Professional Documents
Culture Documents
Chapter 1-3 Updated Budget Reqs
Chapter 1-3 Updated Budget Reqs
INTRODUCTION
This chapter presents the critical variables of the study. The main variables of this
study revolve around the harmonic distortion measurement in the electrical system. The
research problem and the gap are focused upon in this chapter.
Electricity is one of the most significant things sciences has given to humanity.
Electricity has become a part of modern life, and it is hard to envision the world without
it. Furthermore, this may impact people's quality of life and living level [1]. Electricity
meets the demands of consumers, including those in the industrial, commercial, and
residential sectors, to carry out and maintain their daily needs. Knowing the positive
benefits and the potential harm they might cause. One of the most important things to
consider when it comes to electricity is its electrical system; this is to have an effective
machines intended to securely transport, disperse, and generate electrical electricity from
the source of delivery or generation to the different loads within the building that absorb
the electrical energy [2]. The capacity of electrical equipment to use the energy given to it
of power quality issues, such as electrical harmonics, inadequate power factors, voltage
1
In addition to ensuring an electrical system's ability to function, it is critical to
ensure its reliability to protect against unwanted damage. System availability, when
needed, corresponds to the reliability of an electrical system. The modern electric power
electronics are not loaded sequentially. Every sinusoidal form in electrical systems except
the fundamental frequency is known as hThe discrepancy between the ideal sinusoidal
waveform of the supply voltage or the load current waveform and what it is due to a non-
there are variety of causes and effects for why harmonics exist in a system. One of the
Harmonic generation in a system does not necessarily lead to problems. There is a limit
to how many harmonics the system can handle and still function correctly. Harmonics in
the voltage have an impact on any electrical equipment. Harmonic currents only impact
Knowing that one of the causes of harmonics in an electrical system is the usage
of numerous nonlinear loads, the researchers took into consideration the Batangas State
University - Alangilan Campus given that it is a large university and has been using these
harmonics is the variety of loads that are operating. Since these loads are operating
2
continuously, the researchers had the notion that the electrical system potentially contain
harmonic distortion.
In response, the researchers obtained the number of loads and collected data from
support their claim that harmonics were being generated at the stated school.
Additionally, since the school is a large university and a National Engineering University,
the facilities and equipment are expanding and increasing the demand for loads, thus it is
important to deal with this kind of problems to prevent harm and damage.
0%
10% 1%
2%
2%
Fluorescent Lamps, LED tubes
and Bulb
12% Personal Computers
Copiers/Printers
Laptop
Air-conditioning Units
TV (View Board)
Water Pump
72%
is composed of fluorescent lamps with 73%. There have been studies proving that
fluorescent lamps, specifically its ballast have the highest contribution in generating
harmonics. Consequently, there are other sources of harmonics in the university, which
they want to deliver to students, there is an increase in the number of non-linear loads
existing in the facilities. Non-linear loads are those that possess currents that are not
proportional to the voltage and fluctuates based on the alternating load impedance.
Fluorescent lamp, computers, printers TVs, electronic lighting ballasts, and switched-
mode power supplies constitutes the examples of non-linear loads [7]. Waveforms
significantly represent the behavior of the current in any electrical supply and represent
non-linear loads was determined to establish the source of harmonics which is shown in
Table 1.
BUILDING
WHITE STEER
LOADS CEAFA CICS RGR CIT SSC GSO FIC TOTAL
HOUSE HUB
Fluorescent Lamps,
1,082 230 138 429 154 4 45 11 1,021 3,114
LED Tubes and Bulb
Copiers/Printers 27 13 3 7 22 1 4 25 102
Air-conditioning
171 52 23 57 24 9 5 1 68 410
Units
Laptop 30 19 33 11 13 106
TV (View Board) 22 6 2 15 1 1 9 56
4
Water Pump 1 1 1 1 1 1 6
As can be seen in Table 1, the campus currently employs a total of 4,297 non-
linear loads continuously. The CEAFA building, which contains 1,471 pieces, has the
most non-linear loads of all these buildings. The STEER HUB, which has 1,226 non-
linear load pieces, follows in second. The fluorescent lamps, LED tubes and bulb
contains the most equipment in both building, which is 1,082 pieces and 1,021
respectively.
Accordingly, with the existence of these non-linear loads in the electrical system
of the campus there is a high tendency that the level of harmonics in the power supply is
Distribution Code 2017. With the absence of such measurement and analysis, there is a
call-to-action to conduct a study that will focus on such topic. As Batangas State
establish a campus that is at par in standards and regulations, specifically its electrical
system.
As the prominence of these variables in the context of the study becomes more
distinguished, the researchers aim to assess the potential harmonic distortion in the
electrical system of the entire Batangas State University - Alangilan Campus specifically
the main distribution panel of the secondary side of the distribution transformer supplying
power to the campus. Also, the College of Engineering and Fine Arts building is
considered when measuring as it has the highest number of non-linear loads existing in
the campus.
5
Statement of the Problem
Problems like high failure rate for consumer electronics and power system
installations, transient and intransient faults, symmetrical faults, etc., are brought on by
the power system's inadequate reliability. One of several aspects that should be
considered while analyzing the reliability of analyzing the power supply's unreliability is
The short bursts of current are drawn by non-linear loads, which results in a
scenario in which current and voltage are not proportional. These loads produce harmonic
distortion, which may harm your equipment. Modern electrical devices like variable
frequency drives (VFDs), arc furnaces, uninterrupted power supplies, fluorescent lights,
computers, and other items are the most linked to nonlinear loads. In addition, it includes
circuits for rectifying, charging and discharging, and phase control [9]. Excessive current
and heat are caused by current harmonics and equipment malfunctions are triggered on
system wherein it is essential to deal with this kind of problem. Electrical equipment may
incur negative effects from harmonic distortion. Unwanted distortion can raise the current
in power systems, which raises the temperature of distribution transformers and neutral
conductors. Higher frequency harmonics increase core loss in motors, which leads to an
excessive amount of core heating. Since they fluctuate at the same frequencies as the
transmit frequency, these higher order harmonics can also disrupt communication
drastically reduce the lifespan of electronic equipment and impair power systems [11].
6
When harmonic distortion penetrates a power system, it affects its capacity to
operate at its best. Due to the increased need for power consumption, it causes
the effects of harmonics distortion can be seen through motor overheating, audible noise,
motor vibrations, electrical fires, LED lights flickering and the likes [13]. The need for
more current overall leads to greater installation and utility expenses, increased heating
any system, therefore measurement always makes the difference [14]. Especially with the
field leaning towards abstract thinking, study such as this one becomes more significant
to maintain the reasonable energy usage of equipment without waiting for the problem to
occur before taking actions. Power quality surveys such as harmonic distortion
problems [14].
Research Questions
population sample, and what would be the results of the investigation and examination
[15]. In this study, the proponents aim to measure, assess, and mitigate the potential
harmonic distortion in the electrical system of the Batangas State University – Alangilan
Campus. To address the research problem, the following specific questions should be
answered:
7
1. What is the level of harmonic distortion in the electrical system of Batangas State
2. How are the levels of harmonic distortion measured in the electrical system of
recommended standard?
3. How should the harmonic distortion existing in the electrical system be mitigated if
standard limits?
4. What is the impact of the mitigation plan designed for the electrical system of
Research Objectives
The objective of this study aims to measure, assess, and mitigate the potential
harmonic distortion in the electrical system of the Batangas State University – Alangilan
2. Assess the level of harmonic distortion measured in the electrical system of Batangas
3. To design the mitigation plan for the harmonic distortion that exceed and/or complied
with the recommended standards limits in the electrical system of Batangas State
8
4. To test the mitigation plan designed for the electrical system of Batangas State
using simulation.
Research Hypothesis
A good hypothesis shall be able to address the problem of the study, determine
the questions imposed by the methodology, and clearly state the conclusions. By having a
good hypothesis, important variables for the completion of the study would be present
[16]. This qsection of the study presents the affirmative and null hypotheses based on the
1. The levels of voltage and current distortion due to the typical nonlinear loads in the
2. The level of harmonic distortion existing in the electrical system of Batangas State
voltage less than or equal to 1.0kV and current distortion limit from the ratio of short-
circuit current and line current of the system as per Philippine Distribution Code 2017,
3. The design of the corrective action for the level of harmonic distortion that exceeds
and/or complied the recommended standard limits is provided and appropriate to the
system specifications.
4. The mitigation plan designed for the harmonic distortion existing in the electrical
system of Batangas State University – Alangilan Campus was able to limit the
9
Scope and Delimitation of the Study
The design of the study shall be a design and analysis research which primarily
aims to measure, assess, and mitigate the potential harmonic distortion in the electrical
system of the Batangas State University – Alangilan Campus. The scope of this study
shall focus on measuring the potential harmonic distortion on the main distribution panel
panel for CEAFA building. The measurement of the harmonic distortion will be
conducted within four (4) days wherein each main distribution panel is allocated two
days. The assessment of the level of harmonic distortion in the electrical system of the
specifically the single tuned filter will be utilized for the mitigation plan for the level of
harmonic distortion existing in the electrical system whether it exceeds and complied
and/or the recommended PDC limits and shall be designed and assessed using Electrical
Transient Analyzer Program (ETAP) software. The study shall be conducted throughout
the academic year 2022 – 2023 within the premises of Batangas State University –
Alangilan Campus.
Moreover, this study delimits the measurement of the harmonic distortion on the
secondary side transformer and CEAFA building. Additionally, the number of days of the
measurement is delimited to four (4) days due to time constraints of the proponents. The
10
assessment of the level of harmonic distortion in the electrical system of the building
shall not be based on other electrical standards and codes existing, except the
abovementioned. Lastly, the mitigation plan is delimited to the sizing of harmonic filters,
specifically by using single tuned harmonic filters as it is the most widely used method.
The mitigation plan for the harmonic distortion in the electrical system of Batangas State
University – Alangilan Campus shall not be developed and installed in the system.
electricity, from face-to—face and virtual lecture set-ups, laboratories with materials and
equipment that are undeniably keep-up with the needs of the curriculum, and the offices
that suffice the services needed by the students. With the large energy consumption of the
university, the researchers are aiming to measure the harmonics in the electrical system
and present the possible corrections to maintain efficient energy distribution in the
university.
considered by the institution for the rehabilitation of the electrical system. By doing so,
The students, faculty, and staffs. This paper shall contribute in ensuring safe utilization
11
The future researchers. The research shall serve as a guide for the future researchers
who wish to study the same. The recommendations of this study may help them to focus
on more specific areas and continue foreseeing the consideration of applying the results
of this research.
CHAPTER II
LITERATURE REVIEW
This section presents the conceptual literature and related studies of harmonic
distortion measurement and correction in power systems. Stated in this chapter also is the
synthesis of the study which correlates the literatures in the current study.
Conceptual Literature
With the development of alternating current (AC) supply on 1888 by Nikola Tesla
[17], the demand with regards to the utilization of electricity in almost everything became
much relevant as time passes by. Electric utilities make use of AC supply to make the
transmission of electrical power more economical and transmit higher or lower voltages
without maximizing losses [18]. Alternating current is a form of current that changes its
direction sinusoidally and in two directions, positive and negative half-cycle [19]. To
easily represent the behavior of AC voltage, a sine wave is used as shown in Figure 2 and
V =V o si n ( ωt ) (2.1)
12
Figure 2. Graphical Representation of AC Voltage
the peak or maximum value of the voltage, and ω is the pulsatance or angular frequency
of the wave.
through a resistor, inductor, or capacitor produces another waveform with the same
frequency but different magnitude and phase angle. Sinusoids also has the ability to retain
Harmonics and harmonic distortion are the discrepancy between the ideal
sinusoidal waveform of the supply voltage and the load current waveform. A resistance
performs the same in an AC circuit as it does in a DC circuit. In other words, the voltage
across the resistance determines how much current flows through it. This is since a
resistor is a linear device, there is no phase difference between the two sinusoids if a sine
wave is applied to it. Sine wave is produced by the current that flows through it. The
output voltage and current waveforms of AC alternators, generators, and other similar
electrical machinery can all produce complex waveforms. As a result, even though the
voltage waveform is sinusoidal, the current waveform could be different. Most electronic
converters, and other solid-state switches that cut and chop the power supply's sinusoidal
waveform to regulate motor power or convert the sinusoidal AC input to DC. Since the
switching current waveform is non-sinusoidal and these switching circuits often only
demand current at the peak values of the AC supply, the resulting load current is said to
modern electrical and electronic devices and equipment, are known to generate non-
sinusoidal waveforms [21]. There are several forms of non-sinusoidal waveforms as seen
on Figure 3. They are categorized depending on their output wave, specifically dc,
mathematically represented by Fourier Series [22]. Fourier series states that any practical
periodic function can be represented as an infinite sum of sinusoidal waveforms that have
invert of a sine wave. They are also called as cosine wave. Aside from the
fundamental frequency which has the lowest frequency but has the highest amplitude and
one or more harmonic frequencies. Moreover, harmonics affects the waveform of cosine
Before 1980, most loads had been categorized as linear. This means that if a piece
of equipment receives a sine wave as its voltage input, the resulting current waveform
that the load produces will also be a sine wave. Electronic hardware makers switched to
switch-mode power supplies in 1981, an effective internal power supply type (SMPS).
