Features
• Interactive
• Plug-in detector head
• Heat detector intended for use in humid areas
• Short-circuit isolator in each detector
• Conforms to EMC directive
• Additional coating of PCB circuit for environmental protection
• Comprises a built-in alarm indicator (LED)
• Automatic addressing
• Proven technology
• Configurable to class A1, A1R, A2S, B, C
• Immune to electromagnetic disturbance
• Unrivaled reliability due to the SelfVerify function
• The BD-500 is not influenced by dust, humidity, exhaust-
gases, electromagnetic fields i.e.:
Radio transmitters, cellular phones, etc.
• Designed to meet LPCB requirements
Versions
• EN54 pt. 5
• BD-200* Heat detector without SelfVerify
• Designed to meet the requirement of the major maritime
classification societies • BD-300* Heat detector with SelfVerify
• BD-500Heat detector with SelfVerify,
environment protected
Applications
• BD-500/EX* Heat detector with SelfVerify,
BD-500 is a point heat detector for detection of rise in ambi- EExia-version for use in all zones
ent temperature caused by a fire. The detector is designed for
• BD-500/N Heat detector with SelfVerify,
use with Autronica’s interactive fire alarm system, AutroSafe.
SelfVerify function ensures the highest grade of reliability. Eexn-version for use in zone 2 only
All units comprising this function are automatically tested with * See separate data sheet
a calibrated test once every 24 hours.
Technical Specifications
Additional coating of PCB and sealing of the sensing element
makes this detector suitable for rough areas like heavy indus- Weight 140 g
try, maritime and offshore applications. Material PC/ABS
Colour Light grey
BD-500 is often used in areas where the environment is likely Sensitivity Acc. to EN-54/5
to produce false/unwanted alarms from smoke
Voltage 10 - 27V DC
detectors such as:
• Kitchens Current consumption
• Boiler rooms
Stand by: < 0,3mA
• Galleys • Workshops, etc.
External alarm indicator: 6mA
• Bathrooms • Refrigeration rooms, etc. Environm. requirement EN-54/5
Degree of protection IP 44D
Optionally there is a BD-500/N version for use in hazardous
area zone 2. It must be connected to the BSD-310/N loop Working temperature -20 - +80°C
driver. Max. application Ref. table 1
Storage temperature -55 to +70°C
Principle Humidity (non-condensing) Max. 95% RH
Maintenance None
Temperature measurement by means of a thermistor
for registration and reading of temperature at the detector Service Replace if faulty
point. Alarms at temperature according to configured class Approvals See separate documentation
(Ref. table 1). Certificate for BD-500/N NEMKO 03ATEX217X
Dimensions
Table 1
Detector Typical application Maximum application Minimum static Maximum static
class temperature temperature response temperature response temperature
°C °C °C °C
A1 25 50 54 65
A1R* 5 50 54 65
A2S* 25 50 54 70
B 40 65 69 85
C 55 80 84 100
* R= Rate of rise.
* S= (Slow) Does not respond below the minimum static response temperature.
Note: The detector may give prewarning on a temperature below the max. application temperature.