ity. Never disconnect the ground wire. partment, or on or near the generator, as FIRE or
• Wire gauge sizes of electrical wiring, cables and EXPLOSION may result. Keep the area surround-
cord sets must be adequate to handle the maxi- ing the generator clean and free from debris.
mum electrical current (ampacity) to which they • These generator sets may operate using one of
will be subjected. several types of fuels. All fuel types are potentially
• Before installing or servicing this (and related) FLAMMABLE and/or EXPLOSIVE and should be
equipment, make sure that all power voltage handled with care. Comply with all laws regulat-
supplies are positively turned off at their source. ing the storage and handling of fuels. Inspect the
Failure to do so will result in hazardous and pos- unit’s fuel system frequently and correct any leaks
sibly fatal electrical shock.
immediately. Fuel supply lines must be prop-
• Connecting this unit to an electrical system nor- erly installed, purged and leak tested according to
mally supplied by an electric utility shall be by
means of a transfer switch so as to isolate the applicable fuel-gas codes before placing this equip-
generator electric system from the electric utility ment into service.
distribution system when the generator is operat- • Diesel fuels are highly FLAMMABLE. Gaseous
ing. Failure to isolate the two electric system power fluids such as natural gas and liquid propane
sources from each other by such means will result (LP) gas are extremely EXPLOSIVE. Natural gas
in damage to the generator and may also result is lighter than air, and LP gas is heavier than air;
in injury or death to utility power workers due to install leak detectors accordingly.
backfeed of electrical energy.
3
Section 1 – General Information
Standby Generator Sets

IDENTIFICATION RECORD  Identification Code


Use this code to obtain important information about
‹ DATA LABEL the generator. For example, if the code is ...
Every generator set has a DATA LABEL that contains SD 100-- A 1 6 5.0 D 18 HB Y N C
important information pertinent to the generator
(Figure 1.1). The data label, which can be found – identify the generator as follows:
attached to the generator’s lower connection box, • SD – Standby diesel generator (“SG” indicates a standby
lists the unit’s serial number and its rated volt- gaseous fuel unit).
age, amps, wattage capacity, phase, frequency, rpm, • 100 – Rated output is 100,000 watts (100 kW).
power factor, etc. • A – Voltage code (see “Voltage Codes” on this page).
• 1 – Indicates single-phase unit (3 – indicates three-phase
Figure 1.1 — Data Label unit).
• 6 – Indicates unit rated 60 Hertz (Hz) (5 – indicates 50
Hz).
• 5.0 – Engine is 5.0 liter (304 cubic inches).
• D – Unit has diesel fuel system (“N” indicates natural
gas; “L” indicates LP Liquid Withdrawal; “V” indicates
LP Vapor Withdrawal).
• 18 – Alternator rpm rating (1,800 rpm); “36” indicates
3,600 rpm.
• H – Unit has an option “H” control panel (“R”, "E" and "G"
panels are also available on some units).
• B – Indicates a brushless unit (“D” indicates a direct
excited unit with brushes and slip rings; “P” indicates a
permanent magnet excitation).
• Y – Unit is equipped with a standard enclosure (“N” indi-
cates no enclosure; “S” indicates unit has an acoustic
enclosure).
• N – Unit does not have an exhaust muffler (“Y” indicates
a muffler has been mounted; “L” indicates a muffler has
NOTE: been shipped loose with the unit).
The above is a generic representation of a data • Y – Unit has a main line circuit breaker (“C” indicates
label. For actual information related to this par- unit has a UL-listed circuit breaker; “N” indicates no
ticular model, please refer to the “construction circuit breaker has been mounted).
document” located at the end of this manual, or to
the data labels affixed to the unit.
 Groups and Assembly Numbers
The XPL label lists the groups and correspond-
ing assembly numbers for each unit. The assembly
‹ XPL LABEL numbers refer to exploded view drawing numbers
A XPL LABEL is also affixed to the lower connection that are applicable to the specific generator model.
box of each standby generator set. Like the data label, These drawings are located in the back half of this
this card also contains valuable information pertain- manual.
ing to the generator. When requesting information,
ordering replacement parts, asking for service, etc.,  Voltage Codes
the information from this card is needed (see page 17 The identification code letter following the unit’s kilo-
for example of generator set XPL Label). It provides watt rating is the generator’s “voltage code.” Any one
the following information: of the following voltage codes may be listed.
• Generator Model Number A – 120/240 volts, single-phase, four-lead, 60 Hz
• Date of Manufacture D – 120/240 volts, single- and three-phase, 12-lead, 60 Hz
• Generator Identification Code G – 120/208 volts, three-phase, 12-lead, 60 Hz Broad Range
• Generator Assembly Groups J – 120/240 volts, three-phase, 12-lead, 60 Hz Broad Range
K – 277/480 volts, three-phase, 12-lead, 60 Hz Broad Range
 Generator Model Number L – 346/600 volts, three-phase, six-lead, 60 Hz
This number is the key to numerous engineering and M – 110/220 volts, single-phase, four-lead, 50 Hz
manufacturing details pertaining to the unit. Always N – 115/200 volts, three-phase, 12-lead, 50 Hz Broad Range
supply this number when requesting service, order- P – 100/200 volts, three-phase, 12-lead, 50 Hz Broad Range
ing parts or seeking information. R – 231/400 volts, three-phase, 12-lead, 50 Hz Broad Range
S – 277/480 volts, three-phase, six-lead, 50 Hz
4
Section 1 – General Information
Standby Generator Sets

EQUIPMENT DESCRIPTION ‹ COOLANT TEMPERATURE SENDER


This equipment is a revolving field, alternating cur- This sender automatically shuts down the engine if
rent generator set. The generator was designed to the engine coolant temperature rises above a safe
supply electrical power for the operation of compat- level.
ible electrical loads-when the UTILITY power supply
is not available or has dropped to an unacceptable
level. ‹ LOW COOLANT LEVEL SENSOR
The generator’s revolving field is directly connected Should the engine coolant level drop below the level
to and driven by an engine by means of flexible discs. of the high coolant temperature switch, it is possible
Generators with a four-pole rotor are driven at rated for the engine to overheat without automatic shut-
speeds of 1,800 rpm to supply a frequency of 60 down. To prevent such overheating, the engine has a
Hertz. low coolant level sensor. If the level of engine coolant
drops below the level of the low coolant level sensor,
Refer to the data label on this specific generator or the engine automatically shuts down.
to the data label affixed to the unit for rated AC volt-
age, wattage, amperage, number of phases, etc. See
“Identification Code” for an explanation of the way to ‹ OIL PRESSURE SENDER
identify the unit’s features. This sender monitors oil pressure in the engine. If oil
pressure drops below a safe level, the control system
‹ STANDARD GENERATOR FEATURES automatically shuts down the engine.
This generator incorporates the following generator
features: ‹ LOW FUEL PRESSURE SWITCH (GAS UNITS
• The rotor insulation system is Class “H” rated, and
ONLY)
the stator insulation is Class “H” rated as defined This normally closed (N.C.) switch is held open by
by NEMA MG1-22.4 and NEMA MG1-1.65. fuel pressure during operation. If fuel pressure drops
• The generator is self-ventilated and drip-proof con- below a safe level, the switch contacts close, auto-
structed. matically shutting down the engine.
• The voltage waveform deviation, total harmonic
content of the AC waveform and “telephone influ- ‹ OVERSPEED SHUTDOWN
ence factor” have been evaluated and are accept-
A speed circuit controls engine cranking, start-up,
able according to NEMA MG1-22.
operation and shutdown. Engine speed signals are
• All prototype tested models have passed three- delivered to the circuit board whenever the unit is
phase symmetrical short circuit test to ensure running. Should the engine overspeed above a safe,
system protection and reliability. preset value, the circuit board initiates an automatic
engine shutdown.
ENGINE PROTECTIVE DEVICES
The standby generator may be required to operate for ‹ OVERCRANK SHUTDOWN
long periods of time without an operator on hand to
monitor such engine conditions as coolant tempera- After a prespecified duration of cranking, this func-
ture, oil pressure or rpm.-For that reason, the engine tion ends the cranking if the engine has failed to
has several devices designed to protect it against start.
potentially damaging conditions by automatically
shutting down the unit when the oil pressure is too ‹ RPM SENSOR LOSS SHUTDOWN
low, the coolant temperature is too high, the coolant
level is too low, or the engine is running too fast. If the speed signal to the control panel is lost, engine
shutdown will occur.
NOTE:
Engine protective switches and sensors are men-
tioned here for the reader’s convenience. Also DC FUSES
refer to the applicable control panel manual for These fuses are located inside the front panel of the
additional automatic engine shutdown informa- control system. They protect the panel wiring and
tion. components from damaging overload.

5
Section 1 – General Information
Standby Generator Sets

FUEL SYSTEM NOTE:


On units with LP gas liquid withdrawal fuel sys-
‹ FUEL REQUIREMENTS tems, a block heater is included as standard
The standby generator may be equipped with one of equipment. The heater is powered by the UTILITY
the following fuel systems: power source during nonoperating periods. Thus,
heated coolant is always available to aid the fuel
• Diesel fuel system vaporization process.
• Liquid propane (LP) fuel system
• Propane vapor (PV) fuel system ‹ NATURAL GAS FUEL SYSTEM
• Natural gas fuel system
Natural gas is supplied in its vapor state. In most
• Combination LP/natural gas fuel system
cases, the gas distribution company provides piping
The data card that is affixed to the unit includes the from the main gas distribution line to the standby
“Identification Code,” which may be used to identify generator site. The following information applies to
the type of fuel system installed on the unit. natural gas fuel systems.
NOTE: • Gas pressure in a building is usually regulated by
It is the responsibility of the installer to make sure national, state and local codes.
that only the correct recommended fuel is sup- • To reduce gas pressure to a safe level before
plied to the generator fuel system. Thereafter, the the gas enters a building, a primary regulator is
owner/operator must make certain that only the needed. The natural gas supplier may or may not
proper fuel is supplied. supply such a regulator.
For further information on the various types of • It is the responsibility of the gas supplier to make
fuel systems, refer to Engine-Generator Standby sure sufficient gas pressure is available to operate
Electric Power Systems Installer’s Guide and the primary regulator.
Reference Manual (part #046622). • Gas pressure at the inlet to the fuel shutoff sole-
noid should not exceed approximately 14 inches
water column (0.6 psi). Optimum pressure at the
‹ DIESEL FUEL SYSTEM fuel shutoff solenoid is 11 inches water column
Diesel fuel is supplied to the generator set from a (0.4 psi).
base-mounted fuel tank.
Diesel fuels are less volatile than gaseous fuels, how- ‹ COMBINATION LP/NATURAL GAS FUEL
ever, careless installation can lead to safety hazards SYSTEM
and/or serious problems with engine/generator per- In some areas, the cost of natural gas may be reduced
formance and reliability. considerably by procuring the gas on “interrupted
NOTE: service” rates. Such rates may be obtained by using
LP gas as an emergency fuel when natural gas is not
Appropriate care should be taken in applications
available. Automatic changeover is accomplished by
where extremely low ambient temperatures are
using two regulators, (for example, a line pressure
possible to ensure the temperature of the diesel
regulator for natural gas, and a vacuum-operated
fuel is not allowed to fall below levels where “gell-
regulator for LP gas). The difference in pressure com-
ing” could occur.
pensates for the greater Btu value of LP gas.

