Professional Documents
Culture Documents
SSAA-001 - Grupo Electrogeno - GENERAC - SD130
SSAA-001 - Grupo Electrogeno - GENERAC - SD130
Type: SD130
Engine: D7.5M
INTRODUCTION The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recom-
Thank you for purchasing this model of the standby
generator set product line by Generac Power Systems, mends that the operator read this Owner's Manual
Inc.. and thoroughly understand all instructions before
using this equipment. The manufacturer also strong-
Every effort was expended to make sure that the ly recommends instructing other users to properly
information and instructions in this manual were start and operate the unit. This prepares them if they
both accurate and current at the time the manual was need to operate the equipment in an emergency.
written. However, the manufacturer reserves the right
to change, alter or otherwise improve this product(s)
at any time without prior notice. OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety
READ THIS MANUAL THOROUGHLY checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
If any portion of this manual is not understood, con- equipment checked periodically by an Authorized
tact the nearest Authorized Service Dealer for start- Service Dealer. Normal maintenance service and
ing, operating and servicing procedures. replacement of parts are the responsibility of the
Throughout this publication, and on tags and decals owner/operator and, as such, are not considered
affixed to the generator, DANGER, WARNING, defects in materials or workmanship within the
CAUTION and NOTE blocks are used to alert person- terms of the warranty. Individual operating habits
nel to special instructions about a particular service and usage contribute to the need for maintenance
or operation that may be hazardous if performed service.
incorrectly or carelessly. Observe them carefully. Proper maintenance and care of the generator ensure
Their definitions are as follows: a minimum number of problems and keep operating
expenses at a minimum. See an Authorized Service
DANGER Dealer for service aids and accessories.
After this heading, read instructions that, if not Operating instructions presented in this manual
strictly complied with, will result in personal injury assume that the standby electric system has been
or property damage. installed by an Authorized Service Dealer or other
competent, qualified contractor. Installation of this
equipment is not a “do-it-yourself” project.
After this heading, read instructions that, if not
strictly complied with, may result in personal injury HOW TO OBTAIN SERVICE
or property damage. When the generator requires servicing or repairs,
contact an Authorized Service Dealer for assistance.
Service technicians are factory-trained and are capa-
ble of handling all service needs.
After this heading, read instructions that, if not
strictly complied with, could result in damage to When contacting an Authorized Service Dealer about
equipment and/or property. parts and service, always supply the complete model
NOTE: number of the unit as given on the front cover of this
manual or on the DATA LABEL affixed to the unit.
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compli-
ance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates is as follows: AUTHORIZED SERVICE
This symbol points out important safety infor- DEALER LOCATION
mation that, if not followed, could endanger To locate the nearest AUTHORIZED SERVICE
personal safety and/or property of others. DEALER, please call this number:
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted in potential hazard areas. Safety should be stressed to all operators,
potential operators, and service and repair technicians for this equipment.
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.
WARNING:
standards and regulations. The operator also must
comply with all such codes, standards and regula-
This product contains or emits chemicals tions.
known to the state of California to cause • Installation, operation, servicing and repair of this
cancer, birth defects or other reproductive harm. (and related) equipment must always comply with
applicable codes, standards, laws and regulations.
Adhere strictly to local, state and national electri-
cal and building codes. Comply with regulations
Study these SAFETY RULES carefully before install- the Occupational Safety and Health Administration
ing, operating or servicing this equipment. Become (OSHA) has established. Also, ensure that the
familiar with this Owner’s Manual and with the generator is installed, operated and serviced in
unit. The generator can operate safely, efficiently and accordance with the manufacturer’s instructions
reliably only if it is properly installed, operated and and recommendations. Following installation, do
maintained. Many accidents are caused by failing to nothing that might render the unit unsafe or in
follow simple and fundamental rules or precautions. noncompliance with the aforementioned codes,
The manufacturer cannot anticipate every possible standards, laws and regulations.
circumstance that might involve a hazard. The warn- • The engine exhaust fumes contain carbon monox-
ings in this manual, and on tags and decals affixed ide gas, which can be DEADLY. This dangerous gas,
to the unit are, therefore, not all-inclusive. If using a if breathed in sufficient concentrations, can cause
procedure, work method or operating technique that unconsciousness or even death. For that reason,
the manufacturer does not specifically recommend, adequate ventilation must be provided. Exhaust
ensure that it is safe for others. Also make sure the gases must be piped safely away from any building
procedure, work method or operating technique uti- or enclosure that houses the generator to an area
lized does not render the generator unsafe. where people, animals, etc., will not be harmed.
