RELAY TESTING REPORT

CTMM MOTOR PROTECTION RELAY

SUBSTATION ARU S/S MAKE ENGLISH ELECTRIC


SWGR MODEL NO CTMM502DF48A
PANEL NO SERIAL NO M176284
FEEDER UP 15C C T Ratio
Aux VOLT 110 V DC CURRENT RANGE

SETTINGS:
THERMAL OVER LOAD
Ith (Amps) Ith curve No %ith Alarm
5.5 3 90
SWITHES IN ON
FUNCTION EQUATION SET VALUE UNIT
POSITION
STALLING
I1(t) 0.3 (1.5 + Σ) In 9 Amps
Time , (t) 2 (1×Σ) (2×Σ) 2 Sec
UNBALANCE
I2 0.4,1.6 ( 0.3 + Σ ) In 11.5 Amps
Time , (t) 0.5 ( 0.1 + Σ ) 0.6 Sec
EARTH FAULT ( K = 5 )
I0 10,20 K × ( 10 + Σ ) 200 mAmps
Time , (t) 0.5 ( 0.1 + Σ ) 0.6 Sec
INSTANTENOUS OVER CURRENT
I1 -- -- Amps
(Thermal curve reference for 1Φ current injection: error allowed: ± 15%)

Curve No 1 1a 2 2a 3 3a 4 4a 5 5a 6
1Φ time,Sec 4 6 8 12 16 24 32 48 64 96 128

THERMAL OVER LOAD TEST

THEORETICAL
CT SETTINGS I INJECTED ACTUAL TRIP
CURVE OPERATING
TERMINALS 5/1 Amps 16.35/3.27 TIME IN SEC
TIME
07 -- 08 5 3 16.35 16 16.76
09 -- 10 5 3 16.35 16 17.11
07 -- 08 5 4 16.35 32 34.58
09 -- 10 5 4 16.35 32 33.13
07 -- 08 5 5 16.35 64 68.89
09 -- 10 5 5 16.35 64 71.25
STALLING PROTECTION TEST I1 (t)
EXPECTED OPERATING
DESCRIPTION CT TERMINALS PICKUP CURRENT
VALUE TIME
Pick up Current 07 -- 08 (√3 × 1.5 ) In ±15 % = 12.78 --
for 150 % Set 09 -- 10 13 / 2.6 ±15 % 12.82 --
Time for 2 Times 07 -- 08 -- 56 ms
60 mSec
Current injected 09 -- 10 -- 50 ms
Time set at 07 -- 08 -- 57.35 S
30/60 ± 10% Sec
30 / 60 Sec 09 -- 10 -- 62.2 S
Pick up Current 07 -- 08 (√3 × 6 ) In ±15 % 51 --
for 600% Set 09 -- 10 = 52 / 10.4 ±15 % 51 --
NEGATIVE PHASE SEQUENCE – (I2)

EXPECTED OPERATING
DESCRIPTION CT TERMINALS PICKUP CURRENT
VALUE TIME
Pick up Current 07 -- 08 (√3 × 0.3 ) In ±15 % = 2.44 --
for 150 % Set 09 -- 10 2.6 / 0.52 ±15 % 2.62 --
Time for 2 Times 07 -- 08 -- 85 S
60 mSec
Current injected 09 -- 10 -- 80 S
Time set at 07 -- 08 -- 7.61 S
(7.5 ± 0.75 ) Sec
30 / 60 Sec 09 -- 10 -- 7.59 S
Pick up Current 07 -- 08 (√3 × 6.3 ) In ±15 53 --
for 600% Set 09 -- 10 % = 54.6/ 11 ±15 % 53.5 --

INSTANTANEOUS OVER CURRENT (Ii)

INJECTED
CT TERMINALS 1 Φ EQUATION NOT PICKED UP PICKED UP
CURRENT
07 -- 08 NOT PICKED UP --
0.85×√3×6/30 44 / 8.83
09 -- 10 NOT PICKED UP --
07 -- 08 -- PICKED UP
1.15×√3×6/30 59.75 / 12
09 -- 10 -- PICKED UP

EARTH FAULT – (I0)

EXPECTED OPERATING
DESCRIPTION CT TERMINALS PICKUP CURRENT
VALUE TIME
Pick up Current for
160 mA Set
11 -- 12 (160 ± 18) m A 161 mA --
Time for 320 mA
Times Current 11 -- 12 60 m Sec -- 58 mS
injected
Time set at
7.6 Sec
11 -- 12 (7.56 ± 0.75) Sec -- 7.23 mS
Pick up Current for
800 mA Set
11 - - 12 (800 ± 120) m A 794 mA --

REMARKS :

RESULT : TESTED OK

TESTED ON :

TESTED BY :

ENGG IN CHARGE :