Multi-functional electric power monitoring instrument

——LON 913F

Nanjing Longyuan Electric Technology Co., LTD


Nanjing Longyuan Electric Technology Co., LTD

Catalogue
I. Safety instructions ................................................................................................. 1

II Overview .................................................................................................................. 2

III. Product specifications and parameters .................................................................. 2

1. Technical indicators ............................................................................................. 2

2. Functional parameters ......................................................................................... 5

IV. Product hole opening and installation schematic diagram..................................... 8

V. Product wiring schematic diagram and terminal definition diagram ...................... 10

VI. Programming and use ......................................................................................... 11

1. The instrument panel displays the information .................................................. 11

2. Round the interface ........................................................................................... 11

Measurement and display wheel-tracking interface: .......................................... 11

VII Digital communication.......................................................................................... 32

VIII After-sale service ................................................................................................ 40


Nanjing Longyuan Electric Technology Co., LTD

I. Safety instructions
Thank you for choosing our multi-functional power monitoring instrument, in order to

facilitate your purchase and safe, correct and efficient use of this instrument, please read

this manual carefully and must pay attention to the following points when using.

Note the CAUTION:

 The device must be installed and commissioned by professional personnel.

 The input signal and power supply must be cut off before any external wiring

operation of the device.

 Always use a suitable voltage detection device to determine the voltage in any part of

the instrument.

 The parameters supplied to the device shall be within the rated range.

The following conditions can cause device damage or abnormal operation of the

device:

 Auxiliary power supply voltage exceeds the rated range

 The power distribution system frequency exceeds the rated range

 Incorrect current or voltage input polarity

 Live unplug communication plug

 Terminal connection not connected as required

1
Nanjing Longyuan Electric Technology Co., LTD

II Overview

Multi-function power monitoring instrument is a power monitoring instrument

integrating data collection and control functions, It is suitable for power systems of

various voltage levels.This series of instruments replaces a variety of meters, relays,

transmitters, and other components.The instrument is standard with RS485

communication, by expanding Profibus communication, up to 1.5Mbps communication

rate, can fully meet the requirements of real-time data acquisition; can accurately

measure harmonics up to 63 times; users can realize remote monitoring through

software.The terminal is convenient for field wiring and maintenance, and provides a

variety of flexible expansion blocks.The instrument has been widely used in various

industries.

III. Product specifications and parameters

1. Technical indicators

performance
performance parameter
index
U、Level I: Level
0.2, P, Q, PF:
Level 0.5, F: ±
accuracy class 0.01HZ,
Active power:
0.5S, reactive
power: 2
display mode LCD show
Three phase
network three lines, three
phase four lines
AC100V,AC400V
rated voltage
,AC690V
frequency range 45~65HZ
input voltage
1.2Un
overload capacity (continuous); 2Un
(10S allowed)

2
Nanjing Longyuan Electric Technology Co., LTD

measuring range 5V~1.2Un


At 0.1VA per
Functional consumption
phase
rated current AC1A 、AC5A
1.2In
overload capacity (continuous);
20In (allowed 1S)
input currenton 5mA~6A (Rated
measuring range 5A);1mA~1.2A
(rated 1A)
At 0.2VA per
Functional consumption
phase
AC/DC
Operating voltage range
working power supply 85V~265V
power dissipation ≦5VA
Wet node
(external
on-off input Enter the form AC220V± 20%) /
dry node (internal
DC15V)
Mechanical
output form
contact
Switch output
AC250V/5A,
Contact capacity
DC30V/5A
output range 4~20mA
Analog output
Maximum load capacity 500Ω
2-Circuit electric
power pulse
pulse output output, optical
coupling and
isolation
RS485, Profibus,
Interface form
and wireless RF
communication interface Modbus-RTU,
protocol DL645, DP
protocols, etc
Ambient
temperature:
25℃ ~70℃,
ambient condition working temperature relative humidity:
95%,
No corrosive gas
site, elevation of

3
Nanjing Longyuan Electric Technology Co., LTD

2500m
storage temperature -35℃~80℃
GB / T11287 rigor
vibrate
level 1
GB / T14537 rigor
mechanical behavior lash
level 1
GB / T14537 rigor
collide
level 1
GB / T
RF electromagnetic field
17626.3-2006
disturbance resistance test
rigor level 3
GB / T
Fast transient pulse group test 17626.4-2008
Savor Level 4
GB / T
Resistance test of attenuation
17626.12-1998
oscillation wave
rigor level 3
GB / T
Electrostatic discharge test 17626.2-2006
Savor Level 4
Electromagnetic
GB / T
compatibility performance
Wave surge resistance 17626.5-2008
Savor Level 4
GB / T
RF conduction immunity 17626.6-2008
rigor level 3
GB / T
17215.211-2006
radio interference
Class 7.5.8B
devices
GB / T
Power-frequency magnetic field
17626.8-2006
interference degree
rigor level 3
GBT 13729-2002,
insulation resistance not less than
100M
GBT 13729-2002,
Electrical insulation with a power
dielectric strength
performance frequency voltage
of 2KV, for 1 min
GBT
impulse voltage 13729-2002,
1.2/50μs,5KV