This exhaust system must be installed properly, in
strict compliance with applicable codes and stan-
DANGER dards.
• Keep hands, feet, clothing, etc., away from drive
Despite the safe design of this generator, operating
this equipment imprudently, neglecting its mainte-
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
nance or being careless can cause possible injury is operating.
or death. Permit only responsible and capable
• Adequate, unobstructed flow of cooling and venti-
persons to install, operate or maintain this equip- lating air is critical in any room or building hous-
ment. ing the generator to prevent buildup of explosive
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
gases and to ensure correct generator operation.
Do not alter the installation or permit even partial
render the machine safe before attempting to blockage of ventilation provisions, as this can seri-
work on the generator. ously affect safe operation of the generator.
• Keep the area around the generator clean and
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
uncluttered. Remove any materials that could
become hazardous.
generators.
• When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
2
Important Safety Instructions
Standby Generator Sets
• Inspect the generator regularly, and promptly • Generators installed with an automatic transfer
repair or replace all worn, damaged or defective switch will crank and start automatically when
parts using only factory-approved parts. NORMAL (UTILITY) source voltage is removed
• Before performing any maintenance on the gen- or is below an acceptable preset level. To prevent
erator, disconnect its battery cables to prevent such automatic start-up and possible injury to
accidental start-up. Disconnect the cable from the personnel, disable the generator’s automatic start
battery post indicated by a NEGATIVE, NEG or (–) circuit (battery cables, etc.) before working on or
first. Reconnect that cable last. around the unit. Then, place a “Do Not Operate”
• Never use the generator or any of its parts as a tag on the generator control panel and on the
step. Stepping on the unit can stress and break transfer switch.
parts, and may result in dangerous operating con- • In case of accident caused by electric shock, imme-
ditions from leaking exhaust gases, fuel leakage, diately shut down the source of electrical power. If
oil leakage, etc. this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT
ELECTRICAL HAZARDS WITH THE VICTIM. Use a nonconducting imple-
ment, such as a dry rope or board, to free the vic-
• All generators covered by this manual produce tim from the live conductor. If the victim is uncon-
dangerous electrical voltages and can cause fatal scious, apply first aid and get immediate medical
electrical shock. Utility power delivers extremely help.
high and dangerous voltages to the transfer switch • Never wear jewelry when working on this equip-
as well as the standby generator. Avoid contact with ment. Jewelry can conduct electricity resulting in
bare wires, terminals, connections, etc., on the gen- electric shock, or may get caught in moving com-
erator as well as the transfer switch, if applicable. ponents causing injury.
Ensure all appropriate covers, guards and barriers
are in place before operating the generator. If work
must be done around an operating unit, stand on FIRE HAZARDS
an insulated, dry surface to reduce shock hazard.
• Keep a fire extinguisher near the generator at all
• Do not handle any kind of electrical device while times. Do NOT use any carbon tetra-chloride type
standing in water, while barefoot, or while hands
or feet are wet. DANGEROUS ELECTRICAL extinguisher. Its fumes are toxic, and the liquid
SHOCK MAY RESULT. can deteriorate wiring insulation. Keep the extin-
• If people must stand on metal or concrete while guisher properly charged and be familiar with its
installing, operating, servicing, adjusting or repair- use. If there are any questions pertaining to fire
ing this equipment, place insulative mats over a extinguishers, consult the local fire department.
dry wooden platform. Work on the equipment only
while standing on such insulative mats.
• The National Electrical Code (NEC), Article 250
EXPLOSION HAZARDS
requires the frame and external electrically con-
ductive parts of the generator to be connected to • Properly ventilate any room or building housing
an approved earth ground and/or grounding rods. the generator to prevent build-up of explosive gas.
