N2XSEBY/NA2XSEBY

3.6/6(7.2) kV
IEC 60502-2

Copper/Aluminium conductor, XLPE insulated,


Copper tape screened,
Galvanized double steel tape armoured,
PVC/PE sheathed cable
N2XSEBY/NA2XSEBY
3.6/6(7.2) kV
IEC 60502-2

N2XSEYBYCopper/Aluminium
/ NA2XSYBY conductor, XLPE insulated,
3.6/6(7.2) kV Copper tape screened,
SPLN 43-5 / Galvanized
IEC 60502-2double steel tape armoured,
Copper / Aluminium conductor, XLPE insulated,
PVC/PE sheathed cable
with or without swellable tape, Copper wire / tape screened,
Glavanized steel tape armoured, PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness
Insulation diameter (approx)
mm
mm
2.5
12.5
2.5
13.5
2.5
14.7
2.5
N2XSEYBY / NA2XSYBY
16.3
2.5
18.1
2.5
19.5
2.5
20.7
2.5
22.7
2.6
24.8
2.8
27.9
3.0
31.9
Nominal tape armour thickness
Nominal outer sheath thickness
mm
mm
0.5
2.2
0.5
2.3
0.5
2.4
0.5
2.5
0.5
2.6
3.6/6(7.2) kV
0.5
2.7
0.5
2.8
0.5
2.9
0.5
3.1
0.5
3.3
0.8
3.6
Overall cable diameter (approx) mm 39 42 45 49 SPLN 43-5 / IEC 60502-2
53 53 59 64 70 76 85
CU 2,800 3,200 3,800 4,700 5,800 6,800 7,900 9,400 11,700 14,100 18,300
Cable net weight ( approx)
AL
Kg/Km
2,300 2,600 Copper / Aluminium conductor, XLPE insulated,
2,900 3,400 4,000 4,600 5,100 5,900 7,000 8,300 10,900
Standard length per-reel
Minimum bending radius
m 500 with or without swellable tape, Copper wire / tape screene
500 500 500 500 500 500 500 350 350 350
mm 340 370 400 440 490 520 550 600 670 730 820
Max. DC conductor resistance CU 0.727 0.524
Glavanized steel tape armoured, PVC/PE sheathed cab
0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
Ω/Km
at 20 ⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Min. insulation resistance at 20 ⁰C DIMENSIONAL
MΩ.Km AND ELECTRICAL
900 800 DATA
700 600 500 500 500 400 400 400 400
Capacitance per phase µF/Km
Nominal 0.191
cross-sectional 0.216
area 0.240 0.279
mm
2 0.318
25 0.349
35 0.376
50 0.41970 0.45995 0.481
120 0.511
150 185
Inductance per phase mH/km diameter
Conductor 0.322(approx)
0.308 0.298 0.284
mm 0.273
6.05 0.266
7.1 0.261
8.25 0.254
9.9 0.249
11.7 0.246
13.1 0.243
14.3 16.3
Max.short circuit current of CU Nominal insulation
3.73thickness
5.18 7.36 10.26
mm 13.88
2.5 17.49
2.5 21.81
2.5 26.86
2.5 34.78
2.5 43.41
2.5 57.79
2.5 2.5
conductor kA/sec diameter
AL Insulation 2.49(approx)
3.45 4.89 6.81
mm 9.19
12.5 11.58
13.5 14.43
14.7 17.76
16.3 22.98
18.1 28.67
19.5 38.14
20.7 22.7
Max.short circuit current of screen 1.90 thickness
Nominal tape armour 2.05 2.21 2.44
mm 2.69
0.5 2.89
0.5 3.05
0.5 3.330.5 3.70
0.5 4.06
0.5 4.51
0.5 0.5
CU Nominal outer sheath
139 thickness
172 205 256
mm 3122.2 3592.3 4092.4 4682.5 5522.6 6272.7 7582.8 2.9
Maximum current in air
AL Overall cable diameter
102 132
(approx) 159 198
mm 23939 27742 31445 36049 42053 47953 59159 64
carrying A
o CU 132 170 201CU 245 294
2,800 334
3,200 375
3,800 424
4,700 492
5,800 552
6,800 623
7,900 9,400
capacity at 30 C in ground
AL Cable net weight101( approx) 130 155AL Kg/Km
190 228
2,300 259
2,600 291
2,900 330
3,400 384
4,000 412
4,600 493
5,100 5,900
AC test voltage kV/5 min
Standard length per-reel m 12.5
500 (IEC) 500
, 9 (SPLN) 500 500 500 500 500 500
Note : This is only general information. ForMinimum
other specific
bendingrequirement,
radius please contact our
mmmarketing.
340 370 400 440 490 520 550 600
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099
Ω/Km
at 20 ⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.16
Min. insulation resistance at 20 ⁰C MΩ.Km 900 800 700 600 500 500 500 400
Capacitance per phase µF/Km 0.191 0.216 0.240 0.279 0.318 0.349 0.376 0.41
Inductance per phase mH/km 0.322 0.308 0.298 0.284 0.273 0.266 0.261 0.25
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.8
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.7
Max.short circuit current of screen 1.90 2.05 2.21 2.44 2.69 2.89 3.05 3.33
CU 139 172 205 256 312 359 409 468
Maximum current in air
AL26 102 132 159 198 239 277 314 360
carrying A
o CU 132 170 201 245 294 334 375 424
capacity at 30 C in ground
N2XSEBY/NA2XSEBY
6/10(12) kV
IEC 60502-2