‹ LP FUEL SYSTEM During operation on natural gas, a positive pressure


exists in the common line to the carburetor. This
LP is supplied as a liquid in pressure tanks. It is pressure closes the LP gas regulator and stops the
usually made up of propane, butane, or a mixture of flow of LP gas. Loss of natural gas pressure causes a
the two gases. Propane tends to vaporize readily even partial vacuum in the line, and the LP gas regulator
at temperatures as low as -20° F (-29° C). However, then opens to admit LP gas into the system. Adjusting
butane reverts to its liquid state when temperatures a separate power mixture in the LP gas line permits
drop below 32° F (0° C). precise setting of air-to-fuel ratios on each of the
LP in a liquid withdrawal system must be converted fuels. Changeover is automatic with the engine oper-
to its gaseous state before it is introduced into the ating.
engine carburetor. A vaporizer-converter is generally
used to accomplish this. In such a converter, heated
engine coolant is ported through the converter to
provide the necessary heat for conversion of the fuel
from a liquid to a gaseous state.
6
Section 1 – General Information
Standby Generator Sets

‹ PROPANE VAPOR WITHDRAWAL FUEL SYSTEM Fuel System:


Type of Fuel .......................................... No. 2 Diesel (Min Cetaine #40)
This type of system utilizes the vapors formed above
Consumption:*
the liquid fuel in the supply tank. Approximately 10
to 20 percent of the tank capacity is needed for fuel Rated Fuel 25% 50% 75% 100%
expansion from the liquid to the vapor state. The Type Freq. System Load Load Load Load
vapor withdrawal system is generally best suited for SD130 50 Hz Diesel T 2.5 4.7 6.8 8.8
smaller engines that require less fuel. The installer SD150 50 Hz Diesel T/A 2.7 5.1 7.4 9.6
should be aware of the following: SD180 50 Hz Diesel T/A 2.8 5.3 7.6 10.1
SD200 50 Hz Diesel T/A 3.3 6.1 8.8 11.4
• The natural gas and LP gas systems are similar.
SD130 60 Hz Diesel T 3.1 5.9 8.5 11.0
However, the natural gas system delivers gas at a
pressure of approximately five inches water col- SD150 60 Hz Diesel T/A 3.4 6.4 9.2 12.0
umn to the carburetor. The LP gas system delivers SD180 60 Hz Diesel T/A 3.5 6.6 9.5 12.6
gas at a slightly negative pressure (about negative SD200 60 Hz Diesel T/A 4.1 7.6 11.0 14.3
one inch) to the engine carburetor. *Given in ...
• When ambient temperatures are low and engine Diesel: gal/h; Natural Gas (NG): cfh; Liquid Propane Vapor (LP): cfh
fuel consumption is high, the vapor withdrawal
system may not function efficiently. Cooling System:
• Ambient temperatures around the supply tank Type ....................................................... Pressurized, Closed Recovery
must be high enough to sustain adequate vaporiza- Coolant Capacity
tion, or the system will not deliver the needed fuel System ............................................................42.4 L (11.2 U.S. gals.)
volume. Engine ..............................................................13.0 L (3.4 U.S. gals.)
• In addition to the cooling effects of ambient air, the Coolant Flow Per Minute (1,500 rpm / 1,800 rpm)
vaporization process itself provides an additional SD130/150/180/200 ........................................272.6 L (72 U.S. gals.)
cooling effect. Heat Rejection to Coolant (50 Hz and 60 Hz)
SD130 .......................................................................... 451,000 Btu/h
SPECIFICATIONS SD150 .......................................................................... 477,000 Btu/h
SD180 .......................................................................... 500,600 Btu/h
‹ GENERATOR SD200 .......................................................................... 574,000 Btu/h
Cooling Fan ........................................................................Pusher Type
Refer to the data plate on the generator for rated
watts, amperes, frequency, voltage, phase and other Diameter of Fan ............................................................ 762 mm (30 in.)
pertinent information. Cooling Airflow Required
50 Hz Units ................................................354 m3/min. (12,500 cfm)
60 Hz Units ................................................425 m3/min. (15,000 cfm)
‹ ENGINE Recommended Coolant.................................. See “Coolant” on Page 8
General: Combustion Airflow Required (50 Hz / 60 Hz)
Cylinders and Arrangement.......................................................In-line 6 SD130 .................. 349.1 cfm (9.9 m3/min.) / 442 cfm (12.5 m3/min.)
Displacement .................................................................. 7.5 L (457 in3) SD150 ............. 405.7 cfm (11.5 m3/min.) / 512.3 cfm (14.5 m3/min.)
Bore ........................................................................... 118 mm (4.41 in.) SD180 ............. 478.3 cfm (13.5 m3/min.) / 604.1 cfm (17.1 m3/min.)
Stroke ........................................................................ 115 mm (5.00 in.)
SD200 ................ 529.5 cfm (15.0 m3/min.) / 668 cfm (18.9 m3/min.)
Compression Ratio .................................................................. 16.0-to-1
Number of Main Bearings ....................................................................7
Type of Main Bearings............................................................. Cast Iron Exhaust System:
Aspiration Exhaust Flow at Rated Output at 50 Hz / 60 Hz
SD130/150/180/200 ........................ Turbocharged, Aftercooled (T/A) SD130 ............. 1,079 cfm (30.6 m3/min.) / 1,366 cfm (38.7 m3/min.)
Governed Engine Speed ........................................... See DATA LABEL SD150 ............. 1,254 cfm (35.5 m3/min.) / 1,584 cfm (44.8 m3/min.)
Type of Valve Lifters .......................................................................Solid SD180 ............. 1,479 cfm (41.9 m3/min.) / 1,867 cfm (52.9 m3/min.)
Cylinder Head................................................Cast Iron Overhead Valve SD200 ............. 1,627 cfm (46.4 m3/min.) / 2,065 cfm (58.5 m3/min.)
Pistons ............................................... 6-Heat Resistant Aluminum Alloy Exhaust Outlet Size ..............................................................................5
Crankshaft ......................... Case Hardened, Die Forged, Carbon Steel Exhaust Temperature at Rated Output
Number of Flywheel Teeth................................................................129 Maximum ................................................................ (649° C) 1,200° F
Engine Lubrication System:
Type of Oil Pump Engine Electrical System:
SD130/150/180/200 ....................................................................Gear DC Alternator Output.............................................. 30 amps at 24 volts
Oil Filter .................................................................. Full Flow, Cartridge Starter Motor .........................................................................24-volt DC
Crankcase Oil Capacity ............................................11.6 L (6 U.S. qts.) Recommended Battery.............................Two 12-volt, 135 A.H., 4 DLT
Ground Polarity................................................................... Negative (–)
7
Section 1 – General Information
Standby Generator Sets

‹ ENGINE OIL RECOMMENDATIONS GENERATOR AC LEAD CONNECTIONS


The unit has been filled with 15W-40 engine oil at The electrical wires in the unit’s AC connection
the factory. Use a high-quality detergent oil classified (lower) panel should be installed according to the
“For Service CC, SD, SE or SF.” Detergent oils keep number of leads and the voltage/phase required for
the engine cleaner and reduce carbon deposits. Use the application. If there is any question regarding
oil having the following SAE viscosity rating, based on lead connection, refer to the wiring diagrams at the
the ambient temperature range anticipated before the back of this manual.
next oil change:
Temperature Oil Grade (Recommended) ‹ FOUR-LEAD, SINGLE-PHASE STATOR
Above 80º F (27º C) SAE 30W or 15W-40 Four-lead generators are dual voltage coils or wind-
32º to 80º F (-1º to 27º C) SAE 20W-20 or 15W-40 ings (Figure 1.2). Units may be assigned the following
Below 32º F (0º C) SAE 10W or 15W-40 voltage code:
‹ COOLANT • “A” units are rated 120/240 VAC, single-phase, 60
Hertz.
Use a mixture of half Propylene glycol base antifreeze Each stator winding in this case delivers a 120 VAC
and half de-ionized water. Use only de-ionized water output, and connecting the two windings series
and Propylene glycol antifreeze. When adding cool- results in a 240 VAC output.
ant, always add the recommended 50-50 mixture.
The neutral line is formed by a junction of stator
DANGER leads 22 and 33. Therefore, connection of 120 VAC
(60 Hertz) or 110 VAC (50 Hertz) loads across leads
 Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling
11 and neutral, or across leads 44 and neutral can
be made.
liquid or steam could result.
Figure 1.2 – Four-lead, Single-phase Stator
 Propylene glycol base antifreeze is poisonous.
Do not use mouth to siphon coolant from the
radiator, recovery bottle or any container. Wash
hands thoroughly after handling. Never store
used antifreeze in an open container because
animals are attracted to the smell and taste of
antifreeze even though it is poisonous to them.

 Do not use any chromate base rust inhibitor


with propylene glycol base antifreeze. Using any
high silicate antifreeze boosters or additives also
will cause overheating. We also recommend that
any soluble oil inhibitor is NOT USED for this
equipment.

‹ FUEL SYSTEM REQUIREMENTS


AND RECOMMENDATIONS GENERATOR AND LOAD COMPATIBILITY
• Diesel Fuel System: See Chapter 8 of Engine- The generator must be fully compatible with the
Generator Standby Electric Power Systems rated voltage, phase and frequency of the connected
Installer’s Guide and Reference Manual (part no. electrical loads. The generator, connected electrical
046622). devices, or both, can be damaged if voltage, phase
• Gaseous Fuel System: See Chapter 9 of Engine- and frequency are not compatible.
Generator Standby Electric Power Systems NOTE:
Installer’s Guide and Reference Manual (part no.
This manual assumes that the standby generator
046622).
has been properly selected, installed and inter-
connected by a competent, qualified electrician
or installation contractor. Once the installation is
complete, do nothing that may result in noncom-
patibility between the generator and connected
electrical loads.
8
Section 2 – Installation
Standby Generator Sets

STARTING AIDS
This standby generator is equipped with the follow-
ing starting aids that serve to provide quicker, easier
starts under varying climactic conditions.  Ifis an open bottom is used, the engine-generator
to be installed over non-combustible materi-
This generator has been mounted with an engine als and should be located such that combustible
coolant heater and a battery charger. These aids are materials are not capable of accumulating under
powered by a NORMAL (UTILITY) power source dur- the generator set.
ing nonoperating periods. Only qualified, competent installation contractors
or electricians thoroughly familiar with applicable
‹ ENGINE COOLANT HEATERS codes, standards and regulations should install this
standby electric power system. The installation must
This unit is equipped with an engine coolant (block) comply strictly with all codes, standards and regula-
heater (Figure 1.3), it is powered by a circuit nor- tions pertaining to the installation.
mally fed by the utility power supply. The heater acts
to heat the engine coolant when the unit is not operat- This genset must be insalled on a level surface. The
ing. This action keeps the engine warm even in cold base frame must be level within two (2) inches all
weather, thus helping ensure quicker starts. Heated around.
coolant in the engine rises continuously drawing cold
coolant into the heater, thus making certain of a con-
stant flow of warm coolant through the engine.
 After the system has been installed, do nothing
that might render the installation in noncompli-
Figure 1.3 – Typical Engine Coolant Heater ance with such codes, standards and regulations.
OUTPUT NOTE:
For more information about the installation of a
standby system, order Engine-Generator Standby
Electric Power Systems Installer’s Guide and
Reference Manual (part #046622) from an
Authorized Service Dealer.

‹ NFPA STANDARDS
The following published standards booklets pertain-
ing to standby electric systems are available form
the National Fire Protection Association (NFPA),
Batterymarch Park, Quincy, MA 02269:
• NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES.
‹ BATTERY CHARGERS • NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES.
All generators may be ordered with either a 2A or
10A battery charger installed in the control panel. • NFPA No. 220, STANDARD TYPES OF BUILDING
CONSTRUCTION
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
STANDBY GENERATOR INSTALLATION • NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
DANGER LIQUIDS CODE.
• NFPA No. 10, INSTALLATION, MAINTENANCE AND
 Connecting this generator to an electrical system
normally supplied by an electric utility shall be USE OF PORTABLE FIRE EXTINGUISHERS.
by means of a transfer switch (such as the “GTS”
type transfer switch), so as to isolate the electric
system from the utility distribution system when
the generator is operating. Failure to isolate
the electric system by these means will result in
damage to the generator and may also result in
injury or death to utility workers due to back-
feed of electrical energy.
9
Section 2 – Installation
Standby Generator Sets

‹ OTHER PUBLISHED STANDARDS EMERGENCY CIRCUIT ISOLATION


In addition to NFPA standards, the following informa-
tion pertaining to the installation and use of standby
METHOD
This prevents overloading the generator by keeping
electric systems is available: electrical loads below the wattage/amperage capac-
• Article X, NATIONAL BUILDING CODE, available ity of the generator. If the generator is powering only
from the American Insurance Association, 85 John critical loads, within the wattage/amperage capac-
Street, New York, N.Y. 10038. ity, during utility power outages, consider using the
• AGRICULTURAL WIRING HANDBOOK, obtainable emergency circuit isolation method.
from the Food and Energy Council, 909 University Critical electrical loads are grouped together and
Avenue, Columbia, MO, 65201. wired into a separate “Emergency Distribution Panel.”
• ASAE EP-364.2, INSTALLATION AND Load circuits powered by that panel are within the
MAINTENANCE OF FARM STANDBY ELECTRIC wattage/amperage capacity of the generator set. When
POWER, available from the American Society this method is used, it is difficult to overload the gen-
of Agricultural Engineers, 2950 Niles Road, St. erator. The transfer switch must meet the following
Joseph, MI 49085. requirements:
• A52.1, AMERICAN NATIONAL STANDARD
• It must have an ampere rating equal to the total
FOR CHIMNEYS, FIREPLACES AND VENTING
amperage rating of the emergency distribution
SYSTEMS, available from the American National
panel circuit.
Standard Institute, 1430 Broadway, New York, N.Y.
10018. • Have it installed between the building’s main dis-
tribution panel and the emergency distribution
panel.
BASIC STANDBY ELECTRIC SYSTEM
Figure 2.1 shows a schematic diagram of a basic TOTAL CIRCUIT ISOLATION METHOD
standby electric system. Both the UTILITY power When a generator capable of powering all electrical
supply and the STANDBY (GENERATOR) output are loads in the circuit is to be installed, use the “Total
connected to an approved transfer switch. The trans- Circuit Isolation Method.” It is possible for the gen-
fer switch is required by electrical code and serves erator to be overloaded when this isolation method is
the following functions: employed. The following apply to the transfer switch
• Permits the LOAD circuits to be connected to only in this type of system.
one power supply at a time. • Ampere rating of the transfer switch must equal
• Prevents electrical backfeed between the generator the ampere rating of the normal incoming utility
and the UTILITY power circuits. service.
• The transfer switch is installed between the util-
Figure 2.1 – Basic Standby Electric System ity service entrance and the building distribution
panel.

GROUNDING THE GENERATOR


The National Electrical Code requires the frame and
external electrically conductive parts of this equip-
ment to be properly connected to an approved earth
ground and/or grounding rods. For that purpose, a
GROUND LUG (Figure 2.2) is provided on the gen-
erator mounting base. Consult a qualified electrician
for grounding requirements in the area. Grounding
procedures must meet local regulations.

