Control Module
USER MANUAL
(Series C and later)
Bulletin 1503VC
Important User Information
Read this document and the documents listed in the Additional Resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Product Description
Description (cont.)
Vacuum Contactor
External Trip Coil
Capacitor Coil
Current
(Optional) Power
Regulator
Input Supply
Feedback
Altitude
Aux. CC
c
Select
c
Drop-Out c
Select
c
Configuration Module
Contactor c Inputs Status
Select (DIP
c
c
Outputs
Status
switches)
c
c
TDUV
Time c
Select Contactor
c
Interface
Safety
c
IntelliVAC Features
A wide range of supply voltage (110 – 240 V AC 50/60 Hz, 110 -
250 V DC) allows implementation in multiple applications
Consistent vacuum contactor pick-up time (at a given supply
voltage) ensures repeatable performance
Selectable vacuum contactor drop-out time improves coordination
with upstream power fuses
Electronic altitude compensation (400 A only) eliminates
mechanical compensation required for altitudes above 1,000
meters (800 A contactors include a user-friendly altitude
adjustment)
IntelliVAC Versions
Configuration
IntelliVAC is easily configured for a wide variety of medium voltage
motor and feeder control applications. It is configured using DIP
switches, located within the enclosure (front side). Please refer to
Chapter 4 for information.
Firmware
IntelliVAC has firmware stored in flash EEPROM; therefore, this may
be updated in the field (if necessary). The IntelliVAC board firmware
is updated using the mini-DIN connector, which is accessible inside the
enclosure.
⊇ T A = Ambient Temperature
⊄ Includes idle current.
⊂ Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed. The Series C and D IntelliVACs are compatible with most PLC outputs,
and have been verified with Rockwell Automation OA type 120V triac outputs. See Chapter 3, Wiring Guidelines.
1001 to 2000 58
2001 to 3000 56
3001 to 4000 54
4001 to 5000 52
5.1 (0.20)
29.7 165.9 (6.53)
(1.17)
5.8 (0.228)
2 places
174.8
(6.88)
185.3
(7.29)
59.4
(2.34) Dimensions in mm (inches)
Receiving Upon receiving the controller, remove the packing and check for damage
that may have occurred during shipping. Report any damage immediately
to the claims office of the carrier.
General Precautions In addition to the precautions listed throughout this manual, the
following statements, which are general to the system, must be read and
understood.
Figure 3.1 – Typical IntelliVAC Installation within a Bulletin 1500/1900 MV Controller (Shown
with optional external capacitor)
OEM
38.1
(1.50)
Dimensions in mm (inches)
38.1
6.4 (0.25)
(1.50)
Arrangements (cont.)
CONTROL POWER
*
CONTROL M-INTELLIVAC
POWER
FUSE 7 + - 8
OPEN
9 + - 10
CLOSE
OVERLOAD START
STOP
16 CONTACTOR
STATUS
15
MODULE 14
STATUS
13
CAPACITOR
(OPTIONAL)
1 - 4
EC TCO
2 + 3
MOV
M
11 6 M
AUX CCO
12 5
CONFIGURATION
DIP SWITCHES
INPUT POWER
L1 G L2/N
* Refer to Table 3.A for recommended fuse sizing.
Fuse Protection The IntelliVAC module requires external fuse protection to coordinate
with the power supply and contactor. The fuse ratings shown in Table
3.A allow the passage of inrush currents expected when the contactor is
closed, or from recommended external capacitors for the TDUV option.
They will also protect the contactor coils in the event of a module
malfunction.
Connections There are three green connectors on the IntelliVAC module for
connections to the control circuitry. Connector plugs are provided with
the module. If additional plugs are required, refer to Chapter 6, Spare
parts.
Control Power
Status Relays
Status relay connections are accessed with a four-pole connector located
at the bottom front portion of the module. Refer to Figure 3.4 for
connections. There are two status relays, each with one normally-open
contact:
Ground Connection
13 14 15 16 L1 L2/N
CONTACTOR STATUS OUTPUT (N.O.) MODULE STATUS OUTPUT (N.O.) POWER INPUT
Interface Connections
1 2 3 4 5 6 7 8 9 10 11 12
EX. CAP. CONTACTOR INTERFACE
1 External capacitor (negative) Power connection for TDUV or capacitor trip options
2 External capacitor (positive) only
7 Open / Jog command Input to open a mechanical latch contactor or jog
8 Open / Jog command (common) an electrically held contactor (mutually exclusive)
Wiring Guidelines Electrically The IntelliVAC can be applied with two- or three-wire control circuits.
Held Contactors The control system utilized will determine the configuration of the input
wiring. Consider the following input and output for the type of control
used:
In either case, the CLOSE input must receive a maintained voltage high
to keep the contactor closed.
Note:
1. When used with electrically held contactors, the IntelliVAC allows
close commands every six seconds. This is to ensure the rated
contactor duty cycle is not exceeded.