Copper/Aluminium conductor,
XLPE insulated,
Copper tape screened,
Galvanized double steel tape armoured,
PVC/PE sheathed cable

N2XSEBY/NA2XSEBY
6/10(12) kV
IEC 60502-2
N2XSEYBY / NA2XSEYBY
Copper/Aluminium conductor,
6/10(12) kV
XLPE insulated,
SPLN 43-5 / IEC 60502-2 Copper tape screened,
Galvanized
Copper / Aluminium conductor, XLPEdouble steel tape armoured,
insulated,
PVC/PE
with or without swellable, Copper wire / tape sheathed
screened, cable
Galvanized steel tape armoured, PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
Insulation diameter (approx) mm 14.3 15.3 16.5 18.1 19.9 21.3 22.5 24.5 26.9 29.1 31.9
Nominal tape armour thickness mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8
Nominal outer sheath thickness mm 2.3 2.4 2.5 2.6 2.8 2.9 3.0 3.1 3.3 3.4 3.7
Overall cable diameter (approx)

Cable net weight ( approx)


CU
mm

Kg/Km
44
3,200
46
3,700
49
4,300 N2XSEYBY / NA2XSEYBY
53
5,200
57
6,400
61
7,400
64
8,500
68
10,000
74
12,300
79
14,600
87
18,700