The applied voltage sine wave is transformed by the SMPS into a distorted current
waveform that mimics alternating current pulses. The load's impedance clearly varies
during the duration of the applied AC voltage waveform. Harmonics are produced by
most usage equipment today. Voltages or currents that have frequencies that are multiples
In any situation involving an electrical load, linear and non-linear types of loads
are frequently applied. A linear load is one whose impedance remains constant during the
voltage cycle applied. The linear category includes loads that are resistive, inductive, and
capacitive. As opposed to linear loads, non-linear loads are those whose impedance
continually changes with the applied voltage cycle [31]. Waveforms represent sine waves
of current and voltage. Waveforms that represent nonlinear loads has current affecting the
voltage wave. As this current is pulled throughout the system, voltage distortion occurs
[27]. In addition, non-linear loads were also described as loads whose current is not
proportional with the voltage. The waveforms of linear loads, which is an ideal
15
waveform, and non-linear loads, that produce a distorted waveform are presented are
presented in Figure 4.
harmonics, which are typically conveyed by nonlinear loads that draw a non-sinusoidal
Non-linear loads that are very inductive in nature, such as iron-cored inductors,
saturated magnetic devices, and produce harmonics. Some electrical loads on this type
SMPS [28]. The most potent electronic switching circuits including silicon-controlled
rectifiers (SCR), power transistors, power converters, and electronic drives like variable
frequency drives (VFD) or variable voltage variable frequency drives are also to blame
for harmonics (VFD). Only at the peak values of the AC supply do these switching
circuits draw current, and because the switching current behaves nonlinearly, the load
16
To easily understand, harmonics in power systems are brought by non-linear
loads. This type of devices are known to produce non-sinusoidal currents when supplied
with a sinusoidal voltage, like AC supply [30]. With the magnification of the
development in technology, non-linear loads are classified into two as shown in Figure 5.
Transformers
Arc Furnaces
Non-linear Devices
Fluorescent
Lamps
Electronic Controls
Modern Types and Switched-Mode
Power Supplies
Thyristor-
controlled
Devices
transformers, rotating machines, and arc furnaces. Transformers are able to generate
harmonics in power systems due to magnetic materials, while rotating machines like
large generators are generating non-sinusoidal currents due to the supply current passing
through the windings inserted in the slots [30]. In contrast, modern types of non-linear
devices are mostly consisting of fluorescent lamps, electronic controls and switched-
mode power supplies, and thyristor-controlled devices. This non-linear load type is prone
to fluctuation since the load impedance is alternating. They draw currents on sudden short
17
pulses. The generating pulses distort waveforms, which develop as harmonics [28].
Hence, non-linear loads are harmonics-generating loads. Sine waves having frequencies
that are multiples of the fundamental frequency are called harmonics that may interact
with the original sine wave. Interference is a phenomenon that occurs whenever two or
more waves contact. They combine to produce a wave that can have a larger, smaller, or
identical amplitude. Wave interference comes in two types’ constructive interference and
equal frequency and phase that results in a single amplitude that is equal to the sum of the
amplitudes of the individual waves. For constructive interference to take place, the phase
difference between the waves must be zero [32]. The constructive interference model is
depicted in Figure 6.
18
Figure 6. Constructive Interference Waveform
The two waves that are traveling in the same direction and in phase are identified
by the Figure 6 as amplitudes. The upward displacement of the medium occurs when the
waves encounter constructive interference, which is bigger than the displacement of the
interference. The term "resultant amplitude" refers to the total of all individual wave
amplitudes that occur when the crests of two waves of the same frequency cross. The
aggregate amplitudes of all the waves that interact are smaller than the size of the
resulting wave.
It is possible for
the aggregate of
19
alone, this is a destructive interference [33]. The destructive interference model is
depicted in Figure 7.
Based on the illustration, considering two identical waves that are wholly out of
phase with one another. This implies that the crests of one will inevitably fall on the
troughs of the other, and vice versa. The two waves' combined amplitudes are subtracted.
As a result, the combined wave is smaller than the sum of the separate waves [31].
interferences that are both positive and negative are produced because of wave
interactions. There are several harmonics in each wave. In relation to the original
waveform, some of these are in phase and some are out of phase. The harmonics' in-
harmonics are added destructively at the locations where they are out of phase with the
primary wave. So, a warped non-sinusoidal wave is the end consequence [31].
harmonic number 1, while odd harmonics have odd numbers (e.g., 3,5,7,9,11,13) and
20
even harmonics have odd
the waveform is
represented by harmonic
waveform cycle is known as the DC component. Most nonlinear loads create odd
harmonics because even harmonics cancel out. Even harmonics can be produced by
uneven current draw in the positive and negative half of one cycle of operation [26].
Most systems are 60 Hz. Considering this, the harmonic order is 120 Hz, 180 Hz,
240 Hz, the list goes on. Typically, it uses the harmonic frequency or a multiple of the
fundamental frequency to indicate various orders [25]. The multiplicity of harmonic with
the fundamental frequency defines how many cycles were there [34]. Figure 8 below
represents the different order of normal waveform and the complex waveform due to
harmonics [6].
21
Figure 8. Fundamental and Complex Harmonic Waveform
as shown in the Figure 8. As can be seen in the left-hand column, the second harmonic
has a frequency that is twice the fundamental, the third harmonic has a frequency that is
three times the fundamental, and the fourth harmonic has a frequency that is four times
the fundamental. Due to the harmonic content being added to the fundamental frequency,
the red waveforms represent the actual waveform shapes as perceived by a load. The
complex wave structure produced by the interaction between the fundamental waveform
and the harmonic waveform at various harmonic frequencies is displayed in the right-
hand column. In addition to the quantity and strength of the harmonic frequencies, the
final complex waveform's shape will also be influenced by the phase connection between
the fundamental or base frequency and the various harmonic frequencies [6].
A voltage sag is a brief reduction in the rms voltage magnitude, usually at 90%
for 0.5-60 cycles that is typically brought on by a power system fault. The It is the most
significant power quality issue that many industrial customers, particularly those with a
and robotics are examples of equipment utilized in modern industrial plants that is
actually getting more sensitive to voltage sags as the complexity of the system
increases. Even motor starter relays and contactors can be susceptible to voltage sags,
22
Sometimes, voltage sag is assumed to be an interruption. However, it is important
to remember that voltage sag happens when the voltage drops below 90% of the nominal
When large loads were turned off, the voltage on the power line increases for a
short period of time and hence the voltage is beyond the limit of the supply. This
phenomenon is known as voltage surges or voltage swells. The voltage activity can be
referred to as swelling when the voltage increases 10% or more above the nominal-an
opposite of the sagging [36]. Hence, dips can also be described as overcurrent.
A transient voltage is a sudden, unwanted electrical voltage that can range from a
few volts to several thousand volts and lasts for a few microseconds to a few milliseconds
in an electrical circuit. Transient voltages are produced when there is a quick release of
energy as a result of events like lightning strikes, unfiltered electrical equipment, contact
bounce, arcing, capacitor bank switching, or generator ON/OFF. Transient voltages are
stronger in magnitude and last for a shorter time than swells. Lightning and defective
Non-linear loads are those that possess currents that are not proportional to the
voltage and fluctuates based on the alternating load impedance [7]. As shown in Figure 9,
23
fundamental frequency of 60 Hz which is the standard frequency of AC supply in the
frequency [38].
sequence. In a balanced, 3-phase, 4-wire system, harmonic sequence refers to the phase
rotation of the harmonic voltages and currents about the fundamental waveform. The
fourth, seventh, tenth, and so forth in a positive sequence would rotate in the same
typically undesired because the combining of the waveforms causes conductors, power
fundamental frequency (2nd, 5th, 8th, etc.). Negative sequence harmonics circulate
between the phases and cause additional problems for motors because the opposite phase
rotation weakens the rotating magnetic field that motors, especially induction motors,
"triplens" (multiple of three) is zero. Triplens are displaced by zero degrees because, as
their name suggests, they are multiples of the third harmonic (3rd, 6th, 9th, etc.).
Harmonics in the zero sequence go back and forth between the phase and neutral or
24
ground [6]. Triplen harmonics do more than just distort voltage waveforms. It may cause
units, and overheating of the building wiring [39]. Third order or triplen harmonics do not
cancel out, in contrast to the positive and negative sequence harmonic currents that do.
As an alternative, sum the numbers in the common neutral wire, which receives current
from all three phases. As a result, the neutral wire's current amplitude caused by these
triplen harmonics may be up to three times that of the phase current at the fundamental
frequency, which may decrease its efficiency and cause it to overheat [6]. The harmonic
frequency that relates to the 60 Hz fundamental waveforms is shown in the table below.
Name Fundamental 2nd 3rd 4th 5th 6th 7th 8th 9th
Sequence + - 0 + - 0 + - 0
fundamental frequency. Here, the frequencies and magnitudes of the most dominant
fundamental frequency, are directly related to the degree of waveform distortion that is
present and gives a complex waveform its unique appearance. Low order harmonics from
25
the second to the nineteenth are the most predominate harmonic elements, with triplens
being the worst [6]. With this, the third order waveform is shown in Figure 10.
Figure 10 illustrates how the third harmonics between the phases combine to
produce oscillating current. The current in the neutral conductor increases because of the
abrupt increase in the zero-sequence current caused by this. As a result, the third
Figure 11, harmonic components are drawn due to the non-linear load connected to the
circuit [40]. Typically, these sources come from several electrical and electronic
equipment and devices that has rectifier or converter [30]. From these, there are several
supplies and small motor drives [40]. Usually, this type of rectifier is used for universal
power supply (UPS) systems, switched-mode power supply (SMPS) in computers, LEDs,
and battery chargers [41]. Aside from single-phase rectifiers, three-phase rectifiers are
26
another configuration of a rectifier that causes harmonics in power systems [40]. It is
commonly used for high-power applications due to its high utilization factor for three-
fluorescent ballasts. This equipment has is rich in high-frequency voltage and current
harmonics due to increase their efficacy [40], [43]. Figure 12 shows a schematic diagram
electrical supply happens to generate the high voltage necessary to power the lamp [40].
Generally, all the electrical loads that convert AC power to DC power and vice
versa are considered are sources of harmonic frequency [39]. Electrical loads like
microwave ovens, personal computer, copier machines, televisions, welders, and energy-
efficient lighting systems such as fluorescent lamps and LED light were great sources of
harmonics. With the presence of harmonics, electrical waveforms are altered, and power
is distorted.
systems, there are certain information that is required to be determine under steady-state
conditions [44]. Parameters like resonance, harmonic currents and voltages, and
27
distortion levels and factors are just some of the information that is necessary when
conducting such study [30]. The amount of distortion in a voltage or current waveform is
known as total harmonic distortion, or THD [31]. Under IEEE Std 3002.8-2018, common
harmonic distortion indices like Total Harmonic Distortion (THD) and rms value factor
√∑
∞
2
Un
n=2
THD=(100) (2.2)
U1
where:
n – the harmonic order and usually the summation is made starting from
√∑
∞
U rms = U 2n
n=1
(2.3)
where:
n – the harmonic order and usually the summation is made starting from
28
These quantities can be further simplified when used in computation by
introducing several approaches. The first approach of performing harmonic analysis can
be done through a computer program, which utilizes a harmonic power flow analysis
program to conduct the analysis. The second approach of computation can be done
Base MVA, short-circuit capacity, ratings, and fundamental voltages and currents for the
systems [30].
where:
Along with this is the Total Demand Distortion (TDD) is the root mean square of
interharmonics. When necessary, harmonic components with orders greater than 50 may
NL
TDD=THD NL X (2.5)
TL
29
where:
Voltage THD is the total harmonic distortion of the voltage waveform. The ratio
of the root-sum-square value of the harmonic content of the voltage to the root-mean-
square value of the fundamental voltage. The equation for VTHD is presented below.
V THD =
√V 2
2 +V 23 +V 24 +V 25 +…
X 100 % (2.6)
V1
Current THD is the total harmonic distortion of the current waveform. The ratio
of the root-sum-square value of the harmonic content of the current to the root-mean-
square value of the fundamental current. The equation for ITHD is presented below.
I THD=
√ I +I2
2
2
3 + I 24 + I 25+ …
X 100 % (2.7)
I1
The short circuit ratio, also known as I SC/IL, is the relationship between the
greatest fundamental load current and the short circuit current (I SC) available at the point
of common coupling (PCC) (IL). The recommended maximum load current (I L) is the
average current of the maximum demand during the previous 12 months. But because this
value is unclear by nature, it is difficult to calculate at the design stage when measurable
30
Minimizing energy expenditures has become increasingly important as lean
manufacturing has become the industry standard. Controlling usage is important, but so is
the utility's billing policy for that consumption. Here, the power factor is important. The
power factor in an electrical system is the ratio of actual to apparent power. The current
draw increases as the power factor decreases. To reduce power dissipation, higher current
demands thicker wires and a more durable infrastructure. Facilities with low power
factors are charged more because of the increased cost to utilities [47].
power factor and total harmonic distortion make up true power factor. Many times, it is
reduced to only displacement power factor, however that is only true for a particular
category of linear loads. The simplification is no longer valid for nonlinear loads like
servo drives and variable-frequency drives. Diode-bridge rectifiers are used in servo
drives and variable-frequency drives (VFDs). The power signal is distorted by harmonics
introduced by diodes since they only operate during the portion of the cycle where the
However, there are recommended harmonic limits on power systems that vary
depending on the level of voltage distortion as per the IEEE Std 519-2014 [48].
and end-users (customers). It is advised to set harmonic limitations for both voltage and
current. This can keep the voltage distortion within acceptable ranges by limiting the
harmonic currents [39]. It must be noted that these limits are applied only at the point of
31
common coupling of the system and shall not be applied to every individual equipment
[48]. Point of common coupling, as defined by the IEEE, is the connection where the
local electric utility and end-user meets [49]. The figure below shows the flow of point of
common coupling.
