Technical Data Book
Technical Data Book
Technical Data Book
Contents
Page No.
2
Armoured Aluminium Conductor 1.1 kV Grade
Multi- core U.G . Cable.
Area in Sq.mm
sheathed
Sl. No. In In Air In In In Air In
Ground Duct Ground Duct
1. 6 35 30 30 43 40 =
2. 10 46 40 39 57 53 =
3. 16 60 51 50 73 70 58
4. 25 76 70 63 97 95 78
5. 35 92 86 77 116 117 93
3
Current Ratings for Single core PVC
insulated copper wires 650 / 1100 v grade
0.40 mm
0.45 mm
0.3 mm
Area in
Sq.mm
Amps
SWG
Dia.
Dia.
Dia.
1.00 1/8 14 /.3 11
1.50 3 / 22 22 /.3 13
2.00 3 / 20 28 /.3 16
2.50 7 / 24 36 /.3 18
3.00 7 / 22 44 /.3 20
4.00 7 / 21 56 /.3 24
4.50 7 / 20 65 /.3 28
6.00 7 / 18 84 /.3 38 /.45 31
10.00 7 / 17 140/.3 80 /.4 64 /.45 42
16.00 7 / 16 226/.3 126/.4 101/.45 57
25.00 7 / 14 354/.3 196/.4 168/.45 67
35.00 7 / 12 276/.4 224/.45 86
50.00 7 / 11 396/.4 323/.45 116
70.00 7/9 437/.45 185
Sheet Thickness
Cross sectional
Cross sectional
Area of wires
Area of wires
in sq. mm
in sq. mm
wire Dia. /
wire Dia. /
SWG
SWG
In mm
In mm
4
Sheet Metal Thickness &
Dia. Of Wires in SWG
Sheet Thickness
Sheet Thickness
Cross sectional
Cross sectional
Area of wires
Area of wires
in sq. mm
in sq. mm
wire Dia. /
wire Dia. /
SWG
SWG
In mm
In mm
6 4.88 18.68 29 0.35 0.09
7 4.47 15.70 30 0.32 0.08
8 4.06 12.97 31 0.30 0.07
9 3.66 10.51 32 0.27 0.059
10 3.25 8.30 33 0.25 0.051
11 2.95 6.82 34 0.23 0.043
12 2.64 5.48 35 0.21 0.036
13 2.34 4.29 36 0.19 0.029
14 2.03 3.24 37 0.17 0.023
15 1.83 2.62 38 0.15 0.018
16 1.63 2.08 39 0.13 0.014
17 1.42 1.59 40 0.12 0.012
18 1.22 1.17 41 0.11 0.01
19 1.02 0.81 42 0.10 0.008
20 0.91 0.66 43 0.09 0.007
21 0.81 0.52 44 0.08 0.005
22 0.71 0.40 45 0.07 0.004
23 0.61 0.29 46 0.06 0.003
24 0.56 0.25 47 0.05 0.002
25 0.51 0.20 48 0.04 0.001
26 0.46 0.16 49 0.03 0.0007
27 0.42 0.14 50 0.02 0.0005
28 0.38 0.11
5
Current calculation
At 0.8 P.F. 3 Phase 415V single Phase 230 V
( kVA x 1.39 ) A ( kVA x 4.35 ) A
( kW x 1.74 ) A ( kW x 5.43 ) A
( hp x 1.30 ) A ( hp x 4.05 A
At 1.0 P.F. 3 Phase 415V single Phase 230 V
kVA = kW at unity P F
( kVA x 1.39 ) A ( kVA x 4.35 ) A
( kW x 1.39 ) A ( kW x 4.35 ) A
( hp x 1.04 ) A ( hp x 3.25 ) A
6
Yard-stick for staff quarters
Sl Description Type - I V
No Type - I Type - I I Type - I I I
1 Power plug 3 3 3 3
2 Ceiling Fan 2 3 4 5
3 Exhaust Fan Nil Nil Nil 1 in Kitchen
4 Call bell 1 1 1 1
Light Pt. / Fan Pt. / Light - 13 pts.
Call Bell pt. / 5 A Fans/ Exha. Fan
5 Plug Pt. 17 20 23 6 - pts.
5 A plg - 5 pts.
Call bell - 1 pt.