Standard length per-reel


AL
m
2,700
500
3,000
500
3,400
500
3,900
500
4,600
500
6/10(12) kV
5,200
500
5,700
500
6,500
500
7,600
350
8,800
350
11,300
350
Minimum bending radius
Max. DC conductor resistance CU
mm 380
0.727
400
0.524
430
0.387
SPLN 43-5 / IEC 60502-2
470
0.268
520
0.193
560
0.153
590
0.124
630
0.0991
700
0.0754
750
0.0601
830
0.0470
Ω/Km
at
at20
20oC
⁰C AL 1.20 Copper / Aluminium conductor, XLPE insulated,
0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Min. insulation resistance at 20 ⁰C MΩ.Km 1,100 1,000 900 800 700 600 600 500 500 400 400
Capacitance per phase µF/Km 0.161
with or without swellable, Copper wire / tape screened,
0.181 0.200 0.230 0.261 0.286 0.306 0.341 0.382 0.420 0.467
Inductance per phase mH/km 0.346 Galvanized steel tape armoured, PVC/PE sheathed cable
0.331 0.319 0.303 0.291 0.283 0.277 0.269 0.260 0.254 0.248
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.26 22.98 28.67 38.14
DIMENSIONAL AND ELECTRICAL DATA
Max.short circuit current of screen 2.15 2.61 2.77 3.00 3.25 3.44 3.61 3.89 4.23 4.53 4.92
2
Nominal
CU cross-sectional area
134 173 206mm 257 25 313 35 360 50 410 70 469 95 553120 628150 789185 240
Maximum current in air Conductor diameter (approx)
AL 103 133 160mm 1996.05 2407.1 2788.25 3159.9 32111.7 42113.1 48014.3 59216.3 18.2
carrying A
o
Nominal
CU insulation thickness
133 171 202mm 2463.4 2953.4 3353.4 3763.4 4253.4 4933.4 5533.4 6243.4 3.4
capacity at 30 C in ground Insulation diameter (approx)
AL 102 131 156mm 19114.3 22915.3 26016.5 29218.1 33119.9 38521.3 41322.5 49424.5 26.9
AC test voltage Nominal tape armour
kV/5 min thickness mm 0.5 0.5(IEC) , 150.5
21 (SPLN) 0.5 0.5 0.5 0.5 0.5 0.5
Nominal outer sheath thickness mm 2.3 2.4 2.5 2.6 2.8 2.9 3.0 3.1 3.3
Note : This is only general information. For other specific requirement, please contact our marketing.
Overall cable diameter (approx) mm 44 46 49 53 57 61 64 68 74
CU 3,200 3,700 4,300 5,200 6,400 7,400 8,500 10,000 12,300
Cable net weight ( approx) Kg/Km
AL 2,700 3,000 3,400 3,900 4,600 5,200 5,700 6,500 7,600
Standard length per-reel m 500 500 500 500 500 500 500 500 350
Minimum bending radius mm 380 400 430 470 520 560 590 630 700
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754
Ω/Km
at
at20
20oC
⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125
Min. insulation resistance at 20 ⁰C MΩ.Km 1,100 1,000 900 800 700 600 600 500 500
Capacitance per phase µF/Km 0.161 0.181 0.200 0.230 0.261 0.286 0.306 0.341 0.382
Inductance per phase mH/km 27 0.346 0.331 0.319 0.303 0.291 0.283 0.277 0.269 0.260
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78
N2XSEBY/NA2XSEBY
8.7/15(17.5) kV
IEC 60502-2

Copper/Aluminium conductor, XLPE insulated,


Copper tape screened,
Galvanized double steel tape armoured,
PVC/PE sheathed cable

N2XSEBY/NA2XSEBY
8.7/15(17.5) kV
IEC 60502-2
N2XSEYBY / NA2XSEBY
Copper/Aluminium
8.7/15(17.5) kV conductor, XLPE insulated,
Copper tape screened,
SPLN 43-5 / Galvanized
IEC 60502-2double steel tape armoured,
Copper / Aluminium conductor, XLPE insulated,
PVC/PE sheathed cable
with or without swellable tape, Copper wire / tape screened,
Galvanized steel tape armoured, PVC/PE sheathed cable