4
Nanjing Longyuan Electric Technology Co., LTD

79mm*79mm*62.
5mm、
High * wide * deep
100mm*100mm*
67.5mm
size
66±0.5mm*66±0.
5mm、
Open hole size
90±0.5mm*90±0.
5mm

2. Functional parameters

or LCD
fun
de multi-func
ctio
r tion
nal Function
nu Description of functional points complex
mo point
m rate table
dul
be
e LON913F
r
phase
1 Phase Voltage: Ua, Ub, and Uc √
voltage
2 line voltage Line voltage: Uab, Ubc, Uca √
phase
3 Phase current: Ia, Ib, and Ic √
real current
-tim 4 active power Active power: Pa, Pb, Pc, P √
e reactive
5 Reactive power: Qa, Qb, Qc, Q √
me power
asu apparent
6 Visual power: Sa, Sb, Sc, S √
rem output
ent 7 power factor Power factor: Pfa, Pfb, Pfc, and Pf √
phase
8 Voltage / current: Ua, Ub, Uc, Ia, Ib, Ic √
position
9 frequency system frequency:F √
10 temperature Ta、Tb、Tc □
Ele Active Phase separation and phase combination
11 √
ctric power bidirectional active electric energy
ity Reactive Phase separation and phase combination
12 √
me power bidirectional reactive electric energy
asu
See in
rem 13 Divphase, together in electric energy √
magnitude
ent
14 time zone Up to 4 time zones are supported √
Re-
Up to 4 days are supported, and up to 8 days per
rate 15 time interval √
session
5
Nanjing Longyuan Electric Technology Co., LTD

Most support for sharp, peak, flat, valley four


16 rate √
rates
Recurrent Forward / reverse active power complex rate
17 √
rate power degree
The monthly freezing day can be set from 1 to
28, and the electric energy of this month can be
Month
18 automatically recorded at the zero point on the √
frozen
set day of each month, which can be recorded
free
for 36 consecutive months
ze
Automatic record of the electric energy of this
month at zero point a day, and can continuously
19 Day freeze √
record the latest
Electricity on the 90th
Demand
statistics
de
Reactive Slide active / reactive / visual real-time demand
ma 20 □
power statistics, maximum / minimum
nd
See in
magnitude
rem Open into
21 Have an open in, open a remote letter state □
ote open
sign The more
allin 22 limited the With 8 level limit alarm remote message status √
g alarm
The Level 8 overlimit alarm function can realize the
mor The more monitoring of power parameters and remote
e 23 limited the information quantity, generate alarm when the √
limit alarm conditions are met, and can link the alarm exit
ed with the opening
Has no less than 256 SOE records
Features, including switch change, remote
SOE take
24 control, □
notes
inci Limit the alarm, etc., and bring the time mark
den record
t Can count the maximum and minimum value of
rec relevant parameters (each phase / line voltage,
ord The most current, active power, reactive power, apparent
25 □
value record power, power factor, power factor, frequency
and demand) in real time, and record with time
scale
cloc
26 clock With a hardware precision clock √
k
ana 27 Analog Optional 1-3-way analog output, □

6
Nanjing Longyuan Electric Technology Co., LTD

log output Support for 4-20mA


qua
ntity
Up to 1-4-way switch quantity can be selected
28 on-off input Enter, selecas active node □
Or passive node entry
Up to 1-4 circuit switch output, support level /
Switch
29 pulse type, support remote control or as a local □
IO output
over-limit alarm
With active power and reactive electric energy
Pulse output port, used for electrical energy
30 pulse output √
meter
Precision detection
RS485 1 RS485 communication, MODBUS-RTU
co
31 Communica protocol; online upgrade through RS485 √
mm
tion (R) interface
unic
Profibus
atio
32 Communica Dp protocol □
n
tions (P)
inte
Wireless
rfac
33 communicat LoRa、Zigbee □
e
ion
Note: The "" flag is standard with this feature, and "□" means this feature is optional
Note: 39,40,41 differences for the functional parameters in the table above are as
follows
1) . on-off input:

67 * 67 Open hole: up to 1-3 switch input, either active or passive node.