DANGER
Notice that both the STANDBY and the UTILITY
power supplies to the transfer switch are protected
 Do not connect the ground wire to any pipe
that carries a flammable or explosive substance
against overload by a main line circuit breaker. – FIRE or an EXPLOSION may result.
NOTE: Proper grounding helps protect personnel against
electrical shock in the event of a ground fault condi-
The manufacturer recommends the use of a “GTS” tion in the generator or in connected electrical devic-
type transfer switch in conjunction with this gen- es. In addition, grounding helps dissipate static elec-
erator. tricity that often builds up in ungrounded devices.
10
Section 2 – Installation
Standby Generator Sets

Figure 2.2 – Generator Grounding Lug (typical) BATTERY INSTALLATION


DANGER
 Standby generators installed with automatic
transfer switches will crank and start automati-
cally when NORMAL (UTILITY) source voltage is
removed or is below an acceptable preset level.
To prevent such automatic start-up and pos-
sible injury to personnel, do not connect battery
cables until certain that normal source voltage
at the transfer switch is correct and the system
is ready to be placed into operation.
GENERATOR AC NEUTRAL  Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
CONNECTIONS around the battery for several hours after charg-
The manufacturer uses an UNGROUNDED AC neu-
ing. The slightest spark can ignite the gas and
tral. Grounding is recommended only at the main
cause an explosion. Such an explosion can shat-
service entrance. If the neutral wire is grounded and
ter the battery and cause blindness or other
one of the phase loads becomes grounded, the exces-
injury. Any area that houses a storage battery
sive current opens the load circuit breaker or col-
must be properly ventilated. Do not allow smok-
lapses the generator field. The actual result depends
ing, open flame, sparks or any spark producing
on the electrical characteristics of the particular
tools or equipment near the battery.
installed generator.
 Battery electrolyte fluid is an extremely caus-
tic sulfuric acid solution that can cause severe
TRANSFER SWITCH START SIGNAL burns. Do not permit fluid to contact eyes, skin,
CONNECTIONS clothing, painted surfaces, etc. Wear protective
If the generator is to be installed with a standard goggles, protective clothing and gloves when
automatic transfer switch, such as a GTS-type handling a battery. If fluid is spilled, flush the
switch, it will be necessary to connect the two-wire affected area immediately with clear water.
start control system.
Connect the two-wire start signal from the automatic
transfer switch to the automatic start connection,  Do not dispose of the battery in a fire. The
battery is capable of exploding.
which is located in the lower rear of the AC connec-
tion panel. Match wires 178 and 183 in the transfer
switch to 178 and 183 on the terminal strip in the  Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin
connection box. The conductors for the two-wire and eyes.
start circuit must be in their own conduit.
If the generator is to be install with an HTS-type  The battery represents a risk of high short circuit
current. When working on the battery, always
transfer switch, a different connection method is remove watches, rings or other metal objects,
needed. and only use tools that have insulated handles.
Use shielded 2-wire communications cable (such a
Belden #9460) to make the connection from the HTS ‹ VENTED BATTERIES
transfer switch to the engine generator connection
panel. This cabel is to be routed in a separate conduit
between the HTS transfer switch and the engine gen-
erator. The cable is to be connected as follows:  The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
HTS transfer switch - 4 position terminal block, in conductive and corrosive. The following proce-
the bottom of the transfer switch enclosure (labeled dures are to be observed:
"comm. Ports"). • Wear full eye protection and protective clothing,
Engine generator - terminal strip located in the • Where electrolyte contacts the skin, wash it off
lower rear of the AC connection panel. Connect the immediately with water,
RS485+ and RS485- to the respective terminals in • Where electrolyte contacts the eyes, flush thor-
switch and generator. Do not connect the shield at oughly and immediately with water and seek
transfer switch end. medical attention, and
11
Section 2 – Installation
Standby Generator Sets

• Spilled electrolyte is to be washed down with an Before starting the generator for the first time, the
acid-neutralizing agent. A common practice is to installer must complete the following procedures. For
use a solution of one pound (500 grams) bicarbon- follow-up maintenance information and/or service
ate of soda to one gallon (4 liters) of water. The intervals, please refer to Section 4, “Maintenance,”
bicarbonate of soda solution is to be added until and the “Service Schedule”.
the evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the  Transfer Switch
area dried. If this generator is used to supply power to any elec-
 Lead acid batteries present a risk of fire because
they generate hydrogen gas. The following pro-
trical system normally powered by an electric utility,
the National Electrical Code requires that a transfer
cedure are to be followed: switch be installed. The transfer switch prevents elec-
• DO NOT SMOKE when near batteries, trical backfeed between two different electrical sys-
• DO NOT cause flame or spark in battery area, and tems. (For additional information, see the applicable
transfer switch manual for this unit.) The transfer
• Discharge static electricity from body before touch-
switch, as well as the generator and other standby
ing batteries by first touching a grounded metal
components, must be properly located and mounted
surface.
in strict compliance with applicable codes, standards
Servicing of batteries is to be performed or super- and regulations.
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.
 Fuel System
Make sure the fuel supply system to the generator (a)
For recommended batteries, see “Specifications.” delivers the correct fuel at the correct pressure and (b)
All batteries must be at 100 percent state-of-charge is properly purged and leak tested according to code.
before they are installed on the generator. No fuel leakage is permitted. See “Specifications” for
When using maintenance-free batteries, it is not more information.
necessary to check the specific gravity or electrolyte If the unit has been idle for a long period of time,
level. Have these procedures performed at the inter- or if the fuel lines or system components have been
vals specified in Section 4, “Maintenance.” A nega- removed and reinstalled, the fuel system may require
tive ground system is used. Battery connections are bleeding to remove air from the system. Air in the
shown on the wiring diagrams. Make sure all batter- fuel system causes hard starting and rough opera-
ies are correctly connected and terminals are tight. tion. All fuel system lines must be installed and must
Observe battery polarity when connecting batteries be tight. A loose line may show no sign of leakage, but
to the generator set. may draw air into the system.
NOTE:
Damage will result if the battery connections are
made in reverse.
 Use a suitable container to catch the fuel that
will spill during system bleeding process. Clean
PREPARATION BEFORE START-UP up all spilled fuel after bleeding.
The instructions in this section assume that the
standby generator has been properly installed, ser-  Generator Set Lubrication
viced, tested, adjusted and otherwise prepared for Check the engine crankcase oil level before operating
use by a competent, qualified installation contractor. and add oil to the proper level – the dipstick “FULL”
Be sure to read the “Safety Rules” on Pages 2 and 3, mark. Never operate the engine with the oil level
as well as all other safety information in this manual, below the dipstick “ADD” mark. See “Specifications”
before attempting to operate this (and related) equip- and “Engine Oil Recommendations”.
ment.
NOTE:
‹ PRIOR TO INITIAL START-UP This engine is shipped from the manufacturer
with 15W-40 oil. This oil should be changed after
30 hours of operation.

 Prior to initially starting the generator, it must


be properly prepared for use. Any attempt to
The engine is equipped with a mechanical governor.
Make sure the governor is properly lubricated with
crank or start the engine before it has been clean engine oil.
properly serviced with the recommended types
and quantities of engine fluids (oil, coolant, fuel,
etc.) may result in an engine failure.
12
Section 3 – Operation
Standby Generator Sets

 Engine Coolant • White copy: Mail to Generac Warranty Department,


P.O. Box 8, Waukesha, WI 53187.
Have the engine cooling system properly filled with
the recommended coolant mixture. Check the system • Pink Copy: For service file of installing dealer.
for leaks and other problems. See “Specifications” • Yellow Copy: For the customer’s records.
and “Coolant”.
GENERATOR CONTROL AND
 Belt Tension
Check-the engine-fan belt tension and condition prior
OPERATION
Refer to the appropriate control panel operator’s
to placing the unit into service and at recommended manual for this unit.
intervals. Belt tension is correct when a force of
approximately 22 pounds (10 kg), applied midway
between pulleys, deflects the belt about 3/8- to 5/8-
OPERATING UNIT WITH MANUAL
inch (10 to 16 mm). TRANSFER SWITCH
If the generator was installed in conjunction with a
 Electrical System transfer switch capable of manual operation only, the
Make sure the generator is properly connected to an following procedure applies. A manually operated
approved earth ground. transfer switch is one that will not provide automatic
start-up and does not include an intelligence circuit.
Make sure the generator battery is fully charged,
properly installed and interconnected, and ready for
use. ‹ ENGINE START-UP AND TRANSFER
Check to ensure that there are no loose electrical con- For additional information, refer to the applicable
nections. Restrain any loose wires to keep them clear control panel manual for this unit, as well as any lit-
of any moving generator set components. erature pertaining to the transfer switch.

 Rodent Protection DANGER


Make sure the four, 3-inch diameter cap plugs (part
no. 0A8785) are properly installed in the tie-down  The Maintenance Disconnect Switch and the
AUTO/OFF/MANUAL switches (if so equipped)
holes in the side rails of the unit’s base frame (Figure must be set properly, or the generator will crank
2.3). The cap plugs are shipped in a plastic bag and start as soon as the UTILITY power to the
located in the lower connection box. These plugs are transfer switch is turned off. Refer to applicable
needed to prevent rodents from accessing the interior control panel and transfer switch manuals for
of the generator set. On acoustic units, cap plugs also more information.
are needed to stay within noise specification limits.
 Do not proceed until certain that utility source
voltage is available to the transfer switch and
Figure 2.3 – Base Frame Cap Plugs
the transfer switch main contacts are set to
UTILITY.

 Do not attempt manual operation until all


power supplies to the transfer switch have been
positively turned off, or extremely dangerous
— possibly lethal — electrical shock
will result.

 Transfer switch enclosure doors should be kept


closed and locked. Only authorized personnel
should be allowed access to the transfer switch
interior. Extremely high and dangerous voltages
are present in the transfer switch.
‹ START-UP INSPECTION In order to transfer load from the utility source to the
generator, follow these directions:
A standard three-part form titled “Start-up Inspection
for Standby Power Systems” (part no. 067377) • Turn OFF or disconnect the utility power circuit
should be completed by the installation technician or to the transfer switch, using the means provided
engineer. As stated on the form, inspections are to be (such as the utility source main line circuit break-
accomplished only by factory-trained personnel. The er).
installer should complete the form and disseminate
copies as follows:
13
Section 4 – Maintenance
Standby Generator Sets

• Set the transfer handle to its UTILITY (NORMAL)


position with load circuits connected to the utility
SERVICE SCHEDULE
power supply. ‹ AUTHORIZED OPERATOR MAINTENANCE
• Set the standby generator’s main line circuit break-
er to its OFF (or OPEN) position. FUNCTIONS
• Start the generator.
 Every Month or 100 Hours (whichever comes first)
• Test standby generator system.
• Inspect battery (batteries) and cables.
 Do not crank the engine continuously for longer
than 30 seconds, or the heat may damage the
• Check engine oil level.
• Check gearbox oil level (if so equipped).
starter motor. • Check engine coolant level.
• Let engine stabilize and warm up. • Check generator ground connections.
• Check all applicable instrument and gauge read- • Test/inspect starting aids.
ings. When certain that all readings are correct,
move the transfer switch manual handle to its  Every Three Months or Every 120 Hours
STANDBY (GENERATOR) position, i.e., load cir- (whichever comes first)
cuits supplied by the generator.
• Inspect and test fuel system and connections.
• Set the standby generator’s main line circuit break-
er to its ON (or CLOSED) position. • Inspect exhaust system.
• Load circuits are now powered by the standby gen- • Inspect/test fuel supply system.
erator.
‹ AUTHORIZED SERVICE TECHNICIAN
‹ RETRANSFER AND SHUTDOWN MAINTENANCE FUNCTIONS
For additional information, refer to the applicable
control panel manual for this unit, as well as any lit-  After First 30 Hours of Operation
erature pertaining to the transfer switch. • Inspect wiring.
To transfer the load back to the utility power source • Change engine crankcase oil and oil filter.
and shut down the generator, follow these direc- • Inspect engine fan belts.
tions: • Inspect battery (batteries) and cables.
• Set the standby generator’s main line circuit break-  Every Six Months or Every 200 Hours
er to its OFF (or OPEN) position.
(whichever comes first)
• Manually move the transfer switch handle to its
UTILITY (NORMAL) position, i.e., load circuits • Change engine oil and filter.
connected to the utility. • Lubricate engine controls.
• Turn ON the utility power supply to the transfer • Service engine air cleaner.
switch, using the means provided (such as the util- • Service engine fuel filter.
ity power source main line circuit breaker). • Inspect AC generator.
• Let the generator run at no-load for a few minutes • Test engine safety controls.
to stabilize internal temperatures. • Inspect fan belts.
• Shut down the generator. • Check engine coolant level.
• Inspect engine cooling system hoses.
OPERATING UNIT WITH AUTOMATIC • Check optional starting aids.
TRANSFER SWITCH • Check battery (batteries).
If the generator has been installed along with an auto- • Check engine compression.
matic transfer switch, such as a GTS-type switch, the • Check electrical connections.
engine may be started and stopped automatically or • Check/test annunciator panel.
manually. • Perform operational test.
NOTE:
Refer to the applicable manual for the trans-
fer switch and to “Transfer Switch Start Signal
Connections”. In addition, please note the dangers
under “Engine Start-up and Transfer.”