DIMENSIONAL AND ELECTRICAL DATA 3 CORES


2
Nominal cross-sectional area mm 25 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 6.05 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
Insulation diameter (approx) mm 16.5 17.5 18.7 20.3 22.1 23.5 24.7 25.7 29.1 31.3 34.1
Nominal tape armour thickness
Nominal outer sheath thickness
mm
mm
0.5
2.5
0.5
2.6
0.5
2.7 N2XSEYBY / NA2XSEBY
0.5
2.8
0.5
2.9
0.5
3.0
0.5
3.1
0.5
3.3
0.5
3.4
0.8
3.6
0.8
3.9
Overall cable diameter (approx)
CU
mm 49
3,800
51
4,300
54
4,900
58
5,900
8.7/15(17.5) kV
62
7,100
66
8,100
69
9,200
74
10,900
79
13,100
86
16,400
93
19,700
Cable net weight ( approx)
AL
Kg/Km
3,300 3,600 4,000 SPLN 43-5 / IEC 60502-2
4,600 5,300 5,900 6,400 7,400 8,500 10,600 12,300
Standard length per-reel m 500 500 500 500 500 500 350 350 350 350 350
Minimum bending radius mm 410 Copper / Aluminium
440 470 550 conductor, XLPE insulated,
510
590 630 680 780 800 880
Max. DC conductor resistance
at
CU
Ω/Km
0.727
with or without swellable tape, 0.124
0.524 0.387 0.268 0.193 0.153
Copper
0.0991
wire / tape
0.0754 0.0601
screened,
0.0470
at20
20oC
⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Min. insulation resistance at 20 ⁰C MΩ.Km 1,300 Galvanized
1,200 1,100 steel900tape 800
1,000 armoured,
700 PVC/PE
700 600 sheathed
600 cable
500
Capacitance per phase µF/Km 0.138 0.154 0.170 0.193 0.218 0.238 0.254 0.281 0.314 0.344 0.382
Inductance per phase mH/km 0.372 0.355 0.341 0.324 0.310 0.301 0.294 0.285 0.275 0.268 0.261
DIMENSIONAL AND ELECTRICAL DATA
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79
2
conductor Nominal
AL cross-sectional
kA/sec area
2.49 3.45 4.89mm 6.81 25 9.19 35 11.5850 14.4370 17.7695 22.98120 28.67150 38.14185 24
Max.short circuit current of screen Conductor diameter (approx)
2.46 2.61 2.77mm 3.006.05 3.257.1 3.448.25 3.619.9 3.8911.7 4.2313.1 4.5314.3 4.9216.3 18
Nominal
CU insulation thickness
134 173 206mm 257 4.5 313 4.5 360 4.5 410 4.5 469 4.5 553 4.5 629 4.5 760 4.5 4.
Maximum current in air Insulation diameter (approx)
AL 103 199 161mm 20416.5 24517.5 28218.7 31920.3 36522.1 42523.5 48124.7 59325.7 29
carrying A
o
Nominal
CU tape armour thickness
132 171 202mm 246 0.5 295 0.5 335 0.5 376 0.5 425 0.5 492 0.5 554 0.5 625 0.5 0.
capacity at 30 C in ground Nominal outer sheath thickness
AL 102 132 154mm 186 2.5 223 2.6 255 2.7 283 2.8 321 2.9 372 3.0 414 3.1 495 3.3 3.
AC test voltage Overall cable diameter
kV/5 min (approx) mm 49 51(IEC) , 2254(SPLN) 58
30.5 62 66 69 74 7
CU 3,800 4,300 4,900 5,900 7,100 8,100 9,200 10,900 13,
Note : This is only general information. For other specific
Cable net weight ( approx)requirement, please contact
Kg/Km our marketing.
AL 3,300 3,600 4,000 4,600 5,300 5,900 6,400 7,400 8,
Standard length per-reel m 500 500 500 500 500 500 350 350 35
Minimum bending radius mm 410 440 470 510 550 590 630 680 78
Max. DC conductor resistance CU 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.07
Ω/Km
at
at20
20oC
⁰C AL 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.1
Min. insulation resistance at 20 ⁰C MΩ.Km 1,300 1,200 1,100 1,000 900 800 700 700 60
Capacitance per phase µF/Km 0.138 0.154 0.170 0.193 0.218 0.238 0.254 0.281 0.3
Inductance per phase mH/km 0.372 0.355 0.341 0.324 0.310 0.301 0.294 0.285 0.2
Max.short circuit current of CU 3.73 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.
conductor AL kA/sec 2.49 3.45 4.89 6.81 9.19 11.58 14.43 17.76 22.
28
Max.short circuit current of screen 2.46 2.61 2.77 3.00 3.25 3.44 3.61 3.89 4.2
CU 134 173 206 257 313 360 410 469 55
N2XSEBY/NA2XSEYBY
12/20(24) kV
SPLN 43-5/IEC 60502-2

Copper/Aluminium conductor, XLPE insulated,


with or without water sealing,
Copper wire screened,
Galvanized double steel tape armoured,
PVC/PE sheathed cable

N2XSEBY/NA2XSEYBY
12/20(24) kV
SPLN 43-5/IEC 60502-2
N2XSEYBY / NA2XSEYBY
Copper/Aluminium
12/20(24) kV conductor, XLPE insulated,
with or without water sealing,
SPLN 43-5 / IEC 60502-2
Copper wire screened,
Copper / Aluminium conductor,
GalvanizedXLPE insulated,
double steel tape armoured,
with or without swellable tape, Copper wire / tape
PVC/PE sheathed screened,
cable
Galvanized steel tape armoured, PVC/PE sheathed cable