91 * 91 Opening: select up to 1-4 switch quantity input, either active or passive node.

2) . Switch volume output:

67 * 67 Open hole: up to 1-2 switch output, support level / pulse type, support remote

control or as a local over-limit alarm exit.

91 * 91 Hole: you can choose up to 1-4 switch output, support level / pulse type, support

remote control or as a local over-limit alarm exit.

3) . Analog output:

67 * 67 Open hole: Select 1-2 analog output, support 4-20mA.

91 * 91 Open hole: can choose 1-3 analog output, support 4-20mA.

7
Nanjing Longyuan Electric Technology Co., LTD

IV. Product hole opening and installation schematic diagram


Size: 79mm×79mm×62.5mm
Open hole: 66mm and 66mm

8
Nanjing Longyuan Electric Technology Co., LTD

Size: 100mm×100mm×67.5mm
Open hole: 90mm and 90mm

9
Nanjing Longyuan Electric Technology Co., LTD

V. Product wiring schematic diagram and terminal

definition diagram

Fig. (1) Schematic diagram of the product wiring

Figure (2) Terminal definition diagram

10
Nanjing Longyuan Electric Technology Co., LTD

VI. Programming and use

1. The instrument panel displays the information

2. Round the interface

Measurement and display wheel-tracking interface:

pres interface explain pres interface explain


s s
down dow
n

11
Nanjing Longyuan Electric Technology Co., LTD

Display the Displays the


measured phase measuring line
voltage voltage
phase line
1
voltage:Ua.Ub.Uc voltage:Uab.Ubc.Uc
Pow
Three-phase three 2 a
er
lines without this Uab=380V
first
interface Ubc=380V
interf
Ua=220V Uca=380V
ace
Ub=220V Reverse active
Uc=220V power: 6.8KWh
Forward active
power: 3.6KWh
pres interface explain pres interface explain
s s
down dow
n
Display of the Display the
measured measured
three-phase three-phase active
current power
Ia.Ib.Ic Active power of
Ia=5A phase A is 1.00KW
Ib=5A Phase B active
3 4
Ic=5A power is 1.00KW
Forward reactive Phase C active
power: 5.2Kvarh power is 1.00KW
The total active
power is 3.00KW
Reverse reactive
power power
1.2Kvarh

pres interface explain pres interface explain


s s
down dow
n
Three-phase Show the measured
reactive power is three-phase view in
5 displayed 6 the power
Phase A reactive A Phase Vision at
power of 1.73Kvar power 2.00KVA
Phase B reactive B Phase Vision at
power of 1.73Kvar power 2.00KVA
12
Nanjing Longyuan Electric Technology Co., LTD

C phase reactive C Phase Vision at


power of 1.73Kvar power 2.00KVA
Three-phase total The three-phase
no-power is total visual power is
5.20Kvar positive 6.00KVA
To the active power Reverse active
energy of 2.3KWh power: 6.1KWH
pres interface explain pres interface explain
s s
down dow
n
Show the Displays the
three-phase power measurement
factor frequency
Phase A power System frequency is
factor of 0.500 50Hz
7 Phase B power 8 Reverse reactive
factor of 0.500 power power at
Phase C power 5.9Kvarh
factor of 0.500
The system power
factor is 0.500
Forward reactive
power at 7.5Kvarh
pres interface explain pres interface explain
s s
down dow
n
Display the Display the
measured measured
three-phase three-phase current
voltage angle angle
Phase A voltage Phase A voltage
9 angle of 0 10 angle 60
Phase B voltage Phase B voltage
angle of 120 angle of 180
Phase C voltage Phase C voltage
angle 240 angle 360
Forward active Reverse active
power: 0.0KWh power: 0.0KWh

pres pres
interface explain interface explain
s s

13
Nanjing Longyuan Electric Technology Co., LTD

down dow
n
Show the Show the measured
measured DI on-off DI on-off status
status 1 / 2 / 3 / 4 Display
1 / 2 / 3 / 4 Display as a 4-way DO
as a 4-way DI function
11 function 12
0 means points,
and 1 means
combination
Forward reactive
power energy:
0.0KWh

pres
pres
s
s interface explain interface explain
dow
down
n
Displays the
measurement
demand
Active power
demand is 1.3KW
13
Reactive power
requirement is
1.0Kvar
Visual power
demand: 3.9KVA
Forward active
power: 0.0KWh

Rerate display wheel-based interface:

pres interface explain pres interface explain


s s
down dow
n
Displays the Show rate this
current system month
1 time 2 The first period of
electricity
The electric
energy is