7
Cable laying
Cable selection
q = 14.2 Ik t sq.mm
q = 9.4 Ik t sq.mm
8
CABLE LAYING ( M.V & H.T ) IN GROUND
D
A
SAND
C
cushion
B
E 15 15
20 cms
E E
17 cms
30 cms
A
8 cms
D
N1 = No. of additional cables in vertical formation.
N2 = No. of additional cables in horizontal formation.
9
Important points from specification.
Wiring
Point wiring: -
Group `A`: - Quarters type I to type III and hostels.
Group `B`: - Quarters Type IV and above, Exchanges
whose ceiling height is less than 3.6 mts
Group `C` : - all technical buildg and bldg of height 4 mts
and above.
Switch box cover is phenolic laminated 3 mm thick.
Switch box shall be 1.25 mts above floor level
Conduits
Conduit full length is 3 mts.
Upto 32 mm Dia. Conduits 16 swg ( 1.6 mm) wall thickness.
Above 32 mm Dia. Conduits shall be 14 swg ( 2 mm ) wall thickness.
Saddles shall be :- upto 25mm conduits -- 24 gauge ( 0.55
mm) 19 mm wide
Above 25 mm Dia. ----20 gauge (0.9 mm)
25 mm wide
Threaded portion of the conduit shall be 13mm to 19mm long.
For 50 meters length of Conduit , No. of saddles required is 85.
Earthing
Pipe earth :- Salt 5 Kgs. Charcoal 64 kgs. or coke 160 kgs,
Pipe Medium class 40 mm Dia. 4.5 mts long.
Holes 46 Nos 12 mm Dia. each & spaced 75mm from each other. Holes to be drilled
from bottom end of pipe upto 2mts.
G I Plate : - Salt 5 Kgs. Charcoal 96 kgs. or coke 240 kgs
Plate 600 x 600 x 6 mm buried in ground with
top 3 mts below ground level
Water pipe Medium class 20 mm Dia. 2.7 mts
long
Copper plate:- Same as GI plate
Copper plate size is 600 x 600 x 3 mm thick.
Earth sets should be minimum 2 mts apart.
10
Lightning Conductor
Horizontal Run : - For 10mts length 10 Nos saddles are required. ( 1.2 mts apart. )
Vertical Run : - For 10mts length 11 Nos saddles are required. ( 1 mt. apart )
No. of Horizontal runs : - Every 9 mts one run.
No. of vertical runs : - Every 30 mts of perimeter 1No.
Or
1 No. for first 100 sq.mt. of roof area & 1no. for every additional 300 sq.mts. whichever is less
but minimum 2nos are required..
Aluminium shall not be used below ground level.
Earth resistance for down conductor earth set shall be not more than 10 ohms.
Providing Finials are not necessary for horizontal roof but to be provided near isolated projections like
PVC tank. with height more than the projection.
Miscellaneous
Low voltage Not exceeding 250 volts
Medium voltage from 250 V upto 650 V
High voltage from 650 V upto 33 kV
Extra high Voltage Exceeding 33 kV
Every Electrical Installation should be tested for insulation value & earth resistance value once in every
five years.
11
Insulation of windings of Alternator / motor
The insulation rating should be either `E`` or ``B`` or ``F``
F is superior than B.
Class Withstanding Materials
Temperature
90 0 C Cotton, paper without impregnation
Y/
O
105 0 C Impregnated paper or cotton
A
E 120 0 C
B 130 0 C Mica, Glass , Asbestos,
F 155 0 C Mica, Glass , Asbestos,
H 180 0 C Mica, Glass , Asbestos, silicon
C Above Porcelain, quartz, mica
180 0 C
Transformer oil
Tested across two brass spheres of 18 mm Dia. each and separated with a clearance of 4 mm gap, and
immersed in transformer oil at a depth of 50 mm / 2`` minimum. Test voltage is AC with frequency
between 25 to 100 Hzs . The voltage is to be brought up slowly from 0 V to 40 kV in 20 or 30
secs. The transformer oil should withstand 40 kV for one minute.
Minimum transformer oil required for testing is 400 ml.
Electrical installations for insulation value & Earth resistance values are to be tested once in five years.
12
Weight of standard items
Copper items
Copper plate 600 x 600 x 3 mm 9.594 kgs. each
Copper strip 20 x 3 mm 0.533 kg / mt.
25 x 3 mm 0.666 kg / mt.
25 x 5 mm 1.110 kg / mt.