As depicted in the Figure 13, these connections connect the utility system to the
consumer. A PCC is located on the primary side of the transformer for an industrial user
on the left, and a PCC is placed on the secondary side of the transformer for commercial
customers on the right. To limit specific harmonic indices, currents and voltages at the
point of common connection in order to lessen the harmonic impacts at any location
throughout the entire system (PCC), any place that both the utility and the customer may
using mutually acceptable means [50]. Table 4 presents the certain voltage distortion
Total Harmonic
Bus Voltage V at PCC Individual Harmonic (%)
Distortion THD (%)
1 kV ≤ V ≤ 69 kV 3.0 5.0
32
*High-voltage systems can have up to 2.0% THD where the cause is an HVDC terminal whose
effects will have attenuated at points in the network where future users may be connected.
For system levels up to 1,000 volts, IEEE Standard 519-2014 defines harmonic
voltage for any single harmonic. The limits are 5% for total harmonic distortion and 3%
for any single harmonic, with a range of 1,000 volts to 69,000 volts [48]. Voltage
distortion will continually be larger downstream where harmonic currents are generated
and where system impedance is at its highest as voltage distortion is the result of
harmonic current passing through the impedance of the power system [39].
Aside from voltage distortion limits, there are also current distortion limits , as
seen on Table 5, set by the IEEE for systems rated 120 V through 69 kV [48]. Similar to
the voltage distortion limits, these are also applied to the point of common coupling
(PCC) and should be taken as the sum of the currents corresponding to the maximum
17 23 35
33
> 1000 15.0 7.0 6.0 2.5 1.4 20.0
*Even harmonics are limited to 25% of the odd harmonics limits above.
*Current distortions that result in a dc offset, e.g., half-wave converters, are not allowed.
*All power generation equipment is limited to these values of current distortion, regardless of
actual Isc/IL
Where:
ISC – maximum short-circuit current at PCC
IL – maximum demand load current (fundamental frequency component) at the PCC under normal
load operating conditions
The table illustrates the largest value for both the total demand distortion (current)
and the individual harmonic current [48]. The restrictions are strictest for short circuit
ratios under 20, as this lower ratio denotes either a large user, a high impedance power
system, or both. Where the short circuit is low, voltage distortion is more likely to form
service operators to maintain these limit values to limit transient conditions in the
electrical systems [48]. Transient conditions happen when there is a change of operating
conditions such as faults, switching operations, lightning strikes or load variations [52].
The main distinction between how harmonics are constrained at current and voltage. All
specifications for voltage harmonics are rigid. The developers of IEEE 519 decided to set
a restriction on current harmonics dependent on the strength of the voltage source. This
makes sense because a robust grid will be able to suppress current harmonics to a far
greater extent than a weak grid without affecting voltage. Voltage distortion and current
distortion may have comparable levels in extremely weak grids. It may be claimed that
weaker networks require tougher emission regulations than stronger grids do [46].
34
The Philippine Distribution Code has its own standards and limits. It was
indicated in section 3.2.4 of PDC 2017 edition that the THD of the voltage and TDD of
the current shall not exceed 5% during normal operating conditions, with 60Hz as the
machines can measure all the electrical magnitudes in the electrical system. However,
portable analyzes are expensive making them unavailable to some. With that, the table
below can be utilized as a substitute. The table includes the potential damaged electrical
component that has specific indications to be observed. Any marking can be used to
Tripping of protection
CONDUCTOR
35
CONDUCTOR Conductor degradation
Tripping of protection
(loss of capacity)
Capacitor destruction
Decrease performance
Extra-large transformer
Winding degredation
Decrease in performance
36
Surges that destroy the windings
MEASURING equipment
EQUIPMENT
system. This serves as a pre-testing method when proponents are doubtful of buying or
renting testing equipment. Though results from this test are not as precise compared to
network analyzers, manual testing provides ease and peace to the consumers.
Furthermore, the testing process does not have any standard procedures. Interpretation to
the results of the manual testing varies. It must be kept that the higher the indications
there are in the system, there is greater chance of possible decreasing power quality [53].
In the early 20th century, intensified efforts to improve the harmonics became
better main alternators. This, along with the 10% THD AIEE harmonic limit (Section
research or test reveals excessive harmonic levels or a resonance state that could be
37
hazardous. Depending on the circumstance, there are frequently a number of
countermeasures [39].
There are a lot of methods of controlling harmonics when a problem arises. One
of the most common technique in harmonic control is using single-tuned filters for
harmonic currents to have a path that low impedance compared to the fundamental
current [44].
semiconductors and capacitor voltage sources are used in multilevel inverters to produce
voltages with stepped waveforms at their output. MLI is used to convert a DC input
source into an almost sinusoidal signal (AC). MLI is widely used in compressors,
implement, reduces the need for transformers, reduces the need for filters, and enhances
the harmonic quality of the output voltage. The MLI based DC-AC converter is
advantages over the traditional PWM inverter. When used as an inverter, MLI provides
superior output waveform than two level PWM inverters, and when used as active
rectifiers, they enable precise power factor correction and improve sinusoidal current
approximation. Cascaded Multi Level Inverter (CMLI) provides great performance with
less THD and employs less power electronic components than many other traditional
topologies, such as Diode Clamped Multi Level Inverter (DCMLI) and Flying Capacitor
Along with that, third method could be lowering the harmonic currents the load
produces. Fourth, adding filters will either eliminate harmonic currents from the system,
38
prevent harmonic currents from entering the system, or locally supply harmonic currents.
Last, implement filters, inductors, and capacitors to alter the system's frequency response
[56].
Aside from these, other techniques can also be applied when reducing harmonics
Method Description
Power Harmonic Filters Used when there are loads such as power
electronic converters or adjustable speed
drives; capacitors are used as power
harmonic filter to minimize the harmonic
voltage at PCC
Network Topology Reconfiguration Initially done by identifying sectors of the
power systems that generate large
harmonic currents, then distribute these
non-linear loads among different feeders
Increase of Supply Mode and Stiffness In design perspective, this method is done
by adding cogeneration on the supply bus
and increasing the substation’s size; in
electrical concept, this is done in
increasing the short-circuit current and
39
related load current ratio
Series Reactor as Harmonic Attenuator A method done to provide control on
short-circuit current levels; provides
Elements
attenuation to surge and harmonic
currents generated at both sides of the
reactor
Phase balancing Among all the methods, this is by far the
simplest; involves calculation of the
greatest deviation of the phase-to-phase
voltage from the average voltage
reduce harmonics in a power system. When there are loads like power electronic
converters or adjustable speed drives, one approach to assist attenuate the harmonics is to
utilize a power filter. Capacitors are used as power harmonic filters to reduce the
Mitigation techniques for harmonic distortion can be done either passive or active
filter solutions [57]. These solutions vary on how harmonics are mitigated in a power
superposition [57]. On the other hand, passive filter solutions are done by connecting
capacitors, reactors and resistors forming a conventional filter in the power system [57].
Among the many differences of these two, price is one of the most significant factors.
Active filters are relatively cheaper than passive filters due to the development of IGBTs
or insulated gate bipolar transistors and DSPs or digital signal processors [57]. Aside
from that, passive filters require designers to conduct careful network study necessary to
40
design a proper filter and it has no easy compensation in the dynamic changes of the
harmonic distortion [57]. Meanwhile, active filters are simple to retrofit and to scale,
active filters is more costly compared to parallel-connected active filters due to its
structure [57].
Analysis Software which identifies and mitigate harmonic and power-quality problems
straight from a dynamic one-line [58]. It has an intuitive user interface that is meant to
41
Figure 14. User Interface of EasyPower® Harmonic Analysis Software
Among its complex features is the delivery of integer and non-integer harmonics
for the most accurate modeling and real-world calculations. It also has a comprehensive
equipment. The software has the ability to analyze harmonic currents, voltages, and
system interference for IEEE 519 compliance [58]. Another commercial software for
harmonics is Eaton’s CYME Harmonic Analysis Module. Engineers may use it to test
various mitigation strategies and gauge the harmonic level of their electrical network. It
has several studies, including frequency scan, voltage and current distortion calculations,
capacitor rating and filter size analysis, K-Factor and Factor-K calculations, and more
42
Figure 15. User Interface of Eaton’s CYME Harmonic Analysis Module
With the aid of the module as seen on Figure 15, users can readily identify
resonant frequencies caused by capacitor banks as well as simulate non-linear loads and
other sources of harmonic currents, such as converters and arc furnaces. The module
allows for the precise evaluation of the effect of non-linear loads on the electrical
Lastly, ETAP Harmonic Analysis Software is the most sought-after program used
by engineers in conduct harmonic studies. With the help of the harmonic analysis
module, engineers may simulate harmonic current and voltage sources, pinpoint
harmonic issues, lessen nuisance trips, develop and test filters, and detect harmonic
voltage and current distortion limits breaches [60]. A sample illustration of the ETAP
43
Figure 16. Sample Illustration of ETAP Harmonic Study
As seen on Figure 16, power system component frequency models and intricate
harmonic source models are used to make thorough calculations for load flow and
frequency scan. In addition to Crystal Reports, the results are displayed graphically and
include harmonic order, harmonic spectrum plots, and harmonic waveform plots [60].
The power quality analyzer is among the materials and equipment required to
carry out this study. This analyzes electrical power signals to determine the load's
capacity in relation to the source. This can be used to measure the flow in either
alternating current or direct current, considering the discrepancies for AC circuits. It shall
also be used to determine the current and voltage in a system. Given these constraints, the
device can measure other electrical parameters such as harmonic distortion [61].
44
Related Literature
result [62].
Electricity users and utilities alike need to get familiar with the distinctive
waveform distortions that various harmonic sources can cause. This will make it easier to
develop more effective techniques for containing and removing them from the locations
Any non-linear loads that generate voltage harmonics and current harmonics are
the primary sources of harmonics. This happens because of the device's variable
resistance. In actuality, the resistance varies with each sine wave. Therefore, a non-linear
device is one in which the relationship between the applied voltage and the current is not
linear [62].
13% of THD is produced by the equipment and usually brought by the 3 rd harmonic
current [63]. Due to this, the power factor of the electrical system was observed to be
poor, and a capacitor is used to improve this parameter. To carefully analyze the
45
generation of harmonics brought by fluorescent lamps, 18 pieces of this was tested as
seen on Table 8.
NO. PF THD (%) I1(A) I3 (%) I5 (%) I7 (%) I9 (%) I11 (%)
1 0.535 10.95 1.34 10.86 1.10 0.55 0.55 0.19
2 0.534 8.55 1.18 8.39 1.26 1.05 0.21 0.13
3 0.512 10.34 1.20 10.12 1.86 0.83 0.41 0.21
4 0.518 9.84 1.23 8.26 1.61 1.01 0.20 0.40
5 0.527 11.76 1.19 11.64 1.46 0.41 0.62 0.21
6 0.528 10.93 1.28 10.85 1.16 0.58 0.38 0.20
7 0.546 8.93 1.14 8.71 1.52 1.09 0.43 0.43
8 0.536 11.05 1.23 10.89 1.62 0.81 0.40 0.20
9 0.535 11.73 1.22 11.59 1.63 0.40 0.61 0.20
10 0.528 11.87 1.22 11.74 1.62 0.40 0.40 0.20
11 0.549 11.57 1.15 11.40 1.72 0.64 0.64 0.22
12 0.561 8.80 1.15 8.59 1.72 0.64 0.43 0.43
13 0.564 8.38 1.13 8.12 1.76 0.88 0.43 0.43
14 0.557 8.66 1.17 8.47 1.48 0.85 0.42 0.21
15 0.561 8.60 1.13 8.35 1.76 0.88 0.44 0.44
16 0.553 12.53 1.14 12.34 1.95 0.65 0.65 0.22
17 0.552 11.88 1.14 11.71 1.96 0.43 0.22 0.22
18 0.544 9.68 1.13 9.43 1.76 1.10 0.43 0.43
As seen on Table 8, the 16th fluorescent lamp with a power factor of 0.553
generated a Total Harmonic Distortion (THD) value of 12.53%, the highest among all the
46
eighteen fixtures. It can also be observed from table that the power factor among all the
lamps lies between 0.5 and 0.6, causing the need to improve this and design a capacitor
[63].
There are now many energy-efficient products accessible because of the growing
emphasis on energy efficiency. One of these items is a compact fluorescent bulb with an
electronic ballast. CFLs can significantly reduce energy costs compared to energy-saving
initiatives are promoting the use of incandescent lighting. CFLs were created from
traditional fluorescent discharge lamps, however instead of the traditional system's initial
encouragement from power providers and governments. Due to its reduced energy
consumption and longer average useful life with equivalent luminous brightness, CFLs
are being employed more frequently. Although the current drawn from the power source
is far from sinusoidal, using it frequently could have a very negative impact on the
To examine the effects of CFL on the distribution network, some researchers have
distribution network. Adopting CFLs can cut network losses by 27% while the overall
losses for the 110kV network's power transit is still at 2.86%. The losses in the low
47
Based on the study, compact fluorescent lights' behavior with electronic ballasts is
result of CFL operation and increases current THD along CFL loading. The harmonic
performance of CFLs demonstrates a connection between the type of ballast and its
design. The widespread usage of small fluorescent lights would undoubtedly create
Additionally, it raises the peak current, which could damage network fuses and
relays. As a result, consumers need to be informed about how to use CFLs and other light
sources in moderation so that the proportion of CFLs increases may be kept in check, as
found with front-end diode bridge rectifiers of 3-phase, 6-pulse static power convertors,
are known to produce harmonics due to its nonlinear nature. If these generated harmonics
are not treated, the Total Harmonic Current Distortion (THID) usually spikes from 100-
140% with the 5th and 7th harmonics being dominant [65].