2. If IntelliVAC powers up configured for an electrically held contactor,
and the vacuum contactor is detected as being closed, the module will
not respond to a close command until the vacuum contactor auxiliary
contact input is in the correct (closed) state and module power is
removed and re-applied. (See Chapter 5)
3. In general, a Close command should only be applied 4 seconds after
energizing IntelliVAC.
CONTROL POWER
M -IV
*
CONTROL M
2 + 4
POWER EC TCO
FUSE 1 - 3
MOV
M
11 6 M
AUX CCO
12
5
INPUT POWER
L N
G
SOLID STATE
OVERLOAD OUTPUT CR M -IV
9 + CLOSE - 10
CR
CONTROL POWER
CAPACITOR
(OPTIONAL) M-IV
1 4
CONTROL EC TCO
POWER 2 3
MOV
FUSE M
11 6 M
AUX CCO
12 5
L1 G L2/N
EMERGENCY STOP
(when required)
M-IV
OVERLOAD RUN
CLOSE
* Refer to Table 3.A for recommended fuse sizing.
Three-Wire Control
CONTROL POWER
CAPACITOR
(OPTIONAL) M-IV
* 1 - 4
CONTROL EC TCO
POWER 2 + 3
MOV
FUSE M
11 6 M
AUX CCO
12 5
L1 G L2/N
EMERGENCY STOP
(when required)
START M-IV
OVERLOAD STOP
9 + - 10
M-IV CLOSE
15 16
* Refer to Table 3.A for recommended fuse sizing.
CONTACTOR
STATUS
15mS
CLOSE COMMAND DEBOUNCE
TO MICRO
15mS 80mS
SELECTABLE DROP
DEBOUNCE OUT TIME
5mS (0 TO 190mS)
MICRO OUTPUT CLAMP DELAY
TO CLOSE COIL 200mS
CLOSE LEVEL OF
CURRENT TO CLOSE
COIL ACKNOWLEDGE 60mS
WINDOW
CONTACTOR STATUS
RELAY OUTPUT
MODULE STATUS
RELAY OUTPUT CONTACTOR PICK UP
90mS NATURAL
CONTACTOR 30mS
DROP OUT
(@120VAC)
CONTACTOR
AUXLIARY
INPUT TO MICRO
Contact status relay closes on request to close. It will open if the contactor auxiliary contact does not close within 200 milliseconds and
module will fault (opening module status relay).
For this example, the 130 millisecond drop-out time has been selected. The base drop-out time is 50 milliseconds. The microcontroller delay is
130-50=80 milliseconds.
Wiring Guidelines Mechanical IntelliVAC control may be used for mechanical latch contactors.
Latch Contactors A momentary control signal is needed to close the contactor, and a second
momentary control signal is needed to open the contactor. The
momentary open/close commands must be at least 50 milliseconds in
duration.
Refer to Figure 3.10 for a typical mechanical latch control scheme.
Note:
1. A mechanical latch contactor may already be closed when power is
applied to the IntelliVAC control module.
2. It is permissible to apply an open command to the IntelliVAC
module as power is re-applied.
CONTROL POWER
M
MOV
M-IV
* 1 - 4 TC
CONTROL EC TCO
POWER 2 + 3
FUSE
MOV
M
11 6 CC
AUX CCO
12 5
L1 G L2/N
CLOSE M-IV
OVERLOAD
9 + - 10
CLOSE
OPEN M-IV
7 + - 8
OVERLOAD OPEN
* Refer to Table 3.A for recommended fuse sizing.
CONTROL POWER
OPEN M-IV
7 + - 8
OVERLOAD OPEN
*
CONTROL
POWER
FUSE
M
MOV
CAPACITOR M-IV
1 - 4 TC
EC TCO
2 + 3
MOV
M
11 6 CC
AUX CCO
12 5
L1 G L2/N
CLOSE M-IV
OVERLOAD
9 + - 10
CLOSE
* Refer to Table 3.A for recommended fuse sizing.
Motor Jogging Control Note: Jog functionality can work with electrically held contactor only.
When used with electrically held contactors, the IntelliVAC allows close
commands every six seconds. This is to ensure the rated contactor duty
cycle of 600 operations per hour is not exceeded.
CONTROL POWER
M-IV
* 1 - 4
CONTROL EC TCO
POWER 2 + 3
MOV
FUSE M
11 6 M
AUX CCO
12 5
L1 G L2/N
EMERGENCY STOP
(when required)
START M-IV
OVERLOAD STOP
9 + - 10
M-IV CLOSE
15 16
CONTACTOR
STATUS
JOG M-IV
7 + - 8
* Refer to Table 3.A for recommended fuse sizing. OPEN
Undervoltage Protection The IntelliVAC controller protects the contactor from control voltage
dips and loss of power. It provides undervoltage release and prevents
attempts to close the contactor when there is not sufficient power
available to guarantee reliable closing of the contacts. The undervoltage
protection will be initiated under the following conditions, regardless of
nominal control voltage:
1. If the supply voltage drops below 90 V (AC or DC) during the first
200 milliseconds after a Close command is received. This applies to
both electrically held and mechanical latch contactors.