25 x 6 mm 1.333 kg / mt.
32 x 5 mm 1.421 kg / mt.
32 x 6 mm 1.705 kg / mt.
50 x 5 mm 2.221 kg / mt.
50 x 6 mm 2.665 kg / mt.
50 x 12.5 mm 5.552 kg / mt.
Copper wire No. 8 ( 4 mm Dia.) 0.117 kg / mt.
Copper wire No. 6 0.166 kg / mt.
Copper wire No.14 ( 2 mm Dia.) 2.878 / 100 mts.
G.I. items
G.I. plate 600 x 600 x 6 mm 16.6 kgs each
G.I. strip 20 x 3 mm 0.461 kg / mt.
25 x 3 mm 0.576 kg / mt.
25 x 5 mm 0.960 kg / mt.
25 x 6 mm 1.153 kg / mt.
32 x 5 mm 1.230 kg / mt.
32 x 6 mm 1.475 kg / mt.
50 x 5 mm 1.921 kg / mt.
50 x 6 mm 2.305 kg / mt.
50 x 12.5 mm 4.802 kg / mt.
G.I. wire No. 8 ( 4 mm Dia.) 0.100 kg / mt.
G.I. wire No. 6 0.144 kg / mt.
Other items
Transformer oil 0.877 kg / litre
Diesel 1.21 kg / litre
Petrol 0.75 kg / litre
Cement 50 kgs / bag
13
Room inside design conditions
DB Temp. 23 3 C ( 73 5 0 F )
0
RH 30 to 60 % ( 45 15 % )
Fresh Air One Air Change per hour.
Supply Air from Package unit ( called Dehumidified Air) is 450 cfm per TR. ( 770 cu.mts / TR / hr ).
Condenser Air flow is 1350 cu.mts / TR / hour ( 800 cfm / TR )
Supply Air Grill Area = ( Total cfm 500 ) sq.ft
Total cfm = Total tonnage x 500.
Supply Air Grill Area = R/A Grill Area.
Refrigerant required = 1.5 kg per TR.
Duct Details
Longest Upto 750 Above Above Above
side of mm 750 upto 1500 upto 2250 mm
the Duct 1500 mm 2250 mm
Sheet 24 swg 22 swg 20 swg 18 swg
Thickness
Air velocity at S/A Grills or R/A Grills = 500 ft / min.
Air velocity at Fine filters = 250 ft / min.
Air velocity at pre filters = 500 ft / min.
Re-heaters & pan humidifiers are not required as per DOT No 3-1-28 / EW / 99 Dated 02-02-1999 of
Director (EW).
Air velocity in G I Ducts : - In Main Duct = 1200 ft./ min.
In Branch Duct = 800 ft./ min.
In R/A Boxing = 100 ft./ min.
Pre-heaters = 1.08 x total cfm x 3 o F
= kWatts
3410
14
750 1600 750 1600
750 750
1000
Common Plenum 1000 x 1250
7800 mm
15
Dry-
bulb
Wet-bulb depression ( 0C DB - 0C WB )
12 14 16 18 20
0
C 10 20 30 40 50 60 70 80 90 10 0 0 0 0 0 0
00 82 64 48 32 16 2
20 84 69 54 39 24 11 0
40 85 70 56 43 32 19 7
%
60 87 72 59 46 34 23 15 4
R.H.in
80 87 75 62 50 39 28 18 8 2
10 0 88 76 65 54 44 33 23 14 5
12 0 89 78 68 57 48 38 29 20 11 3
14 0 90 79 70 60 51 42 33 25 17 9
16 0 90 81 71 62 54 46 37 30 22 14 0
18 0 91 82 73 65 56 49 40 34 27 20 6
20 0 91 83 74 66 59 51 44 37 30 24 11 0
22 0 92 83 76 68 61 54 47 40 34 28 16 5
24 0 92 84 77 69 62 56 49 43 37 31 20 9 0
26 0 92 84 77 70 63 57 51 45 39 34 24 14 5
28 0 92 85 78 72 64 58 53 47 42 36 27 17 8 0
30 0 93 86 79 73 66 61 55 49 44 39 29 21 12 4
32 0 93 87 80 73 67 62 57 51 46 41 32 23 15 8 1