14
Nanjing Longyuan Electric Technology Co., LTD

1.0KWh

pres interface explain pres interface explain


s s
down dow
n
Show rate this Show rate this
month month
3 4
The second period The third period
of electricity of electricity
Electricity rate is Electricity rate
8.8KWh was 8.0KWh
pres interface explain pres interface explain
s s
down dow
n
Show rate this Display the
month measurement of
5 The fourth period 6 last month
of electricity Total electric
Electrical energy is energy
0.0KWh Electrical energy
is 0.0KWh
pres interface explain pres interface explain
s s
down dow
n
Display the Display the
measurement of measurement of
last month last month
7 8
Total electric power Total electric
in the first period energy in the
Electrical energy is second period
0.0KWh Electrical energy
is 0.0KWh
pres interface explain pres interface explain
s s
down dow
n

15
Nanjing Longyuan Electric Technology Co., LTD

Display the Display the


measurement of measurement of
last month last month
9 Total electric 10 Total electric
energy in the third power energy in
period the fourth period
Electrical energy is Electrical energy
0.0KWh is 0.0KWh

pres
pres
s
s interface explain interface explain
dow
down
n
Show Show
measurement last measurement
February last February
11 12
Total electric Total electric
energy power in the first
Electrical energy is period
0.0KWh Electrical energy
is 0.0KWh
pres
pres
s
s interface explain interface explain
dow
down
n
Show Show
measurement last measurement
February last February
13 14
Total electric Total electric
energy in the energy in the
second period third period
Electrical energy is Electrical energy
0.0KWh is 0.0KWh
pres
pres
s
s interface explain interface explain
dow
down
n
Show Show the
measurement last measurements
15 16
February last March
Total electric power Total electric
energy in the fourth energy
period Electrical energy

16
Nanjing Longyuan Electric Technology Co., LTD

Electrical energy is is 0.0KWh


0.0KWh
pres
pres
s
s interface explain interface explain
dow
down
n
Show the Show the
measurements last measurements
March last March
17 18
Total electric power Total electric
in the first period energy in the
Electrical energy is second period
0.0KWh Electrical energy
is 0.0KWh
pres
pres
s
s interface explain interface explain
dow
down
n
Show the Show the
measurements last measurements
March last March
19 20
Total electric Total electric
energy in the third power energy in
period the fourth period
Electrical energy is Electrical energy
0.0KWh is 0.0KWh

Power quality wheel-tracking interface

pres interface explain pres interface explain


s s
down dow
n
Show the positive Show the positive
order, the negative order, the
1 2
order, and negative order,
residual voltage and
zero-sequence
current
pres interface explain pres interface explain
s s
down dow

17
Nanjing Longyuan Electric Technology Co., LTD

n
Display the total Display the
voltage harmonic voltage-odd
3 4
harmonics

pres interface explain pres interface explain


s s
down dow
n
Displays the Displays the total
voltage-even current
5 6
harmonics harmonics

pres interface explain pres interface explain


s s
down dow
n
Display the Show the current
current-odd even harmonics
7 8
harmonics

pres interface explain pres interface explain


s s
down dow
n
Displays the Display plays
voltage wave peak voltage harmonic
9 10
coefficient form factor

pres
pres
s
s interface explain interface explain
dow
down
n

18
Nanjing Longyuan Electric Technology Co., LTD

Current K Displays the


coefficient is shown voltage and
11 12
current
imbalance value

pres
pres
s
s interface explain interface explain
dow
down
n
Display the voltage Display the
for 2 harmonics voltage for 2
13 14 harmonics

pres
pres
s
s interface explain interface explain
dow
down
n
Display the voltage Display the
for 3 times current for 3
15 harmonics 16 times harmonics

pres
pres
s
s interface explain interface explain
dow
down
n
Display the voltage Display the
of 4 harmonics current for 4
17 18
harmonics

pres
pres
s
s interface explain interface explain
dow
down
n

19
Nanjing Longyuan Electric Technology Co., LTD

Display the voltage Show the current


of 5 harmonics for 5 harmonics
19 20

pres
pres
s
s interface explain interface explain
dow
down
n
Display a voltage of Show the current
6 harmonics for 6 harmonics
21 22

pres
pres
s
s interface explain interface explain
dow
down
n
Display a voltage of Show the current
7 harmonics for 7 harmonics
23 24

pres
pres
s
s interface explain interface explain
dow
down
n
Display the voltage Show the current
of 8 harmonics for 8 harmonics
25 26