This grounding will help prevent dangerous electri- • Do not smoke around the generator. Wipe up any
cal shock that might be caused by a ground fault fuel or oil spills immediately. Ensure that no com-
condition in the generator set or by static electric- bustible materials are left in the generator com-
ity. Never disconnect the ground wire. partment, or on or near the generator, as FIRE or
• Wire gauge sizes of electrical wiring, cables and EXPLOSION may result. Keep the area surround-
cord sets must be adequate to handle the maxi- ing the generator clean and free from debris.
mum electrical current (ampacity) to which they • These generator sets may operate using one of
will be subjected. several types of fuels. All fuel types are potentially
• Before installing or servicing this (and related) FLAMMABLE and/or EXPLOSIVE and should be
equipment, make sure that all power voltage handled with care. Comply with all laws regulat-
supplies are positively turned off at their source. ing the storage and handling of fuels. Inspect the
Failure to do so will result in hazardous and pos- unit’s fuel system frequently and correct any leaks
sibly fatal electrical shock.
immediately. Fuel supply lines must be prop-
• Connecting this unit to an electrical system nor- erly installed, purged and leak tested according to
mally supplied by an electric utility shall be by
means of a transfer switch so as to isolate the applicable fuel-gas codes before placing this equip-
generator electric system from the electric utility ment into service.
distribution system when the generator is operat- • Diesel fuels are highly FLAMMABLE. Gaseous
ing. Failure to isolate the two electric system power fluids such as natural gas and liquid propane
sources from each other by such means will result (LP) gas are extremely EXPLOSIVE. Natural gas
in damage to the generator and may also result is lighter than air, and LP gas is heavier than air;
in injury or death to utility power workers due to install leak detectors accordingly.
backfeed of electrical energy.
3
Section 1 – General Information
Standby Generator Sets
5
Section 1 – General Information
Standby Generator Sets
STARTING AIDS
This standby generator is equipped with the follow-
ing starting aids that serve to provide quicker, easier
starts under varying climactic conditions. Ifis an open bottom is used, the engine-generator
to be installed over non-combustible materi-
This generator has been mounted with an engine als and should be located such that combustible
coolant heater and a battery charger. These aids are materials are not capable of accumulating under
powered by a NORMAL (UTILITY) power source dur- the generator set.
ing nonoperating periods. Only qualified, competent installation contractors
or electricians thoroughly familiar with applicable
ENGINE COOLANT HEATERS codes, standards and regulations should install this
standby electric power system. The installation must
This unit is equipped with an engine coolant (block) comply strictly with all codes, standards and regula-
heater (Figure 1.3), it is powered by a circuit nor- tions pertaining to the installation.
mally fed by the utility power supply. The heater acts
to heat the engine coolant when the unit is not operat- This genset must be insalled on a level surface. The
ing. This action keeps the engine warm even in cold base frame must be level within two (2) inches all
weather, thus helping ensure quicker starts. Heated around.
coolant in the engine rises continuously drawing cold
coolant into the heater, thus making certain of a con-
stant flow of warm coolant through the engine.
After the system has been installed, do nothing
that might render the installation in noncompli-
Figure 1.3 – Typical Engine Coolant Heater ance with such codes, standards and regulations.
OUTPUT NOTE:
For more information about the installation of a
standby system, order Engine-Generator Standby
Electric Power Systems Installer’s Guide and
Reference Manual (part #046622) from an
Authorized Service Dealer.
NFPA STANDARDS
The following published standards booklets pertain-
ing to standby electric systems are available form
the National Fire Protection Association (NFPA),
Batterymarch Park, Quincy, MA 02269:
• NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES.
BATTERY CHARGERS • NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES.
All generators may be ordered with either a 2A or
10A battery charger installed in the control panel. • NFPA No. 220, STANDARD TYPES OF BUILDING
CONSTRUCTION
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
STANDBY GENERATOR INSTALLATION • NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
DANGER LIQUIDS CODE.