34 0 93 87 81 74 69 63 58 53 48 43 35 26 19 11 4
36 0 94 87 81 75 70 64 59 54 50 45 37 29 21 14 8
38 0 94 88 81 76 71 66 61 56 51 47 38 31 24 17 11
40 0 94 88 82 77 72 67 62 57 53 48 40 33 26 19 13
42 0 94 89 83 78 72 67 63 58 54 50 42 34 28 22 16
44 0 94 89 83 78 73 68 64 59 55 51 43 36 30 24 18
46 0 94 89 84 78 74 69 64 60 56 52 45 38 32 26 20
48 0 94 89 84 79 74 70 65 61 57 53 46 39 33 27 22
50 0 94 89 84 79 75 71 66 62 58 54 47 40 34 29 23
16
Temperature Conversion
0 0 0 0
C F C F
-17.78 0.00 11.11 52.00
0.00 32.00 11.67 53.00
0.56 33.00 12.00 53.60
1.00 33.80 12.22 54.00
1.11 34.00 12.78 55.00
1.67 35.00 13.00 55.40
2.00 35.60 13.33 56.00
2.22 36.00 13.89 57.00
2.78 37.00 14.00 57.20
3.00 37.40 14.44 58.00
3.33 38.00 15.00 59.00
3.89 39.00 15.56 60.00
4.00 39.20 16.00 60.80
4.44 40.00 16.11 61.00
5.00 41.00 16.67 62.00
5.56 42.00 17.00 62.60
6.00 42.80 17.22 63.00
6.11 43.00 17.78 64.00
6.67 44.00 18.00 64.40
7.00 44.60 18.33 65.00
7.22 45.00 18.89 66.00
7.78 46.00 19.00 66.20
8.00 46.40 19.44 67.00
8.33 47.00 20.00 68.00
8.89 48.00 20.56 69.00
9.00 48.20 21.00 69.80
9.44 49.00 21.11 70.00
10.00 50.00 21.67 71.00
10.56 51.00 22.00 71.60
11.00 51.80 22.22 72.00
Continued in next
page
17
0 0 0 0
C F C F
22.78 73.00 37.00 98.60
23.00 73.40 37.22 99.00
23.33 74.00 37.78 100.00
23.89 75.00 38.00 100.40
24.00 75.20 38.33 101.00
24.44 76.00 38.89 102.00
25.00 77.00 39.00 102.20
25.56 78.00 39.44 103.00
26.00 78.80 40.00 104.00
26.11 79.00 40.56 105.00
26.67 80.00 41.00 105.80
27.00 80.60 41.11 106.00
27.22 81.00 41.67 107.00
27.78 82.00 42.00 107.60
28.00 82.40 42.22 108.00
28.33 83.00 42.78 109.00
28.89 84.00 43.00 109.40
29.00 84.20 43.33 110.00
29.44 85.00 43.89 111.00
30.00 86.00 44.00 111.20
30.56 87.00 44.44 112.00
31.00 87.80 45.00 113.00
31.11 88.00 45.56 114.00
31.67 89.00 46.00 114.80
32.00 89.60 46.11 115.00
32.22 90.00 46.67 116.00
32.78 91.00 47.00 116.60
33.00 91.40 47.22 117.00
33.33 92.00 47.78 118.00
33.89 93.00 48.00 118.40
34.00 93.20 48.33 119.00
34.44 94.00 48.89 120.00
35.00 95.00 49.00 120.20
35.56 96.00 49.44 121.00
36.00 96.80 50.00 122.00
36.11 97.00 50.56 123.00
36.67 98.00 100.00 212.00
18
Air Conditioning Units & Transformers Details
A C Air
cooled
Room unit Outdoor unit
current R-
1.5 TR AC Wt. Wt. Wattage
L W Ht. L W Ht. 22
Units Kgs Kgs kW
Amps kg
Window 11 A to 2.2 to
AC 720 470 685 105 /// /// /// /// 13 A 2.6 0.95
Spilt Floor 11 A to 2.2 to
mounting 975 585 220 50 890 658 345 65 13 A 2.6 1.8.
Split 11 A to 2.2 to
HWM 1015 375 200 50 890 658 345 65 13 A 2.6 1.8.