pres
pres
s
s interface explain interface explain
dow
down
n

20
Nanjing Longyuan Electric Technology Co., LTD

Display the Show the current


voltage, 9 of 9 harmonics
27 28
harmonics

Event records display the wheel-based interface

pres interface explain pres interface explain


s s
down dow
n
Show the power Show the first road
reset event to exit
Date: April 18,2019 Open the event
1 2
12:11:48 Date: April 18,2019
12:11:48

pres interface explain pres interface explain


s s
down dow
n
Show the first road Show no event
to exit record
Open the event
3 4
Date: April 18,2019
12:11:48

pres interface explain pres interface explain


s s
down dow
n

21
Nanjing Longyuan Electric Technology Co., LTD

Show no event Show no event


record record

5 6

pres interface explain pres interface explain


s s
down dow
n
Show no event Show no event
record record
7 8

pres interface explain pres interface explain


s s
down dow
n
Show no event Show no event
record record
9 10

pres
pres
s
s interface explain interface explain
dow
down
n
Show no event Show no event
record record
11 12

The most valued wheel follows the interface

pres interface explain pres interface explain


s s
22
Nanjing Longyuan Electric Technology Co., LTD

down dow
n
Displays the Displays the
measured phase measured phase
1 voltage maximum 2 voltage minimum
value value

pres interface explain pres interface explain


s s
down dow
n
Displays the Displays the
maximum measured line
3 4
measurement line voltage minimum
voltage value

pres interface explain pres interface explain


s s
down dow
n
Displays the Displays the
maximum minimum measured
5 6
measured current current value
value

pres interface explain pres interface explain


s s
down dow
n
Displays the Displays the
measurement measurement
Maximum active Minimum of active
7 8
power value power value
Reactive power Reactive power
maximum value minimum value
Visual power Visual power
maximum value minimum value
pres interface explain pres interface explain
s s
down dow

23
Nanjing Longyuan Electric Technology Co., LTD

n
Displays the Displays the
measurement measurement
9 10
Power factor Power factor
maximum value minimum value
Maximum Minimum frequency
frequency
pres
pres
s
s interface explain interface explain
dow
down
n
Displays the Displays the
measurement measurement
Maximum active Active power
power demand demand minimum
11 value 12 value
Reactive power Reactive power
demand maximum requirement
value minimum
Maximum apparent Visual power
power demand demand minimum
value
Note: Please refer to the corresponding function interface described above
according to the product function and model comparison.

24
Nanjing Longyuan Electric Technology Co., LTD

3. Set the interface

Basic parameter setting interface

25
Nanjing Longyuan Electric Technology Co., LTD

Setting interface of switching quantity and simulation quantity

pres interface explain pres interface explain


s s
down dow
n
Press the Press the
interface into the interface into the
first route open second route open
volume output volume output
mode: remote mode: remote
control level control level
pattern pattern
Press, to flash in Press, to flash in
1 the position the position
2
Press, to Press, to
modify it modify it
Set up: Remote Set up: Remote
control pulse control pulse
Warning level Warning level
Alarm pulse Alarm pulse
Press OK to Press OK to
complete the complete the
settings settings
pres interface explain pres interface explain
s s
down dow
n
Press the Press the
interface into the interface of the
third route open fourth output output
volume output mode: remote
mode: remote control level
control level pattern
pattern Press, to flash in
3
Press, to flash in 4 the position
the position Press, to
Press, to modify it
modify it Set up: Remote
Set up: Remote control pulse
control pulse Warning level
Warning level Alarm pulse
Alarm pulse Press OK to
26
Nanjing Longyuan Electric Technology Co., LTD

Press OK to complete the


complete the settings
settings
pres interface explain pres interface explain
s s
down dow
n
Press into the Press into the first
first route of analog route of analog
volume volume
Output Setup Output upper limit
Interface setting interface
Press, to flash in Press, to flash in
the position the position
5 6
Press, to Press, to
modify it modify it
association Can be set
object:IA from-120% to 120%
Press OK to Press OK to
complete the complete the
settings settings
pres interface explain pres interface explain
s s
down dow
n
Press into the Press into the
first route of analog second route of
volume analog quantity
Output lower floor Output Setup
setting interface Interface
Press, to flash in Press, to flash in
the position the position
7 Press, to 8 Press, to
modify it modify it
Can be set association
from-120% to object:PS
120% Press OK to
Press OK to complete the
complete the settings
settings
pres interface explain pres interface explain
s s
down dow