DIMENSIONAL AND ELECTRICAL DATA 3 CORES


2
Nominal cross-sectional area mm 35 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Insulation diameter (approx) mm 19.7 20.9 22.5 24.3 25.7 26.9 28.9 31.3 33.5 36.3
Nominal tape armour thickness mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8 0.8 0.8
Nominal outer sheath thickness mm 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.6 3.8 4.0
Overall cable diameter (approx)
CU
mm 57
4,900
60
5,600
64
6,600
N2XSEYBY / NA2XSEYBY
68
7,800
71
8,900
74
10,100
79
11,700
86
14,900
91
17,400
98
20,800
Cable net weight ( approx)
AL
Kg/Km
4,200 4,700 5,300 6,000 12/20(24) kV
6,600 7,200 8,200 10,200 11,600 13,400

SPLN 43-5 / IEC 60502-2


Standard length per-reel m 500 500 500 500 350 350 350 300 300 300
Minimum bending radius mm 480 510 550 600 630 660 720 790 840 910
Max. DC conductor resistance
at
at20
20oC
⁰C
CU
AL
Ω/Km
0.524
0.868
0.387
0.641
Copper / Aluminium conductor, XLPE insulated,
0.268
0.443
0.193
0.320
0.153
0.253
0.124
0.206
0.0991
0.164
0.0754
0.125
0.0601
0.100
0.0470
0.0778
Min. insulation resistance at 20 ⁰C MΩ.Km 1,400 with or without swellable tape, Copper wire / tape screene
1,300 1,100 1,000 900 900 800 700 700 600
Capacitance per phase µF/Km 0.136 0.149 0.169 0.190 0.206 0.220 0.243 0.270 0.294 0.326
Inductance per phase mH/km 0.377
Galvanized steel tape armoured, PVC/PE sheathed cab
0.362 0.344 0.328 0.318 0.310 0.300 0.289 0.281 0.273
Max.short circuit current of CU 5.18 7.36 10.26 13.88 17.49 21.81 26.86 34.78 43.41 57.79
conductor DIMENSIONAL
AL kA/secAND ELECTRICAL
3.45 4.89 DATA6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.14
Max.short circuit current of screen 2.77 2.92 3.14 2 3.38 3.57 4.66 3.99 4.31 4.60 6.21
Nominal cross-sectional area mm 35 50 70 95 120 150 185 240
CU 173 206 257 313 360 410 469 553 629 760
Maximum current in air Conductor diameter (approx) mm 7.1 8.25 9.9 11.7 13.1 14.3 16.3 18.
AL 139 161 199 242 280 318 365 425 481 593
carrying Nominal insulation
A thickness mm 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
o CU 171 202 246 295 335 376 425 492 554 625
capacity at 30 C in ground Insulation diameter (approx) mm 19.7 20.9 22.5 24.3 25.7 26.9 28.9 31.
AL 132 154 191 228 260 292 331 385 437 495
Nominal tape armour thickness mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.8
AC test voltage kV/5 min 42 (IEC) , 30(SPLN)
Nominal outer sheath thickness mm 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.6
Note : This is only general information. For other
Overall cablespecific
diameterrequirement,
(approx) please contact ourmm marketing.57 60 64 68 71 74 79 86
CU 4,900 5,600 6,600 7,800 8,900 10,100 11,700 14,9
Cable net weight ( approx) Kg/Km
AL 4,200 4,700 5,300 6,000 6,600 7,200 8,200 10,2
Standard length per-reel m 500 500 500 500 350 350 350 300
Minimum bending radius mm 480 510 550 600 630 660 720 790
Max. DC conductor resistance CU 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.07
Ω/Km
at
at20
20oC
⁰C AL 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.12
Min. insulation resistance at 20 ⁰C 29 MΩ.Km 1,400 1,300 1,100 1,000 900 900 800 700
Capacitance per phase µF/Km 0.136 0.149 0.169 0.190 0.206 0.220 0.243 0.27
Inductance per phase mH/km 0.377 0.362 0.344 0.328 0.318 0.310 0.300 0.28
N2XSEBY/NA2XSEBY
18/30(36) kV
IEC 60502-2
Copper/Aluminium conductor,
XLPE insulated, Copper tape screened,
Galvanized double steel tape armoured,
PVC/PE sheathed cable