6A/3
3 TR Slim 560 300 1800 900 950 680 80 ph 3.4 2.3
AC Package unit Twin circuits ( Recent R / C )
7 TR 18 to 12 to
1500 750 1800 1550 770 1100 120 24 15 20
10 / 9 TR 2x
1600 910 1950 400 2x1775 2x775 2x1315 65 35
Copper wound Transformer
Heig
Weight H V Panel size
length Width ht
Transform 250
with oil w / o oil 11 kV 1 i/c +2 o/gs
er 1800 1600 0
100 kVA 870 kgs 495 kgs 4500
250
22 kV 1 i/c + 2 o/gs to 3000
1220 kgs 600 kgs 0
150 kVA 3000
200
1500 kgs 750 kgs
200 kVA M V Panel 650 0
315 kVA 2000 kgs 1025 kgs if ACB involved width is 1200
500 kVA 2800 kgs 1400 kgs
750 kVA 3750 kgs 1900 kgs
19
EA Sets sizes
Starting Batterry
EA set Air W. Ht . Fuel
L . mm Wt . Kgs consumption
cooled mm mm Voltage AH
20
Current consumption by various Exchanges
FOR C - DOT
Lines 2k 2.5 k 3k 3.5 k
Power consumption 7.5 kW 8.5 kW 9.25 kW 11 kW
Lines 4k 5k 6k 10 k
Power consumption 11 kW 12.75 kW 15.65 kW 18.65 kW
In the range of 6 k to 10 k, for every 1 k add 0.75 kW
Rectifier efficiency = 75 % ; P.F = 0.7 lag.
21
Out Door Transformer cum Pole structure
300 mm
1800
E B Side Consumer side
Door
1200
EB post
3000
Door Post I Joist
6600 mm
A
Transformer
1800
9100 mm
Fencing 1800 mm high.
.
R S Joist 30 ft. long
Concrete foundation 175 x 88 ( 7`` x 3.5 ``)
1.Consumer posts may be
22
Machine room
900 x 1600
mm
Lift hook or Beam
2000 kgs
Top most
Floor
Sill st
1 Floor
Projection
110 mm in
each landing
Entrance
height G. Floor
2100 mm
23
Passenger Lift for speed
1 metre / sec.
projection
Sill
A
B Lift Shaft
Door
Landing
Length
Height
Width
In
A B C
kgs
Dt.18-05-95
3-1-8 / EW-
of DG P&T
-MMS (LA)
of BSNL
SPEC/94
4-69 / 76
of DOT
06-09-01
8-39 /
tem
24
Fax 5
Computer (residual
value
5 %) 7
25
Life of assets in Years
Dt.09-12- 83
Dt.18-05-95
2001- PHN
3-1-8 / EW-
Dt. 06-09-01
of DG P&T
-MMS (LA)
SPEC/94
4-69 / 76
of BSNL
of DOT
8-39 /
Item
Land Permanent
Buildg 50
Water supply & Sanitory
Fitting 25
Electronic Exchanges I/c
telex & TAX 25 12
Testing Apparatus 10
Crane 18 18
Trailors 10 10
Power plant 25 15
Battery less than 200 AH 8 4
Battery 200 AH & Above 10 6
Mtce Free Batteries upto
200 Ah 4
Mtce Free Batteries
above 200 Ah 6
AC Plant Centralised 12 12
W/T & Split AC 6 6
Package type AC 6 9
Refrigerator 8 8
Cold storage plant with
air cooled condenser 8
Cold storage plant with
water cooled condenser 12
Desert cooler 1500-2000
cfm Evaporative type 7 6
Water cooler 7 6
Room cooler cheap type
about 100 cfm 5 6
HT breaker 16
Transformer 16
EI / Substation 16
Continues in next page
26
Dt.09-12- 83
Dt.18-05-95
2001- PHN
3-1-8 / EW-
Dt. 06-09-01
of DG P&T
-MMS (LA)
of BSNL
SPEC/94
4-69 / 76
of DOT
8-39 /
Item
Electric Lifts 20 20
Electric Motor 1 ph. 8 8
Electric Motor 3 ph. 15
Pump small 3000 rpm 8 10
Pump Medium 1500 rpm 10 10
Engine Pump small upto
10 H.P. 10 10
Engine Pump big above
10 H.P. 12 10
EA set upto 50 kVA &
Portable set 10
Diesel Generator upto 50
kW 12
Diesel Generator above
50 kW 15 15
Continues in next page
27
Fire fighting
Requirement : - For all buildings 15 mts & above.
No. of wet risers : - 1 No. for every 1000 sq.mts or part thereof. The nearest riser should not be more
than 30 mts away from any point in the area covered.