• NFPA No. 10, INSTALLATION, MAINTENANCE AND
Connecting this generator to an electrical system
normally supplied by an electric utility shall be USE OF PORTABLE FIRE EXTINGUISHERS.
by means of a transfer switch (such as the “GTS”
type transfer switch), so as to isolate the electric
system from the utility distribution system when
the generator is operating. Failure to isolate
the electric system by these means will result in
damage to the generator and may also result in
injury or death to utility workers due to back-
feed of electrical energy.
9
Section 2 – Installation
Standby Generator Sets
DANGER
Notice that both the STANDBY and the UTILITY
power supplies to the transfer switch are protected
Do not connect the ground wire to any pipe
that carries a flammable or explosive substance
against overload by a main line circuit breaker. – FIRE or an EXPLOSION may result.
NOTE: Proper grounding helps protect personnel against
electrical shock in the event of a ground fault condi-
The manufacturer recommends the use of a “GTS” tion in the generator or in connected electrical devic-
type transfer switch in conjunction with this gen- es. In addition, grounding helps dissipate static elec-
erator. tricity that often builds up in ungrounded devices.
10
Section 2 – Installation
Standby Generator Sets
• Spilled electrolyte is to be washed down with an Before starting the generator for the first time, the
acid-neutralizing agent. A common practice is to installer must complete the following procedures. For
use a solution of one pound (500 grams) bicarbon- follow-up maintenance information and/or service
ate of soda to one gallon (4 liters) of water. The intervals, please refer to Section 4, “Maintenance,”
bicarbonate of soda solution is to be added until and the “Service Schedule”.
the evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the Transfer Switch
area dried. If this generator is used to supply power to any elec-
Lead acid batteries present a risk of fire because
they generate hydrogen gas. The following pro-
trical system normally powered by an electric utility,
the National Electrical Code requires that a transfer
cedure are to be followed: switch be installed. The transfer switch prevents elec-
• DO NOT SMOKE when near batteries, trical backfeed between two different electrical sys-
• DO NOT cause flame or spark in battery area, and tems. (For additional information, see the applicable
transfer switch manual for this unit.) The transfer
• Discharge static electricity from body before touch-
switch, as well as the generator and other standby
ing batteries by first touching a grounded metal
components, must be properly located and mounted
surface.
in strict compliance with applicable codes, standards
Servicing of batteries is to be performed or super- and regulations.
vised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized person-
nel away from batteries.
Fuel System
Make sure the fuel supply system to the generator (a)
For recommended batteries, see “Specifications.” delivers the correct fuel at the correct pressure and (b)
All batteries must be at 100 percent state-of-charge is properly purged and leak tested according to code.
before they are installed on the generator. No fuel leakage is permitted. See “Specifications” for
When using maintenance-free batteries, it is not more information.
necessary to check the specific gravity or electrolyte If the unit has been idle for a long period of time,
level. Have these procedures performed at the inter- or if the fuel lines or system components have been
vals specified in Section 4, “Maintenance.” A nega- removed and reinstalled, the fuel system may require
tive ground system is used. Battery connections are bleeding to remove air from the system. Air in the
shown on the wiring diagrams. Make sure all batter- fuel system causes hard starting and rough opera-
ies are correctly connected and terminals are tight. tion. All fuel system lines must be installed and must
Observe battery polarity when connecting batteries be tight. A loose line may show no sign of leakage, but
to the generator set. may draw air into the system.
NOTE:
Damage will result if the battery connections are
made in reverse.
Use a suitable container to catch the fuel that
will spill during system bleeding process. Clean
PREPARATION BEFORE START-UP up all spilled fuel after bleeding.
The instructions in this section assume that the
standby generator has been properly installed, ser- Generator Set Lubrication
viced, tested, adjusted and otherwise prepared for Check the engine crankcase oil level before operating
use by a competent, qualified installation contractor. and add oil to the proper level – the dipstick “FULL”
Be sure to read the “Safety Rules” on Pages 2 and 3, mark. Never operate the engine with the oil level
as well as all other safety information in this manual, below the dipstick “ADD” mark. See “Specifications”
before attempting to operate this (and related) equip- and “Engine Oil Recommendations”.
ment.
NOTE:
PRIOR TO INITIAL START-UP This engine is shipped from the manufacturer
with 15W-40 oil. This oil should be changed after
30 hours of operation.