14
Section 4 – Maintenance
Standby Generator Sets

 Annually or Every 600 Hours ‹ TEST STANDBY GENERATOR SYSTEM


(whichever comes first) OPERATION AND COMPONENTS
• Check engine valve clearance. An authorized operator should test the operation of
• Test fuel injection nozzles. the standby generator system and inspect its compo-
• Test injection timing. nents monthly (or 100 hours). This should include
• Inspect all wiring. inspecting the transfer switch for evidence of arc-
• Test engine starter operation. ing, and pitted or burned contacts; inspecting wir-
• Drain water from fuel tank. ing and grounding connections (see “Grounding the
• Retorque fan bolts. Generator”); and ensuring that starting devices are
operational. During this operational test, all instru-
• Drain and refill gearbox (If so equipped, contact ment and gauge readings should be recorded in a
sales for availability.) “Maintenance Log.” The transfer system also should
 Every Two Years be tested at this time; the engine should be run at
least 30 minutes and any discrepancies corrected
• Replace all rubber hoses. immediately.
• Replace engine fan belts.
Every six months (or 200 hours), an Authorized
• Inspect the Standby Generator System.
Service Technician should perform a system opera-
• Drain, flush, refill cooling system. tional test.
 Every 1,000 Operating Hours
• Inspect engine DC alternator. ‹ INSPECT BATTERY
• Inspect engine starter.
• Retorque engine mounting brackets.
DANGER


Remove/test fuel injection pump.
Remove/test cooling system thermostat.  Standby generators installed with automatic
transfer switches will crank and start automati-
cally when NORMAL (UTILITY) source voltage is
 As Required removed or is below an acceptable preset level.
• Bleed engine fuel system. To prevent such automatic start-up and pos-
sible injury to personnel, do not connect battery
PERIODIC MAINTENANCE cables until certain that normal source voltage
A rigorous program of scheduled periodic mainte- at the transfer switch is correct and the system
nance should be established and maintained. Such a is ready to be placed into operation.
program, if adhered to diligently, will provide added
assurance that the power system functions properly
 Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
when it is needed. around the battery for several hours after charg-
Keeping a “Maintenance Log” is highly recommended. ing. The slightest spark can ignite the gas and
Such a log should be a continuous record of repairs, cause an explosion. Such an explosion can shat-
parts replacements, gauge and instrument readings ter the battery and cause blindness or other
during operational tests, etc. injury. Any area that houses a storage battery
must be properly ventilated. Do not allow smok-
The manufacturer recommends that a “Customer ing, open flame, sparks or any spark producing
Maintenance Inspection Agreement” be established tools or equipment near the battery.
between the user of this equipment and the install-
ing Authorized Service Dealer. Under this agreement,
(Part No. 053263), an Authorized Service Technician
performs prestart and engine running tests and
checks at six-month and one-year intervals. Ask an
Authorized Service Dealer about this agreement.
The tasks listed in the “Service Schedule” cover the
minimum recommended maintenance requirements
for this equipment.
Note that many of the tests and checks listed in the
schedule are to be performed only by an Authorized
Service Technician. Fluid capacities and recommen-
dations, as well as other applicable specifications,
are listed in “Specifications”.
15
Section 4 – Maintenance
Standby Generator Sets

‹ INSPECT EXHAUST SYSTEM


 Battery electrolyte fluid is an extremely caus-
tic sulfuric acid solution that can cause severe Every three months (or 120 hours), an authorized
burns. Do not permit fluid to contact eyes, skin, operator should inspect the entire exhaust system.
clothing, painted surfaces, etc. Wear protective Abnormal noise levels heard during each operational
goggles, protective clothing and gloves when test may indicate a defective exhaust pipe or muf-
handling a battery. If fluid is spilled, flush the fler. Any defective or leaking component should be
affected area immediately with clear water. repaired or replaced immediately by an Authorized
Service Technician.

‹ INSPECT/TEST FUEL SUPPLY SYSTEM


 Do not dispose of the battery in a fire. The
battery is capable of exploding. Every three months (or 120 hours), an authorized
operator should inspect and test the fuel supply sys-
 Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin tem, as well as all fuel system connections. All con-
and eyes. nections must be tight and in good condition. A loose
fuel system line may show no signs of leakage, but
 The battery represents a risk of high short circuit
current. When working on the battery, always
may draw air into the system causing rough opera-
tion and starting difficulties. Any defective or leaking
remove watches, rings or other metal objects, and component should be repaired or replaced immedi-
only use tools that have insulated handles. ately by an Authorized Service Technician.
An authorized operator should inspect the engine
battery system monthly (or 100 hours). At this time,
the battery fluid level should be checked and distilled REPAIR PARTS
water added if needed. Battery cables and connec- The latter portion of this manual consist of exploded
tions also should be inspected for cleanliness and views, parts lists and electrical data pertaining to this
corrosion. generator set. The parts lists consist of (a) an item
number, (b) a part number, (c) the quantity required,
Once every six months (or 200 hours), an Authorized and (d) a description of the part. The item number
Service Technician should inspect the battery system. corresponds to an identical number on the exploded
At this time the battery condition and state of charge view drawing.
should be checked using a battery hydrometer. The
battery should be recharge or replaced as required.
‹ GENERATOR SET XPL LABEL
‹ BATTERY REPLACEMENT Every generator set has a XPL LABEL affixed to the
lower connection box (Figure 4.1). Additionally, a
When replacing batteries, use the same number and printed CONSTRUCTION DOCUMENT containing
the following type batteries. identical information can be found at the end of this
Part No. BCI Group No. CCA manual.
058665 27F 700 @ 0 deg. F When requesting information, ordering replacement
parts, asking for service, etc., one or more of the fol-
NOTE: lowing may be needed:
The BCI number should be located directly • Generator Model Number
on the battery. For more information, see • Date of Manufacture
“Specifications.” • Generator Identification Code
• Generator Assembly Groups
‹ CHECK FLUIDS
An authorized operator should check the levels
of engine oil, and engine coolant monthly (or 100
hours). The oil level should be maintained between
the “FULL” and “ADD” marks on the engine dip-
stick. Recommended fluids are listed are in the
"Specifications" section.

16
Section 4 – Maintenance
Standby Generator Sets

Figure 4.1 — XPL Label ‹ HOW TO ORDER PARTS


GENERAC POWER SYSTEMS To order a replacement part, locate the part in the
applicable exploded view. Contact an Authorized
MODEL NO. 00A 00000 S DATE 00/00/06 Service Dealer (call 800-333-1322 to locate one in the
(Generator ID Code) area) and provide the following information:
• The generator model number.
GROUP DESCRIPTION ASSEMBLY NUMBERS
• The generator identification code, which indicates
A Generator 00000 00000 the specific generator assembly for each unit.
B Control Panel 00000 00000 00000 • The part number and corresponding description
C Mounting Base 00000 00000 00000 from the applicable parts list in this manual.
D Engine & Accy. 00000 00000
E Fuel Systems 00000
• The applicable exploded view “Group” letter (A-H)
F Compartments 00000 00000
and drawing number (five-digit number), which
G Wiring Diagrams 00000 00000 00000
can be found on the exploded view drawing.
H Kits 00000 00000 NOTE:
In most cases, repair parts can be obtained by
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE providing the Authorized Service Dealer with the
ABOVE INFORMATION data label information and a description of the
required part. If unable to locate either the data
NOTE: label or the construction document, describe the
The above is a generic representation of a data part needed and provide the unit’s model number.
card. For actual information related to this par- This number can be found on the DATA LABEL
ticular model, please refer to the “construction attached to the generator’s lower connection box.
document” located at the end of this manual, or to
the data cards affixed to the unit.

17
Section 5 – Warranty
Standby Generator Sets

NOTE: This Emission Control Warranty Statement applies only to mobile (trailerized) non-road diesel engine powered
generators (model year 2000) as follows: The EPA portion of this statement pertains to this product; The CARB portion
of this statement pertains to this product only IF the generator size is (1) 15 kW or below OR (2) 130 kW or greater.

CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT


YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and the United States Environmental Protection Agency (EPA), together with
Generac Power Systems, Inc. (Generac), are pleased to explain the Emission Control System Warranty on your new non-road
diesel engine.* New non-road diesel engines must be designed, built and equipped to meet stringent anti-smog standards
for the state of California and the federal government. Generac will warrant the emission control system on your non-road
diesel engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or
improper maintenance of your non-road diesel engine.
Your emission control system may include such parts as the fuel injection system and the air induction system. Also included
may be hoses, belts, connectors and other emission-related assemblies. Generac will repair your non-road diesel engine at
no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.

MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:


Emission control systems on 1996 and later model year non-road diesel engines are warranted for five years, or 3,000 hours
of use, whichever occurs first. In the absence of an hourmeter, the said coverage is five years. If, during said warranty period,
any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or
replacement will be performed by a Generac Authorized Warranty Service Facility.

PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:


As the non-road diesel engine purchaser/owner, you are responsible for the completion of all required maintenance as listed
in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering
maintenance of your non-road diesel engine. However, Generac cannot deny warranty solely due to lack of receipts or for
your failure to ensure the completion of all scheduled maintenance.
As the non-road diesel engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all war-
ranty coverage or responsibility if your non-road diesel engine, or a part/component thereof, has failed due to abuse, neglect,
improper maintenance or unapproved modifications., or the use of counterfeit and/or “grey market” parts not made, sup-
plied or approved by Generac.
Your engine is designed to operate on diesel fuel only. Use of any other fuel may result in your engine no longer operating in
compliance with federal or California emission requirements.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:

1-800-333-1322
IMPORTANT NOTE: This Warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to federal and California law. See also the “Generac
Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you
by Generac. The ECS Warranty applies only to the emission control system of your new non-road diesel engine. If there is
any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circum-
stances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac describe
important rights and obligations with respect to your new non-road diesel engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser-
vice, evidence must be presented showing the date of sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the
following address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
211 MURPHY DRIVE
EAGLE, WI 53119
Part 1
18
Section 5 – Warranty
Standby Generator Sets

EMISSION CONTROL SYSTEM WARRANTY


Emission Control System Warranty (ECS Warranty) for 1996 and later model year non-road diesel engines:
(a) Applicability: This warranty shall apply to 1996 and later model year non-road diesel engines. The ECS Warranty shall
begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall
continue for 60 months, or 3,000 hours of use, thereafter, whichever occurs first.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new non-road
diesel engine or equipment, and to each subsequent purchaser/owner, that each non-road diesel engine is …
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the EPA and CARB pursuant
to their respective authority, and
(2) Free from defects in materials and workmanship, which, at any time during the ECS Warranty Period, may cause a
warranted emission-related part to fail to be identical in all material respects to the part as described in the engine
manufacturer’s application for certification.
(c) The ECS Warranty pertains only to emissions-related parts on your non-road diesel engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace
as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty
shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair and replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner by a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emissions-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emissions-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
warranty maintenance or repairs and will be provided without charge to the owner. Such use will not reduce Generac’s
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
non-road diesel engine. Such use voids this ECS warranty and shall be sufficient grounds for disallowing an ECS
Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac non-road
diesel engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System: 3) Exhaust System:
a) Fuel injection system a) Exhaust manifold and gasket (turbocharged engines
only)
2) Air Induction System: b) Catalytic converter (if so equipped)
a) Intake manifold and gasket
b) Turbocharger systems (if so equipped) 4) Miscellaneous Items used in above systems:
c) Charge air cooling systems (if so equipped) a) Hoses, connectors, assemblies, clamps, fittings, tubing,
sealing gaskets or devices, and mounting hardware

*Generac non-road diesel engine types covered by this warranty statement include the following:
1) Standby Generator
Part 2

19
Section 5 – Warranty
Standby Generator Sets

GENERAC POWER SYSTEMS STANDARD TWO-YEAR LIMITED WARRANTY


FOR STANDBY POWER SYSTEMS
NOTE: ALL UNITS MUST HAVE A START-UP INSPECTION PERFORMED BY AN AUTHORIZED GENERAC DEALER.
For a period of two (2) years or two thousand (2,000) hours of operation from the date of sale, which ever occurs first, Generac Power Systems, Inc.
will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified
Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule
set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/Certified Generac Power
Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby" applications, as Generac
Power Systems, Inc. has defined Standby, provided said generator has been initially installed and/or inspected on-site by an Authorized/Certified
Generac Power Systems Dealer, or branch thereof. Scheduled maintenance, as outlined by the generator owner's manual, must be performed by an
Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the warranty
period. This warranty is limited to and available only on Liquid-cooled units.
WARRANTY SCHEDULE
YEAR ONE — One hundred percent (100%) coverage on mileage, labor, and parts listed.
• ALL COMPONENTS — ENGINE, ALTERNATOR, AND TRANSFER SWITCH
YEAR TWO — One hundred percent (100%) coverage on parts listed.
• ALL COMPONENTS — ENGINE, ALTERNATOR, AND TRANSFER SWITCH PARTS ONLY
Gearbox Equipped Units - Limited Gearbox Coverage
YEARS ONE THROUGH FIVE — Parts and labor coverage on gearbox and components.
YEARS SIX THROUGH TEN — Parts only coverage on gearbox and components.
Guidelines:
Travel allowance is limited to 300 miles maximum, and 7.5 hours maximum (per occurrence), round trip, to the nearest authorized Generac Service
Facility, and only applies to permanently wired and mounted units.
• Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or
branch thereof.
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the generator set. If a Non-Generac Power
Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the generator set, no warranty coverage shall apply.
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, Procedures and Flat Rate Manual.
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
• Unit enclosure is only covered during the first year of the warranty provision.
• Use of Non-Generac replacement part(s) will void the warranty in its entirety.
• Engine coolant heaters (block-heaters), heater controls and circulating pumps are only covered during the first year of the warranty provision.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
1. Any unit built/manufactured prior to July 1, 2004.
2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).
3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.
4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems has defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and
warranty.
5. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.
6. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
7. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.
8. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s).
9. Damage related to rodent and/or insect infestation.
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.
11. Telephone, facsimile, cellular phone, satellite, Internet, or any other communication expenses.
12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.).
13. Overtime, holiday, or emergency labor.
14. Modes of transportation deemed abnormal (refer to Generac Power Systems Warranty, Policies, Procedures and Flat Rate Manual).
15. Steel enclosures that are rusting due to improper installation, location in a harsh or saltwater environment or scratched where integrity of paint
applied is compromised.
16. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem.
17. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limi-
tations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT
SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A
DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/
owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner
specific legal rights. Purchaser/owner also may have other rights that vary from state to state.
Generac Power Systems, Inc. • P.O. Box 8 • Waukesha, WI 53187
Ph: (262) 544-4811 • Fax: (262) 544-4851 Bulletin 0166290SBY / Printed in U.S.A. 6.04