Figure 17 shows the schematic diagram of this variable speed drive and the bar
48
Figure 17. Variable Speed Drive with 3-phase, 6-Pulse Static Power Converter
As seen on Figure 17, the 5th harmonic level of the equipment was able to
generate 75% harmonic current of the fundamental frequency of 60 Hz [65]. With that,
that support modern civilization are based on alternating voltage and current that have
sinusoidal waveforms. A nearly flawless sine wave of current underlies every physical
phenomenon upon which the energy system is built. The sine wave is maintained, and the
system components are linear when loads made up of inductances, capacitances, and
resistances are connected to it. The system's essential sinusoidal nature of the current
flowing through it remains when nonlinear devices are coupled to it. The issue with
nonlinear load converters of power (rectifiers and thyristor power supplies) are linked to
the network. There are numerous types of static power converters available for various
uses. Different circuit topologies for static power converters are referred to by different
way, double-way, bridge, star connection, and six-pulse. They are all nonlinear, which is
something they all share. They need non-sinusoidal current from the power system. Even
49
so, they are subject to a few fundamental laws that allow for a study of the nonlinearity's
impacts [66].
systems [67]. Network systems such as wireless access network and fixed access network
are just some of the areas of telecommunications where rectifiers are deemed to be used
[67]. Consequently, electronic devices such as televisions are also composed of rectifiers
the THD value generated, as seen on Table 9. These rectifier circuits are commonly
applied in power appliances like televisions among other electronic devices [69].
As seen on Table 9, several types of rectifiers are studies in terms of its THD
output. The diode rectifier with filter capacitor at output has produced the highest THD
50
value of 300%. Usually this type of rectifier circuit is used to perform signal processing
and have a stable DC voltage [70]. As observed, the diode rectifier without filter
in malfunctions. Harmonics modify and move zero pass points as well as the voltage
waveform. In electronic control systems like PLCs, the zero pass point serves as a crucial
reference point, and any change to this reference has an impact on the system's overall
performance [71].
Buildings like office spaces, hospitals, data centers, and others must have
HVACR (heating, ventilation, air conditioning, and refrigeration) systems to keep the air
conditioned and comfortable. Systems for heating, ventilation, and air conditioning use a
lot of energy. Variable-frequency drives (VFDs) used properly in these systems will
significantly lower their energy usage. Power line harmonics is a phenomenon that is
harmonics, the potential issues they can lead to, and the solutions that are available to
eliminate those harmonics because the benefits of utilizing a VFD greatly exceed the
disadvantages [72].
It's crucial to remember that VFDs are not a system's lone source of harmonics.
However, because VFDs in HVACR applications may account for a sizable fraction of
the total building power consumption, they are frequently the subject of discussions about
harmonic calculation and reduction. For HVACR applications, some examples of VFDs
are pumps (for chilled water, condenser water, and hot water), fans (for supply,
compressors, return, exhaust, and cooling tower). Other sources of strong harmonics, for
51
instance, include fans with electronically commutated motors (ECMs), lighting systems,
both single-phase power supplies and uninterruptible power supply (UPS) systems [72].
The EEP had presented that air-conditioning units can produce a %THD of less than 5%
[73].
The most common VFD design operates by rectifying a three-phase AC line input
voltage using diodes. This converts the voltage across a bank of capacitors into a steady
DC voltage. The motor's speed, torque, and direction are then controlled by the VFD by
significantly risen. Those VFDs air handlers, pumps, chillers, and tower fans are now
often used. A deeper comprehension of VFDs will improve the use and selection of
HVAC systems as well as equipment. Only when the line voltage is higher than the
internal DC Bus voltage do VFDs draw current from the line. This only happens close to
the sine wave's peaks. As a result, the entire current is drawn in brief bursts (i.e., at higher
frequencies). The harmonics generated are impacted by variations in VFD design [62].
Electric arcs have very non-linear voltage-current properties. After the arc ignites,
the short-circuit current, whose value is solely constrained by the power system
impedance, causes the voltage to drop. The electric arc furnace is the category's primary
harmonic source. It has magnetic ballasts and discharge lighting. Due to variations in the
arc feed material, the harmonics generated by electric arc furnaces cannot be accurately
predicted. The arc current exhibits a continuous range of harmonic frequencies of both
integer and non-integer order and is very nonlinear. The arc furnace load exhibits the
52
worst distortion as a result of the physical phenomenon of the melting with a moving
electrode and molten material. From cycle to cycle, the wave might not be the same [62].
computers are utilized in the campus. Aside from the offices that uses computers for their
transactions, there are numerous computer laboratories in the campus to help students in
the learning process as those were mostly used for research purposes, programming, and
other academic-related lectures [74], [75]. To continuously adapt and get on to the
However, personal computers are nonlinear load and the number of personal
Depending on the amount, single-phase nonlinear loads have the potential to cause
harmonic distortion in the voltage and current of the electrical system which may lead to
oscillations in generators and motors. The power quality in King Fahd University was
inside the university. The single line diagram of a specific building at the university is
53
Figure 18. Building 14 Single Line Diagram and Points of Measurements and Switch
Boards
The figure above shows that there are three different points of connection. The
point 1 has the connections of each of the classrooms and laboratories in Building 14;
point 2 has the uninterruptible power supply connection; and point 3 has the electrical
power distancing problem connection, a 4KW connection, and is the one connected to the
Each point was tested separately using Fluke 43B power quality analyzer. Three
1 10.6 %
2 10.7 %
3 10.8 %
The table shows that the THD level increases after each testing. Moreover, the
1 29 %
2 28.4 %
3 28.9 %
Unlike the results from testing point one, the THD level at point two were
unstable. The maximum THD level at point two is at 28.9%, considering that this is the
median among the three. Lastly, the maximum THD at point 3 is at 20.6%. The
maximum THD levels were analyzed according to the standards provided by the PQ
analyzer, which states that harmonic distortion is probably acceptable if the THD is less
than 20%. The point one has only the maximum THD level within the standards, hence
harmonic distortion produced by points two and three are alarming. The huge difference
between the THD measured in points one and two were caused by the uninterruptible
power supply connected at point two. This point has the connections of the personal
computers from the main student laboratory in the building [74], [75].
information. A study made by Bajpai, U., et al. focused on the heavy-duty printers used
usually in printing industry and its harmonics. A certain printing shop establishment was
being tested. It has its own 11kV sub-station, 11kV/433V outdoor transformer, and
500kVA transformer connected indoor. Active filters are also installed in the power
system to filter harmonics. Using Fluke 434 Series 2 PQ and Energy analyzer, the
harmonics in the system was measured. The device was connected at two different points
and several electrical parameters were gathered such as the THD, IHD, Power Factor, %
55
Unbalance, and voltage and current rms. After the testing, the maximum THD was at
20.46% for condition 1 and 27.6% at condition 2; while the minimum THD was 1.54% at
condition 1 and 1.35% at condition 2. The harmonic order was predominantly above 4%.
In addition, after turning off the filter, the maximum THD reached 37.2%, with the
current waveform heavily distorted. The harmonic orders 2, 3, 4, 5, 7, 11, and 13 were
observed [76].
distortion in an electrical system. Idemne et al., had studied the level of harmonics
produced by induction type water pump motor. It was found that a 5-HP water pump
motor alone can generate 2.10% THD. However, when the motor was controlled by a
variable frequency drive it was found that it can generate higher THD that can be as high
as 8.42% [12]. The THD generated by the water pump motor is within the IEEE 519
limit; on the other hand, controlling such by a VFD results to a THD level that is beyond
the limits. Thus, it is not the water pump motor that largely contributes to the harmonic
distortion in the electrical system, but rather the addition of variable speed drive that acts
as a controller.
harmonics is determined. The installed active filters are ineffective for eliminating the
voltages, which can increase or decrease current harmonics depending on the nature of
the voltage distortion. Utilizing SMPS can improve the reliability and efficiency of the
system. However, this draws high frequency, speed, sensitivity, reliability, and
56
versatility, with its small size. It can increase the power density of power electronic
devices. Turning off and on the SMPS during high frequency will result to generating
Through using three-phase passive filters, the harmonics generated can be filtered.
The supply system can be on its ideal effect. This causes the harmonics to be lower than
lighting, and CFL bulbs. Harmonics are produced by all these nonlinear loads' properties.
Because there are very few disruptions, earlier harmonics generated by home loads in the
grid are disregarded. These new loads advance and become more prevalent. However, a
huge number of these gadgets will have a major negative impact on the energy network,
generating distortion, dips, and harmonics. This replacement entails the conversion of
resistive loads into electronic loads, and the ongoing replacement has a detrimental
Power quality analyzer Fluke 43B was used to assess THD and distorted current
consist of a laptop, tabletop, charger, and other small appliances printer, copier, scanner,
and CFL and LED lighting. Using power quality, the consumer load has been measured
due to current distortion. If there are more people carrying such loads, then significant
This significant harmonic distortion has an impact on the grid's overall power
57
solutions, newer equipment can save a substantial amount of energy, but at the expense of
There are several studies that deal with how power quality-related problems,
power, the need to have an accurate and effective measurement of this power becomes
Any system's reliable and effective operation requires an electrical system that is
this, capacitors are used in harmonic environments. They are advantageous because they
lead to reduced THD and increased power factor and the abolition of penalty for power
factor [81]. There are two methods for detecting harmonics, and these are selective
mechanism. This method provides the highest level of precision and bandwidth [81].
There is also a new approach to measuring time-varying frequency harmonic wherein this
is based on the adaptive evaluation of the power signal's fundamental frequency and its
Harmonic distortion and harmonic components can both derived from a distortion
meter. This makes use of a microcontroller-based harmonic distortion meter, and its
58
amplitude is found using DFT. This refers for frequency domain approaches of selective
measure its harmonics and interharmonics. However, this is possible by using an adaptive
notch filter. This approach values for fundamental frequency, harmonic frequency, and
Poor performance is caused by non-linear load in power system where these leads
to harmonic sources. Since this is becoming a really significant issue, one of the most
(LPC2138). The supply voltage is divided into 6V for matching power rating employing
a voltage divider. Using this harmonic analyzer, frequency, and harmonics in a single-
phase supply range of harmonics. This system's benefit is that being inexpensively
available [81]. Experimental results demonstrate that the provided device is more
accurate to obtained, and the flow of harmonic power is also analyzed [83].
Králiková & Čičáková [80] has conducted a research that deals mainly with the
measurement of distortion power measurement. The application has used the harmonic
to effective in measuring any kind of periodic voltage and current waveforms [80].
59
Using the tools and environment of LabVIEW and a DAQ card to transfer all the
voltage and current signals to the computer, the program was able to simulate the
parameters of the voltage and current such as rms values, mean value, and total harmonic
A present in the commercial building at Carre are classified into four classes depending
Household Appliances
Audio equipment
Portable tools
B Very Short Usage
Arc welding equipment
shape TV sets
60
After such classification, the measurement of harmonic distortion proceeded. In
measuring the voltage total harmonic distortion (V-THD), two instruments were used,
specifically PSL PQube and Dranetz PowerXplorer. These two devices were utilized for
different purposes; the PQube for measuring the voltage in the offices; and the
Figure 19 shows the schematic diagram of the power supply of the establishment
As seen on Figure 19, the main switchboard is connected to the low voltage side
of the feeding transformer, M1 counted as the first location, the distribution board M 2 as
the second location, and the office building at Carre as the final location of the
measurement which is M3 [84]. The measurement of the result is presented on the table
below.
VA VB VC VA VB VC
61
Main Switchboard M1 5.3 5.4 5.7 2.4 2.3 2.3
Timens et al [84] concluded that due to the construction of this new modern
building and existence of non-linear loads in its offices, the V-THD was measured to be
higher than expected as seen on Table 13. The effect of harmonic distortion led to the
In the earlier, the magnetic saturation of transformers and industrial loads like arc
furnaces and arc welding machines caused the harmonic problem in the power system.
The main issues were harmonics' effects, particularly on induction and synchronous
devices. But today, further approaches to harmonics are required for the following
considerations [85].
1. In recent years, nonlinear loads have increased rapidly in locations that are
3. The equipment and system loads in a power system are typically harmonically
sensitive.
and simulation. Harmonics modelling are done to estimate the harmonic impact of a new
or existing customers and electric utility and assess the effectiveness of harmonic
62
harmonic models and their differences in terms of data requirements, complexity,
not sensitive to
variations.
Constant
Used for wider range
Current
of operating
Source Model
conditions; loads are
Norton Model
modeled in parallel
harmonic number.
63
Cross
Frequency
Admittance
Matrix Model
Among all the harmonic models cited by Balci et al, the study concluded that
statistically proven by having a standard deviation of 0.0735, the lowest among the three
models [86].
nonlinear loads owing to the upsurge in harmonics in the distribution system, which is
brought on by a swift increase in the generation of equipment that controls power [87].
The most often used technique for removing harmonics from a system is filtering,
which can be done with passive, active, or hybrid filters. Passive filters are those that
have passive components like capacitors, inductors, etc. and operate without the use of an
external power source. These filters, which are the least expensive kind, can be linked in
64
Active filters are a type of analog electronic filter that are frequently employed in
high- and variable-voltage environments. They are expensive and complicated, yet they
Hybrid filters, which combine passive filters with fundamental active filters, are
an additional filter used to improve power quality. The drawbacks of passive and active
filters used separately can be solved by hybrid filters, improving performance quality.