27
Nanjing Longyuan Electric Technology Co., LTD

n
Press into the Press into the
second route of second route of
analog quantity analog quantity
Output upper limit Output lower floor
setting interface setting interface
Press, to flash in Press, to flash in
the position the position
9 Press, to 10 Press, to
modify it modify it
Can be set Can be set
from-120% to from-120% to 120%
120% Press OK to
Press OK to complete the
complete the settings
settings
pres
pres
s
s interface explain interface explain
dow
down
n
Press into the Press into the
third route of third route of analog
analog volume volume
Output Setup Output upper limit
Interface setting interface
Press, to flash in Press, to flash in
the position the position
11 12
Press, to Press, to
modify it modify it
association Can be set
object:PF from-120% to 120%
Press OK to Press OK to
complete the complete the
settings settings
pres
pres
s
s interface explain interface explain
dow
down
n

28
Nanjing Longyuan Electric Technology Co., LTD

Press into the Press the entry


third route of demand calculation
analog volume cycle
Output lower floor Time setting
setting interface interface
Press, to flash in Press, to flash in
the position the position
13 Press, to 14 Press, to
modify it modify it
Can be set Can be set for
from-120% to 1-30min
120% Press OK to
Press OK to complete the
complete the settings
settings
pres
pres
s
s interface explain interface explain
dow
down
n
Press to enter Press the enter
the power energy event reset interface
zero clearance Press, to flash in
interface the position
Press, to flash Press, to
in the position modify it
15 Press, to 16 NO: no zero, YES:
modify it no zero
NO: no zero, YES: Press OK to
no zero complete the
Press OK to settings
complete the
settings
pres
pres
s
s interface explain interface explain
dow
down
n
Press the enter
maximum reset
interface
17 Press, to flash
in the position
Press, to
modify it

29
Nanjing Longyuan Electric Technology Co., LTD

NO: no zero, YES:


no zero
Press OK to
complete the
settings

Note 1: Analog quantity output


The instrument can have a 3-way analog output function, and the set rated
parameter percentage from 0-100% corresponding analog output is
4-20mA DC current.

Compound rate setting interface


pres interface explain pres interface explain
s s
down dow
n
Press the enter Press the enter
rate clock setting rate period setting
interface interface
Press, to flash in Press, to flash in
the position the position
1 2
Press, to Press, to
modify it modify it
Press OK to Set up: 0-8 time
complete the periods
settings Press OK to
complete the
settings
pres interface explain pres interface explain
s s
down dow
n

30
Nanjing Longyuan Electric Technology Co., LTD

Press the four Press the four rate


rate time setting time setting
interface for the interface for the
first rate period second rate period
3 Press, to flash in 4 Press, to flash in
the position the position
Press, to Press, to
modify it modify it
Press OK to Press OK to
complete the complete the
settings settings
pres interface explain pres interface explain
s s
down dow
n
Press the four Press the four rate
rate time setting time setting
interface in the interface in the
third rerate period fourth rerate period
5 Press, to flash in 6 Press, to flash in
the position the position
Press, to Press, to
modify it modify it
Press OK to Press OK to
complete the complete the
settings settings
pres interface explain pres interface explain
s s
down dow
n
Press the four Press enter
rate time setting Rerate 6
interface in the fifth Four-segment rate
rerate period time setting
Press, to flash in interface
7 8
the position Press, to flash in
Press, to the position
modify it Press, to
Press OK to modify it
complete the Press OK to
settings complete the
settings
pres interface explain pres interface explain

31
Nanjing Longyuan Electric Technology Co., LTD

s s
down dow
n
Press to enter Press into Rerate
prime rate 7 8
Four-segment rate Four-segment rate
time setting time setting
interface interface
9 10
Press, to flash in Press, to flash in
the position the position
Press, to Press, to
modify it modify it
Press OK to Press OK to
complete the complete the
settings settings

Note: Please set the above corresponding function interface according to the
product function model comparison.

VII Digital communication

Provide serial asynchronous semi-work RS485 communication interface, using

MODBUS-RTU protocol, all kinds of data recording and interest can be transmitted on the

communication line.Up to 32 network power meters can be connected simultaneously on

one line, and each network power instrument can set its communication address (Address

No.), Communication terminal number of different series of instruments is different,

communication connection shall be shielded twisted pair wire with copper network, wire

diameter not less than 0.5mm2. When wiring, communication lines should be used away

from the strong electric cable or other strong electric field environment. The connection

mode of bus network is recommended, and the star shape or other connection mode is

not recommended.

MODBUS-RTU communication protocol: the MODBUS protocol adopts the main and

slave response communication connection mode on one communication line.First, the

signal of the host computer is addressed to a unique address terminal device (slave), and

then the response signal from the terminal device is transmitted to the host in the opposite

32
Nanjing Longyuan Electric Technology Co., LTD

direction, that is, all the communication data flow of the signal (semi-duplex working mode)

in a separate communication line in two opposite directions.