Printed in U.S.A.
Notes
Standby Generator Sets

21
1 1 GENERATOR
2 1 BOX, CONNECTOR
3 2 SUPPORT, CONNECTION BOX
4 4 BRACKET-CONNECTION BOX
5 052250 1 TAPE FOAM 1 X 1 (63”)
6 022131 16 WASHER FLAT 3/8-M10 ZINC
7 046526 8 WASHER LOCK M10
8 045772 8 NUT HEX M10-1.5 G8 YEL CHR
9 049814 8 SCREW HHC M10-1.5 X 25 G8.8
10 056326 1 TRIM VINYL BLACK 1/8GP (63”)
1 080774 1 LOWER PANEL 520-LAM
0E0185 1 WELDMENT CONBOX 520/900A+
080774F ++ 1 CONNECTION BOX SHORT 52MM 520S
2 073392 1 PANEL REAR COVER
3 0D7949 1 BLANK COVER LOWER CONBOX 520
0E0212 1 BLANK COVER 520/900A+
4 022473 21/25 WASHER FLAT 1/4 ZINC
5 022097 21/25 WASHER LOCK M6-1/4
6 022287 21/25 SCREW HHC 1/4-20 X 3/4 G5
7 045452S REF NAMEPLATE DATA
9 ++ 0E5885 1 REAR COVER, LOWR PNL SHORT BOX
11 ++ 022203 4 SCREW HHC 1/4-20 X 1-1/4 G5
15 0D2481 1 HARNESS LOWER PANEL 520
(046357) REF. BLOCK TERM 20A 6 X 6 X 1100V
16 022155 2 WASHER LOCK #6
17 036904 2 SCREW PPHM #6-32 X 3/4
18 0D3388 1 DECAL REMOTE START CONNECTION
19 022985 2 WASHER FLAT #6 ZINC
20 022129 6 WASHER LOCK M8-5/16
22 + 058710 3 TRANSFRM 200A TO 5A 5VA
058377 3 TRANSFRM 300A TO 5A 12.5VA
057909 3 TRANSFRM 400A TO 5A 12.5VA
059923 3 TRANSFRM 500A TO 5A 12.5VA
059925 3 TRANSFRM 600A TO 5A
059926 3 TRANSFRM 800A TO 5A
23 +++ 022145 6 WASHER FLAT 5/16-M8 ZINC
24 +++ 039253 6 SCREW HHC M8-1.25 X 20 G8.8
25 056326 1 VINYL TRIM BLACK 1/8 GP (63” LG)
30 * 056739 1 RELAY SOLENOID 12VDC PANEL MOUNT
082982 1 RELAY SOLENOID 24VDC
31 * 022473 2 WASHER FLAT 1/4 ZINC
32 * 022097 2 WASHER LOCK M6-1/4
33 * 022287 2 SCREW HHC 1/4-20 X 3/4 G5
34 052250 1 TAPE FOAM 1 X 1 (63” LG)

* QUANTITIES DOUBLE FOR DIESEL UNITS

+ QTY: 2 FOR SINGLE PHASE UNITS

++ FOR 150-180KW 7.5L MITSUBISHI C-GROUP ONLY/7.1L DUETZ

+++ QTY. 4 FOR SINGLE PHASE UNITS


1 0A2865A * 1 STATOR ASSEMBLY 520 150KW 57 090152 1 BRIDGE RECTIFIER ASSEMBLY
0A2865B ** 1 STATOR ASSEMBLY 520 200KW 58 092261 3 BOARD SOLID LEAD TERMINAL
0A2865C 1 STATOR ASSEMBLY 520 250KW 59 039287 6 SCREW HHC M8-1.25 X 45 G8.8
0A2865D 1 STATOR ASSEMBLY 520 300KW 60 095152 12 SCREW SHM M10-1.5 X 40.5
0A2865E 1 STATOR ASSEMBLY 520 350KW 61 095586 12 WASHER FLAT .41 ID X .75 OD
0A2865L 1 STATOR ASSEMBLY 520 400KW 62 096139 12 NUT HEX JAM M10-1.5
0A6424 1 STR-520-210QP2 SAE X 63 095153 6 PLATE JUMPER
2 0F2199A 1 ASSY RTR 520 150KW 4P 1800 DD 64 0A7633 1 SCREW HHC M20-1.5 X 35 G8.8
0F2199B 1 ASSY RTR 520 200KW 4P 1800 DD 65 0C8129 *** 1 DEFLECTOR 13.3L IRR
0F2199C 1 ASSY RTR 520 250KW 4P 1800 DD 66 0A2110 2 SCREW SWAGE 1/4-20 X 1/2 ZYC
0F2199D 1 ASSY RTR 520 275KW 4P 1800 DD 67 0D8468 ++ 6 WASHER LOCK M12 RIBBED
0F2199E 1 ASSY RTR 520 330KW 4P 1800 DD 68 022097 4 WASHER LOCK M6-1/4
0F2199F 1 ASSY RTR 520 400KW 4P 1800 DD 69 0A1786 .5CC ADH LOCTITE #8931 AA W/S
0F2199M 1 ASSY RTR 520 150KW 4P 1PH DD
0F2199N 1 ASSY RTR 520 200KW 4P 1PH DD
3 0G5957 REF HUB, MACHINED 520 ALT, 14MM * NOTE: ALSO USED FOR 105KW IRRIGATION
4 081825 + 1 KEY SQ 16MM X 76MM STEEL
5 081831 + 1 BALL BEARING SINGLE ROW ** NOTE: ALSO USED FOR 160KW IRRIGATION
6 0E4891 1 FAN 520MM CAST ALUMINUM
7 049814 6 SCREW HHC M10-1.5 X 25 G8.8 *** NOTE: USED ON 105/160KW IRRIGATION
8 022129 6 WASHER LOCK M8-5/16 ONLY.
9 022145 6 WASHER FLAT 5/16 ZINC
10 0A2716 + 1 WASHER FLAT .813 ID X 4.0 OD + ROTOR REPLACEMENT PARTS
11 0A7633 + 1 SCREW HHC M20-1.5 X 35 G8.8
12 021322A REF FLEX PLATE,520,SAE11-1/2,14MM ++ USED ON 7.5L MITSUBISHI
021406A REF FLEX PLATE SAE 14 M14 BOLTS
13 0G5956 6 M14-1.5 X 45 BOLT, CLASS 10.9
15 0G5961 6 WASHER FLAT M14, CLASS 10
16 0A7092 1 SCROLL ASSEMBLY 520 SAE (ITEMS 17-23)
17 0A2727 2 SHROUD 520 SAE
18 0A2729 2 SCREEN 520 SHROUD
19 056326 1 TRIM VINYL BLACK 1/8 GP (160” LG)
20 045757 4 SCREW HHC M6-1.0 X 25 G8.8
21 022097 4 WASHER LOCK M6-1/4
22 022473 4 WASHER FLAT 1/4-M6 ZINC
23 0A2110 12/20 SCREW SWAGE 1/4-20 X 1/2 Z/YC
24 0A7671 1 CARRIER REAR BEARING (MACH)
25 0A5615 4 SCREW HHC M16-2 X 170 G8.8
26 021504 4 WASHER TRIANGLE 520 SAE
27 070265 4 WASHER LOCK M16
28 0A5618 4 NUT HEX M16-2.00 G8 YEL CHR
29 085369 1 SPACER 520 ROTOR BEARING
30 094511 1 STATOR ASSEMBLY PME 520MM
0C8011 1 STATOR ASSEMBLY PME 13.3IR
31 080934 1 RING PME STATOR RETAINING
32 082460 4 SCREW SHC M6-1.0 X 65 G10.9
33 022473 4 WASHER FLAT 1/4 ZINC
34 0A7821 1 COLLAR SLIP FIT 116.7MM
35 084828 1 HOUSING 520 PME MAGNET
36 042558 1 KEY SQ 3/8 X 1 STEEL
37 080933 1 FAN PME COOLING
38 0A7807 1 COLLAR SLIP FIT 92.5MM
0A7808 1 COLLAR SLIP FIT 108MM
39 021147 1 EXCITER FIELD 2-3/4"
021148 1 EXCITER FIELD 3-3/4"
0C8012 1 EXCITER FIELD 2-3/4" IRRIG.
40 072878 1 KEY SQ 3/8 X 3-1/4 STEEL
0E7708 1 KEY SQ 3/8 X 4 1/4 STEEL
41 0F5992 1 ASSY EXCITER 2-3/4"
0F5993 1 ASSY EXCITER 3-3/4"
42 04576100CB 4 STUD M10-1.5 X 320 G5 ZINC
43 022131 22 WASHER FLAT 3/8-M10 ZINC
44 046526 22 WASHER LOCK M10
45 045772 16 NUT HEX M10-1.5 G8 YEL CHR
47 081814 1 WASHER LOCK M20
48 0E9107 1 MOUNT RECTIFIER
51 089520 2 SCREW PFHM M4-0.7 X 16
53 023365 2 WASHER SHAKEPROOF INT #8
55 043180 2 WASHER FLAT M4
1) N/A N/A UL CIRCUIT BREAKER ED E 0F7836 2 ANGLE CB MOUNT 520
A N/A N/A SEE TABLE PART NUMBER 0D8789 F 0F7841 1 MOUNT CB LMD 520
B 0F7053 1 KIT COVER CB ED 520 G 0E2962 2 INSULATOR (NOMEX)
0F8031 1 KIT COVER CB ED/AC 520 H 049814 12 SCREW HHC M10-1.5 X 25 G8.8
C 0F7048 1 COVER CB ED 520 TOP I 070264 12 WASHER FLAT M10
0F7699 1 COVER CB ED/AC 520 TOP J 046526 12 WASHER LOCK M10
D 0F7048A 1 COVER CB ED 520 BOTTOM K 045772 12 NUT HEX M10-1.5 G8 YEL CHR
0F7699A 1 COVER CB ED/AC 520 BOTTOM L 065960 4 SCREW SHC 1/4-20 X 4 G8.8 NZ
E 066715 4 SCREW RHM #8-32 X 4-1/2 M 022473 4 WASHER FLAT 1/4-M6 ZINC
F 038150 8 WASHER FLAT #8 ZINC N 022097 4 WASHER LOCK M6-1/4
G 022264 4 WASHER LOCK #8-M4 O 022127 4 NUT HEX 1/4-20 STEEL
H 022471 4 NUT HEX #8-32 STEEL P 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS
I 0A8278 3 SCREW SHC 1/4-28 X 3/4 G8.8 NZ Q 026076 6 SCREW SHC 3/8-16 X 1.5 G8.8 NZ
J 022097 3 WASHER LOCK M6-1/4 R 022131 15 WASHER FLAT 3/8-M10 ZINC
K 0D5621 3 WASHER-STEP 1/2 OD X 9/32 ID BRASS S 022237 15 WASHER LOCK 3/8
L 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS T 022241 9 NUT HEX 3/8-16 STEEL
U 026082 9 SCREW HHC 3/8-16 X 2-1/4 G5
2) N/A N/A UL CIRCUIT BREAKER FD V 0G0732 2 BUS BAR CB TO LEAD SHORT 95MM
A N/A N/A SEE TABLE PART NUMBER 0D8789 W 0G0732A 1 BUS BAR CB TO LEAD TALL 145MM
B 0F7054 1 KIT COVER CB FD 520
C 0F7049 1 COVER CB FD 520 TOP 6) 0D6684 1 KIT NEUTRAL UPTO 600A (520/MAR)
D 0F7049A 1 COVER CB FD 520 BOTTOM PARTS SHOWN BELOW (I/N: A-L)
E 081320 4 SCREW SHC 1/4-20 X 4.5 G8.8 NZ A 0D6683 1 ASSY NEUTRAL UPTO 600A (520)
F 022473 8 WASHER FLAT 1/4-M6 ZINC B 057073 2 JUNCTION BLOCK 3/8-16
G 022097 4 WASHER LOCK M6-1/4 C 022152 8 WASHER LOCK #10
H 022127 4 NUT HEX 1/4-20 STEEL D 033530 4 SCREW PHM #10-32 X 5/8 CAD
I 048527 3 SCREW SHC 3/8-16 X 3/4 G8.8 NZ E 022237 2 WASHER LOCK 3/8
J 022237 3 WASHER LOCK 3/8 F 022241 8 NUT HEX 3/8-16 STEEL
K 022131 3 WASHER FLAT 3/8-M10 ZINC G 022131 6 WASHER FLAT 3/8-M10 ZINC
L 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS H 022237 6 WASHER LOCK 3/8
J 0D7484 1 BRACKET NEUTRAL BLOCK 0-1600A
3) N/A N/A UL CIRCUIT BREAKER JD K 022097 2 WASHER LOCK M6-1/4
A N/A N/A SEE TABLE PART NUMBER 0D8789 L 022287 2 SCREW HHC 1/4-20 X 3/4 G5
B 0F7055 1 KIT COVER CB JD 520 M 022473 4 WASHER FLAT 1/4-M6 ZINC
C 0F7050 1 COVER CB JD 520 TOP N 022127 2 NUT HEX 1/4-20 STEEL
D 0F7050A 1 COVER CB JD 520 BOTTOM P 023897 8 WASHER FLAT #10 ZINC
E 081320 4 SCREW SHC 1/4-20 X 4.5 G8.8 NZ Q 022158 4 NUT HEX #10-32 STEEL
F 022473 8 WASHER FLAT 1/4-M6 ZINC
G 022097 4 WASHER LOCK M6-1/4 7) 0D6684A 1 KIT NEUTRAL 700-1600A (520)
H 022127 4 NUT HEX 1/4-20 STEEL PARTS SHOWN BELOW (I/N: A-L)
I 048527 3 SCREW SHC 3/8-16 X 3/4 G8.8 NZ A 0D6683A 1 ASSY NEUTRAL 700-1600A (520)
J 022237 3 WASHER LOCK 3/8 B 057073 2 JUNCTION BLOCK 3/8-16
K 022131 3 WASHER FLAT 3/8-M10 ZINC C 022152 8 WASHER LOCK #10
L 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS D 033530 4 SCREW PHM #10-32 X 5/8 CAD
E 022237 2 WASHER LOCK 3/8
4) N/A N/A UL CIRCUIT BREAKER ND F 022241 8 NUT HEX 3/8-16 STEEL
A N/A N/A SEE TABLE PART NUMBER 0D8789 G 022131 6 WASHER FLAT 3/8-M10 ZINC
B 0F7525 1 KIT COVER CB ND 520 1 PHASE H 022237 6 WASHER LOCK 3/8
0G0738 1 KIT COVER CB ND 520 3 PHASE J 0D7484 1 BRACKET NEUTRAL BLOCK 0-1600A
C 0F7523 1 COVER CB ND 520 TOP K 022097 2 WASHER LOCK M6-1/4
D 0F7524 1 COVER CB ND 520 BOTTOM L 022287 2 SCREW HHC 1/4-20 X 3/4 G5
E 0F7836 2 ANGLE CB MOUNT 520 M 022473 4 WASHER FLAT 1/4 ZINC
F 0F7838 1 MOUNT CB MD/ND 520 N 022127 2 NUT HEX 1/4-20 STEEL
G 0E8571 2 INSUL MD/ND CB FRAME P 023897 8 WASHER FLAT #10 ZINC
H 0G0732 2 BUS BAR CB TO LEAD SHORT 95MM Q 022158 4 NUT HEX #10-32 STEEL
I 049814 12 SCREW HHC M10-1.5 X 25 G8.8
J 070264 16 WASHER FLAT M10
K 046526 16 WASHER LOCK M10
L 045772 12 NUT HEX M10-1.5 G8 YEL CHR
M 038752 4 SCREW SHC 3/8-16 X 2.5 G8.8 NZ
N 022241 10 / 13 NUT HEX 3/8-16 STEEL
O 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS
R 026082 10 / 15 SCREW HHC 3/8-16 X 2-1/4 G5
S 022237 10 / 15 WASHER LOCK 3/8
T 022131 10 / 15 WASHER FLAT 3/8-M10 ZINC
U 0G0732A 1 BUS BAR CB TO LEAD TALL 145MM