N2XSEBY/NA2XSEBY
18/30(36) kV
N2XSEYBY / NA2XSEBY
IEC 60502-2
18/30(36)Copper/Aluminium
kV conductor,
IEC 60502-2
XLPE insulated, Copper tape screened,
Galvanized
Copper / Aluminium double
conductor, XLPEsteel tape armoured,
insulated,
PVC/PE sheathed cable
Copper wire / tape screened, Galvanized steel tape armoured,
PVC/PE sheathed cable
DIMENSIONAL AND ELECTRICAL DATA 3 CORES
2
Nominal cross-sectional area mm 50 70 95 120 150 185 240 300 400
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3 18.2 20.9 23.7
Nominal insulation thickness mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Insulation diameter (approx) mm 25.9 27.5 29.3 30.7 31.9 33.9 36.3 38.5 41.3

N2XSEYBY / NA2XSEBY
Nominal tape armour thickness mm 0.5 0.5 0.5 0.8 0.8 0.8 0.8 0.8 0.8
Nominal outer sheath thickness mm 3.2 3.3 3.5 3.6 3.7 3.9 4.0 4.2 4.4
Overall cable diameter (approx)

Cable net weight ( approx)


CU
mm

Kg/Km
72
7,300
75
8,400
80
9,700 18/30(36) kV
84
11,700
87
12,900
92
14,800
98
17,300
103
20,000
110
23,500

Standard length per-reel


AL
m
6,400
500
7,100
500
7,900
500
IEC 60502-2
9,400
350
10,100
350
11,300
350
12,600
300
14,100
300
16,000
300
Minimum bending radius mm Copper / Aluminium conductor, XLPE insulated,
600 640 690 730 760 810 880 930 1,000
Max. DC conductor resistance
at
CU Copper wire / tape screened, Galvanized steel tape armoured
Ω/Km
0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
at20
20oC⁰C AL 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
Min. insulation resistance at 20 ⁰ C MΩ.Km PVC/PE sheathed cable
1,600 1,500 1,300 1,200 1,200 1,100 1,000 900 800
Capacitance per phase µF/Km 0.121 0.136 0.151 0.163 0.173 0.190 0.209 0.227 0.250
Inductance per phase DIMENSIONAL AND ELECTRICAL
mH/km 0.402 DATA 0.381 0.363 0.352 0.343 0.330 0.317 0.308 0.297
Max.short circuit current of Nominal cross-sectional
CU 7.36 10.26 13.88
area mm
2
5017.49 7021.81 9526.86 12034.78 15043.41 18557.79 240
conductor AL kA/sec 4.89 6.81 9.19 11.58 14.43 17.76 22.98 28.67 38.14
Conductor diameter (approx) mm 8.25 9.9 11.7 13.1 14.3 16.3 18.2
Max.short circuit current of screen 3.77 4.00 4.25 4.45 4.62 4.9 559 5.54 5.93
Nominal insulation thickness mm 8.0 8.0 8.0 8.0 8.0 8.0 8.0
CU 207 258 314 361 411 470 554 630 766
Maximum current inInsulation
air diameter (approx) mm 25.9 27.5 29.3 30.7 31.9 33.9 36.3
AL 162 205 246 283 320 365 426 482 594
carrying Nominal tape armour thickness
A mm 0.5 0.5 0.5 0.8 0.8 0.8 0.8
o CU 203 247 296 336 377 426 483 555 626
capacity at 30 C Nominal outer sheath thickness
in ground mm 3.2 3.3 3.5 3.6 3.7 3.9 4.0
AL 155 187 224 256 284 322 373 415 496
Overall cable diameter (approx) mm 72 75 80 84 87 92 98
AC test voltage kV/5 min 63
CU 7,300 8,400 9,700 11,700 12,900 14,800 17,300
Cable net
Note : This is only general information. weight
For ( approx)requirement, please contact
other specific Kg/Km
our marketing.
AL 6,400 7,100 7,900 9,400 10,100 11,300 12,600
Standard length per-reel m 500 500 500 350 350 350 300
Minimum bending radius mm 600 640 690 730 760 810 880
Max. DC conductor resistance CU 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754
Ω/Km
at
at20
20oC
⁰C AL 0.641 0.443 0.320 0.253 0.206 0.164 0.125
Min. insulation resistance at 20 ⁰ C MΩ.Km
30 1,600 1,500 1,300 1,200 1,200 1,100 1,000
Capacitance per phase µF/Km 0.121 0.136 0.151 0.163 0.173 0.190 0.209
Inductance per phase mH/km 0.402 0.381 0.363 0.352 0.343 0.330 0.317