14
Section 4 – Maintenance
Standby Generator Sets
16
Section 4 – Maintenance
Standby Generator Sets
17
Section 5 – Warranty
Standby Generator Sets
NOTE: This Emission Control Warranty Statement applies only to mobile (trailerized) non-road diesel engine powered
generators (model year 2000) as follows: The EPA portion of this statement pertains to this product; The CARB portion
of this statement pertains to this product only IF the generator size is (1) 15 kW or below OR (2) 130 kW or greater.
1-800-333-1322
IMPORTANT NOTE: This Warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to federal and California law. See also the “Generac
Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you
by Generac. The ECS Warranty applies only to the emission control system of your new non-road diesel engine. If there is
any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circum-
stances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac describe
important rights and obligations with respect to your new non-road diesel engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser-
vice, evidence must be presented showing the date of sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the
following address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
211 MURPHY DRIVE
EAGLE, WI 53119
Part 1
18
Section 5 – Warranty
Standby Generator Sets
*Generac non-road diesel engine types covered by this warranty statement include the following:
1) Standby Generator
Part 2
19
Section 5 – Warranty
Standby Generator Sets
Printed in U.S.A.
Notes
Standby Generator Sets
21
1 1 GENERATOR
2 1 BOX, CONNECTOR
3 2 SUPPORT, CONNECTION BOX
4 4 BRACKET-CONNECTION BOX
5 052250 1 TAPE FOAM 1 X 1 (63”)
6 022131 16 WASHER FLAT 3/8-M10 ZINC
7 046526 8 WASHER LOCK M10
8 045772 8 NUT HEX M10-1.5 G8 YEL CHR
9 049814 8 SCREW HHC M10-1.5 X 25 G8.8
10 056326 1 TRIM VINYL BLACK 1/8GP (63”)
1 080774 1 LOWER PANEL 520-LAM
0E0185 1 WELDMENT CONBOX 520/900A+
080774F ++ 1 CONNECTION BOX SHORT 52MM 520S
2 073392 1 PANEL REAR COVER
3 0D7949 1 BLANK COVER LOWER CONBOX 520
0E0212 1 BLANK COVER 520/900A+
4 022473 21/25 WASHER FLAT 1/4 ZINC
5 022097 21/25 WASHER LOCK M6-1/4
6 022287 21/25 SCREW HHC 1/4-20 X 3/4 G5
7 045452S REF NAMEPLATE DATA
9 ++ 0E5885 1 REAR COVER, LOWR PNL SHORT BOX
11 ++ 022203 4 SCREW HHC 1/4-20 X 1-1/4 G5
15 0D2481 1 HARNESS LOWER PANEL 520
(046357) REF. BLOCK TERM 20A 6 X 6 X 1100V
16 022155 2 WASHER LOCK #6
17 036904 2 SCREW PPHM #6-32 X 3/4
18 0D3388 1 DECAL REMOTE START CONNECTION
19 022985 2 WASHER FLAT #6 ZINC
20 022129 6 WASHER LOCK M8-5/16
22 + 058710 3 TRANSFRM 200A TO 5A 5VA
058377 3 TRANSFRM 300A TO 5A 12.5VA
057909 3 TRANSFRM 400A TO 5A 12.5VA
059923 3 TRANSFRM 500A TO 5A 12.5VA
059925 3 TRANSFRM 600A TO 5A
059926 3 TRANSFRM 800A TO 5A
23 +++ 022145 6 WASHER FLAT 5/16-M8 ZINC
24 +++ 039253 6 SCREW HHC M8-1.25 X 20 G8.8
25 056326 1 VINYL TRIM BLACK 1/8 GP (63” LG)
30 * 056739 1 RELAY SOLENOID 12VDC PANEL MOUNT
082982 1 RELAY SOLENOID 24VDC
31 * 022473 2 WASHER FLAT 1/4 ZINC
32 * 022097 2 WASHER LOCK M6-1/4
33 * 022287 2 SCREW HHC 1/4-20 X 3/4 G5
34 052250 1 TAPE FOAM 1 X 1 (63” LG)