These kinds of filters also help to lessen electromagnetic interference and switching
noise. The fundamental goal of a hybrid filter is to dynamically improve the efficiency of
Hybrid filters are used to reduce the level of harmonics in the source current and
improve the system's power quality. A series passive filter and an active filter based on p-
q theory have been developed. Based on the results of the simulation, it also compares
passive and hybrid filters and determines that hybrid filters are better suited for lowering
65
For the study of Faraby et al [88], another approach in mitigating harmonic
planning was applied to solve the power quality issue brought using non-linear loads.
Using a hybrid particle swarm optimization (HPSO), the best locations, sizing of
along with the compliance of IEEE 33-bus radial distribution system. The solution was
modeled and simulated using MATLAB2018 and results were compared to related
previous literatures [88]. Figure 20 shows the comparison of the %THDv before and after
From the trend of the graph on Figure 20, there can be seen some sight of
decrease in the different scenarios of the simulation. Through the use of HPSO in
harmonic distortion, there is a significant effect in minimizing the %THDv of the system
Industries are integrating capacitor banks in their power circuits to use the
electrical system efficiently. In recent years, there has been a growth in the usage of
power electronic equipment, which has led to an increase in harmonics in the power
66
system. According to the study, this explains how harmonics are produced, their impact
on the electricity grid, and how to lessen (mitigate) their effects. With the aid of a
waveform that displays % current and voltage harmonic distortion variation at the
incomer with respect to APFC ON/OFF status and harmonic reduction strategies, a
Harmonic mitigation approach and the capacitor bank energizing transients is done
according to the study. Reactive compensation factors make a capacitor bank connection
generated during capacitor bank energizing that reach in harmonics may be detrimental to
the capacitor and represent a growing concern for both electric utilities and customers.
Power factor correction capacitors are susceptible to harmonics, and one cause of power
capacitor failures is the presence of prime odd harmonics, such as the fifth, seventh,
There are currently devices available for capacitor bank energizing transient
control, and these are used to reduce the transient overcurrent and overvoltage effect at
the point of application. According to modelling and simulation studies, choosing the best
control scheme necessitates a thorough analysis because the effectiveness of these control
methods is system dependent. Each of these techniques has different benefits and
Synthesis
67
In 1888, Nikola Tesla had recognized the alternating current [17]. This type of
current changes its direction sinusoidal, positive and negative half-cycle [19]. The
minimal losses [18]. Being one of the known universities when it comes to engineering
and as the newly hailed National Engineering University, the BatState-U Alangilan has
Rotating machines are the common sources of sinusoidal currents, which when
passed through a resistor, inductor, or capacitor produces another waveform with the
The discrepancy between the ideal sinusoidal waveform of the supply voltage and
the current waveform is referred to as the harmonics and harmonic distortion. The
behavior of resistance in an AC and DC machine is similar, hence the voltage across the
resistance determines the amount of current flowing. This is because a resistor is a linear
device. Complex waveforms produced by machines can affect the behavior of the current
demands current at the peak values of the AC supply, hence the resulting load current is
voltage acting upon it, or the circuit is composed of non-linear elements but a sinusoidal
voltage act on it. The inductive resistance of an element rises as with the harmonic
number, in contrary of the capacitive element. A DC component does not have any
These waves can be mathematically computed through the Fourier Series which states
that any practical periodic function can be represented as an infinite sum of sinusoidal
waveforms that have frequencies which are integral multiple of ω o. In addition, other
a sine wave. This produces non-sinusoidal currents which is characterized by time as the
independent variable. Cosine waves can also be from two or more sine waves. With its
complex structure, cosine waves have one fundamental frequency which has the lowest
frequency but has the highest amplitude and one or more harmonic frequencies. It is the
Loads had been linear before 1980. The shift happened in 1981 when electronic
hardware makers shifted to switch-more power supply (SMPS). This transforms the
applied voltage into distorted current waveform which copies AC pulses. Voltages or
currents that have frequencies are multiples of the fundamental frequency were referred
to as harmonics [34]. With the status of technological advancements, almost all the
electrical loads present today generate harmonics. Voltages or currents that have
[34].
Waveforms represent sine waves, and those that represent nonlinear loads has
current affecting the voltage wave. The affecting current results to voltage distortion
those that has rectifier or converter or those that convert AC to DC power vice versa [34].
Non-linear loads are highly inductive in nature, and they were the harmonic producers.
These are the loads that whose impedance changes according to the applied voltage cycle.
This is because devices of this kind draw current at the peak values of the AC supply
which then causes the current to behave nonlinearly. This includes loads like computers,
printers, televisions, and those that utilizes SMPS [26], [28]. Hence, nonlinear loads were
loads whose current is not proportional with the voltage that produces distorted waveform
[51]. With the presence of harmonics, electrical waves are altered and power is distorted
[33]. Nonlinear load type is prone to fluctuation because of the alternating load
impedance. Current were drawn at short pulses which distort waveforms and result to
harmonics [28].
When two or more waves interact with each other, wave interference occurs. This
can result to large, smaller, or identical amplitude. Wave interference may either be
between waves with equal frequency is zero, this results to single amplitude which is also
equivalent to the sum of the amplitudes of the individual waves [32]. On the other hand,
when the resultant amplitude is a smaller than the aggregates, the interference is
waves and destructive interference are an invert, which results to smaller sine waves
Both positive and negative interference are produced during the interaction.
Considering the original waveform and the harmonics present, the harmonics’ in-phase
70
location is combined constructively and those destructively added to the out of phase
0. The odd harmonics which are represented by odd numbers are commonly produced by
nonlinear loads, and the even harmonics represented by even numbers are generated by
uneven current drawn in the positive and negative half of one cycle of operation [31].
Philippines where it is considered as the standard frequency for the AC supply. Any
frequency higher than this is its multiple, and the multiplicity defines the number of
balanced system, the harmonics refers to the phase rotation of the harmonic voltages and
current like the direction of the fundamental frequency. This is considered as the positive
sequence harmonics because they rotate on the clockwise direction, however this is
causes reduction in the mechanical torque of motors as the rotating magnetic field
that are multiples of 3 rotates on this sequence. This is displaced by zero degrees, which
results for the harmonics to bounce back between the phase and the ground. This makes
the current in the neutral wire to be up to thrice of the phase current, since the numbers in
71
the common neutral wire were added up. Therefore, the third order harmonics causes
The decrease in supply voltage is known as sag. This usually results to an assumed
interruption. However, voltage sag happen suddenly as during sagging the voltage drops,
while complete loss of voltage occurs when there is interruption. An opposite of sag is
likely to occur when the voltage is increased by 10% of the nominal, this is described as
dips or voltage swells. A resemblance of voltage swell can also be observed in a system-
transient voltage. Its occurrence has stronger magnitude and lasts quickly than drips. The
common reasons for such voltage disturbances revolve within sudden turning ON/OFF of
Generally, all electrical loads that convert AC to DC powers and vice versa are
back, most of the indicated loads can be found inside Batangas State University -
Alangilan campus.
different nonlinear loads. Single phase rectifiers are used in electrical system to convert
AC power to DC power, they can be found on universal power supplies and switched-
72
High frequency electronic ballasts are commonly found on fluorescent lamps.
This equipment is loaded with high frequency voltage and current harmonics to achieve
Harmonic resonance occurs when the natural frequency of the power system and
series when the inductance and capacitance are combined in series or almost in series,
this results to low impedance path of the harmonic currents of the natural frequency [39].
techniques. The analysis can be done through computations, having known the different
electrical parameters such as resonance, harmonic currents and voltages, and distortion
levels. Common harmonic distortion indices like Total Harmonic Distortion (THD), rms
value, telephone interference factor was indicated under IEEE Std 3002.8-2018. [30],
[45].
this requires harmonic power flow analysis. Another is a spreadsheet that results to
harmonic impedances by having the required variables [30]. The voltage and current
THD were both the root-sum-square of the harmonic content of the voltage or current to
maximum load current shall be the average current of the maximum demand during the
previous 12 months. This is used to calculate the short circuit ratio [39].
The concerns regarding minimizing the expenditures and controlling the usage
can be addressed by the power factor, which is the ratio between the actual and apparent
73
power. As the current increases, the power factor decreases. Facilities with low power
factor are charged more in terms of utilities because they require thicker wires and more
durable infrastructure. However, there are methods on how the power factor and the
The recommended limits of voltage and current harmonics can be found at Tables
3 and 4 respectively. There were as indicated in IEEE Std 519-2014 [48]. These limits
between the utility and the customers [39], [48]. The limits were categorized according to
the conditions of the electrical system and the strength of the voltage source. In cases
where the harmonic current limit needs to be increased, multipliers were used. Setting the
electrical systems, maintaining such can limit the transient conditions [48]. The
restrictions set on the current harmonics is dependent on the strength of the voltage
source, as huge grids can be able to suppress current harmonics to a far greater extent
Since the standard frequency in the Philippines is different from the standard in
other countries, the country has set its own electrical requirements and limits. It was
started in the 3.2.4 of the Philippine Distribution Code 2017 Edition that THD and TDD
reduce harmonics that can be hazardous. Using single-tuned filters provides path for
harmonic current that lowers impedance [44]. Multilevel inverter is one of the key
waveform [55]. Other methods for controlling harmonics include lowering the harmonic
current of loads, adding filters to the electrical system, and implementing filters,
inductors, and capacitors that may alter the frequency response of the system [40], [44],
[56] .
There are five different methods available which can be used to decrease the
harmonic in an electrical system. Capacitors can be added to the system to decrease the
existing harmonic level in the system; the capacitor acts as the power harmonic filter. The
specific loads or sections in the system who were found generating high levels of
harmonics can be distributed to other feeders, in some cases harmonic generating loads
are also eliminated from the system. However, the network topology reconfiguration
cannot be adopted by the BatState-U Alangilan considering the functions of the existing
nonlinear loads. Another method that can be adopted is done by increasing the supply
mode stiffness, this requires the addition of cogeneration system which can be seen inside
the university through the solar-powered streetlights and PV modules installed on some
of its buildings. Series reactors can also be used to reduce the harmonic element, but this
method is only ideal for neutral to ground connection of power transformers. Lastly, the
phase balancing method which is the simplest among the five methods mentioned.
However, the expected outcome of this method is difficult to attain as single phase loads
are constantly changing which then generates unbalanced voltages [40], [44].
The abovementioned methods were further studied by the researchers. Given that
system is already existing, and the phase balancing and addition of series reactors is
75
difficult to attain, the researchers came up with the addition of power harmonic filters to
the electrical system. This method provides a more accurate expected outcome and is
more convenient to be applied. There are different filters available in the market that may
Mitigation techniques for harmonic distortion can be done either passive or active.
Active filter solutions generate actively harmonics in opposite phase to the distorting
harmonic and eliminate them by superposition. Passive filter solutions are done by
connecting capacitors, reactors and resistors forming a conventional filter. Active filters
are way cheaper that passive filters. Such is also simple to retrofit and scale but requires
costly serial connection to achieve the desired function. Passive filters on the other hand
measurement and mitigation. EasyPower® Harmonic Analysis Software can identify and
providing ease in utilization. But it can also provide integer and non-integer harmonics
which can be used for accurate modelling and calculations. This has the ability to
measure and examine harmonic currents, voltages, and system interference [58]. Aside
from this, Eaton’s CYME Harmonic Analysis Module is also used by engineers to
measure and test different applicable mitigation techniques in a power system. This
software can provide frequency scanning, calculations for voltage and current distortion,
capacitor rating and filter size analysis, K-Factor and Factor-K calculations, and others.
The resonant frequencies caused by capacitor banks as well as the effects of the nonlinear
76
loads can be projected in the testing. With these features, the Eaton’s CYME Harmonic
Analysis Module can provide precise assessment of an electrical system [59]. Moreover,
the Harmonic Analysis feature of ETAP is considered the most used program when it
comes to harmonic measurement and assessment. Through this software, users can
simulate harmonic current and voltage sources, pinpoint harmonic issues, lessen nuisance
trips, develop and test filters, and detect harmonic voltage and current distortion limits
breaches [60]. Aside from the Crystal reports, the result of testing is also projected in
graphs which provides clearer understanding. The source and power system component
frequency are modelled in the program and are used for calculations of load flow and
frequency scanning. The features and capabilities of ETAP Harmonic Analysis Module
provides ease, such that even students can make a mitigation model for harmonics in a
power system. The said software is also used in other electrical system testing and
modelling [60].
harmonic sources can help to easily develop techniques in detecting and eliminating
harmonics [62].
made by Chang et al, [63] and is presented above. From there it can be drawn that the
power factor is poor, and a capacitor is used to improve. The quality of the power factor
is caused by THD is produced by the equipment; this is usually produced by the third
harmonic current [63]. One of the commonly seen and used device that utilizes electronic
ballasts are the compact fluorescent bulbs that significantly reduce energy costs
77
compared to incandescent lightings. Adopting such lighting can cut the network losses
by 27%, while the overall losses for the 110kV networks power transit is still at 2.86%.