2. If the supply voltage drops below 72 V (AC or DC) after the 200
millisecond close sequence (electrically held contactors only).
Time Delay Undervoltage The IntelliVAC can be configured to provide time delay undervoltage
(TDUV) protection. The feature is available to keep electrically held
contactors closed during a voltage dip or brief power loss. This option
may require the addition of a capacitor (see below). Refer to Chapter 6
for typical capacitor sizing. The capacitor is connected to terminals 1(-)
and 2(+) of the IntelliVAC. (Refer to Figure 3.13.)
Table 4.B of the “Setup and Commissioning” chapter has the dip switch
settings to provide TDUV from 0.2 to 2 seconds. IntelliVAC can
provide TDUV protection without the use of an external capacitor, as
shown in Table 3.D.
If the undervoltage condition persists beyond the set delay time, the
contactor will be opened and an undervoltage fault or warning condition will
occur (see Chapter 5).
CONTROL POWER
CAPACITOR M-IV
* 1 - 4
CONTROL EC TCO
POWER 2 + 3
MOV
FUSE M
11 6 M
AUX CCO
12 5
L1 G L2/N
START M-IV
OVERLOAD STOP
9 + - 10
M-IV CLOSE
* Refer to Table 3.A for recommended fuse sizing. 15 16
CONTACTOR
STATUS
IntelliVAC Configuration The IntelliVAC module is configured for a specific application by setting
DIP switches. They are accessed by loosening the two screws on the front
of the unit, and removing the cover by sliding it forward. The switches
are found on the front edge of the IntelliVAC circuit board (see Figure
4.1). There are 12 switches, with number 1 being at the top next to the
mini DIN connector. (Refer to Table 4.B).
Interface Connections
DIP Switches
LEDs
Ground Stud
9 TDUV config.
0 No TDUV
200 msec 1 1 0
240 msec 1 1 1
The altitude compensation by DIP switch settings applie s to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted
for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).
By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.
Refer to Appendix A for typical drop-out time settings used when power fuses are provided by Rockwell Automation.
Introduction The IntelliVAC module has two light emitting diodes (LEDs) and relay
outputs to indicate the status of the contactor and the module. The LEDs
are visible on the front of the module and the relay outputs are accessed
on the bottom front of the module.
Note: This user manual contains information for both Series C and
Series D IntelliVAC versions. Refer to the correct information
below for the IntelliVAC series in use.
Module Status The Module Status is indicated with a Green LED if the module is
functioning properly and has a valid configuration. If the module powers
up with an invalid configuration the LED will be Red (flashing once),
indicating a Fault condition which will not allow the contactor to close. If
the module powers up properly and experiences an undervoltage condition
when attempting to close the contactor or while the contactor is closed:
• Series C – the LED will be Red (Fault). If the contactor does not
close properly, a Fault is generated, the LED turns Red, and inputs
are inhibited until the module power is removed and reapplied.
Module Status (cont.) If the processor has an internal fault, the LED will be Red, the outputs
will be cleared, and the processor must be reset (input power must be
cycled). If the reset is successful, the LED will be Green and the module
will respond to the control inputs. The input command must be toggled
before the module will respond to a new command (rising edge triggered).
For Series D, the Module Status LED is also used to indicate various
“Warning” conditions related to the contactor performance (see Table
5.B).
Module Status output relay has a normally open contact. The contact is
open during a Fault condition (LED red), and closed during a healthy
condition (LED green). The relay is open for some warning conditions,
but closed for less severe issues.
Contactor Status The Contactor Status is indicated with a yellow LED that is off until a
CLOSE command is received. The yellow LED will stay on if the
contactor closes properly, until the contactor is opened. If the processor
has an internal fault, the LED will be red.
Contactor Status output relay has a normally open contact. The contact
is open when the contactor is open (LED off), and closed when the
contactor has received a close command (for 200 milliseconds) or if it is
closed (LED on).
Refer to Table 5.A (Series C) or Table 5.B (Series D) for definition of Module
LED states.
Contactor does not open • Series C – Module Status LED ‘Green’ and Contactor • Contactor welded or mechanisms binding. Inspect and
(electrically held) Status ‘Red Flash 3’ repair if needed.
• Series D – Module Status LED ‘Yellow – R3’ and
Contactor Status LED ‘Yellow’
Refer to Table 5.A (Series C) or Table 5.B (Series D) for definition of Module
LED states.
Spare Parts
Optional Equipment
TDUV Capacitor
For 110/120V AC control (1650 µF) 80158-779-51-R
For 220/240V AC control (330 µF) 80158-779-52-R
The Series Letter is printed on the large label on the right-hand side of the enclosure,
beside the part number.
The contactor drop-out time settings shown in the following table are
typical minimum values used when the power fuses are provided as part of
a complete MV controller from Rockwell Automation. The
recommendations are based on Ferraz-Shawmut power fuses. Other fuse
types may require alternate drop-out time settings.
The IntelliVAC module DIP switches are set up to provide the minimum
drop-out times shown (refer to Chapter 4).