Wet riser pipe :- 150 mm Dia. ( internal ) CI class `B`.pipe. The pressure at the top most landing valve
shall be not less than 3.5 kg / cm2 . An air vessel of steel 10 mm thick 450 mm Dia. and
2mts high shall be mounted on top of each riser with air release valve.
At landings : - The landing hydrant shall have double headed gunmetal female instantaneous coupling
with 6 mm thick Stainless steel orifice plate to reduce pressure to 3 kg / cm2 at a height
of 1.2 mts above floor level. One valve to be connected permanently to a hose drum.
Hose box shall be provided with 2 Nos. hose reels each of 15 mts long and 63 mm Dia.
with a coupling and branch pipe nozzle of 20 mm Dia.. Space required for Landing
valve & riser is 1200 x 650 in each floor.
Yard hydrant : -Ring main hydrant CI pipe of 150 mm Dia. shall be buried below the ground at a depth
of 1mt. and to be treated with anti-corrosive bitumen. A minimum of one yard hydrant
for every 60 mts of perimeter of building is to be provided. Each yard hydrant shall have
1 No. 63 mm Dia. gunmetal oblique single headed female coupling with 6 mm thick
Stainless steel orifice plate to reduce pressure to 3 kg / cm 2.. Each hydrant shall have one
hose box containing 2 nos. 15 mts 63 mm Dia. hose reels with coupling and nozzle.
Fire brigade inlets:- a) ; - To fire sump :- one inlet CI stand post of 80 mm Dia. and 1mt. high, with 4 Nos.
63 mm instantaneous male inlet couplings with plug & chain, without any valves to the
sump for fire brigade`s use at street level are to be provided. B):- To the riser. :- Each
riser shall have one firebrigade inlet made of 80 mm Dia. CI stand post 1 mt. high,
and inlet coupling as above but with a non- return valve.
28
Fire pump room: - Minimum 20` x 20` x 10` high ( 6mts x 6mts x 3 mts high )
Electric Fire pump size : - 1600 x 670 x 700 ( width with suction & delivery
Bends is 2000 mm.)
Diesel Pump size : -2100 x 670 x 1500 ( ------------------- do---------- ).
Jockey pump size : - 1000 x 450 x 500.
29
TEST REPORT OF LIFT
30
xii) Bottom car clearance :1520 vi) Whether control circuits have
xiii) Top counter wt. clearance : 920 independent fuses ? : yes
xiv) Bottom car runby : 400 (Less than 600 ) vii) Whether rope break
xv) Bottom counter wt. runby : 300 ( less than 900 ) protection is provided ? : Speed governor
8.In m/c room , Check for provision of :- fitted.
i) Hand lamp with flexible cord : yes viii) Whether Ferrules for cables
ii) plug & socket outlet : yes provided at terminations ? : yes
iii) Adequate ventilation : exhaust fan provided ix) IR test for power & control lines :
iv) Danger Notice Plate on Door : yes satisfactory
v) Trap door : provided
vi)Main switch on incoming side : provided 11. Operation ; - A) From within the Car
vii) Circuit Diagram hung on wall : provided i) Operation of all floor buttons
9. Whether Machine body, controller, car frame, in `UP` & `Down` directions on
limit switches, & conduits properly earthed : yes both Auto and Attendant controls :
Earth continuity tested : yes satisfactory
10. In m/c & controller check for : - ii) Operation door close & Door
i) oil leakage ; nil open buttons :
ii) Abnormal temperature rise satisfactory
of oil, bearing & motor. : no temp. rise iii) Car light & Fan : provided
iii) Abnormal vibration & noise : checked iv) Emergency light : provided
iv) `UP` & `Down` Direction control is OK. : yes v) Emergency Stop button : provided
v) Vibration pads provided for machines : yes vi) Emergency Alarm : provided
v) working of car position Indicator:
Satisfactory
vi) Functioning of sensitive reopening
of car door / Landing door when moving
edge senses any obstruction :
satisfactory
31
vii) Smooth sliding of car door vi)Working of position indicators
Page No 32
32
viii) Operation of safety switches : satisfactory 16. Load test : -Supply volts R- 395 v Y- 401v B-400v
ix) operation of upper limit & lower a. Starting : At no load ; Up – 7 A : Down –15A
limit switches and position of car : satisfactory current At half load :Up –12A : Down –9 A
x) opening of emergency door At full load : Up –14A : Down –7 A
while lift is in operation : Not applicable
xi) Functioning of slack rope b. Running : At no load ; Up – 1.1A: Down –6.2 A
safety device : Not applicable current At half load :Up – 3.6A: Down –1.9 A
in Traction type At full load : Up – 7.1A: Down –1.2 A
13. Check rope slip after three `up` c. Travel speed :
and `down` trips by a reference At no load : Up –16 sec. : Down –16 sec.
mark on the sheave / rope : satisfactory At half load : Up –16 sec. : Down –16 sec.