The widespread usage of small fluorescent lights would undoubtedly create harmonic
Due to its nonlinear nature, VFDs found with front-end diode bridge rectifiers of
3-phase and 6-pulse static power convertors are known to produce harmonics. If the
generated harmonics are not treated, the THID can raise up to 100-140% with fifth and
systems [67] as they were used to convert AC to DC power. A table obtained from
research made by Anga et al [68] is presented above as table 10 to exhibit the THD
this uses as lot of energy. But with the addition of VFDs, the power usage can be
lowered. The most common VFD design operates by rectifying a three-phase AC line
produces nonlinear current [72]. Air-conditioning units which are prominent in the
Electric arcs, especially electric arc furnace is another harmonic source. After the
arc ignites, the short circuit current causes the voltage to drop. It has magnetic ballasts
and discharge lighting, but the harmonics generated cannot be easily predicted as the
78
The power quality at King Fahd University was measured with the personal
computers as the existing load. The research has shown that the THD level was beyond
the 20% limit of the standards. Hence, it can be proved that depending on the amount
single-phase nonlinear loads can contribute to the harmonic distortion in the system [74],
[75].
a large-scale printing industry. After conducting the testing using a power quality
analyzer, it was found that the maximum THD level was also beyond the 20% limit.
Also, the harmonic orders such as 2, 3, 4, 5, 7, 11, and 13 were observed [76].
Water pump motor is another type of harmonic generating load. The %THD
generated by such can range from 2.10% to 8.42%. Idemne et al., presented that the
minimum THD is generated by the motor alone and the maximum THD is produced
when variable frequency drive is added to the motor as a controller [77]. From there, it
voltages, that can increase or decrease current harmonics. This produces high frequency
speed, that when the SMPS is turned off and on, can generate high levels of harmonics
With three-phase passive filters, harmonics can be filtered out; and it can be lower
than the IEEE standards [78]. The significant harmonic distortion has an impact in the
grid’s overall power quality as well as to the distribution system. Compared to repairing
79
broken electric and electronic devices, newer ones can save substantial amount of energy
[79].
Capacitors may be used as they reduce THD and increase power factor. There are
different approaches available for detecting harmonics, each providing the needs of the
end-users. Microcontroller-based harmonic distortion meter with its software does DFT
Using an algorithm for harmonic analysis, the Fast Fourier Transform technique
was applied [83]. FFT is used to construct a harmonic analyzer on an ARM7 core CPU
(LPC2138). Using a voltage divider, the source voltage is divided into 6V for matching
power rating. With the use of this harmonic analyzer, one may determine the frequency
and harmonic range of a single-phase supply. The fact that this system is reasonably
priced makes it advantageous. Experimental findings show that the suggested gadget is
more accurate to use, and an analysis of harmonic power flow is also presented [83].
Researchers Králiková & Iáková have undertaken research that primarily focuses
on the measuring of distortion power. The application has demonstrated its effectiveness
in measuring any type of periodic voltage and current waveforms by using harmonic
was able to simulate the parameters of the voltage and current, such as rms values, mean
values, and total harmonic distortion (THD), using the tools and environment of
LabVIEW and a DAQ card to transport all the voltage and current signals to the
computer [80].
80
In addition, Table 13 shows the classification of equipment with rating smaller
than or equal to 16 A as proposed in the study of Timens et al [88]. This makes use of
concluding that the overheating of transformers and voltage distortion were caused by
harmonic distortion.
The harmonic problem in the power supply was previously brought on by the
magnetic saturation of transformers and commercial loads like arc furnaces and arc
devices, were the main problems. But today, more harmonics-related techniques are
1. In recent years, nonlinear loads have increased rapidly in locations that are
3. The equipment and system loads in a power system are typically harmonically
sensitive.
existing customers and electric utility and assess the effectiveness of harmonic mitigation
techniques are the commonly used harmonics models as studied by Balci et al. It is being
said that the Norton model is the best modelling approach. This has the lowest standard
The (IEEE-519) standards for power quality improvement, states that there is a
of such nonlinear loads owing to the upsurge in harmonics in the distribution system,
81
which is brought on by a swift increase in the generation of equipment that controls
power. The most common approach used is filtering, which uses active, passive or hybrid
filters [87].
In addition, the network configuration technique was also developed. This utilizes
HPSO, the best locations, sizing of distributed generation (DG), capacitor, and network
reconfiguration were determined along with the compliance of IEEE 33-bus radial
There were also industries who uses capacitor banks as mitigation. This helps for
the switching to happen frequently. Capacitor banks were used to reduce transient
and selected depending on the research objectives of this research paper and the available
resources. Any of the measuring and testing methods stated above can be utilized,
provided that the researchers have enough resources, most especially to the testing
devices and the access to the software. Afterwards, the appropriate controlling methods
Alangilan, there were an estimated 3114 fluorescent lamps, 503 personal computers, 102
copiers and printers, and 410 ACU. With this huge amount of the electrical and electronic
loads resent in the university, high level of harmonics can be expected. However, after
testing and mitigation a more efficient and reliable power distribution shall be expected
inside.
82
CHAPTER III
This chapter presents the methodologies that will be applied in the conduct of the
study. This includes the research paradigm, experimental design and procedures which
Conceptual Framework
Conceptual frameworks are visual representation of the flow of study and help on
describing the natural progression of the research [93]. It is important to have a good of
choice of paradigm for this affects the research questions, data collection instruments and
collection procedures, and data analysis [94]. Figure 21 shows the illustration of the
research paradigm for the assessment and mitigation of the potential harmonic distortion
83
Figure 21. Research Paradigm
As seen on Figure 21, the paradigm to be utilized for this study is divided into
four (4) phases: Conceptual Phase, Philosophical Phase, Methodological Phase, and
Implementation Phase.
On the conceptual phase, this frame of the study determines the vital concepts and
key variables in establishing the foundation of the study, specifically, these variables are
harmonic distortion and electrical system. Aside from these, the statement of the problem
and research questions and objectives shall be known to define the direction of the study.
84
Succeeding this is the philosophical phase which contains the hypotheses of the
research. Also, the related studies and literature are vital to this phase to provide the basis
determine the recommended limits of total harmonic distortion (THD) and Total Demand
design and procedures, and the data collection and treatment that will be adhered to this
study. This includes the procedures that would be implemented in measuring the potential
Campus, the necessary equipment and facilities required, the appropriate software and
computational analysis for the assessment of the level of harmonic distortion, and the
Lastly in the paradigm of the study is the implementation phase which covers the
system of the said campus, design of the mitigation plan for the harmonic distortion in the
electrical system of the building, and recommendation for a mitigation plan for the
harmonic distortion that may occur in the electrical system in the future.
85
Experimental Design and Procedures
The steps to attaining the goals of this research are outlined in the Figure 22. This
involves various stages, which are discussed in even more detail below.
and procedures shall be adhered throughout the study to collect data that are accurate and
al [95] was utilized and retrofitted to the objectives of the study to execute the
Methods of Experiment
harmonic distortion in the electrical system. The materials and equipment needed
for the measurement consists of a 3-phase power quality analyzer (PQA) FLUKE
438-II and a laptop. The power quality analyzer was made sure that is calibrated
and working properly. For the laptop would be used supplementary with the PQA
to record the data that were measured using the instrument. The necessary
(THD) and total demand distortion of the feeder panel on the secondary side of
Engineering and Fine Arts building inside the powerhouse with the highest
number of nonlinear loads. The feeder panel of the transformer will serve as the
point of connection where the values would be determined. The THD and TDD
values that would be measured at these points would represent the potential
harmonic distortion existing throughout the electrical system. Both voltage and
87
existence of harmonic distortion in the electrical system of the building. The
duration of the measurement shall last for five (5) days to attain the maximum
demand of the loads. Tables 15 and 16 are provided to record the data that would
a. Locate the main distribution panel of the secondary side of the distribution
b. Trace the cables connected from the secondary side of the transformer to
the main distribution panel. The number of cables should be three (3) to
c. Switch the power quality analyzer on and configure the device for
harmonic measurement.
d. Connect the leads and current sensors to their respective terminals on the
e. With the device powered up and connected to the system, measure the
88
h. The integration period over which the measurements of each recorded
values are averaged, is set to be fifteen (15) minutes over the span of five
(5) days.
THD
THD %
Result
Remarks
THD
TDD %
Result
Remarks
89
Table 16. Current Distortion at Point of Connection
3. Compute the ratio of the short-circuit current and line current at the feeder
panel on the secondary side of the transformer and the main distribution panel of
the CEAFA building. The values obtained from this computation shall be used
these points using the power quality analyzer exceeds the 2017 Philippine
4. Obtain electrical system single-line diagram and determine the location of the
point of connection. The single line diagram shall be made with the help of the
university electrician and would be drawn using ETAP. This drawing includes the
(ETAP) and perform harmonic analysis at the respective buses determined at the
actual measurement. Table 17 records the harmonic distortion measured using the
said software.
Point 1
Point 2
Point 3
Methods of Assessment
90
1. Evaluate the results of the measurement of harmonic distortion. Comparing
the result of the harmonic levels to the recommended limits mandated at Chapter
3 Sec.2.4 of the 2017 Philippine Distribution Code, the voltage and current
not. For the voltage distortion limits, the assessment of the THD% is based on the
bus voltage of the point of connection where the harmonics was measured.
According to the said provision, the total harmonic distortion (THD) of the
voltage shall not exceed 5% during normal operating conditions. On the other
hand, the assessment of current distortion is based on the ratio of the short-circuit
current and line current at specified bus or point. Typically, this ratio is valued
less than or equal to 20 for systems rated 1 kV and below. Under this ratio the
acceptable limit of total demand distortion (TDD) for current is 5.0%. Table 15
includes the result of the assessment for voltage distortion and shall be remarked
current and line current as well as the allowable TDD % which shall be a
Isc/IL
91
Allowable TDD (%)
2. If results are within allowable range, prepare a pro-active mitigation plan that
will address the potential increase of harmonic distortion in the electrical system
3. If results exceed the allowable range, design a mitigation plan to address the
4. Model the modified electrical network after applying the mitigation plan. ETAP
In this study, the mitigation plan that would be designed for the potential
harmonic distortion in the electrical system of the university mainly focuses on the design
of a harmonic filter. A high-pass passive filter would be used to mitigate the harmonic
distortion in the electrical system of the campus. This type of filter is commonly used in
industries to suppress a wider range of frequencies and reduce the size of the
components, and to avoid a capacitive power factor when the system is not loaded. The
harmonic filter would then be sized appropriately based on the readings from the actual
measurement and ETAP simulation. The method of mitigation for both when the
harmonic distortion level is within recommended limits or not shall be similar. The
mitigation for these different scenarios would only vary on how the harmonic filter would
be sized. The following steps would be taken in designing the mitigation plan:
92
1. Utilize the ETAP software in sizing the harmonic filter. The data obtained
from the actual measurement using the power quality analyzer and ETAP
simulation shall be used for the appropriate sizing of the harmonic filter.
2. Determine the necessary parameters of the filters. Parameters such as the filter
type, and capacitor and inductor ratings are to be determined to size the filter fit
for the harmonic distortion in the electrical system. Table 19 shows all the
Rated Voltage
kVAR
Inductor XL
Maximum Current
Q Factor
Harmonic Current
PF Correction Existing PF
Desired PF
Load MVA
modified with a harmonic filter shall be simulated using the software to determine
93
whether the harmonic levels are mitigated to allowable levels. Table 18 shall also
Equipment/Facilities/Program
1. Equipment
specifically FLUKE 428-II would be used to measure the voltage distortion and current
distortion. The measuring instrument mainly consists of the power quality analyzer itself,
test leads, and AC Current clamps. The current clamps are put around the conductors per
phase, and oriented on the correct signal polarity. After this, the test leads are connected
to the conductors for voltage connections. The connection of the test leads starts with the
ground and then in succession with the neutral conductor, Phase A, B, and then C. When
that might result in significant workplace diseases and injuries. Contact with chemical,
radioactive, physical, electrical, mechanical, or other job hazards may cause these
wounds and illnesses. Items like gloves, safety goggles, shoes, earplugs or muffs, hard
hats, respirators, or coveralls, vests, and full body suits are examples of personal
94
Gloves are one such item of PPE, or personal protective equipment that is
essential. Through this, users can protect themselves from electric shocks and ensure their
safety. In the field of work, this helped to avoid all electrical risks. Additionally, these
there is a risk of exposure to electrical conductors that could possibly come into contact
with the head or where there is a risk of head injuries from falling objects [98].
2. Facilities
hundred rooms, including laboratories and offices. The campus’ electrical system is
determined through the electrical system one-line diagram, which would be vital in
determining the point of connections of the selected equipment that would be measured.
3. Program
The programs needed to conduct the study and for measuring the harmonics are
accessible for use by the researchers. The following applications would be used by the
95
3.1 Electrical Transient Analyzer Program or ETAP
industrial power systems may all be done using ETAP, which is the most complete
analysis platform available. ETAP is a high impact software that is utilized all over the
world and is produced in accordance with a recognized quality assurance program [99].