5) N/A N/A UL CIRCUIT BREAKER LMD


A N/A N/A SEE TABLE PART NUMBER 0D8789
B 0F7056 1 KIT COVER CB LMD 520
C 0F7050 1 COVER CB JD 520 TOP
D 0F7050A 1 COVER CB JD 520 BOTTOM
8) N/A N/A UL CIIRCUIT BREAKER GENERAC (203)
A N/A N/A SEE TABLE P/N 0F4165$
B 0F9674 1 COVER CB G 225AF 520 TOP
C 0F9674A 1 COVER CB G 225AF 520 BOTTOM
D 090602 4 SCREW RHM #8-32 X 4.0
E 038150 8 WASHER FLAT #8 ZINC
F 022264 4 WASHER LOCK #8-M4
G 022471 4 NUT HEX #8-32 STEEL
H 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS
J 049897 6/9 SCREW SHC M8-1.25 X 20 G8
K 022129 6/9 WASHER LOCK M8-5/16
L 022145 6/9 WASHER FLAT 5/16-M8 ZINC
M 0F8451 2/3 LUG SLDLSS 300 MCM-6 AL/CU
N W/CB 2 TERM COVER CB GENERAC 203
P 0F8843 2/3 BUS BAR 200A LUG ADAPTOR
R 045771 2/3 NUT HEX M8-1.25 G8 CLEAR ZINC
S 039253 2/3 SCREW HHC M8-1.25 X 20 C8.8
T 043107 2/3 SCREW HHC M8-1.25 X 25 C8.8
U 0G3259 1 DECAL TERMINAL SHOCK HZD BI

9) N/A N/A UL CIIRCUIT BREAKER GENERAC (403)


A N/A N/A SEE TABLE P/N 0F4166$
B 0F9675 1 COVER CB G 400AF 520 TOP
C 0F9675A 1 COVER CB G 400AF 520 BOTTOM
D 048927 4 SCREW RHM #10-32 X 4-1/2
E 023897 8 WASHER FLAT #10 ZINC
F 022152 4/6 WASHER LOCK #10
G 022158 4 NUT HEX #10-32 STEEL
H 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS
J 052647 4/6 SCREW SHC M10-1.5 X 25 C12.9
K 022131 4/6 WASHER FLAT 3/8-M10 ZINC
L 0A7822 2/3 LUG SLDLSS 600/250-1/0 X 1/4-28
M W/CB 2/3 BUS BAR CB ADAPTER 225-400 A
N W/CB 2 TERM COVER CB 80MM GENERAC 403
P 022473 4/6 WASHER FLAT 1/4-M6 ZINC
R 022097 4/6 WASHER LOCK M6-1/4
S 023334 4/6 SCREW HHC 1/4-28 X 1/2 G5
T 0G3259 1 DECAL TERMINAL SHOCK HZD BI

10) N/A N/A UL CIIRCUIT BREAKER GENERAC (803)


A N/A N/A SEE TABLE P/N 0F4167$
B 0F9676 1 COVER CB 803 UPPER 520
C 0F9676A 1 COVER CB 803 LOWER 520
D 081320 4 SCREW SHC 1/4-20 X 4.5 C8.8 NZ
E 022473 8 WASHER FLAT 1/4-M6 ZINC
F 022097 4 WASHER LOCK M6-1/4
G 022127 4 NUT HEX 1/4-20 STEEL
H 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS
J 060619 2/3 SCREW SHC M10-1.50 X 40 C12.9
K 022131 2/3 WASHER FLAT 3/8-M10 ZINC
L 022237 2/3 WASHER LOCK 3/8-M10
M 045772 2/3 NUT HEX M10-1.5 G8 YEL CHR
N 0F9721 2/3 LUG SLDLSS 3/0-400X3 MCM AL/CU
P 0D2157 4/6 SCREW SHC M6-1.0 X 50 C8.8
R W/CB 2 TERM COVER CB 94MM GENERAC 803
S** 097962 4/6 SCREW SHC M6-1.0 X 25 C12.9 ZP
T** 022097 4/6 WASHER LOCK M6-1/4
U** 0G0013 2/3 BUS BAR GENERAC 803 CB
V 0G3259 1 DECAL TERMINAL SHOCK HZD BI
W 022097 4/6 WASHER LOCK M6-1/4

* HARDWARE FOR CB TERMINAL COVERS IS SUPPLIED WITH CIRCUIT BREAKERS

** PARTS SUPPLIED WITH KIT 0G1721.


1 0F4964 1 CONN BOX 520 H-100
0F7666 1 CONN BOX 520S H-100
2 042568 8 SCREW HHC M6-1.0 X 20 C8.8
3 022473 12 WASHER FLAT 1/4-M6 ZINC
4 022097 8 WASHER LOCK M6-1/4
5 049813 8 NUT HEX M6 X 1.0 G8 YEL CHR
6 0F5035 1 BRACKET CUST CONN 520
7 0C2454 12 SCREW THF M6-1 X 16 N WA Z/JS
8 0E9764 1 RAIL SNAPTRACK PCB HOLDER BULK (6” LG)
9 0C2266 6 SCREW PHTT M5-0.8 X 16 ZYC
10 * 0F7862 1 HARN 520 ALT CONBOX 3PH H-100
0F7863 1 HARN 520 ALT CONBOX 1PH H-100
11 0F7357 1 BOX SQUARE 4-11/16 W/KNO'S
12 0F4776 1 OUTLET 15A 250V NEMA 6-15R IVY
13 0F5034 1 COVER REAR 520 CONN BOX
14 0F8045 1 PLATE GLAND 520
15 0F1958 1 PLATE HARNESS CLAMP
16 051713 2 WASHER FLAT M5
17 049226 2 WASHER LOCK M5
18 ** 045771 6/4 NUT HEX M8-1.25 G8 CLEAR ZINC
20 052250 1 TAPE FOAM 1 X 1 (55” LG)
21 0G6962A REF. ASSY RELAY PCB 24VDC
0G6962B REF. ASSY RELAY PCB 12VDC
22 0C2212 4 SCREW PHTT M4-0.7 X 16 ZYC
23 0F5103 REF. INTERFACE 3PH 416/480V
0F5104 REF. INTERFACE 3PH 208/240V
0F5105 REF. INTERFACE 1PH 120/240V
24 ** 022129 6/4 WASHER LOCK M8-5/16
25 ** 022145 12/8 WASHER FLAT 5/16-M8 ZINC
26 ** 042907 6/4 SCREW HHC M8-1.25 X 16 C8.8
27 070208 1 GROMMET .87 X .25 X .62
28 047411 6 SCREW HHC M6-1.0 X 16 C8.8
29 022097 6 WASHER LOCK M6-1/4
30 022473 6 WASHER FLAT 1/4-M6 ZINC
31 022127 REF. NUT HEX 1/4-20 STEEL
32 022287 REF. SCREW HHC 1/4-20 X 3/4 G5
33 082982 REF. RELAY CONTACTOR 24VDC
056739 REF. RELAY SOLENOID 12VDC PNL MNT
34 ** 0F4281A 3/2 XFMR CURRENT 100A W/BRKT
0F4281B 3/2 XFMR CURRENT 150A W/BRKT
0F4281C 3/2 XFMR CURRENT 200A W/BRKT
0F4281D 3/2 XFMR CURRENT 300A W/BRKT
0F4281E 3/2 XFMR CURRENT 400A W/BRKT
0F4281F 3/2 XFMR CURRENT 500A W/BRKT
0F4281G 3/2 XFMR CURRENT 600A W/BRKT
0F4281H 3 XFMR CURRENT 800A W/BRKT
0F4281J 2 XFMR CURRENT 1000A W/BRKT
35 *** 0C3211G 1 SOCKET RELAY 8 PIN
36 *** 0C3211E 1 RELAY PNL 12VDC DPDT 8PIN
0C3211F 1 RELAY 24VDC DPDT 8 PIN
37 *** 033503 2 SCREW PHM #6-32 X 7/8 ZINC
38 *** 022155 2 WASHER LOCK #6
39 *** 022188 2 NUT HEX #6-32 STEEL
40 **** 0F7185 REF MOUNT GOV CONTROL H-100
41 **** 0F7186 REF COVER GOV CONTROL
42 0F6207 1 OUTLET 20A GFCI
43 0F5683 1 DECAL H-100 CUST CONNECTIONS
44 036901 4 SCREW PPHM #6-32 X 3/8
45 022155 4 WASHER LOCK #6
46 0F7278 1 COVER DUAL RECEPT 120/240
47 0F8565 1 DECAL H-100 RB3 CUST CONN
48 0A1658 1 WASHER LOCK SPECIAL 1/4”
49 0F5683A 1 DECAL CUST CONNECTIONS