14. Test to see that the car does At full load : Up –16 sec. : Down –16 sec.
not start on `no` load in `up` d. Floor leveling accuracy : Less than 5 mm in all
direction and on `full` load in floors
`down` direction while SINGLE e. No. of floors & each floor height :-
PHASING. : not starting on single phasing.
15.check operation of break while
moving on full load in `down`
direction at full speed by switching Signatures of all participants.
`off` the power & check for any
over-heating : satisfactory
33
Lift : : Meaning of some words & clearances
1.Selective collective operation : - Applicable even to a single lift. All intermediate landings
shall have two buttons & the top-most and bottom-most landings shall have a single button. This is an
automatic operation where-in all `up` landing calls are answered by the car going up , and all `down`
landing calls are answered by down-going car. The stops are made in the sequence of the landings
reached in the required direction and not in the order of buttons pressed.
2.Rated speed : - The speed attained by the lift car in the up direction with full rated load.
3.Safety Device : - A device which stops the car / counter weight if the rope breaks, or governor
operates and holds it to the guides.
5.Quantity of service: -Also called Handling capacity. It is the No of passengers handled in any
five minute period during peak hours expressed as a percentage. For diversified tenancy buildg. it is 10 to
15 % .For single purpose office occupancy it is 15 to 25 %. For residential buildg, it is 7.5 %.
6.Bottom car / counter weight Runby : - It is the vertical clearance between the buffer striking
plate attached to the car / counter wt. and top surface of the buffer spring when the car floor is in level
with the ( bottom most floor for car runby : top-most floor for counter wt, runby). This should be
within the limits of 300 to 600 mm for car and 300 to 900 mm for counter weight.
7.Top car clearance : - It is the vertical clearance between top of the car cross head and shaft
ceiling or any over head obstruction on the ceiling when the car floor is in level with the top terminal
landing. This should not be less than the sum of 600 + counter weight runby + counter weight spring
stroke + Half of the gravity stopping distance of the car when governor is activated.
34
TYPICAL ROOM LAYOUT FOR 40/63 KVA EA SET
4700
D
1100
Door
700
750 2400
900
3000
40 / 60 kVA side
1000
35
Conversions
Linear Inverse
1 inch := 2.54 cms 0.3937
1 mt := 3.28083 ft 0.3048
1 mile := 1.6093 km 0.6214
1 mile := 5280 fts
1 mile := 8 furlongs
1 nautical mile := 6080 ft
1 yard := 3 feet
1 yard := 0.9144 mts 1.09364
1 lb := 0.4535 kg 2.205
1 quintal := 100 kgs
1 ton := 1.016 metric ton 0.984
1 ton := 2240 lbs
1 ton := 1016 kg
1 ton := 20 cwt
1 metric ton := 1000 kg
1 metric ton := 2205 lbs
1 quarter := 28 lbs
1 cwt := 112 lbs
1 ounce := 28.35 grams 0.0353
1 ounce := 0.0625 lbs 16
Continued in next Page
36
1 cfm (Cu.ft./min) := 1.699 cu.mts / hr 0.5886
1 HP := 0.746 kw 1.341
1 metric HP := 0.7355 kw
1 joule := 107 ergs
1 joule := 1 watt-sec.
1 joule := 0.238 calorie 4.2
1 kw := 1000 joules / sec.
1 kw := 860 k.calories / hr
1 kw := 3413 Btu / hr
1 unit := 1 kw-hr
1 TR := 12,000 btu / hr
1 TR := 3,024 kcal / hr
1 TR := 3.5211 kw 0.284
:= 3.1415927
e := 2.71828
:= 1.73205
:= 1.4142136
Temperature 0F = ( 0C x 1.8 ) + 32
10 Abs := 0C + 273
10 Abs := 0F + 460
37