The researchers will construct a single line diagram of the campus through ETAP. The
corrective measure to reduce the harmonics of the school has should be employed using
monitoring, control, optimization, and automation. The most complete and integrated
suite of power system enterprise solutions, from modelling through operation, is provided
by ETAP software. ETAP provides a great interface for conducting thorough analysis on
electrical power systems. One of its many unique features is its connection with
combined with a thorough user manual that guides the user through any simulation-
related concerns [100]. See Appendix for the module of ETAP’s Harmonic Analysis.
to organize data and numbers using spreadsheets [101]. As one of the benefits of the
ETAP is its connection with this program, the researchers will utilize Microsoft Excel to
conveniently collect, analyze, and integrate all the data and results that the equipment
96
will generate. This would also be used in recording the harmonic values that would
The methodology of the experiment in this study involves obtaining data from an
the electrical system of the campus, a 3-phase power quality analyzer would be used to
obtain the data needed in assessing the potential harmonics. The measurement of the
potential harmonic distortion begins at the feeder panel on the secondary side of the
distribution transformer which supplies power for the entire university. This would then
be followed with the measurement of harmonic distortion at the main distribution panels
with the highest number of nonlinear loads. The number of nonlinear loads was obtained
from the DOE Inventory Form requested at the Environmental Management Unit (EMU)
Office – Alangilan. The data collection for the measurement of the potential harmonic
distortion shall be done within five (5) days with allocated recording of data every one
(1) second and integration period of fifteen (15) minutes. The measurement would be
conducted during the peak demand of the said loads to acquire accurate data.
Consecutively, harmonic distortion measurement would also be done using the Electrical
Transient Analysis Program (ETAP) to compare the two results. The electrical system
that would be used on the simulation shall be based on the system one-line diagram of the
the building shall be done based on the 2017 Philippine Distribution Code, specifically
97
Chapter 3 Section 2.4. The recommended limits given for the voltage and current
distortion shall be followed with the appropriate steps in using it. This assessment acts as
the treatment for the data obtained from the actual measurement of the harmonic
distortion and simulation of the harmonic analysis in the ETAP. Upon assessment, it shall
For the mitigation plan of the harmonic distortion in the electrical system of the
campus, the design of the plan shall be made appropriate for the existing specification of
the electrical system. The data collected from the ETAP simulation and actual
measurement would be used in completing the parameters needed in sizing the harmonic
filter. After sizing the harmonic filter, the application of the mitigation plan would be
simulated using ETAP and to determine and assess the level of harmonic distortion after
the application.
Budget Requirements
University – Alangilan Campus. The expenses associated with the materials, components,
and equipment that will be used are all listed in the budget requirements as seen on Table
20 below. It displays the quantity of each commodity along with its details, cost, and total
cost.
98
Table 20. Budget Requirements
(Php) (Php)
Power
Quality 20,000.0
4 day 3-Phase, FLUKE 438-II 5,000.00
Analyzer 0
Rental
University
Consultation of Harmonic
authorized personnel
Expected Output
99
With the nature of the study, its output is oriented towards the acquisition of data
regarding the harmonic distortion in the electrical system of Batangas State University –
Alangilan Campus. These data are expected to contribute to the existing knowledge
regarding the power quality of the campus, since harmonics is one of its components.
To signify the determination of the harmonic levels in the electrical system of the
campus, tables would be provided as an outcome of the study. This data could further be
used in assessing the power quality of the electrical system. With the harmonics being
measured by this study, the ease on the study of the system’s power quality would be
higher.
harmonic distortion in the electrical system of the campus. The design of the mitigation
plan may diminish the impermissible level of harmonic distortion that may have been
measured on the experiment or a plan that would anticipate the increase of harmonic
presented upon the end of the study to further expand the body of knowledge regarding
this concept.
100
Gantt Chart
Table 21 provides the detailed view of the Gantt Chart of the study. The table entails the contents of the study that are needed
to be accomplished discerned with appropriate deadlines. The Gantt Chart shall provide the timetable and visual representation of the
99
BIBLIOGRPAHY
[1] L. S, “Importance of electricity,” The Hindu, Mar. 08, 2010. Accessed: Oct. 08, 2022.
[Online]. Available:
https://www.thehindu.com/features/kids/Importance-of-electricity/article16544961.ece
[2] ECA, “Electrical system.” https://www.designingbuildings.co.uk/wiki/Electrical_system
(accessed Oct. 13, 2022).
[3] E. Hoade, “What is Power Quality? - Captech Power Quality Experts,” Captech.
https://captech.com.au/what-is-power-quality/ (accessed Oct. 13, 2022).
[4] D. Steiner, “Reliability 101: The Basics of Electrical Distribution System Reliability,” D.L.
Steiner, Inc. | Electrical Engineers | Arc Flash Specialists.
https://www.dlsteiner.com/blog/2012/12/21/reliability-101-the-basics-of-electrical-
distribution-system-reliability (accessed Oct. 13, 2022).
[5] K. Metin, H. Ceylan, E. Demirkesen, K. Canatan, and M. Hizli, “Problems in Electric
Systems Caused by Harmonics and Solution Proposals,” Eur. J. Eng. Technol. Res., vol. 6,
no. 1, pp. 137–141, Jan. 2021, doi: 10.24018/ejers.2021.6.1.2343.
[6] W. Storr, “Harmonics and Harmonic Frequency in AC Circuits,” Basic Electronics Tutorials,
Jun. 25, 2013. https://www.electronics-tutorials.ws/accircuits/harmonics.html (accessed
Oct. 13, 2022).
[7] “What’s The Difference Between Linear And Non-Linear Electrical Loads?”
https://www.riello-ups.co.uk/questions/39-what-s-the-difference-between-linear-and-
non-linear-electrical-loads (accessed Oct. 08, 2022).
[8] M. Anumaka, “Fundamentals of Reliability of Electric Power System and Equipment,” Int.
J. Eng. Sci. Technol. IJEST, vol. 3, Jun. 2011.
[9] MTEAdmin, “What causes harmonics? | Causes of harmonics in Electrical Systems | MTE
Corp,” MTE Corporation, Apr. 13, 2018.
https://www.mtecorp.com/blog/2018/04/13/what-causes-harmonics/ (accessed Oct. 13,
2022).
[10] “Harmonic symptoms | Effects of harmonics,” Eaton. https://www.eaton.com/us/en-
us/products/controls-drives-automation-sensors/harmonics/harmonic-symptoms---
effects-of-harmonics.html (accessed Oct. 13, 2022).
[11] power technologies associated, “total harmonic distortion effects in an electrical
system.”
[12] MTEAdmin, “Effects of Harmonics in Power System | Linear and Nonlinear Loads,” MTE
Corporation, Apr. 09, 2018. https://www.mtecorp.com/blog/2018/04/09/effects-of-
harmonics-in-power-system/ (accessed Oct. 13, 2022).
[13] “Harmonic symptoms | Effects of harmonics,” Eaton. https://www.eaton.com/us/en-
us/products/controls-drives-automation-sensors/harmonics/harmonic-symptoms---
effects-of-harmonics.html (accessed Oct. 08, 2022).
[14] “Causes and Effects of Harmonics in Electrical Power Systems.”
https://www.fluke.com/en-ph/learn/blog/power-quality/how-to-find-harmonics-in-
electrical-systems-2 (accessed Dec. 18, 2022).
[15] “Why the research question is so important,” Ingham Institute for Applied Medical
Research. https://inghaminstitute.org.au/resource/why-the-research-question-is-so-
important/ (accessed Sep. 18, 2022).
100
[16] A. H. Toledo, R. Flikkema, and L. H. Toledo-Pereyra, “Developing the Research
Hypothesis,” J. Invest. Surg., vol. 24, no. 5, pp. 191–194, Aug. 2011, doi:
10.3109/08941939.2011.609449.
[17] “This Month in Physics History.”
http://www.aps.org/publications/apsnews/200305/history.cfm (accessed Oct. 11, 2022).
[18] “The Reason for Using Alternating Current.” https://pwg.gsfc.nasa.gov/Electric/-E11-
reason.htm (accessed Oct. 11, 2022).
[19] Administrator, “AC Waveforms and Theory,” Electronics Hub, Jun. 11, 2015.
https://www.electronicshub.org/ac-waveforms-and-theory/ (accessed Oct. 11, 2022).
[20] J. R. Lucas, “Alternating Current Theory.” Nov. 2001. [Online]. Available:
https://uom.lk/sites/default/files/elect/files/EE201_ac_theory.pdf
[21] P. M. Donohue and S. Islam, “The Effect of Non-Sinusoidal Current Waveforms on Electro-
Mechanical & Solid State Overcurrent Relay Operation,” in 2009 IEEE Industry
Applications Society Annual Meeting, Oct. 2009, pp. 1–6. doi: 10.1109/IAS.2009.5324811.
[22] R. L. Boylestad, Introductory circuit analysis, Thirteenth edition. Boston: Pearson, 2016.
[23] “EE201_non_sinusoidal_part_1.pdf.” Accessed: Oct. 19, 2022. [Online]. Available:
https://uom.lk/sites/default/files/elect/files/EE201_non_sinusoidal_part_1.pdf
[24] D. Herres, “Basics of non-sinusoidal waveforms,” Test and Measurement Tips, Dec. 24,
2014. https://www.testandmeasurementtips.com/basics-non-sinusoidal-waveforms/
#:~:text=A%20non%2Dsinusoidal%20waveform%20is,time%20as%20the%20independent
%20variable.
[25] K. Michaels, “Fundamentals of Harmonics,” EC&M, Jun. 01, 1999.
https://www.ecmweb.com/content/article/20897096/fundamentals-of-harmonics
(accessed Oct. 18, 2022).
[26] C. P. Editor, “Harmonics in Power System | Electrical India Magazine.”
https://www.electricalindia.in/harmonics-in-power-system/ (accessed Nov. 03, 2022).
[27] Eaton, “What is nonlinear load?,” Eaton.
https://www.eaton.com/us/en-us/products/controls-drives-automation-sensors/
harmonics/harmonics-faq-video-library/what-is-a-non-liner-load.html
[28] Riello ups, “How do Linear and non-Linear Loads Differ?,” Riello ups- Reliable power for a
sustainable world. https://www.riello-ups.co.uk/questions/39-what-s-the-difference-
between-linear-and-non-linear-electrical-loads#:~:text=Non%2Dlinear%20loads%20draw
%20in,the%20loads%20connected%20to%20it.
[29] “Fundamental Frequency And Harmonics: What Are They? | Electrical4U,”
https://www.electrical4u.com/. https://www.electrical4u.com/fundamental-frequency-
and-harmonics/ (accessed Oct. 18, 2022).
[30] G. J. Wakileh, Power Systems Harmonics: Fundamentals, Analysis and Filter Design.
Berlin, Heidelberg: Springer Berlin Heidelberg, 2001. doi: 10.1007/978-3-662-04343-1.
[31] “Total Harmonic Distortion (THD) – What It Is & What It Does,” Generator Bible.
https://generatorbible.com/blog/what-is-thd/ (accessed Nov. 03, 2022).
[32] “Constructive Interference: Know Definition, Formula, Condition,” Testbook Learn, Sep.
08, 2022. https://testbook.com/learn/physics-constructive-interference/ (accessed Nov.
04, 2022).
[33] “Constructive and Destructive Interference.”
https://www.phys.uconn.edu/~gibson/Notes/Section5_2/Sec5_2.htm (accessed Nov. 04,
2022).
[34] K. Michaels, “Fundamentals of Harmonics,” EC & M, Jun. 01, 1999.
https://www.ecmweb.com/content/article/20897096/fundamentals-of-harmonics
101
[35] Pacific Gas and Electric Company, “Short Duration Voltage Sags can Cause Disruptions,”
Pacific Gas and Electric Company, Jun. 2000.
https://www.pge.com/includes/docs/pdfs/mybusiness/customerservice/energystatus/
powerquality/voltagesags.pdf
[36] Riello ups, “WHAT’S THE DIFFERENCE BETWEEN A VOLTAGE SAG AND A SURGE?,” Riello
Ups. https://www.riello-ups.com/questions/48-what-s-the-difference-between-a-
voltage-sag-and-a-surge
[37] Fluke, “What are voltage sags, dips, swells and transients?,” Fluke.
https://www.fluke.com/en-ph/learn/blog/power-quality/what-are-voltage-sags-dips-
swells-and-transients-2#:~:text=A%20transient%20voltage%20is%20a,up%20to%20a
%20few%20milliseconds.
[38] “HarmonicsInYourElecSystem.pdf.” Accessed: Oct. 08, 2022. [Online]. Available:
https://www.newark.com/pdfs/techarticles/eaton/Eaton_Technical_Articles/
UPS_Training/Powerware_Training/HarmonicsInYourElecSystem.pdf
[39] Harmonics in Electrical Power Distribution Systems, (Jun. 16, 2018). Accessed: Nov. 03,
2022. [Online Video]. Available: https://www.youtube.com/watch?v=NvuPlntsTpE
[40] A. Kusko and M. T. Thompson, Power quality in electrical systems. New York, NY:
McGraw-Hill, 2007.
[41] “Single-Phase Rectifier - an overview | ScienceDirect Topics.”
https://www.sciencedirect.com/topics/engineering/single-phase-rectifier (accessed Oct.
19, 2022).
[42] “Three Phase Bridge Rectifier - an overview | ScienceDirect Topics.”
https://www.sciencedirect.com/topics/engineering/three-phase-bridge-rectifier
(accessed Oct. 19, 2022).
[43] “High Frequency Ballast : Beam Lighting Engineering.”
http://beam-lighting.com/en/technicals/technical-information/high-frequency-ballast/,
http://beam-lighting.com/en/technicals/technical-information/high-frequency-ballast/
(accessed Oct. 19, 2022).
[44] F. C. De La Rosa, Harmonics and Power Systems, 0 ed. CRC Press, 2006. doi:
10.1201/9781420004519.
[45] “IEEE Recommended Practice for Conducting Harmonic Studies and Analysis of Industrial
and Commercial Power Systems,” IEEE. doi: 10.1109/IEEESTD.2018.8479357.