* NOT SHOWN
** 1 PHASE ONLY USES 2 CURRENT TRANSFORMERS.
3 PHASE USES 3 CURRENT TRANSFORMERS.
*** OPTIONAL EQUIPMENT
COMPO NENTS INCLUDED IN 0G4144E
1 0F1823CST03 1 ENCL H/G CONTROL PANEL
2 0F1824AST03 1 COVER CONTROL PANEL H
3 0F2606 1 HINGE CONTINUOUS H PANEL
4 036261 7 RIVET PO P .125 X .275 SS
5 0F5763 1 ASSY PROGRAMMED H-100
6 0F1732 1 DECAL FUSES LO CATED INSIDE
7 0E9764 1 RAIL SNAPT RACK PCB HO LDER BUL K (12”LG)
8 0F1740D 1 ASSY PCB 10A UL BATT CHRG R 24V
9 0F1958 1 PLATE HARNESS CLAMP
10 0F2256 1 ASSY PCB PWR AVR W/AMP HEADER
11 0F9581 1 ASSY PCB 12V BOSCH W/24V INPT
12 048476 1 CB 4.5X1 AUT30KW CNT45K
13 029673 1 DIO BRIDG E 25A 600V
14 0F5752D 1 RES WW 75R 5% 25W QK CO NN
15 049226 11 WASHER LOCK M5
16 079224 2 SCREW PPHM M5-0.8 X 30 SS
17 051713 13 WASHER FLAT M5
18 0F5886 6 SCREW HHPM M5-0.8 X 12
19 043182 4 WASHER LOCK M3
20 051714 4 NUT HEX M3-0.5 G8 YEL CHR
21 052777 4 WASHER FLAT M3
22 051716 5 NUT HEX M5-0.8 G8 CLEAR ZINC
23 043180 3 WASHER FLAT M4
24 0C3990 3 SCREW PHTT M4-0.7 X 10 ZYC
25 0F4333 1 CONN DUST CAP W/CHAIN DB9
26 0F5883 1 WASHER FLAT M3.5
27 0F5884 1 SCREW PHTT M3.5-0.6 X 10
28 055014 10 SCREW PPHM M4-0.7 X 8 BLX OX
29 022264 10 WASHER LOCK #8-M4
30 0G3546 1 DECAL W RN BATT CHRG 12/24V BI
31 0F5752A 1 RES WW 10R 5% 15W QK CO NN
32 080823 2 SCREW PPHM M5-0.8 X 50 ZNC
33 0G3648 1 M5-0.8 CAPTIVE PANEL KNLD HD
34 0F6305 2 SEAL COVER 3.18 X 12.7 X 382
35 0F6305A 1 SEAL COVER 3.18 X 12.7 X 283
36 0G4329 1 HARNESS H-PNL INTEG RATED SW (NOT SHOWN)
DESCRIPTION
• Digital controls for all safety shutdowns
• Built-in diagnostics
• Internal PLC
STANDARD FEATURES
The Quiet-Test™ H-100 Control Panel is a digital microprocessor In addition, the generator set parameters can be
electronic controller that integrates all engine and transfer switch manipulated and monitored without standing in front
functions into a single control system. of the control panel with GenLink® software. The Generac
• Two 4 line x 20 displays H-100 control also monitors and controls transfer switch
functions when used with the HTS Transfer Switch.
• Full system status
• Monitors utility voltage
• 3 phase sensing digital voltage regulator
• Monitors generator voltage
• Remote ports
• Timer for line interrupt delay
- RS232
• Timer for engine warmup
- RS485
• Timer for minimum engine run time
- Canbus
• Timer for return to utility position
• Water proof connections
• Timer for engine cooldown
• All engine sensors are 4-20 ma for minimal interference
• Built in exerciser timer (7 day)
• Built in PLC
• Additional 2 wire start controls for any 2 wire
transfer switch.
FEATURES QUIET-TEST™ H-100 Controller
HTS
QUIET-TEST™ H-100 Controller Transfer
on Generator RS485 - 2 wire Switch
with ground
connection
for control
OR Any 2-Wire
Start ATS
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2009 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0172110SBY/Printed in U.S.A. 08.05, rev: 03.09