The MODBUS protocol only allows communication between the host (PC, PLC, etc.)

and the terminal devices, but not data exchange between independent terminal devices,

so that each terminal device does not occupy the communication line when they initialize,

but only respond to query signals that reach the local machine.

Host query: the query message frame includes the device address code, function

code, data information code and check code.The address code indicates the slave device

to be selected; the function code tells the selected slave device to perform, such as the

function code 03 or 04 requires the registers to be read and returned from the device; the

data segment contains other additional information to perform functions from the device,

such as the number of registers to read from in the read command; the check code is

used to check the correctness of a frame information, providing a means to verify the

correctness of the message content using the calibration rule of CRC16.

slave response: If a normal response is generated from the device, there are slave

address code, function code, data information code and CRC16 check code in the

response message.The data information code includes data collected from the device:

such as a register value or status.If an error occurs, we agree that the slave will not

respond.

Transmission mode refers to a series of independent data structures within a data

frame and limited rules for transmitting data, defined the following transmission mode

compatible with the MODBUS protocol-RTU mode.Bit per byte: 1 start bit, 8 data bits, 2

stop bits (no parity bits).

Structure of the data frame: that is, the message format.


address code FC numeric data code check code
1 BYTE 1 BYTE N individual BYTE 2 BYTE
Address code at the beginning of the frame, composed of a byte (8-bit binary code),

decimal is 0~255, only 1~247 is used in our system, other addresses are retained.These

bits indicate the address of a user-specified terminal device that will receive host data

from being connected to it.Each terminal device's address must be unique, and only the

33
Nanjing Longyuan Electric Technology Co., LTD

addressed terminal will respond to a query containing that address.When the terminal

sends back a response, the slave address data in the response tells the host which

terminal is communicating with it.

The function code tells the addressed terminal what functions to perform.The

following table lists the supported function codes, as well as their meaning and

functionality.
code meaning action
Get the current binary value for one or
03/04 Read the data register
more registers
Power data reset (clear 0) Clear the electricity data of the operated
08
instrument to 0
Set the binary value to the relevant
16 Write the preset register
register
The data code contains data required for the terminal to perform specific functions or

data collected when the terminal responds to a query.The contents of these data may be

numerical values, reference addresses, or set values.For example, the functional domain

code tells the terminal to read a register, the data domain needs to reflect which register

starts and how many data to read, and the slave data code return content contains the

data length and the corresponding data.

The Check Code Error Check (CRC) domain takes up two bytes and contains a 16-bit

binary value.The CRC value is calculated by the transmission device and then attached to

the data frame, where the receiving device recalculates the CRC value upon receiving the

data and then compares it with the value in the received CRC domain.If the two values are

not equal, an error occurs.

The process for generating a CRC is:

(1) To preset a 16-bit register is OFFFFH (16 decimal system, all 1), called the CRC

register.

(2) Put the 8 bits of the first byte in the data frame together with the low bytes in the CRC

register, and save the results back to the CRC register.

(3) Move the CRC register to one bit to the right, the highest bit fill in to 0, the lowest shift

out and detect.

34
Nanjing Longyuan Electric Technology Co., LTD

(4) If the bit removed in the previous step is 0: repeat the third step (next shift); 1: compare

the CRC register with a preset fixed value (0A001H).

(5) Repeat the third and fourth steps until 8 shifts.This completes a complete eight bits.

(6) Repeat steps 2 through 5 to process the next octet until all bytes are finished.

(7) The value of the final CRC register is the value of the CRC.

35
Nanjing Longyuan Electric Technology Co., LTD

1. Read the data (function code: 03 / 04): This function enables users to obtain the

data collected and recorded by the terminal equipment, as well as the system

parameters.There is no limit on the number of data collected by the host upon request at a

time, but it cannot exceed the defined address range.The following example starts from

the data Ia, Ib and Ic (Ia has 18 (12H) in the data frame is 18 (12 H) and the data length is

6 (06H).Word communication mode.)

Query the data frame (host)

36
Nanjing Longyuan Electric Technology Co., LTD

Start
Number of CRC1 CEC1
register Start register Number of
addr registers 6 6
order address address registers
ess (high-order low-or high-o
(high-order (low-order) (low-order)
) der rder
)

0CH 03H 00H 12H 00H 06H 64H D0H

Response Data Frame (slave)


CRC16
addre CRC16
order DL Data 1 to 12 low-ord
ss low-order
er
43556680H、43203040H、
0CH 03H 0CH 78H DEH
42DDCC80H

Indicates that the Ia=43556680H(213.4A), Ib=43203040H(160.1A),

Ic=42DDCC80(110.8A).