[46] “Power quality – IEEE 519-2022,” Comsys. https://comsys.se/our-adf-technology/power-
quality-ieee-519-2022/ (accessed Oct. 19, 2022).
[47] “Understanding Power Factor and Harmonics,” Automate.
https://www.automate.org/industry-insights/understanding-power-factor-and-
harmonics (accessed Nov. 11, 2022).
[48] “IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power
Systems,” IEEE. doi: 10.1109/IEEESTD.2014.6826459.
[49] S. Jain, “Power Quality,” in Modeling and Control of Power Electronics Converter System
for Power Quality Improvements, Elsevier, 2018, pp. 1–29. doi: 10.1016/B978-0-12-
814568-5.00001-6.
[50] T. M. Blooming and D. J. Carnovale, “Application of IEEE STD 519-1992 Harmonic Limits,”
in Conference Record of 2006 Annual Pulp and Paper Industry Technical Conference,
Appleton, WI, USA, 2006, pp. 1–9. doi: 10.1109/PAPCON.2006.1673767.
[51] Harmonics in Electrical Power Distribution Systems, (Jun. 16, 2018). Accessed: Nov. 04,
2022. [Online Video]. Available: https://www.youtube.com/watch?v=NvuPlntsTpE
102
[52] J. L. Naredo and J. A. Martinez-Velasco, “Introduction to Transient Analysis of Power
Systems,” POWER Syst. TRANSIENTS, p. 21.
[53] F. Forniels, “How to analyse Harmonic Problems?,” in PROCEDURE FOR THE STUDY AND
THE ANALYSIS OF HARMONIC DISTURBANCE, [Online]. Available:
https://circutor.de/docs/procedimientos_EN.pdf
[54] D. Fallows, S. Nuzzo, A. Costabeber, and M. Galea, “Harmonic reduction methods for
electrical generation: a review,” IET Gener. Transm. Distrib., vol. 12, no. 13, pp. 3107–
3113, Jul. 2018, doi: 10.1049/iet-gtd.2018.0008.
[55] S. Kumar and R. Ullah, “Harmonic Reduction Using Multilevel Inverter Concepts”,
Accessed: Oct. 19, 2022. [Online]. Available:
https://www.academia.edu/en/30707781/Harmonic_Reduction_Using_Multilevel_Invert
er_Concepts
[56] E.-E. E. Portal and Edvard, “Principles for Controlling Harmonics,” EEP - Electrical
Engineering Portal, Aug. 05, 2011. https://electrical-engineering-portal.com/principles-
for-controlling-harmonics (accessed Oct. 19, 2022).
[57] L. Motta and N. Faúndes, “Active / passive harmonic filters: Applications, challenges &
trends,” in 2016 17th International Conference on Harmonics and Quality of Power
(ICHQP), Oct. 2016, pp. 657–662. doi: 10.1109/ICHQP.2016.7783319.
[58] “Harmonic Analysis Software | EasyPower Electrical Software.”
https://www.easypower.com/index.php/products/features/harmonics (accessed Nov.
19, 2022).
[59] “Harmonic analysis,” Eaton. https://www.eaton.com/us/en-us/products/utility-grid-
solutions/software-modules/harmonic-analysis.html (accessed Nov. 19, 2022).
[60] “Harmonic Analysis Software | Power Quality Software | Harmonics.”
https://etap.com/product/harmonic-analysis-software (accessed Nov. 19, 2022).
[61] HBK, “Definition of a Power Analyzer.” https://www.hbm.com/en/8099/what-is-a-power-
analyzer-definition/
[62] Department of Electrical and Electronic Engineering, Ahsanullah University of Science and
Technology, Dhaka, Bangladesh and I. Ahmed, “An Overview of Harmonic Sources in
Power System,” IOSR J. Electr. Electron. Eng., vol. 7, no. 3, pp. 01–03, 2013, doi:
10.9790/1676-0730103.
[63] Y. N. Chang, C. S. Moo, and J. C. Jeng, “Harmonic analysis of fluorescent lamps with
electromagnetic ballasts,” in IEEE Region 10 International Conference on Computers,
Communications and Automation Proceedings of TENCON ’93, Oct. 1993, vol. 5, pp. 499–
502 vol.5. doi: 10.1109/TENCON.1993.320691.
[64] K. Mohamed, H. Shareef, and A. Mohamed, “HARMONICS FROM COMPACT
FLUORESCENT LAMPS,” presented at the IEEE Transactions on Industry Applications - IEEE
TRANS IND APPL, Sep. 2010, vol. 29.
[65] T. Hoevenaars, “A New Solution for Harmonics Generated by Variable Speed Drives,” p. 4.
[66] R. P. Stratford, “Rectifier Harmonics in Power Systems,” IEEE Trans. Ind. Appl., vol. IA-16,
no. 2, pp. 271–276, Mar. 1980, doi: 10.1109/TIA.1980.4503781.
[67] “Different Types of Rectifiers - Blog,” Carritech Telecommunications.
https://www.carritech.com/news/rectifier-types/ (accessed Nov. 06, 2022).
[68] H. Anga, S. Gite, S. Bhave, S. Divya, and Fr.C.Rodrigues Institute of Technology, “Power
Factor and Harmonic Analysis in Single Phase AC to DC Converter,” Int. J. Eng. Res., vol.
V4, no. 04, p. IJERTV4IS040599, Apr. 2015, doi: 10.17577/IJERTV4IS040599.
[69] “What is Rectifier? - Know its uses and applications,” BYJUS.
https://byjus.com/physics/uses-of-rectifier/ (accessed Nov. 06, 2022).
103
[70] T. Agarwal, “Capacitor Filter using Half Wave and Full Wave Rectifiers,” ElProCus -
Electronic Projects for Engineering Students, Feb. 12, 2019.
https://www.elprocus.com/half-wave-and-full-wave-rectifier-with-capacitor-filter/
(accessed Nov. 06, 2022).
[71] Aktif, “Problems Caused by Harmonics in Electrical Plants,” Aktif, Feb. 02, 2021.
https://aktif.net/en/problems-caused-by-harmonics-in-electrical-plants/ (accessed Nov.
06, 2022).
[72] ABB, “Harmonics_in_HVAC_applications_EN_REV A.,” 2018, p. 16.
[73] ElectricalEngineering Portal, “EssentialBasics of Total Harmonic Distortion (THD).”
https://electrical-engineering-portal.com/essential-basics-of-total-harmonic-distortion-
thd#:~:text=Importance%20of%20Mitigating%20THD&text=Computers%20and%20allied
%20equipment%2C%20such,3%25%20of%20the%20fundamental%20voltage.
[74] M. H. Shwehdi and F. S. AL-Ismail, “Investigating University Personnel Computers (PC)
Produced Harmonics Effect on Line Currents,” King Fahd University, Middle East, 2012.
[Online]. Available: https://icrepq.com/icrepq'12/651-shwehdi.pdf
[75] T. Key, “Diagnosing Power Quality-Related Computer Problems,” IEEExplore.
https://ieeexplore.ieee.org/document/4503677
[76] U. Bajpai et al., “Harmonics Assessment in Real Time Printing Industry,” Indian Institute
of Technology Delhi, 2019. [Online]. Available:
https://www.researchgate.net/publication/340665523_Harmonics_Assessment_in_Real_
Time_Printing_Industry
[77] V. E. Idemne et al., “Level of Harmonics Produced by Variable Frequency Drive Controller
Used in Induction Type Water Pump Motor.”
https://repository.cpu.edu.ph/bitstream/handle/20.500.12852/21/ScientiaetFides_Inde
mne.pdf?sequence=1&isAllowed=y
[78] J. Zhu, D. Xie, F. Wang, and T. Cao, “Study on the Harmonics of Switching Power Supply,”
2012. [Online]. Available: https://core.ac.uk/download/pdf/82654033.pdf
[79] K. Nikum, R. Saxena, and A. Wagh, “Effect on power quality by large penetration of
household non linear load,” in 2016 IEEE 1st International Conference on Power
Electronics, Intelligent Control and Energy Systems (ICPEICES), Delhi, India, Jul. 2016, pp.
1–5. doi: 10.1109/ICPEICES.2016.7853241.
[80] E. Králiková, “Distortion Power Measurements in Education,” p. 4, 2013.
[81] S. R. and D. D., “A Review of Harmonics Detection and Measurement in Power System,”
Int. J. Comput. Appl., vol. 143, no. 10, pp. 42–45, Jun. 2016, doi: 10.5120/ijca2016910394.
[82] L. Asiminoaei, F. Blaabjerg, and S. Hansen, “Evaluation of harmonic detection methods
for active power filter applications,” Twent. Annu. IEEE Appl. Power Electron. Conf. Expo.
2005 APEC 2005 Vol1, pp. 635–641, 2005.
[83] S. R. Durdhavale and D. D. Ahire, “A Review of Harmonics Detection and Measurement in
Power System,” Int. J. Comput. Appl., vol. 143, no. 10, pp. 42–45, Jun. 2016.
[84] R. B. Timens, F. J. K. Buesink, V. Cuk, J. F. G. Cobben, W. L. Kling, and F. B. J. Leferink,
“High harmonic distortion in a new building due to a multitude of electronic equipment,”
in 2011 IEEE International Symposium on Electromagnetic Compatibility, Long Beach, CA,
USA, Aug. 2011, pp. 393–398. doi: 10.1109/ISEMC.2011.6038343.
[85] habusadeh,
[86] M. E. Balci, D. Ozturk, O. Karacasu, and M. H. Hocaoglu, “Experimental verification of
harmonic load models,” in 2008 43rd International Universities Power Engineering
Conference, Sep. 2008, pp. 1–4. doi: 10.1109/UPEC.2008.4651607.
104
[87] J. Aswal and Y. Pal, “Harmonic Mitigation in a 3-Phase, 3-Wire System Using Hybrid
Filter,” in 2018 2nd International Conference on Trends in Electronics and Informatics
(ICOEI), Tirunelveli, May 2018, pp. 743–746. doi: 10.1109/ICOEI.2018.8553776.
[88] M. D. Faraby, O. Penangsang, R. S. Wibowo, S. Sofyan, A. R. Idris, and A. Asri, “Harmonic
Mitigation Through Enhancement Network Reconfiguration Technique on Coordinated
Planning Using Hybrid Particle Swarm Optimization in Radial Distribution System,” in
2021 3rd International Conference on Electrical, Control and Instrumentation Engineering
(ICECIE), Nov. 2021, pp. 1–6. doi: 10.1109/ICECIE52348.2021.9664728.
[89] vijay mohan Rachabattuni, “Capacitor Banks and its effects on the power system with
high harmonic loads.,” Apr. 08, 2018.
[90] L. Cipcigan et al., “Mitigation of Capacitor Bank Energization Harmonic Transients,” in
2006 IEEE/PES Transmission & Distribution Conference and Exposition: Latin America,
Aug. 2006, pp. 1–5. doi: 10.1109/TDCLA.2006.311440.
[91] N. Eghtedarpour, M. A. Karimi, and M. Tavakoli, “Harmonic resonance in power systems -
a documented case,” in 2014 16th International Conference on Harmonics and Quality of
Power (ICHQP), May 2014, pp. 857–861. doi: 10.1109/ICHQP.2014.6842806.
[92] R. Samikannu, R. Rohini, V. Sampath Kumar, and V. Mezhuyev, “Design and Development
of Shunt Active Filter Using MATLAB for Minimization of Harmonics,” Int. J. Eng. Technol.,
vol. 7, no. 3.10, p. 179, Jul. 2018, doi: 10.14419/ijet.v7i3.10.15655.
[93] W. G. Camp, “Formulating and Evaluating Theoretical Frameworks for Career and
Technical Education Research,” J. Vocat. Educ. Res., vol. 26, no. 1, pp. 4–25, Jan. 2001,
doi: 10.5328/JVER26.1.4.
[94] C. Kivunja and A. B. Kuyini, “Understanding and Applying Research Paradigms in
Educational Contexts,” Int. J. High. Educ., vol. 6, no. 5, p. 26, Sep. 2017, doi:
10.5430/ijhe.v6n5p26.
[95] S. F. Mekhamer, A. Y. Abdelaziz, and S. M. Ismael, “Design Practices in Harmonic Analysis
Studies Applied to Industrial Electrical Power Systems,” Eng. Technol. Appl. Sci. Res., vol.
3, no. 4, pp. 467–472, Aug. 2013, doi: 10.48084/etasr.309.
[96] “Personal Protective Equipment - Overview | Occupational Safety and Health
Administration.” https://www.osha.gov/personal-protective-equipment (accessed Nov.
12, 2022).
[97] A. Refersion, “Best Disposable Gloves for Electrical Work,” Gloves.com, 00:01 500.
https://www.gloves.com/blogs/news/best-disposable-gloves-for-electrical-work
(accessed Nov. 12, 2022).
[98] “Home | Occupational Safety and Health Administration.” https://www.osha.gov/
(accessed Nov. 12, 2022).
[99] E.-E. E. Portal, “ETAP | EEP,” EEP - Electrical Engineering Portal. https://electrical-
engineering-portal.com/download-center/electrical-software/etap (accessed Nov. 12,
2022).
[100] M. Sarwar, “Introduction to ETAP for Power System Modeling & Simulations,” EE Power
School, Feb. 02, 2018. https://www.eepowerschool.com/tutorials/etap-for-power-
system-modeling-simulations/ (accessed Nov. 12, 2022).
[101] “Excel Definition,” Corporate Finance Institute.
https://corporatefinanceinstitute.com/resources/excel/excel-definition-overview/
(accessed Nov. 12, 2022).
105
106