* NOT SHOWN
** 1 PHASE ONLY USES 2 CURRENT TRANSFORMERS.
3 PHASE USES 3 CURRENT TRANSFORMERS.
*** OPTIONAL EQUIPMENT
COMPO NENTS INCLUDED IN 0G4144E
1 0F1823CST03 1 ENCL H/G CONTROL PANEL
2 0F1824AST03 1 COVER CONTROL PANEL H
3 0F2606 1 HINGE CONTINUOUS H PANEL
4 036261 7 RIVET PO P .125 X .275 SS
5 0F5763 1 ASSY PROGRAMMED H-100
6 0F1732 1 DECAL FUSES LO CATED INSIDE
7 0E9764 1 RAIL SNAPT RACK PCB HO LDER BUL K (12”LG)
8 0F1740D 1 ASSY PCB 10A UL BATT CHRG R 24V
9 0F1958 1 PLATE HARNESS CLAMP
10 0F2256 1 ASSY PCB PWR AVR W/AMP HEADER
11 0F9581 1 ASSY PCB 12V BOSCH W/24V INPT
12 048476 1 CB 4.5X1 AUT30KW CNT45K
13 029673 1 DIO BRIDG E 25A 600V
14 0F5752D 1 RES WW 75R 5% 25W QK CO NN
15 049226 11 WASHER LOCK M5
16 079224 2 SCREW PPHM M5-0.8 X 30 SS
17 051713 13 WASHER FLAT M5
18 0F5886 6 SCREW HHPM M5-0.8 X 12
19 043182 4 WASHER LOCK M3
20 051714 4 NUT HEX M3-0.5 G8 YEL CHR
21 052777 4 WASHER FLAT M3
22 051716 5 NUT HEX M5-0.8 G8 CLEAR ZINC
23 043180 3 WASHER FLAT M4
24 0C3990 3 SCREW PHTT M4-0.7 X 10 ZYC
25 0F4333 1 CONN DUST CAP W/CHAIN DB9
26 0F5883 1 WASHER FLAT M3.5
27 0F5884 1 SCREW PHTT M3.5-0.6 X 10
28 055014 10 SCREW PPHM M4-0.7 X 8 BLX OX
29 022264 10 WASHER LOCK #8-M4
30 0G3546 1 DECAL W RN BATT CHRG 12/24V BI
31 0F5752A 1 RES WW 10R 5% 15W QK CO NN
32 080823 2 SCREW PPHM M5-0.8 X 50 ZNC
33 0G3648 1 M5-0.8 CAPTIVE PANEL KNLD HD
34 0F6305 2 SEAL COVER 3.18 X 12.7 X 382
35 0F6305A 1 SEAL COVER 3.18 X 12.7 X 283
36 0G4329 1 HARNESS H-PNL INTEG RATED SW (NOT SHOWN)

COMPO NENTS INCLUDED IN WIRE HARNESS


A 0F1263 1 ADPT R RH SIDE W ICKMANN 178.6191
B 0F1262 4 HOLDER F USE WICKMANN 178.6150
C 0F1264 1 ADPT R LH SIDE W ICKMANN 178.6192
D 0E9049A 2 ASSY PCB G -PANEL RELAY 24VDC
E 055911 1 BLOCK TERM 20A 12 X 6 X 1100V

COMPO NENTS NOT INCLUDED IN 0G4144E O R W IRE HARNESS


50 082982 REF. RELAY CONTACT OR 24VDC
51 022287 REF. SCREW HHC 1/4-20 X 3/4 G5
52 022473 REF. WASHER FLAT 1/4-M6 ZINC
53 022097 REF. WASHER LOCK M6-1/4
54 022127 REF. NUT HEX 1/4-20 STEEL
55 0E7403C 1 FUSE ATO TYPE 15 AMP (BL UE)
56 0E7403B 2 FUSE ATO TYPE 10 AMP (RED)
57 0C2323 2 SCREW PHTT #6-32 X 5/8 ZYC
58 0C2699 2 SCREW PHTT #6-32 X 3/8 ZYC
59 0F5459 1 DECAL CPL CO NTROL PANEL FUSES
60 0F5773 1 DECAL H-100 RELAY BD 24V RB2
61 0F5772 1 DECAL H-100 RELAY BD 24V RB1
62 0F7582 1 DECAL 24VDC TB3
63 0F6145 A/R SEAL WEATHER .45"DIA
1 0D6719 1 TANK 97 GALLON- 1FT 27 ***0A1476 1 LABEL FUEL FILL
0D6720 1 TANK 233 G ALLON- 2FT 28 ***0A1546 1 LABEL FUEL LEVEL
2 0C6789 10 SCREW HHC M12-1.75 X 30 SS FT 29 ***0A1480 1 LABEL SENSOR FUEL LEVEL
3 087171 20 WASHER FLAT 1/2 SS 30 ***0A1479 1 LABEL VENT
4 051548 10 NUT HEX M12- 1.75 G 8 SS 31 ***021826 2 LABEL VENT EMERGENCY
5 0D3747 1 COVER STUB-UP- 1FT 32 ***0A1481 1 LABEL DETECTO R LEAK
0D3747A 1 COVER STUB-UP- 2 FT 33 ***0A1482 1 LABEL DRAIN
6 050190 6 WASHER FLAT .344 ID X 1.0 O D 34 ***021824 1 LABEL WARNING
7 051754 6 SCREW HHC M8-1.25 X 12 G 8.8 35 083215 10 WASHER LO CK 1/2 SS
9 035472 2 CLAMP HO SE #6 .43 - .78
10 021623 2 PIPE FUEL DIP-1 F T-FUEL INLET
021623B 2 PIPE FUEL DIP-2 F T-FUEL INLET * ITEMS ARE STANDARD COMPONENTS.
11 070327 1 VALVE CHECK 3/8 NPT ** ITEMS ARE O PTIONAL COMPONENTS.
12 ***021825C 1 LABEL EMERGENCY REL IEF VENTING *** UL LABEL KIT P/N 0A1493C.
13 0D3038A 2 BARBED STR FE 3/8 NPT X 3/8
LOW FUEL SENSOR IS OPTIO NAL ON UNITS EQUIPPED WITH
14 0D2728 1 FUEL LEVEL G AUGE KIT -1FT MECHANICAL “D” O R “E” CONTROL PANELS, BUT IS ST ANDARD WITH A “C”
(TO INCLUDE ITEMS 14A, 14B, & 14C) CONTROL PANEL. PIPE PLUG IS FITTED IN ABSENSE OF LO W
14A 021973 1 FUEL LEVEL GAUGE (IN KIT D2728) FUEL SENSOR.
14B 0D2669 1 PLATE ADAPTOR (IN KIT D2728)
14C 052829 3 SCREW SHC M8-1.25 X 14 G12.9 (IN KIT D2728)

14 0D2730 1 FUEL LEVEL G AUGE KIT -2FT MECHANICAL


(TO INCLUDE ITEMS 14A, 14B, & 14C)
14A 021973B 1 FUEL LEVEL GAUGE (IN KIT D2730)
14B 0D2669 1 PLATE ADAPTOR (IN KIT D2730)
14C 052829 3 SCREW SHC M8-1.25 X 14 G12.9 (IN KIT D2730)

14 0G8046 1 FUEL LEVEL GAUGE KIT-1FT EL ECTRICAL


(TO INCLUDE ITEMS 14A, 14B, 14C & 14D)
14A 0G8010A 1 ELEC FUEL GAUGE 1FT DW (IN KIT 0G8046)
14B 0D2668 1 PLATE ADAPTOR (IN KIT 0G8046)
14C 052829 3 SCREW SHC M8-1.25 X 14 G12.9 (IN KIT 0G8046)
14D 097962 4 SCREW SHC M6-1.0 X 25 G12.9 (IN KIT 0G8046)

14 0G8047 1 FUEL LEVEL GAUGE KIT-2FT EL ECTRICAL


(TO INCLUDE ITEMS 14A, 14B, 14C & 14D)
14A 0G8010B 1 FUEL LEVEL GAUGE (IN KIT 0G 8047)
14B 0D2668 1 PLATE ADAPTOR (IN KIT 0G8047)
14C 052829 3 SCREW SHC M8-1.25 X 14 G12.9 (IN KIT 0G8047)
14D 097962 4 SCREW SHC M6-1.0 X 25 G12.9 (IN KIT 0G8047)

15 0A1492 1 CAP FUEL FILL


16 *0D2670 1 NECK FUEL FILL (STANDARD-4”)
**0D2737 1 FUEL F ILL AND PRIMARY VENT EXT. KIT 8”
**0D2739 1 FUEL F ILL AND PRIMARY VENT EXT. KIT 13”
**0D2740 FUEL F ILL AND PRIMARY VENT EXT. KIT 19”
17 063831 1 PLUG STD PIPE 1.25”NPT STEEL SQ HD
021592 1 SENSO R FUEL LEVEL-LO W FUEL- 1FT TANK
021592B SENSO R FUEL LEVEL-LO W FUEL- 2FT TANK

18 021178 1 VENT OEM 2” NPT


19 *0A7238 1 NIPPLE PIPE 2NPT X 3.5 BL IRON
**0D2737 1 FUEL F ILL AND PRIMARY VENT EXT. KIT 8”
**0D2739 1 FUEL F ILL AND PRIMARY VENT EXT. KIT 13”
**0D2740 1 FUEL F ILL AND PRIMARY VENT EXT. KIT 19”
20 *028619B 2 PLUG PIPE 4" SQ.HD.

20 **0D2450 1 VENT EMERGENCY KIT 4" NPT


(TO INCLUDE ITEM 20A AND 20B)
20A 0A1380 2 VENT EMERGENCY 4” NPT
20B 028667 1 ELBO W 90D ST REET 4” NPT
21 096500V 1 ASSY FUEL L EAK DET ALARM W/CON
22 025655 1 PLUG STD PIPE 3/4" STEEL SQ HD
23 021821 1 PLATE GENERAC
24 021823 1 PLATE UL
25 ***0A1478 1 LABEL FUEL RETURN
26 ***0A1477 1 LABEL FUEL SUPPLY
1 0E3960 1 LEVEL ONE TOP 7.5L C-GROUP
2 0E3964 1 LEVEL ONE LH SIDE 7.5L C-GRP
3 0E3963 1 LEVEL ONE RH SIDE 7.5L C-GRP
4 0E3962 1 LEVEL ONE BOTTOM 7.5L C-GRP
5 0E3966 1 LEVEL ONE ALT COVER 7.5L C-GRP
6 0A2110 42 SCREW SWAGE 1/4-20 X 1/2 Z/YC
1 0F7650 1 ASSY MOUNTING BASE 7.5L 520
2 0D8199 REF. MOUNT ENGINE 7.5L MITSUBISHI
3 049814 1 SCREW HHC M10-1.5 X 25 G8.8
4 061383 1 LUG SLDLSS 3/0-#4 X 13/32 CU
5 025507 2 WASHER SHAKEPROOF EXT 7/16 STL
6 052859 2 NUT LOCK FL M10-1.5
7 059676 6 MOUNT LOWER VIBRATION
8 060079 6 NUT LOCK HEX M14-2.0 NYL INSRT
9 059675 6 MOUNT UPPER VIBRATION
10 059984 2 SCREW HHC M14-2.0 X 120 G8.8
11 022132 6 WASHER FLAT 9/16 ZINC
12 030985 1 NIPPLE CLOSE 1/2 X 1.125
13 078944 1 VALVE BALL
14 044118 1 BARBED STRAIGHT 1/2 NPT X 5/8
15 057822 1 CLAMP HOSE #8 .53 - 1.00
16 035461 2 BARBED STRAIGHT 1/4 NPT X 3/8
17 0C7649 2 CLAMP HOSE .38 - .87
18 051756 1 SCREW HHC M10-1.5 X 20 G8.8
19 0536210999 1 ASSY WIRE GND #4 X 14" 3/8 LUG
20 046526 2 WASHER LOCK M10
21 0A5580 2 SCREW HHC M14-2.0 X 140 G8.8
22 024310 1 PLUG STD PIPE 1/2 STEEL SQ HD
23 0D7019 2 SCREW HHC M14-2.0 X 100 G 8.8
24 026073A 2 PLUG STD PIPE 1/4 STEEL SQ HD
25 022131 1 WASHER FLAT 3/8-M10 ZINC
E GROUND FRAME (520)
1 058665 2 BATTERY 12VDC 90-AH 27F
058665A 2 BATTERY SERVICE DRY
061119 2 BATTERY BCI GRP 31
06119A 2 31E BATTERY SERVICE DRY
2 065314 1 BATTERY JUMPER CABLE 8"
3 038805H 1 CABLE BATTERY BLACK #1 X 23.00
4 038804U 1 CABLE BATTERY RED #1 X 28.00
5 059568H 1 BATTERY HOLD-DOWN BAR 390 MM
6 059567 2 J-BOLT 5/16-18 X 11.0 ZINC
7 050331A 3 BATTERY POST COVER RED +
8 050331 1 BATTERY POST COVER BLACK -
9 075763 1 BOOT BATTERY CABLE
10 022145 2 WASHER FLAT 5/16-M8 ZINC
11 022129 2 WASHER LOCK M8-5/16
12 022259 2 NUT HEX 5/16-18 STEEL
13 051769 1 WASHER LOCK M12
14 052617 1 SCREW HHC M12-1.75 X 20 G8.8