Preset data (function code: 16): This feature allows users to change the contents of

multiple registers (emphasizing that the written data is a writable attribute parameter).The

number does not exceed the address range, the following example is the write current

change ratio of 400A / 5A=80 communication mode.

Preset data frame (host)


Start
Start Numbe Numb
registe
register r of er of CRC CEC1
add r write
addres register registe byte 16 6
res order addres in
s s rs length low-o high-o
s s data
(low-or (high-or (low-or rder rder
(high-
der) der) der)
order)

0C 00H
10H 00H 03H 00H 01H 02H FFH CFH
H 50H

Response data frame (slave), indicating that the data has been written.
Start Start Number Number
register register of of CEC16
addres orde CRC16
address address registers registers high-or
s r low-order
(high-order (low-order (high-or (low-ord der
) ) der) er)

0CH 10H 00H 04H 00H 01H 41H 15H

37
Nanjing Longyuan Electric Technology Co., LTD

Address table
Measured value, base address: 0x0500
offset address length name unit Symbol property
Phase voltage (primary value)
0x00 2 UA voltage V float
0x02 2 UB voltage V float
0x04 2 UC voltage V float
Line voltage (primary value)
0x06 2 UAB voltage V float
0x08 2 UBC voltage V float
0x0A 2 UAC voltage V float
Current (primary value)
0x0C 2 A phase current A float
0x0E 2 B phase current A float
0x10 2 C phase current A float
Active power (primary value)
A phase
0x12 2 meritorious KW float
service
0x14 2 B KW float
0x16 2 C KW float
Total active
0x18 2 KW float
power
Reactive power (primary value)
A phase without
0x1A 2 kvar float
work
B phase without
0x1C 2 kvar float
work
C phase without
0x1E 2 kvar float
work
Total reactive
0x20 2 kvar float
power
Visual power (primary value)
A looks at the
0x22 2 KVA float
power
B looks at the
0x24 2 KVA float
power
C looks at the
0x26 2 KVA float
power
Always see in
0x28 2 KVA float
power

38
Nanjing Longyuan Electric Technology Co., LTD

Power factor (primary value)


Phase A power
0x2A 1 1 float
factor
Phase B power
0x2C 1 1 float
factor
Phase C power
0x2E 1 1 float
factor
Total power
0x30 1 1 float
factor
angle
Phase A voltage
0x32 1 ° float
angle
Phase B voltage
0x34 1 ° float
angle
C Phase voltage
0x36 1 ° float
angle
Angle of phase A
0x38 1 ° float
current
Phase B current
0x3A 1 ° float
angle
C phase current
0x3C 1 ° float
angle
frequency
Voltage
0x3E 1 Hz float
frequency

address length name unit Symbol property


Combined phase electric energy
0x3c 2 Positive active power 0.1KWh Unsigned type
0x3e 2 continue to have Unsigned type
0x40 2 Reverse active power 0.1KWh Unsigned type
0x42 2 continue to have Unsigned type
0x44 2 Positive reactive power 0.1KWh Unsigned type
0x46 2 continue to have Unsigned type
0x48 2 Reverse reactive power 0.1KWh Unsigned type
0x4a 2 continue to have Unsigned type
Always see in the
0x4c 2 0.1KWh Unsigned type
degree of electricity
0x4e 2 continue to have Unsigned type

39
Nanjing Longyuan Electric Technology Co., LTD

VIII After-sale service


Ensure the timely delivery of the products to the customer during the supply period.

The company's products have been strictly inspected qualified products, along with the

product with the certificate, instructions and related accessories.

The products sold by the company are free of charge within 18 months, free

maintenance within 19-36 months, and lifelong maintenance. Except for man-made or

natural disasters, they all belong to the service scope of our company.

All products sold by the company enjoy lifelong maintenance, products beyond warranty,

provide free service, only for the replacement of components.

Our company undertakes the obligation to provide product technical consultation to

users, solve the problems encountered in the installation and use process, and produce

special products according to customer requirements.

If the user found product quality problems or damaged in transportation and can't use

normally, please call our national service hotline: 400-653-7168, our company will reply

within one working day, the company according to replace the product situation, if the

technical personnel to arrive at the site assistance or guidance, the time is; 800 km 24

hours, 2000 km within 48 hours.Within 96 hours, 2,000 km away.

40
This manual is prepared as standard. If the user finds the product inconsistent with

this manual, the function is not selected or has been upgraded.The contents in this

manual will be reviewed regularly and make necessary modifications in the next edition.

Recommendations are welcome.

The copyright of the specification belongs to Nanjing Longyuan Electric Technology

Co., Ltd. and shall not be reproduced, disseminated or used in this document and its

contents without written permission.