C GROUND FRAME 390/520


1 058665 2 BATTERY 12VDC 90-AH 27F
058665A 2 BATTERY SERVICE DRY
061119 2 BATTERY BCI GRP 31
06119A 2 31E BATTERY SERVICE DRY
2 065314C 1 BATTERY JUMPER CABLE 33”
3 038804A 1 CABLE BATTERY RED #1 X 28.00
4 0388805H 1 CABLE BATTERY BLACK #1 X 23.00
5 059568H 2 BATTERY HOLD-DOWN BAR 390 MM
6 059567 4 J-BOLT 5/16-18 X 11.0 ZINC
7 050331A 2 BATTERY POST COVER RED +
8 050331 2 BATTERY POST COVER BLACK -
9 075763 1 BOOT BATTERY CABLE
10 022145 4 WASHER FLAT 5/16-M8 ZINC
11 022129 4 WASHER LOCK M8-5/16
12 022259 4 NUT HEX 5/16-18 STEEL
13 051769 1 WASHER LOCK M12
14 052617 1 SCREW HHC M12-1.75 X 20 G8.8
1 0G1286C 1 RAD W/EXT FRAME R/H-IN L/H-OUT
2 0A5160 1 ASSEMBLY CAC 19 CORE
3 0E0500 1 SUPPORT RAD RH 150KW 7.5L MITS
4 0E0501 1 SUPPORT RAD LH 150KW 7.5L MITS
5 0E0498 1 VENTURI 150KW 7.5L MITUSBISHI
6 049814 24 SCREW HHC M10-1.5 X 25 G8.8
7 046526 28 WASHER LOCK M10
8 022131 28 WASHER FLAT 3/8-M10 ZINC
9 086133C 2 CLAMP HI TORQUE 1.75 - 2.625
10 046627 2 CAP RADIATOR 14PSI
11 059981 8 SCREW HHC M10-1.5 X 30 G10.9
12 045772 6 NUT HEX M10-1.5 G8 YEL CHR
13 035461 1 BARBED STR 1/4 NPT X 3/8
(3) 14 0E1702 1 GUARD COOLING FAN TOP 7.5L M
(3) 15 0E1703 1 GUARD COOLING FAN BOTTOM 7.5L
16 0A2110 2 SCREW SWAGE 1/4-20 X 1/2 Z/YC
17 0E2025 1 AIR TUBE CAC TO TURBO
18 0E1782 1 TUBE CAC INTAKE SIDE 7.5L CGRP
19 0A5260A 1 HOSE 3" ID X 3.0" LG
20 080773B 1 HOSE RES 3" TURBO
21 086133E 6 CLAMP HI TORQUE 2.75 - 3.625
22 0E1932 1 RAD HOSE UPPER 7.5L MITS C-GRP
23 0E1933 1 RAD HOSE LOWER 7.5L MITS C-GRP
24 086133D 6 CLAMP HI TORQUE 2.25 - 3.125
25 0E6619 1 TUBE 2.0" O.D. 1.0" TEE CONECT
26 035587 1 HOSE 1IN ID CVR NEOP SAE-20R3 (48” LG)
27 057824 2 CLAMP HOSE #16 .87 - 1.50
29 040173 8 CLAMP HOSE #5.5 .62 - .62
30 052250 1 TAPE FOAM 1 X 1 (276” LG)
(1) 32 0E2671 2 RH/LH SIDE AIR DUCT 3.9L MITSU
(1) 33 0G36660ST03 2 TOP/BOTTOM AIR DUCT 3.9L MITSU
34 0A2110 (1) 14 SCREW SWAGE 1/4-20 X 1/2 Z/YC
0A2110 (2) 6 SCREW SWAGE 1/4-20 X 1/2 Z/YC
0A2110 (3) 24 SCREW SWAGE 1/4-20 X 1/2 Z/YC
(2) 35 0G36690ST03 1 STONE GUARD FRONT 3.9L MITSU
36 047290 2 HOSE 3/8 ID SINGLE BRAID (36” LG)
37 0E2507 1 PROBE, COOLANT LEVEL 3/8NPTF
38 0E4969 1 TANK SURGE SMALL WELDED
39 046525 4 NUT HEX M10-1.25 G8 YEL CHR
40 047290 1 HOSE 3/8 ID SINGLE BRAID (60” LG)
41 047290 1 HOSE 3/8 ID SINGLE BRAID (12” LG)
42 071296B 1 HOSE 2" ID X 4.0" LG
43 076749 1 TANK COOLANT RECOVERY
44 0F1433 1 BRACKET WATER BOTTLE
45 043107 1 SCREW HHC M8-1.25 X 25 G8.8
46 022145 2 WASHER FLAT 5/16-M8 ZINC
47 022129 1 WASHER LOCK M8-5/16
48 045771 1 NUT HEX M8-1.25 G8 CLEAR ZINC
49 0C9079A 1 BARBED TEE 5/16" BRASS
50 077043H 1 CONDUIT FLEX .25"ID (80”LG)
51 0G7895A 1 HARN RADIATOR GND 80"
52 0A4456 1 WASHER LOCK SPECIAL 3/8

(1) OPTIONAL AIR DUCT KIT (0G3935) PARTS.


(2) OPTIONAL STONE GUARD (0G3936) PARTS.
(3) FANGUARD KIT (0E4223) PARTS.
1 084918G 1 HEATER ENG 1500W 120V
084918H 1 HEATER ENG 1500W 240V
2 0E6417 1 BRACKET, BLOCK HEATER 7.5L MIT
3 050967 1 HOSE COOL 5/8 ID 20R3 (53”LG)
4 050967 1 HOSE COOL 5/8 ID 20R3 (24”LG)
5 0C4905 1 BARBED EL 45 3/8NPT X 5/8OD
6 0G0015 4 CLAMP, HOSE 5/8" DOUBLE WIRE
7 042568 4 SCREW HHC M6-1.0 X 20 G8.8
8 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR
9 022097 4 WASHER LOCK M6-1/4
10 022473 4 WASHER FLAT 1/4-M6 ZINC
1 090625 1 AIR CLEANER 7 3/4
2 090624 1 MOUNTING CLAMP 7 3/4
3 0D6749 1 INTAKE TUBE 4" OD X 10 LG 7.5L
4 072448 1 HOSE RUBBER HUMP RDCR 4-2-3/4
5 0E6428 1 BRKT, AIR CLEANER 7.5L MITSU.
6 086133G 2 CLAMP HI TORQUE 3.75 - 4.625
7 086133D 1 CLAMP HI TORQUE 2.25 - 3.125
8 049814 2 SCREW HHC M10-1.5 X 25 G8.8
9 022131 8 WASHER FLAT 3/8-M10 ZINC
10 045772 4 NUT HEX M10-1.5 G8 YEL CHR
11 046526 4 WASHER LOCK M10
12 0E0176 1 HEAT SHIELD, TURBO 7.5L MITSU.
13 0D9247 1 GASKET, THERMOSTAT HOUSING 7.5
14 0E6426 1 BRACKET AIR CLEANER EAGLE
1 090185 2 ROD END 10-32 R/H
2 022152 4 WASHER LOCK #10
3 0F7771 1 STUD #10-32 X 13.5" 1.0" THRD
4 022158 4 NUT HEX #10-32 STEEL
5 0E8015 1 ASSY ACTUATOR, 68MM
6 022390 2 SCREW RHM #10-32 X 1
7 023897 1 WASHER FLAT #10 ZINC
8 0F7390 1 ARM THROTTLE CONTROL D7.5L
9 022678 1cc LOCTITE THRDOK 242BLUE
10 0F7391 1 MOUNT ELEC GOV CONTROL 7.5L
11 051751 4 SCREW HHC M6-1.0 X 50 G8.8
12 052857 4 NUT TOP LOCK FL M6-1.0
13 REF 4 SUPPLIED WITH ENGINE
14 052647 1 SCREW SHC M10-1.5 X 25 G12.9
15 0F8391 1 TORSION SPRING 7.5L ACT
16 0D3052 1 WASHER FLAT 5/16 SS
1 0G7213 1 ENGINE 7.5L G2 6D16-T EXPORT
2 0D5760 1 HOUSING FLYWHEEL ADPT MACH 7.5
3 021322A 5 FLEX PLATE,520,SAE11-1/2,14MM
4 0E1931 1 REWORK FAN 26 INCH 7 BLADE
5 0E1692 1 SPACER, COOLING FAN 7.5L M C-G
6 0D9311 1 WASHER FLAT M16 COPPER 1.5 THK
7 051698 2 SCREW HHC M8-1.25 X 75 G8.8
8 022145 2 WASHER FLAT 5/16 ZINC
9 0D8199 2 MOUNT ENGINE 7.5L MITSUBISHI
10 0C4905 1 BARBED EL 45 3/8NPT X 5/8OD
11 051769 12 WASHER LOCK M12
12 0F4612 1 SENDER OIL PRESSURE 1/8"NPT
13 042574 1 ADAPTOR 1/8 NPTF TO 1/8-28
14 0F2776A 3 BRACKET, SIGNAL CONDITIONER
15 034339 1 BARBED EL 90 3/8NPT X 5/8
16 0G5718 1 DECAL EMSN INFO SERVICE ONLY
17 0E0502 1 TEMPERATURE SENDER, DELPHI
18 030418 1 BSHG RDCR HEX 1/2 TO 3/8
19 031919 1 PLUG STD PIPE 3/8 COUNTERSUNK
20 0D2244M 1 ASSEMBLY MAGPICKUP (3/8-24 MALE)
21 0D9247 1 GASKET THERMOSTAT HOUSING 7.5
22 081816 12 SCREW HHC M12-1.75 X 55 G10.9
23 045773 12 NUT HEX M12-1.75 G8 YEL CHR
24 049808 8 WASHER FLAT M12
25 046526 26 WASHER LOCK M10
26 0D1547 12 SCREW SHC M10-1.5 X 45 BLK OX
27 022131 32 WASHER FLAT 3/8-M10 ZINC
28 057644 6 SCREW HHC M10-1.5 X 100 G8.8
30 043097 8 SCREW SHC 3/8-16 X 1 G8.8NZ
31 059355 12 SCREW SHC M10-1.50 X 50 G10.9
32 0536210860 REF. ASSEMBLY GROUND WIRE
33 051756 10 SCREW HHC M10-1.5 X 20 G8.8
34 025507 2 WASHER SHAKEPROOF EXT 7/16 STL
35 0D9260A 1 REWORK THERM HOUSING 7.5L MIT.
36 0F7391 REF. MOUNT ELEC GOV CONTROL 7.5L
37 0E3691 1 PULLEY WATER PUMP
38 0E3235 1 GASKET THERMOSTAT NECK 7.5L
39 035578 - NIPPLE CLOSE 1/8 NPT
40 028405 1 ELBOW 90D 1/8 NPT
41 0E5262 1 GASKET INTAKE SMALL 7.5 C-GRP
42 049814 2 SCREW HHC M10-1.5 X 25 G8.8
43 0A1786 .5CC ADH LOCTITE #8931 AA W/S
44 0A4707E 1 ADAPTER 3/8NPT X M18-1.5
H-100 Control Panel

DESCRIPTION
• Digital controls for all safety shutdowns

• Isochronous governor control

• Digital 3ø sensing voltage regulator

• Sealed Digital Circuit Board

• 2 Amp static battery charger

• Mates with HTS transfer switch and


any 2-wire start ATS

• Alarm and event logging

• Built-in diagnostics

• Internal PLC

• Optional modem with dialout

STANDARD FEATURES
The Quiet-Test™ H-100 Control Panel is a digital microprocessor In addition, the generator set parameters can be
electronic controller that integrates all engine and transfer switch manipulated and monitored without standing in front
functions into a single control system. of the control panel with GenLink® software. The Generac
• Two 4 line x 20 displays H-100 control also monitors and controls transfer switch
functions when used with the HTS Transfer Switch.
• Full system status
• Monitors utility voltage
• 3 phase sensing digital voltage regulator
• Monitors generator voltage
• Remote ports
• Timer for line interrupt delay
- RS232
• Timer for engine warmup
- RS485
• Timer for minimum engine run time
- Canbus
• Timer for return to utility position
• Water proof connections
• Timer for engine cooldown
• All engine sensors are 4-20 ma for minimal interference
• Built in exerciser timer (7 day)
• Built in PLC
• Additional 2 wire start controls for any 2 wire
transfer switch.
FEATURES QUIET-TEST™ H-100 Controller

• Full range stand-by operation • Shutdowns


• Full system status - Overvoltage
- 3 phase AC volts - Overspeed
- 3 phase amps - Low oil pressure
- kW - High coolant temperature
- Power factor - Low coolant level
- Reactive power • Remote communication
- Oil pressure - RS232
- Water temperature - Optional modem
- Water level - Canbus
- Oil temperature (optional) • Configurable to NFPA 110, level 1 or 2
- Fuel pressure • Programmable auto crank
- Engine speed • Emergency Stop
- Battery voltage • On Off Manual Switch
- Alternator frequency • Not in Auto flashing light
- Time • Audible alarm for fault condition
- Date • Transfer switch logic communicates with HTS transfer switch
- Transfer switch status • Weekly exerciser (programmable)
- Run hours • Selectable Low speed exercise
- Service reminders • Digital voltage regulator with 3 phase sensing (3 phase units)
- Trending • Isochronous governor
- Fault history (alarm log) • Waterproof electrical connectors
- I2t function for full generator protection • Temperature Range -40° to 70° C
- Built in PLC for special applications

TYPICAL CONTROL CONNECTION

HTS
QUIET-TEST™ H-100 Controller Transfer
on Generator RS485 - 2 wire Switch
with ground
connection
for control

OR Any 2-Wire
Start ATS

Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0172110SBY/Printed in U.S.A. 08.05, rev: 03.09

You might also like